SMC ITV1000 Series Electro-Pneumatic Regulator Instruction Manual

June 6, 2024
SMC

Doc. No.DIT-69900-OM005-E
PRODUCT NAME
IO-Link/ELECTRO-PNEUMATIC REGULATOR
MODEL / Series / Product Number
*ITV1000/2000/3000-IO Series
Operation Manual**

This is the operation manual for the IO-Link compliant ITV.
For other contents which are not described in this manual, please refer to the operation manual for the standard product.

Product Specifications

Item Specified value
Power supply voltage DC24 V ±10% F.S.
Current consumption 0.12 ADC or less
Communication specifications IO-Link communication
Vendor ID 131(Dec)
Device ID 272(Dec)
ITV FW Version *1 Version1.2

*1 It becomes the FW version of the software of ITV.
Please contact the confirmed method of the FW version of our company.
Safety Instructions, precautions, and other specifications are the same as the standard series.

Wiring

  • Please don’t do the insert and remove of live-wire after the power supply is turned on.
    It causes the communication abnormality with the master by the situation.

Communication specifications

Item Specification Note
Protocol 10-Link
version Version 1.1
Communication speed 230.4 kbps (COM3) *1
10-Link port Class A
10-Link type Device
Process data 2 bytes IN
2 bytes OUT Resolution 12 BIT

*1 If parameters are not saved, it may be improved by changing master cycle time to 3.5msec or more.

Pressure setting method and output monitoring

Pressure can be set by sending input data from the master PLC to the regulator where the F.S is based on a 12 BIT resolution.
Do not operate the product outside of the specifications.

Set data 0x0000 0x7FF8
Output pressure 0% 100%

From the 16 BIT process data (2byte), input the 12BIT resolution starting from 3rd BIT to the 14th BIT.
Refer to the communication data for further details.

Communication data

Process data map

PD OUT (to ITV)

15*1 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
Set pressure value.(13 BIT) Disabled*2 Value

100% F.S.is indicated using 12 BITs, from the 3rd BIT to the 14th BIT.
1 Setting up to 120% F.S is possible by using the 15th BIT (However this is out of warranty).
2 Either 0 or 1 will have no effect.
PD IN (from ITV)

15*1 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
Set pressure value.(13 BIT) On hold*4 BDC1 Value

100% F.S. is indicated using 12 BITs, from the 3rd BIT to the 14th BIT.
3 Setting up to 120% F.S is possible by using the 15th BIT (However this is out of warranty).
4 0 is returned in an unused area.
Detection of the set pressure

BDC1 1 When set pressure is reached
0 When set pressure is not reached

*It detects when the output pressure reaches within ±10% F.S. of the set pressure.

List of parameters
INDEX Name: Function
OxOC Device access lock The setting of the device access lock is changed.
0x42 Gain tuning function Sets the response time.
0x43 Sensitivity tuning function Sets the sensitivity.
0x41 HOLD/CLEAR setting Sets the operation in response to a communication

error.
0x44| Initialization| Resets the settings to the default value.
0x46| Zero adjustment| Sets the minimum pressure.
0x47| Span adjustment| Sets the maximum pressure.

Parameter index OxOC
Parameter name Device access lock
Function In ITV for 10-Link, you can set “lock / unlock” for the data storage

function. Locking data storage functions will invalidate data storage functions.
When backing up data storage (Parameter setting data to read) or restoring (Overwriting parameter setting data) is instructed while the data storage function is locked, the access rejection is answered.
Default: 0(unlock)
Bit| Bit 1, 0
Value| Bit
-:-| 1| 0| Content|
0| 0| Unlocking the data storage function (Available data storage function)
1| 0| Data storage function lock. (Disable data storage function.)

  • indicates the initial shipping value.
Parameter index 0x42
Parameter name Gain tuning function
Function The response time can be changed by turning the gain. When the gain

is increased, the response time tends to be faster, but stability will be lost, which may cause hunting (unstable pressure).
Default: Gain 9
Bit| Bit 3, 2, 1, 0
Value| Bit
*| 3| 2| 1| 0| Setting|
0| 0| 0| 0| Gain 0
0| 0| 0| 1| Gain 1
0| 0| 1| 0| Gain 2
0| 0| 1| 1| Gain 3
0| 1| 0| 0| Gain 4
0| 1| 0| 1| Gain 5
0| 1| 1| 0| Gain 6
| | 0111Gain7| |
1| 0| 0| 0| Gain 8
1| 0| 0| 1| Gain 9
1| 0| 1| 0| Gain A
1| 0| 1| 1| Gain B
1| 1| 0| 0| Gain C
1| 1| 0| 1| Gain D
1| 1| 1| 0| Gain E
1| 1| 1| 1| Gain F

