K-KDU572KVE Drain Up Kit
Drain Up Kit
Installation Manual
K-KDU572KVE
Please read this manual and the air conditioner manual carefully before use.
Safety Precautions
Please read these”Safety Precautions”carefully before performing installation
work.
The precautions shown here are divided into” Warning”and” Caution”,but those
that are likely to lead to serious consequences such as death or serious
injury if installation is performed incorrectly are noted collectively in the
” Warning”area. However,even the items described in the” Caution”area may lead
to serious consequences depending on the situation.Observe all of the
following,as each contains important information regarding safety.
After the installation work is complete,perform a test run and check that
there are no abnormalities. In addition,please ask the customer to keep this
manual.
Drain position/lift/service space
Hole position on the ceiling(50)
The drain up kit can be installed on the left or right of the air conditioner. The figure below shows the case of installation on the left.
Warning
For drainage of air conditioners. Do not use for any other application.If the
usage application is incorrect,fire/water leakage,etc.may result.
Regarding installation,ask your dealer or a specialist. If you perform
installation yourself and there are imperfections in the installation,water
leakage/ electrocution/fire may result.
For installation parts,be sure to use accessories and parts with the
designated specifications. If parts with the designated specifications are not
used,water leakage/electrocution/fire may result.
Be sure to turn off the power supply before performing installation work.If
electrical parts are touched while the power supply is turned on,electrocution
may result.
Make sure to perform installation work properly
Connect the wire securely using the specified power wire,
according to the installation manual.If there are
and secure it properly so that the external force from
imperfections in the installation,wataer leakage/
the wire is not applied to the terminal connection part.
electrocution/fire may result.
If connections are incomplete or incompletely secured,
For the safety circuit power wire shape the wire so that heat generation/fire at the terminals may result.
the cover does not rise,and install the lid securely.
Install the product securely in a place that can
If the lid is not installed completely,electrocution/fire sufficiently withstand the weight of the kit.
may result.
If the strength is insuficient,injury due to falling
Please perform earthing work.
of the kit may result.
Do not connect earth wire to gas pipes,water pipes,
The power supply should be separate from the air conditioner.
lightning rods,or telephone earth wires.If earthing is If power is branched from the power supply wire of the air
incomplete,electrocution may result.
conditioner,transmission abnormalities/electrocution/fire
may result.
Caution
For drainage work,install the pipes according to this installation manual to
ensure proper drainage,and insulate it to prevent condensation. If there are
imperfections in the pipe work,water may leak and cause household goods to get
wet.
Do not install in locations such as the following. Locations where flammable
gas may leak,locations where carbon fibre and flammable dust float,or
locations where volatile flammable materials such as thinner and gasoline are
handled. If gas leaks and collects around the drain up kit,ignition of fire
may result. Locations where there are machines that generates electromagnetic
waves. It may cause abnormalities to occur in the control system,making normal
operation impossible.
Drain up specifications
Main applicable models
Described below
Insulation
Exterior
White(Munsell 10Y9/0.5) Drain inlet connection pipe diameter
Maximum lift(mm)
1,000 (NOTE 1) Drain outlet connection pipe diameter
Drain discharge flow rate(L/h)
24
Safety device
Power supply Single-phase 220-240V/220V,5060Hz Operation sound(dB)
Power consumption(W)
14.1 12.9
Product weight(kg)
Operation current(A)
0.18 0.16
(NOTE 1) Height from the bottom of the drain up kit to the drain pipe (NOTE 2Connected with the drain hose(accessory) (NOTE 3) Connected to VP20 with the soft drain pipe(accessory)
Type E VP13 (NOTE 2) VP20 (NOTE 3) Float switch
25 3.2
Applicable models
Capacity Indoor unit model name
Low capacity models
FXA202532LVE(C)
FXAQ202532M(A)VE FXAQ202532PV1 FXAQ202532PVE
Capacity
High capacity models
Indoor unit model name
FXA405063LVE FXAQ405063M(A)VE FXAQ405063PV1 FXAQ405063PVE FAY71LVE,FAYP71LV1
FAQ71BUV1B FAQ71BVV1B FAQ71100CVEB
Caution Only the above applicable models can be used. Components
Name
Shape
Quantity Name
Shape Quantity Name
Shape Quantity
Drain up kit
Relay harness
(Green)
1 (Red) 1
Thermal insulation (For drain inlet) 30X130Xt5
Thermal insulation (For drain outlet)
50X180Xt10
Hose clamp
VP20
1 Soft drain pipe
(For drain outlet)
200
1
1
Screw Washer
(White) 1
4
Screw
5 M5X35
Connection harness (White)
Power supply wire (Blue)
Thermal insulation
15X70Xt3
1 Soft socket VP13 80
1
Drain hose 1 (For drain inlet)
Clamp
material
1 Installation
pattern paper
1 Installation
manual
4 1 1
Operation manual
1
Parts required for installation(locally procured)
Elbow
Thermal insulation
Standing drain pipe
(VP20)
Horizontal drain pipe (VP20)
Indoor unit
Refrigerant Downward slope of 1/100 or more pipe
Standing drain pipe(VP20) (Locally procured)
Drain pipe(VP20) (Locally procured)
Soft drain pipe (accessory)
MAX.1000mm
MIN.50mm
( ) Space required for installation
Installation on left or right possible
NOTE 1)Please secure the space required for installation on the left or right
of the air conditioner, and the space required for service around the drain up
kit installation location.
