WEIL-McLAIN 384-000-157 Combustion Air Damper Kit Installation Guide
- June 6, 2024
- Weil-McLain
Table of Contents
384-000-157 Combustion Air Damper Kit
Installation Guide
Series Identification
Read the boiler rating label to determine the series number. The rating
label is located on the back of the boiler.
STOP! Read before proceeding
Hazard definitions
The following defined terms are used throughout this manual to bring
attention to the presence of hazards of various risk levels or to important
information concerning the life of the product.
| Indicates presence of hazards that will cause severe personal injury, death
or substantial property damage.
---|---
| Indicates presence of hazards that can cause severe personal injury, death
or substantial property damage.
| Indicates the presence of hazards that will or can cause minor personal
injury or property damage.
| Indicates special instructions on installation, operation or maintenance
that are important but not related to personal injury or property damage.
| These instructions must only be used by a qualified installer/service
technician. Read all instructions completely
before beginning the installation. Failure to follow all instructions can
cause severe personal injury, death or substantial property damage.
| You must read and have the SVF™ Boiler Manual with you to proceed with these
instructions.
The Boiler Manual is available online at Weil-McLain.com
P/N 384-000-157 Kit contents:
Item | Description | Qty |
---|---|---|
1 | Damper | 1 |
2 | Fernco Fitting | 1 |
3 | Damper Installation Instructions | 1 |
STOP! Read before proceeding
| The boiler contains ceramic fiber and fiberglass materials. Use care when
handling these materials per instructions in the Boiler Manual, available
online at Weil-McLain.com. Failure to comply could
result in severe personal injury.
| Shut off power to the boiler and close the main gas valve. Close all
isolation valves. failure to do so can result in severe personal injury,
death, or substantial property damage.
| Wait for the heat exchanger to cool down before proceeding. Failure to do so
can result in severe personal injury.
| Removing and reinstalling components can change boiler behavior. After any
maintenance procedure, you must prove the boiler is operating correctly. To do
so, follow the complete procedure for boiler and system start-up as instructed
in the Boiler Manual. Failure to comply could result in severe personal
injury, death, or substantial property damage.
| For component location reference, see previous pages. This is duplicated
from the SVF™ Boiler manual but included here for convenience. All
instructions in the Boiler manual must be followed, including fuel
requirements, water requirements, and start-up/operation.
Recommended tools
4mm Allen Wrench | Phillips Head Screwdriver |
---|---|
8mm Wrench |
Clearance requirements
This procedure requires adequate clearance to do the following:
- Remove the top panel and top front panel.
- Access internal components of the boiler, remove components, and set components aside in a clean staging area.
It is assumed that the boiler will NOT need to be moved in order to meet these clearance requirements.
Isolate the boiler
- Shut off power to the boiler.
- Shut off the supply of gas to the boiler.
Remove ALL jacket panels for access to internal components
- Remove the top panel
a. Remove four (4) screws.
b. Lift off the boiler. Set aside.
Remove the air inlet hose
- Use a screwdriver to loosen the two hose clamps holding the air inlet hose.
- Slide the air inlet hose off the air inlet elbow and the air inlet adapter. Set the air inlet hose aside.
Figure 1 Removal of the flexible air tube
Figure 2 Slide Fernco fitting and air inlet hose onto the damper
Modify the air inlet hose
- Remove the hose clamps.
- Using a tool, cut the air inlet hose to a relaxed length of 10 inches.
- Slide the hose clamps over the ends of the air inlet hose.
Figure 3 Air inlet hose cut to 10 inches in relaxed length
Install the damper kit assembly
-
Get the damper and 6″ Fernco fitting from the replacement kit.
-
Slide the Fernco fitting and modified air inlet hose onto the damper as shown in Figure 2 and tighten the hose clamps.
NOTE: The flexible conduit should be located on the side of the damper facing the gas valve, NOT the side facing the right jacket panel. -
Slide the Fernco fitting onto the air inlet adapter and tighten the hose clamp.
-
Slide the air inlet hose onto the air inlet elbow and tighten the hose clamp.
Figure 4 Damper Assembly Installed
Install the damper wiring
-
Open the rear terminal box using a Phillips head screwdriver.
-
Route the flexible conduit down the rear terminal box. Secure the conduit fitting through an available knockout in the first five knockouts from the top.
-
Attach wires as shown in Figure 5.
a. Red wires to “Closure Switch 2” and “Closure Switch 1” in Block “P11”
b. Choose output 2 or 3 (OUTPUT 3 shown)
c. Green wire to selected output ground in block “P2”
d. White wire to selected output neutral in block “P2”
e. Blue wire to selected output hot in block “P2”
f. Black wire to “1 Power (HOT) 120 VAC” in block “P1” -
Close the rear terminal box using one (1) screw with a Phillips head screwdriver
Reinstall all jacket panels
- Reinstall the top panel using four (4) screws with a Phillips head screwdriver.
Adjust control settings
- Assign INPUT 2 or INPUT3 (whichever was selected when wiring) as AUX PUMP/OUTPUT function.
- See NOTE A on page 5
- OUTPUT 2 or OUTPUT 3 (whichever was selected when wiring) will provide 120VAC to the damper motor.
NOTE: Whichever output is selected will also make the corresponding input unusable. For example, if OUTPUT 3 is selected INPUT 3 would be unusable.
The startup, test, and adjust boiler
- Refer to Boiler Manual for proper startup procedure
- Follow all instructions in the Boiler Manual to start up, test, and adjust the boiler
Figure 5 Damper Wiring
Figure 6 Adjusted Control Settings
The screens shown above are typical only. Actual screens depend on the control
settings chosen.
INPUT 2 OR INPUT 3
Assign INPUT 2 or INPUT 3 (whichever was selected when wiring) as AUX / PUMP
OUTPUT (INPUT 3 shown)
NOTE A
For the AUX PUMP/OUTPUT operating mode:
a. If a single boiler installation, select ANY BURNER DEMAND or DAMPER
CONTROL.
b. If multiple boiler installations, select DAMPER CONTROL.
This ensures the damper will be activated any time the boiler is called on to
fire.
If DAMPER CONTROL is not shown as an option, please consult the Weil-McLain
Factory.
Weil-McLain
500 Blaine Street
Michigan City, IN 46360-2388
http://www.weil-mclain.corn
Part number 550-142-964/1020