Tigo TS4-A-F Rapid Shutdown Device User Guide
- June 5, 2024
- Tigo
Table of Contents
TS4-A-F Quick
Start Guide
General Information – Specifications
ATTENTION – READ FIRST
- This document is for quick guidance only. For details, please refer to the TS4-A-F/-2F Installation and Operations Manual.
- Damage caused by failure to follow the contents of the TS4-A-F/-2F Installation and Operations manual is not covered by the warranty.
- Install all TS4-F, TS4-A-F, and/or TS4-A-2F BEFORE powering on the RSS transmitter.
- TS4-A-F, TS4-A-2F, and a Tigo RSS Transmitter are a solution to meet NEC 2017 & 2020 690.12 Rapid Shutdown requirements. TS4-F, TS4A-F, and TS4-A-2F units automatically enter rapid shutdown mode when the RSS Transmitter is switched off, and resume energy production when power is restored to the RSS Transmitter. Wait for 30 seconds after rapid shutdown activation before disconnecting DC cables or turning off DC disconnect.
1.1 Package Contents
Item | Quantity |
---|---|
TS4-A-F | 20 |
Quick Start Guide | 1 |
Rapid Shutdown label | 1 |
A Tigo RSS Transmitter is required for the proper operation of this rapid
shutdown system. For more information, scan the QR code here.
https://qrco.de/bcLMsY
1.2 Rapid Shutdown (RSD) System Wiring Diagram
Each module in the PV system must contain a TS4-A-F of TS4-A-2F for safe
and proper operation of the PV system.
System components:
- PV inverter
- Tigo PV RSS Transmitter
- Tigo TS4-A-Fs (qty. will vary)
- PV modules (qty. = TS4)
A PLC-based RSD system consists of a transmitter and receivers.
Many leading inverters integrate the Tigo RSS Transmitter. Look for the Tigo
Enhanced label or check for Tigo integration partners at
https://www.tigoenergy.com/ul-pvrss
1.3 TS4-A-F Overview
-
PV module Input
• Negative (-) LEFT
• Positive (+) RIGHT -
Output to String
• Negative (-) LEFT
• Positive (+) RIGHT -
Module clips
• Removed
• Mounting holes (M8)
Max voltage: 80VDC
Max current Imp/Isc: 20/25ADC
Max power: 700W
Max string voltage: 1000/1500VDC (connector dependent)
Wear and USE appropriate PPE for the application. Suggestions: gloves,
sunscreen,….
Energy is supplied to the Tigo TS4 output cables immediately upon
connection to a PV module exposed to sunlight. Use care when handling. Do not
mate connectors from different manufacturers.
Installation
**** Install the TS4-F, TS4-A-F, and/or TS4-A-2F BEFORE powering on the RSS
transmitter.
All PV modules from the same inverter must have a TS4 connected.
- MOUNT
- Connect MODULES to TS4s
- Then connect the TS4s together
Mount the TS4 to the module and dress the PV input conductors with appropriate wire management means BEFORE taking the PV module to the roof.
Commissioning
3.1 Pre-commissioning checklist
**** Wear and USE appropriate PPE for the application. Suggestions: gloves,
sunscreen,….
**** | Check Item | Acceptance Criteria |
---|---|---|
TS4 installation | **All PV modules are connected to a |
TS4-F/TS4-A-F/TS4-A-2F.**
| Tigo RSS Transmitter| The Tigo RSS Transmitter is installed per the RSS
Transmitter Installation Manual. If the Inverter is integrated, follow the
inverter manufacturer’s instructions for signal/power.
| Connections| All connectors are securely mated and of the same type.
| Voltage check| The TS4-A-F passes 0.6VDC when the keep-alive signal is not
present. String voltage = 0.6V x # of modules in the string
| Wire Management| All conductors are properly secured throughout the array.
ANSI/NFPA 70 wiring methods were used. Multi-transmitter systems either:
•have followed the PV Conductor Installation Required Practices in the full
Manual,
•or have installed the Tigo RSS Transmitter 2.0 and have linked all
transmitters in the system together.
| Workmanship| Wire management and general best practices were used.
3.2 Commissioning notes
- Each PV string will produce less than 30VDC until the RSS Transmitter is activated/powered.
- When power is provided to the RSS Transmitter the PV strings will produce full voltage under environmental conditions.
- Commission the PV system as per best practice.
Troubleshooting
**** Wear and USE appropriate PPE for the application. Live voltages may be present.
Issue | Check |
---|---|
No string voltage | Check that all string connectors are securely connected. |
Lower voltage than expected | Check that all PV module connectors are securely |
connected.
Note — with no keep-alive signal the string voltage will equal: # PV modules x
0.6VDC Check that the RSS transmitter is powered on.
Inconsistent voltage reading when no signal is present| 1. Apply power to the
RSS Transmitter
2.Use an RSS Signal Detector to determine if the individual TS4s are receiving
the keep-alive signal.
Your Customer Service Contact
United States (HQ):
Tigo Energy, Inc.
655 Campbell Technology Pkwy
Campbell, CA 95008
EMEA Office:
Tigo Energy Italy
Srl Via Calamandrei 36 52025
Montevarchi Tuscany, Italy
Americas: +1 408 402 0802
International: 00800 2255 8446
https://support.tigoenergy.com/
|
---|---
https://qrco.de/bcLMsY| https://qrco.de/bcLMhf
|
https://qrco.de/bcCFuP| https://qrco.de/bc8vmm
Class II double insulation
High Voltage
Documents / Resources