NOTE 2)Local pipe such as PVC pipe cannot be directly connected to the drain
inlet and drain outlet of the drain up kit.Be sure to use the accessories
described in the installation manual.
Preparation before installation
Preparation of the drain up kit
Separate the casing and drain up kit from the mounting plate.
(1)Remove the 1 casing fixing screw and washer,lower the casing,
and then pull it forward to separate it.
(2)Remove the 2 drain up kit fixing screws,and lift the drain up kit
upward to separate it.
Drain up kit lift and separate
Mounting plate
Drain up kit fixing screw
Casing
Washer
Casing fixing screw
Preparation of the indoor unit
For things such as the construction procedure of the indoor unit,refer to the installation manual attached to the indoor unit.
Caution
Be sure to work with the power supply turned off
When connecting terminals to the inter-unit wiring terminal block,
attach them correctly as shown in the figure below. If the crimp terminals are
both installed in the same orientation accidentally,the terminal contact area
will decrease and there will be a risk of overheating and burning.
Lead wire
Screw
Crimp terminal
Precautions for power supply wire/earth wire
Use round type crimp terminals for connecting the inter-unit wiring terminal block and
the earth wire. If you for some reason cannot use round type crimp terminals,
be sure to observe the following items.
Do not connect 2 wires with different diameters to the inter-unit wiring terminal block.
(There is a risk of abnormal heat generation due to loose wires, etc.)
Connect the wire securely using the specified power wire, and secure it so that
external force is not applied to the terminal part. Use an appropriate screwdriver to tighten the terminal
Round type crimp terminal
Power wire
screws. A screwdriver with a head that is too small will
damage the screw heads and make proper tightening impossible.
If the terminal screws are tightened too much, the screws may be damaged.
Refer to the table on the right for the tightening torque of the terminal
screws.
Tightening torque
Inter-unit wiring terminal block
1.181.44
Earth terminal 1.441.94
For the FAY71LVE,FAYP71LV1,FXA202532LVE(C) FXA405063LVE,FXAQ2063M(A)VE
FXAQ2063PV1,FXAQ2063PVE
(1)Connect the relay harness and the power supply wire to the indoor unit.
(a)Remove the front grill according to the instruction manual that came with
the indoor unit.
(b)Remove the service lid. (c)Remove the indoor circuit board assembly
CN15 short-circuit connector and connect the relay harness connector.
(d)Connect the power supply wire to the indoor unit inter-unit wiring terminal
block. The terminal nos.of connection terminals
vary depending on models.Be sure to check the electrical wiring diagram on the
back side when connecting wires. (e)Using the earth connection screw from the
indoor unit,secure the earth wire(locally procured 2 mm2or more copper
wire)between the indoor unit and the drain up kit.
After tightening,trim away the unnecessary portion of the cable tie.
Power supply wire
Clamp material (Attached to the
indoor unit)
For the FAQ71BUV1B,FAQ71BVV1B,FAQ71100CVEB
(1)Connect the relay harness,the connecting harness, and the power supply wire
to the indoor unit.
