NLII-RH+T-RS485 | Combined RH/temperature sensor with RS485
Room sensor NLII-RH is used to monitor the air quality inside buildings and control ventilation (HVAC) systems according to current levels of air pollution. The sensor measures relative humidity (RH) and temperature (T). It is suitable for living rooms, bathrooms, warehouses, ateliers, etc.
- measures RH and temperature
- RS485 bus communication with Modbus RTU protocol
- maintenance during operation is not required
- long life and stability
Description
Measurement of the relative humidity is based on the principle of capacitive
polymer sensor.
The sensor provides two outputs over the RS485 bus – one for the actual
temperature and the other for the actual relative humidity.
Sensors can efficiently manage ventilation and heat recovery units, based on
current air quality.
The current air quality can easily be determined by looking at the three LED
indicators. The eco level means good indoor air quality that is needed to
achieve a sense of well-being and at the same time optimal energy costs for
heating or air conditioning.
For information on the communication protocol, use the document NLII-Modbus-
komunikace.
Explanation of abbreviations and technical terms can be found on our website in the Glossary section.
Technical data
Parameter | Value | Unit |
---|---|---|
Supply voltage range | 12 – 35 | V DC |
Average consumption | 12 – 24 | V AC |
RH measuring range | 0,2 | W |
RH accuracy 20 – 80 % | 0 – 100 % | RH |
RH accuracy 0 – 100 % | ± 3 % | RH |
T measuring range | ± 6 % | RH |
T accuracy | 0 – 50 | °C |
Working temperature | ± 0,4 | °C |
Working humidity | 0 to +50 | °C |
non condensing | 0 – 90 % | RH |
Storage temperature | -20 to +60 | °C |
Expected lifetime | min. 10 | years |
Ingress protection | IP20 | |
Dimensions | 90x80x31 | mm |
RS485 bus | ||
A-B voltage difference | max 5 | V |
A-B common input voltage | -7 to 12 | V |
A-B common output voltage | max 3 | V |
Typical RH measurement accuracy at 25 °C
Typical T measurement accuracy
CAUTION:
Warm-up: operational after 1 minute since power on.
The declared accuracy is reached after 4 days of continuous power supply.
It is necessary to avoid the severe mechanical shock of the sensor.
Combined RH/temperature sensor with RS485
LED indication description
White LED lights:
****Less than 40 % RH or less than 18 °C.
(according to the quantity selected for indication)
- low concentrations of RH. Too dry air feels cooler as compared to equally hot but more humid air – risk of drying of the mucous membranes – respiratory problems
- low temperature and its higher fluctuation is not economically profitable
Green LED lights:
More than or equal to 40 % RH or 18 °C, less than or equal to 60 % RH or 22
°C.
(according to the quantity selected for indication)
- optimal relative humidity for humans
- optimal balance of air quality and energy the efficiency of ventilation and air conditioning
Yellow LED lights:
More than 60 % RH or more than 22 °C.
(according to the quantity selected for indication)
- too high humidity, the risk of mold growth, and associated health complications
- higher temperature T – high temperature can cause fatigue, restlessness, headache, and feeling hot
Sensor start after power on
All three LEDs flash simultaneously until the first readings are available,
but no longer than 10 seconds.
Sensor failure indication
All three LEDs are shining permanently.
Electronic board controls and terminals
Terminals
- ~ + supply AC or DC (+) plus pole
- ~ GND supply AC or DC (-) minus pole, GND
- OUT1 RS485 bus – signal line B
- GND GND
- OUT2 RS485 bus – signal line A
- GND GND
Jumpers
JP6 – LED indication settings
Jumpers on the electronics board
Mark | Description | Settings | Meaning |
---|
JP6 – 1
JP6 – 3| Enabling LED indication and selecting the
quantity for indication(factory setting is RH)
| | LED indication disabled
| LED indication enabled,
indication by RH
| LED indication enabled,
indication by T
Sensor assembly
Box color
Front: White – RAL9016
Base: gray – RAL7035
Way to use
The product is intended for indoor use only. You can read the
recommendations for sensor placement on our web pages.
End of product life
Discard the product in according to the electronic waste law and the EU
directives.
Dimensions