PROTRONIX NLII-CO2+RH+T-5-RS485 Room Sensor with RS485 User Manual
- June 6, 2024
- PROTRONIX
Table of Contents
SENSE & EASY
User manual
NLII-CO2+RH+T-5-RS485 | Room CO2/RH/T sensor with RS485
Room sensor NLII-CO2 is used to continuously monitor air quality inside
buildings and then control ventilation (HVAC) systems according to current
levels of internal air quality. The sensor measures the concentration of
carbon dioxide (CO2), relative humidity (RH), and temperature (T). It can be
effectively used in offices, classrooms, shopping centers, homes, restaurants,
fitness centers, commercial buildings, etc.
measures CO2, RH, and temperature
RS485 bus communication with Modbus RTU protocol
maintenance during operation is not required
Sensor type / Order code| CO 2 measurement| RH measurement|
T measurement| CO 2 ppm range
---|---|---|---|---
NLII-CO2-5-RS485|
√
|
–
|
–
| 400-5000
NLII-CO2+RH+T-RS485|
√
|
√
|
√
| 400-2000
NLII-CO2+RH+T-5-RS485|
√
|
√
|
√
| 400-5000
Description
The measuring of CO2 is based on the principle of infrared radiation
attenuation dependence on the CO2 concentration in the air (NDIR). Built-in
autocalibration function ensures very good long-term stability.
Measurement of the relative humidity is based on the principle of capacitive
polymer sensor. Sensors can efficiently manage ventilation and heat recovery
units, based on current air quality. The current air quality can easily be
determined by looking at the three LED indicators. The eco level means
good indoor air quality necessary to achieve a sense of well-being and at the
same time optimal energy costs for heating, ventilation, or air conditioning.
All outputs of measurement are available through the RS485 bus. For
information on the communication protocol, use the document NLII-Modbus-
komunikace.
Explanation of abbreviations and technical terms can be found on our website
in the Glossary section.
Parameter
| Value|
Unit
---|---|---
Supply voltage range| 12 – 35
12 – 24
| V DC
V AC
Average consumption| 0,5| W
CO2 measuring range| 400 – 2000 (5000)| ppm
CO2 accuracy| ± 35 ppm ±5 % of reading
CO2 startup| max 1| min
CO2 step response| (90 %) 80| s
RH measuring range| 0 – 100 %| RH
RH accuracy 20 – 80 %| ± 3 %| RH
RH accuracy 0 – 100 %| ± 6 %| RH
Working humidity non-condensing| 0 – 95 %| RH
Working temperature| 0 to +50| °C
Storage temperature| -20 to +60| °C
Expected lifetime| min. 10| years
Ingress protection| IP20|
Dimensions| 90x80x31| mm
RS485 bus| |
A-B voltage difference| max 5| V
A-B common input voltage| -7 to 12| V
A-B common output voltage| max 3| V
CO2 sensor autocalibration function
Autocalibration compensates for the long-term aging of the key components of
the sensor. This function is available only when the sensor power supply is
continuous and uninterrupted. Calibration during operation is not necessary.
Typical RH measurement accuracy at 25 °C
Typical T measurement accuracy
CAUTION:
Warm-up: operational after 1 minute since power on.
The declared accuracy is reached after 4 days of continuous power supply.
It is necessary to avoid the severe mechanical shock of the sensor.
LED indication description
White LED lights:
Less than 600 ppm CO2 or less than 40 % RH. (according to the quantity
selected for indication)
– maintaining low concentrations of CO2 is not cost-effective – slightly
increased concentration does not cause any health complications
– low concentrations of RH. Too dry air feels cooler as compared to equally
hot but more humid air – the risk of drying of the mucous membranes –
respiratory problems
Green LED lights:
More than or equal to 600 ppm CO2 or 40 % RH, less than or equal to 1200 ppm
CO2 or 60 % RH. (according to the quantity selected for indication)
– the optimal balance of air quality and energy the efficiency of ventilation
and air conditioning
– optimal relative humidity for humans
Yellow LED lights:
More than 1200 ppm CO2 or more than 60 % RH. (according to the quantity
selected for indication)
– higher concentration of CO2 – a further increase of CO2 concentrations above
this level can cause fatigue, restlessness, headache
– too high humidity – the risk of mold growth and associated health
complications
Sensor start after power on
All three LEDs flash simultaneously until the first readings are available,
but no longer than 10 seconds.
Sensor failure indication
All three LEDs are shining permanently.
Electronic board controls and terminals
Terminals
1. ~ + supply AC or DC (+) plus pole
2. ~ GND supply AC or DC (-) minus pole, GND
3. OUT1 RS485 bus – signal line B
4. GND GND
5. OUT2 RS485 bus – signal line A
6. GND GND| Jumpers
JP6 – LED indication settings
---|---
Jumpers on the electronics board
Mark| Description| Settings|
Meaning
---|---|---|---
JP6 – 1| LED indication
(factory setting – CO2)
– LED indication according to ambient light – when ambient light is dimmed (at
night), LED indicators to turn off automatically.| | permanent LED
indication enabled
| LED indication according to ambient light
JP6 – 3| Selecting the sensor for an LED indication – CO 2 or RH.|
| LED indication by CO 2
| LED indication by RH
JP6 – 4
JP6 – 5| These positions are not intended for user settings.| |
Sensor assembly
Box color
Front: white – RAL9016
Base: gray – RAL7035
Way to use
The product is intended for indoor use only. You can read the
recommendations for sensor placement on our web pages.
End of product life
Discard the product according to the electronic waste law and the EU
directives.
Dimensions