(a)Remove the connection harness of the relay harness and connect the attached
connection harness.
Connection harness
Connection harness
Relay harness
Remove
(b)Remove the front panel and electrical box lid according to the indoor unit installation manual. [ How to remove the front panel and electrical box lid ]
1. Open the front panel until it stops.
2. Push both the left and right rotation axles of the front panel toward the centre of the main unit to remove the front panel. (You can also remove the front panel by sliding it to the left or right and pulling it toward you.)
3. Remove the screw from the electrical box lid and pull it
toward you using the tab to remove it.
Electrical box lid
Rotation axle
Front panel Rotation
(1)
axle
(2)
(2)
Rotation axle
(3)Screw Tab
4. Remove the front grille by following the directions described in the installation manual for the indoor unit. In the case of FAQ100CVEB,remove the griile retaining fixtures.
Coin,etc.
Screw position(locations)
Remove the fixtures at the bottom of the front grille with something such as a coin.
Grille fixture position (locations)
Front grille fixture position of 100-class unit
(c)Remove short circuit connector X15A on the indoor unit circuit board and connect the relay harness connector.
FAQ71100CVEB
Float switch connector (X15A)
Short circuit connector
Relay harness
Unit other than FAQ71100CVEB Float switch connector (X15A)
Relay harness
Short circuit connector
Clamp material
Connector
X15A connector side Clamp material
(Clamp material attachment position)
(d)Connect the power supply wire to the indoor unit inter-unit wiring terminal
block.
The terminal nos.of connection terminals vary depending on models.
Be sure to check the electrical wiring diagram on the back side when
connecting wires.
(e)Using the earth connection screw from the indoor unit,secure the earth wire
(locally procured 2 mm 2or more copper wire)between the indoor unit and
the drain up kit.
Power supply terminal block
Put the inter-unit wire and earth wire together,then tighten.
After tightening,trim away the unnecessary portion of the cable tie.
Earth terminal
Clamp material
(Attached to the indoor unit)
Earth wire
Clamp material
(Attached to the indoor unit)
Earth wire Power supply wire
Power supply wire
N P F1 F2
(2)Take out the relay harness,power supply wire,and earth wire from the back of the indoor unit,and return the indoor unit to its original position.
Switch box
Earth wire (Locally procured product)
Relay harness Power supply wire
(3)Decide on which side of the indoor unit you’d like to install the drain up
kit,and perform the following steps.
1.Take out the drain hose attached to the indoor unit. If installing the drain
up kit on the left,move the indoor unit drain cap to the right side and re-
attach it. For how to move and re-attach,check the indoor unit installation
manual.
Drain cap Move and re-attach when installing on the left
Indoor unit dirain hose Take out
C a u t i o n If installing the drain up kit on the left,be sure to move the
indoor unit drain cap to the right side and re-attach it. If you forget to re-
attach it,water will leak.
(4)Cut out and remove the covering of the indoor unit pipe outlet on the
installation side of the drain up kit with something such as a cutter.
Pipe outlet (Cut out either one)
(5)Attach the drain hoseto the drain pan socket of the indoor unit.
3P635301-1
X5A X4A X3A
1 m or less
(6)When installing the drain up kit right next to the indoor unit, cut the
drain hose with a something such as a cutter to dimension A and dimension B
below(in that order).
Dimension B may not be as specified depending on the size of the indoor unit
pipe outlet,so use dimension B as a guide only.
If you want to install the drain up kit at a distance from the indoor
unit,adjust the distance using hard PVC pipe(VP13)and the soft socket.
Cut (Indoor unit socket side)
Drain hose
An arrow is stamped showing the direction of drain water flow
Dimension 40mm
Arrow view
Hose clamps (accessory)
Indoor unit
Cut (Drain up kit side)
Dimension 50mm
(Dimension of protrusion)
Arrow view
Soft socket (accessory)
Hard PVC pipeVP13 (Locally procured product)
Thermal insulation (Locally procured product)
When installing at a distance from the indoor unit
Installation of mounting plate and tentative placement of Drain Up Kit
(1)Install the indoor unit with the drain hose attached as it is. (2)Secure
the installation pattern paper with something such as tape,
using the side and bottom of the indoor unit as a guide.