  • indicates the initial shipping value.
Parameter index 0x43
Parameter name Sensitivity tuning function
Function Changing the sensitivity will change the pressure correction

operation near the set pressure point. When the sensitivity is increased, hunting may occur. When the sensitivity is decreased, hunting will be reduced, but the pressure correction will be reduced, so there may be moderate pressure instability.
Default value: Sensitivity 0
Bit| Bit 2, 1, 0
Value| Bit
..-| 2| 1| 0| Setting|
0| 0| 0| Sensitivity –
0| 0| 1| Sensitivity
0| 1| 0| Sensitivity 0
0| 1| 1| Sensitivity 1
1| 0| 0| Sensitivity 2
1| 0| 1| Sensitivity 3
1| 1| 0| Sensitivity 4
1| 1| 1| Sensitivity 5

  • indicates the initial shipping value.
Parameter index 0x41
Parameter name Hold/Clear setting
Function Sets the output setting when a communication error occurs. 0:

Exhaust completely (Clear).
1: Output pressure is maintained (Hold).
Default value: Clear
Bit| Bit 0
Value| Bit| 0| Setting|
0| Clear
1| Hold

  • indicates the initial shipping value.
Parameter name 0x44
Parameter name Initialization
Function All of the setup including the internal control constant is

initialized with this function. Perform this function only when the product is completely stopped due to an error.
Bit| BIT 0 to 7
Value| Any value between 0 to 11111111

Parameter index 0x46(Zero adjusting), 0x47(Span adjusting)
Parameter name Zero adjusting, Span adjusting
Function Zero adjusting (hereinafter referred to as F_1) corresponds to set

the minimum pressure, Span adjusting (hereinafter referred to as F_2) to set the maximum pressure. F_1 and F_2 have setting ranges of 0-90%F.S. and 10-120%F.S., respectively. However, the set pressure exceeds the rated output; 100%F.S. is out of warranty. (refer to Fig.2,3)
The values are necessary to satisfy “F_1 + 10%F.S. < F2”. If not, the previous values are reflected in this function.
Default of Zero adjusting: Ox0000
Default of Span adjusting: OxOFFF(Hexadecimal Number)
Bit| BIT 13 (It is Bit 12 up to 100%.)
Value| Relationship between F1/F2 and the set pressure (Hexadecimal Number)
| Zero adjusting F_1| Span adjusting F_2|
Minimum| Maximum| Minimum| Maximum
| Input value| Ox0000| Ox0E65| Ox019A| 0x1332
Set pressure| 0°/0F.S.| 90%F.S.| 10%F.S.| 120%F.S.

Error Message

LED

Item ON OFF Flashing
Power Power is supplied (Green) Internal diagnosis error (Red) The power
supply is not connected
Communication Communication in stand-by mode(Green) Communication
disconnected Communication exchange (Green)

Error code

Error No. Name: Description
0x5000 Internal diagnosis error ROM read/write error

Control depends on the Hold/Clear set.
Power LED turned ON Red.
If the error is not corrected even after disconnecting the power supply, perform “Initialization”.
0x6320| Target value over range error| The data of the target value has exceeded the specification (120% F.S. is exceeded).
Input a target value within the specification.
Ox8C20| Output pressure value over range error| The data of the output pressure value has exceeded the specification (120% F.S. is exceeded).
Adjust the output pressure to within the specification.

Product ID

When reading the product ID from the master side, the following product ID is readout.
In addition, when selecting a product ID from the IODD file, you will choose from the following.

Product ID

ITV1010-IO-X395 1
ITV1030-IO-X395
1
ITV1050-IO-X395 1
ITV2010-IO-X395
1
ITV2030-IO-X395 1
ITV2050-IO-X395
1
ITV2090-IO-X395 1
ITV3010-IO-X395
1
ITV3030-IO-X395 1
ITV3050-IO-X395
1
ITV3050-IOF3N-DIT00375

*1: This becomes product ID added since FW Ver1.2.
Revision
E: Correction concerning communication data, Product ID addition, and correction by software modification.
SMC Corporation
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPANTel: + 81 3 5207 8249 Fax: +81 3 5298 5362
URL http://www.smcworld.com
0120-837-838