PROTRONIX NLII-CO2+RH+T-5-SX Combined CO2/RH/T Sensor with Sigfox User Manual
- June 6, 2024
- PROTRONIX
Table of Contents
- Description
- Technical data
- CO2 sensor autocalibration function
- LED indication description
- Electronic board controls and terminals
- Jumpers on the electronics board
- Factory settings
- Sensor assembly
- Disassembly
- Dimensions
- Box color
- Way to use
- End of product life
- Customer Support
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PROTRONIX NLII-CO2+RH+T-5-SX Combined CO2/RH/T Sensor with Sigfox User
Manual
Room sensor NLII-CO2 is used to continuously monitor air quality inside buildings and then control ventilation (HVAC) systems according to current levels of air internal air quality. The sensor measures concentration of carbon dioxide (CO2), relative humidity (RH) and temperature (T). It can be effectively used in offices, classrooms, shopping centers, homes, restaurants, fitness centers, commercial buildings, etc.
- measures CO2, RH and temperature
- 2x analog voltage/current output
- SIGFOX wireless communication
- maintenance during operation is not required
Description
The measuring of CO2 is based on the principle of infrared radiation attenuation dependence on the CO2 concentration in the air (NDIR). Built-in autocalibration function ensures very good long term stability.
Measurement of the relative humidity is based on the principle of capacitive
polymer sensor.
The sensor has built-in two separate analog outputs – one for the actual
concentration of CO2 and the other for the current relative humidity.
Temperature output is available by Sigfox communication.
So the sensor efficiently manages ventilation and heat recovery units, based
on current room air quality.
The current air quality can easily be determined by looking at the three LED
indicators.
The eco level means good indoor air quality necessary to achieve a sense of well-being and at the same time optimal energy costs for heating, ventilation or air conditioning.
For detailed information on the communication protocol, use the document NLII-SigfoxCommunication.
Explanation of abbreviations and technical terms can be found on our website in the Glossary section.
Technical data
Parameter | Value | Unit |
---|---|---|
Supply voltage range | 12 – 35 12 – 24 | V DC V AC |
Average consumption | 0,5 | W |
CO2 measuring range | 400 – 5000 | ppm |
CO2 accuracy | ± 35 ppm ±5 % of reading | |
CO2 startup | max 1 | min |
CO2 step response | (90 %) 80 | s |
RH measuring range | 0 – 100 % | RH |
RH accuracy 20 – 80 % | ± 3 % | RH |
RH accuracy 0 – 100 % | ± 6 % | RH |
T measuring range | 0 – 50 | °C |
T accuracy | ± 0,4 | °C |
Output 1) | 0-10 V / 0-20 mA / 4-20 mA |
Working humidity
non condensing
| 0 – 95 %| RH
Working temperature| 0 to +50| °C
Storage temperature| -20 to +60| °C
Expected lifetime| min. 10| years
Ingress protection| IP20|
Dimensions| 110x158x31| mm
It is possible to select the desired type of analog output by a jumper.
Minimum achievable output value corresponds to minimum value of the measuring
range.
CO2 sensor autocalibration function
Autocalibration compensates for long-term aging of the key components of the sensor. This function is available only when sensor power supply is continuous and uninterrupted. Calibration during operation is not necessary
-
Selected analog output values versus actual CO2 concentration
-
Selected analog output values versus actual RH
-
Typical RH measurement accuracy at 25 °C
-
Typical T measurement accuracy
LED indication description
White LED lights:
Less than 600 ppm CO2 or less than 40 % RH. (according to the quantity selected for indication)
- maintaining low concentrations of CO2 is not cost-effective – slightly increased concentration does not cause any health complication
- low concentrations of RH. Too dry air feels cooler as compared to equally hot but more humid air – risk of drying of the mucous membranes – respiratory problems
Green LED lights:
More than or equal to 600 ppm CO2 or 40 % RH, less than or equal to 1200 ppm CO2 or 60 % RH. (according to the quantity selected for indication)
- optimal balance of air quality and energy efficiency of ventilation and air conditioning
- optimal relative humidity for humans
Yellow LED lights:
More than 1200 ppm CO2 or more than 60 % RH. (according to the quantity selected for indication)
- higher concentration of CO2 – further increase of CO2 concentrations above this level can cause fatigue, restlessness, headache
- too high humidity – the risk of mold growth and associated health complications
Sensor start after power on
All three LEDs flash simultaneously until the first readings are available, but no longer than 10 seconds.
Sensor failure indication
All three LEDs are shining permanently.
CAUTION:
Warm-up: operational after 1 minute since power on.
The declared accuracy is reached after 4 days of continuous power supply.
It is necessary to avoid severe mechanical shock of the sensor.
Electronic board controls and terminals
Terminals
- ~ + supply AC or DC (+) plus pole
- ~ GND supply AC or DC (-) minus pole, GND
- OUT1 CO2 sensor analog output, 0-10 V or 0-20 mA or 4-20 mA
- GND CO2 sensor output GND
- OUT2 RH sensor analog output, 0-10 V or 0-20 mA or 4-20 mA
- GND RH sensor output GND
Jumpers
- JP1 – Current output offset RH
- JP2 – Current output offset CO2
- JP3 – Voltage/current output CO2
- JP4 – Voltage/current output RH
- JP6 – LED indication settings
Jumpers on the electronics board
Mark | Description | Settings | Meaning |
---|---|---|---|
JP1 | Current output offset RH |
- shift quiescent current from 0 mA to 4 mA
| | current output RH 0-20 mA
| current output RH 4-20 mA
JP2| Current output offset CO 2
- shift quiescent current from 0 mA to 4 mA
| | current output CO2 0-20 mA
| current output CO2 4-20 mA
JP3| Voltage/current output CO 2
- select the type of analog output
- if the selected voltage output is CO2, JP2 must not be shorted
| | voltage output CO2
| ****
current output CO2
JP4| Voltage/current output RH
- select the type of analog output
- if the selected voltage output is RH, JP1 must not be shorted
| | voltage output RH
| ****
current output RH
JP6 – 1| LED indication
- LED indication according to ambient light
- when ambient light is dimmed (at night), LED indicators turn offautomatically.
| |
permanent LED indication enabled
| LED
indication according to ambient light
JP6 – 4 JP6 – 5| These positions are not intended for user
setting.| |
Factory settings
- LED indication: by CO2, indication turns off when ambient light dims
- CO2 analog output: voltage output
- RH analog output: voltage output
Example of CO2 sensor connection for direct EC motor control using 0-10 V signal
If you connect other devices to the same AC power source as the NL sensor, it is necessary to meet GND wiring of all analog inputs and outputs, as well as power wires.
Sensor assembly
Disassembly
When disassembling, be careful not to rip-out the antenna cable. It connects the antenna in lower part of the sensor with the electronics in the upper part.
Dimensions
Box color
- Front: white – RAL9016
- Base: gray – RAL7035
Way to use
The product is intended for indoor use only. You can read the recommendations for sensor placement on our web pages.
End of product life
Discard the product in according to the electronic waste law and the EU directives.
The producer reserves the right of technical changes in order to product improvements its properties and functions without previous notice.