Drain hose Attached as is
Installation pattern paper Secured with tape etc.
(3)Install the mounting plate of the drain up using the installation pattern
paper as a guide.
Using screws,attach at 4 or more locations.
After installation, remove the installation pattern paper.
Mounting plate fixing hole (Secure at 4 or more locations)
Mounting plate
Installation pattern paper
(4)Insert the drain hose into the hose clamp. Work will be easier if you
orient the hose clamp so that it can be tightened from below.
(6)Insert the drain pan socket of the drain up kit into the drain hose, then
place it tentatively by hooking it on the tabs (3 locations) of the
mounting plate. Do not tighten the hose clamp until wiring work is completed,
and
do not screw it to the mounting plate. Wiring work may be difficult. (7)Remove
the circuit board cover.
Circuit board cover
Tabs (3 locations)
Mounting plate
Drain up kit
Drain pan socket
Installation of relay harness/connection harness/power supply wire
Caution Be sure to work with the power supply turned off
Electrical wiring diagram
Drain up kit
Circuit board DS1
P1
NOTE 3) K2R
Float switch
P2 (For operation)
X2A X6A
M1P
Drain up
Float switch (For abnormalities)
Air conditioner stop signal
Relay harness (NOTE 2)
Indoor unit
Indoor printed circuit board
X15A or CN15
Refer to the following applicable models for connection
Power supply wire
Locally procured
The earth wire (copper) must be 2 mm² or more or 1.6 mm or more.
Applicable models
FAY71LVE FAY71LV1
Connection X2M diagram Tes2
123
FXA2032LVE(C) FXA4063LVE FXAQ2032M(A)VE FXAQ4063M(A)VE FXAQ2063PV1 FXAQ2063PVE
FAQ71BUV1B FAQ71BVV1B
FAQ71100CVEB
LN
123
1 23
X2M
X2M
X2M
When connecting the relay harness, remove either the CN15 or X15A short
circuit connector. NOTE 1) Be sure to turn on the drain up kit power supply.
If the power supply is not turned
on, the air conditioner will stop abnormally and operation will not be
possible. NOTE 2) The relay harness cannot be extended. (It may malfunction
due to noise) NOTE 3) When the power supply is turned on, the K2R contact
closes and becomes a
non-voltage constant B contact.
(1)Lay the relay harness, power supply wire, and earth wire in the indoor unit
piping space.
(2)Connect the relay harness to the circuit board connector (X6A) of the drain
up kit
(3)Connect the power supply wire to the circuit board connector (X1A) of the
drain up kit.
(4)Secure the earth wire (locally procured 2 mm² or more copper wire) to the
drain up kit using the earth connection screw.
Bundle excess harness with a clamp material .
Earth wire
Hose clamp
(5)When installing the drain up kit on the right, move the drain plug and
thermal insulation sleeve of the drain up kit to the left side and re-attach.
(Not required in case of left installation)
Thermal insulation sleeve
Drain plug
Thermal insulation
sleeve
Hex wrench
Clamp material
Relay harness Power supply wire
(5)Secure the relay harness with a clamp material. (6)Wrap the thermal
insulation around the relay harness.
(To ensure protection, wrap it so that there is no gap between the relay
harness and the circuit board cover) (7)Check that the DIP switch (DS1) on the
circuit board assembly of the drain up kit is set to P2 and (DS1) is set to
P1. (8)Attach the circuit board cover. (9)Secure the relay harness, power
supply wire, and earth wire (locally procured) with a clamp material.
(10)Connect the earth wire. Be sure to perform Class D earthing work. The
earth resistance value should be 100 ohms or less.
DS1 P1 P2
H/F b/a
X1A
Power supply wire Circuit board cover notch
Circuit board Relay harness
Power supply wire Connector (X1A)
Secure with a clamp material
Relay harness (X1A)
Circuit board cover notch
Thermal insulation (Wrap together with the clamp material)
In case of installation on the left
In case of installation on the right
Earth wire connection Circuit board cover
Circuit board cover Relay harness
Secure with a clamp material
Relay harness
Earth wire
Earth wire
Power supply wire
Power supply wire
Earth wire connection
Secure with a clamp material
Drain up kit installation and drain piping procedure
(1)Install the drain up kit fixing screws (2 pcs) and secure the drain up kit
to the mounting plate.
