Tigo AGF-AE-D/200 Solar Power Monitoring User Manual
- June 6, 2024
- Tigo
Table of Contents
Tigo AGF-AE-D/200 Solar Power Monitoring
Tigo Energy, Inc. | www.tigoenergy.com | support@tigoenergy.com
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for Model SM-US-200 that shall be
followed during installation and maintenance of the inverter.
CAUTION: Risk of Electric Shock, Do Not Remove Cover. No User Serviceable
Parts Inside.
Refer Servicing To Qualified Service Personnel.
WARNING: Hazardous voltage is still present 5 minutes after all power sources have been disconnected.
INFORMATION: Information notes, provided that will ensure the optimal operation of the system.
Warning: These instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions
Introduction
This meter is supplied with 2 current transformers for use in monitoring the
energy from the inverter output and/or from the utility grid. This meter is
recommended for use with the Tigo TSI inverters and required for use when
installing a Tigo TSB storage system.
The application of this meter will provide accurate data to the Tigo Energy
Intelligence monitoring platform showing the energy usage throughout the PV
system.
Required For Installation
- AC Wire for connection to AC load center: 22-18AWG stranded, 600V
- RS-485 for data connection to inverter: minimum 3-wire shielded, twisted pair, 24-18AWG Conduit/conduit fittings, and associated tools to install, if necessary
- Over current protection device, 20A or less
- Enclosure, if not installed in the AC load center
- Cable ties
- Screwdriver
Note: If using a cable longer than 10m/33ft in areas where there is a risk of induced voltage surges by lightening, it is recommended to use external surge protection devices. If grounded metal conduit is used for routing the communication wires, there is no need for a lightening protection device.
Installation Guidelines
- All prevailing electrical codes and requirements, national and local, must be followed in the installation of this product.
- The meter is considered “permanently connected equipment” and requires a disconnect means (circuit breaker or disconnect switch) and over current protection (fuse or circuit breaker).
- The meter draws 10-30mA, therefore the rating of any disconnect switches, fuses, and/or circuit breakers is determined by the wire gauge, the service voltage, and the required current interrupting rating.
- Use circuit breakers or fuses rated for 20A or less.
- The circuit breaker or fuses must protect the meter’s input terminals labeled L1 and L2. If a neutral conductor is used and it has over current protection, the over current protection device must interrupt both neutral and ungrounded conductors simultaneously.
- The disconnect switch or circuit breaker must be located near the meter and easily operated.
Mounting the Meter
This meter is intended to be mounted in an AC load center or other outdoor
enclosure. The meter clamps to a 35mm DIN rail. Dimensions of the meter and
Current Transformers (CTs) can be found at the end of this document.
Mount in an appropriate enclosure prior to wiring the meter or CTs.
CAUTION This meter is to be wired only by qualified personnel. Hazardous voltage and the risk of electric shock is present.
Wiring the Meter to the Tigo Inverter
The meter is connected to the inverter which communicates this data to the
cloud to be monitored in the Energy Intelligence app or web portal. The meter
connects to the TSI inverter using an RS-485 cable through a 3-pin connector
labeled “RGM” above the PV input terminals, as shown below.
- Verify power is OFF before making connections.
- Open any knockouts in the meter enclosure and run conduit from the meter enclosure to the inverter’s “comm” knockouts. Use appropriate conduit fittings for the environment in which the equipment is installed.
- Feed the RS-485 cable through the conduit to the inverter.
- Connect the RS-485 cable to the 4-pin terminal (pin 4 is empty: G, B-, A+) and insert into the meter terminal block ensuring a fully seated connection.
Wiring the Meter to the AC
The meter senses voltage over a wired connection to the AC panel using the
lower terminals labeled ØL1, ØL2, N and G.
- Verify power is OFF before making connections.
- Open any knockouts in the meter enclosure and run conduit from the meter enclosure to the AC load panel. Use appropriate conduit fittings for the environment in which the equipment is installed.
- Feed the conductors through the conduit to the AC load panel.
- Loosen the 4 labeled screw terminals on the lower section of the meter.
- Insert AC conductors into the proper screw terminal and tighten the set screw to 0.4Nm:
- ØL1 to pin 1
- ØL2 to pin 2
- Neutral to pin 3
- Ground to pin 5
- Wire conductors to the AC load panel through a double-pole circuit breaker (20A or less).
Note: If the meter is used in a single-phase two-wire system (no neutral), connect L2 and N at the meter’s terminals.
Installing the Current Transformers
- Turn off the AC power before clamping the CTs.
- Install the CTs around the ØL1 and ØL2 conductors installed in the previous step. The split-core CTs can be opened for easy installation around a conductor. A nylon cable tie may be used around the CT to prevent accidental opening.
- Install the CT with the arrow pointing to the grid for consumption or export measurement.
- Connect the CT conductors to the 4-pin terminal block to the right of the inverter connection (L2, CT, L1, CT).
Core 1: L1 (blue) to pin 1 Core 1: CT (brown) to pin 2 Core 2: L2 (blue) to pin 3 Core 2: CT (brown) to pin 4
LED Indicators
Three status LEDs on the front face of the meter indicate operation and correct measurement. At normal startup, when power is first applied, all LEDs will light up sequentially for one second.
Power Status LED
LED | LED Color | Function | Indication | Troubleshooting |
---|---|---|---|---|
RUN | GREEN | Flashing ON/OFF (for 1 sec) | Normal | N/A |
RED | ON for > 3 sec | Internal Error | Contact Support | |
YELLOW | **** |
Flashing ON/OFF (for 1 sec)
| No communication| Check that the communications cable
is properly connected
Phase Status LED
LED | LED Color | Function | Indication | Troubleshooting |
---|---|---|---|---|
L1/L2 | GREEN | ON for >3 sec | No Current | |
Flashing ON/OFF (for 1 sec) | Positive Power |
RED
| ****
Flashing ON/OFF (for 1 sec)
| ****
Negative Power
| Check for reversed CTs, swapped CT wires, or CTs not matched with
lines.
Flashing with GREEN LED| High Voltage > 130V| Check the line voltages and the
meter rating.
Flashing with YELLOW LED| Low voltage < 70V
YELLOW| Flashing ON/OFF (for 1 sec)| Break fault <
30V
ON for > 3 sec
| Frequency is below 45Hz or
above 70Hz| Check for the presence of high noise.
Reset button
If the software version of the meter needs to be updated a connection to a
computer is necessary.
- Connect to the meter via RS-485
- Open the programming software provided by Tigo and load the new version
- Press the “reset” button on the front face of the meter; the meter will restart
- Wait for the upload to complete
Technical Specifications
Electrical Meter | Units |
---|---|
Model | SM-US-200 |
Rated Voltage-Line to N | 120 |
Rated Voltage-Line to Line | 208/240 |
Extended Voltage Range | 88%~110% |
AC Frequency | 60 |
Grids Supported | L1/L2/N/PE |
Power Consumption | 1.2 |
Communication
Meter Communication Interfaces| RS-485|
Response Time| ≤1| S
Meter Accuracy
Rated RMS current| 100| 200| A
1%-100% of CT Current| ±0.5| ±1| %
Current Transformers
Number of Supplied Current Transformers| 2|
Dimensions
| I.D:15
O.D:35
| 70.5×54.5×39 (H×W×D)| ****
mm
Standard Compliance
Safety| UL1741|
Installation Specifications
Dimensions(H×W×D)| 54.1×87.8×52| mm
Weight| 0.2| kg
Operating Temperature Range| -30~55| ℃
Relative Humidity (noncondensing)| 5 – 90| %
Mounting Type| DIN-Rail,35mm|
This meter is intended to be installed in an appropriately rated enclosure.
Dimensions
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>