(2)Tighten the hose clamp around the drain hose. (3)Wrap the thermal
insulation around the hose clamp to insulate it.
Drain up kit fixing screw (2 pcs)
Thermal insulation (Wrap)
Hose clamps (Tighten)
Caution
Local pipe such as PVC pipe cannot be directly connected to the drain
socket.Be sure to use the attached drain hose.
Tighten the hose clamp with a torque of 1.0 to 1.2 Nm.
(4)Connect the outlet pipe. Connect the soft drain pipe to the soft drain pipe
connection port. Tighten the connection between the drain up kit and the soft
socket
with a hose clamp and wrap it with thermal insulation. Be sure to use adhesive
to connect the soft drain pipe and the
local drain pipe in the ceiling.
Caution
Outlet pipe parts are locally procured. Be sure to thermally insulate the
drain pipe. Be sure to make a downward slope (1/100 or more) for the
horizontal
section of the drain pipe so that there will be no trapped air. If the
horizontal section is long, install a support bracket in the middle to prevent
the pipe from sagging. Local pipe such as PVC pipe cannot be directly
connected to the soft drain pipe connection port.Be sure to use the attached
soft drain pipe . Tighten the hose clamp with a torque of 1.0 to 1.2 Nm.
Thermal insulation sleeve Elbow (VP20) (locally (locally procured) procured)
Standing drain pipe(VP20) (locally procured)
Ceiling slab
Support bracket
Soft drain pipe Hose clamp
Secure with adhesive Horizontal drain pipe(VP20) (Downward slope at 1/100 or more)
Thermal insulation
Soft drain pipe connection port
In case of centralised pipe
When branching into one central pipe, follow the procedure shown below to
absolutely prevent water from flowing backward into the unit.
Make this distance as large as possible
Downward slope (1/50 to 1/100)
Use as thick a pipe as possible
Test run
Caution Work with the circuit board cover attached.
Using something such as a tester, check whether single-phase 220-240V/220V,
(50/60Hz) power supply voltage is supplied to the drain up kit. Do not splash
water onto the drain up motor.
Drainage check
Check that the pump operates and drains. When draining, check that there is no
water
leakage from the pipe.
(1)Remove the front cover of the drain up kit and pour water into the drain
pan until the drain pan is about half-full of water.
(2)Turn on the drain up kit power supply and check that the drain up process
works normally and the drain water flow is smooth.
Circuit board cover
Abnormal stop check
Front cover Remove the screw
Float switch (For abnormalities)
Plastic container
(3)Start the air conditioner.
for drainage
(4)Push up the float switch (for abnormalities) for 5 seconds
or more and check that the air conditioner stops.
After checking, reattach the front cover.
Installation of casing
Cut out and remove the covering of the casing pipe outlet with something such
as a cutter.
Install the casing as shown in the figure below and secure it with the fixing
screws and washers.Use the 1 accessory screw and washer when securing the
casing on either the left or the right.
Drain up kit
Casing
Cut along the perforations
Washer Casing fixing screw
Casing fixing screw/washer
(Accessory,1 pc.)
Casing
Check for after installation work is completed
Please check these items again after the construction is completed.
Check item
Check column
Check item
Check column
Are the indoor unit and drain up kit level?
Is the drain pipe pointing downward? (1/50 to 1/100)
Is the drain pipe securely connected? Is there any risk of water leakage?
Is the drain hose insulated properly? Is all the wiring correct?
After the air conditioner test run, perform cooling operation and check the operating sound coming from the drain up kit.
Precautions when operating
The pump will repeatedly stop and start operating due to the action of the
cooling operation float switch.
After cooling operation is stopped, remaining water needs to be discharged, so
do not turn off the power supply immediately.
If turning off the power supply, be sure to wait at least 5 minutes after
stopping operation.If the power supply is not turned off, the drain pump will
stop after about 20 minutes of residual operation.If the safety circuit is
activated, the operation of the air conditioner will stop.
If water leaks from the inside of the air conditioner or the drain up kit
during cooling operation, stop operation immediately.The drain outlet may be
clogged or the safety circuit may not be working properly, so contact your
dealer.
3P635302-1