phocos SPS48D150B Solar Power Supply Controller
DESCRIPTION
The SPSD is designed to control the charging of batteries from photovoltaic panels and to control the load voltage supply for voltage-sensitive equipment. It is designed for use in remote power supply systems for telecommunications or monitoring equipment. The charge regulation and load control voltages are fully adjustable. The display is used to show battery voltage, load voltage, solar array voltage, charge current and load current. On the charge side, two- stage boost/float regulation is used. The regulation voltages are adjustable via the keypad and display. Up to four-stage bank switching can be used which allows taper charging in the boost mode and low-speed switching regulation in the float mode. Coupled with controlled rise and fall time switching, this allows the regulator to achieve very low levels of audio and radio frequency emissions. These low levels of interference make the unit particularly well suited to operation of telecommunication equipment in weak signal areas. A Temperature sensor may be added to compensate for changes in battery temperature. The load disconnect feature forces load disconnection when the battery voltage is too low or too high. The low and high disconnect voltages are adjustable. A load of up to 50 amps can be drawn. The control board uses a microcontroller integrated circuit coupled with a 16 x 2 line liquid crystal alphanumeric display and a 12-key membrane switch keypad. The display and indicators will automatically turn off after 10 minutes if no key has been pressed. Set-up data is stored in non-volatile EEPROM. To protect against program loops or errors, a hardware watchdog timer is used to automatically force a processor reset if an error should occur. The use of a microcontroller allows the unit to collect statistics on the performance of the power supply system. It logs daily charge and discharges amp hours and battery maximum and minimum voltages for 32 days. This makes system performance assessment easier. For adjustment, a sealed membrane keypad is used rather than a set of switches and potentiometers. This eliminates the need for elaborate sealing against high humidity and the risk of settings drifting. A comprehensive set of alarms is provided. Seven user-definable alarm inputs are provided as well as internally generated alarms. Six of these are available via voltage-free relay contact pairs. For more accurate remote control and monitoring, a serial port is available. This allows remote examination of the performance of the system and adjustment of the operating parameters if necessary. It can help reduce the need for high-cost field trips into areas where access is difficult. The serial port can be connected to a modem so that the unit may be dialed up over the switched telephone network. Both RS232 and RS485 ports are provided. The serial port is DC isolated to make connection to other equipment easier. Simple modular construction allows field repair to be done in a short period by changing over modules. Two special test modes can be enabled to help in rapid testing of the unit. The unit is designed to be housed in a cabinet 500H x 400W x 210D mm which is sealed to IP66 standard. The circuit boards have a conformal coating applied and the aluminium parts are either anodized or powder coated. Circuit breakers are provided to protect the batteries against fault conditions. This version of the regulator is positive ground. That is, it switches on the negative side. To guard against lightning, surge protection has been included on the array inputs and the control logic board. High power Transorb diodes are mounted across each bank switch, the load switch and the input to the logic board. All FET gates are protected with zener diodes from each gate to the source. All sense inputs have additional series resistance to help protect them. This operating manual contains a description of the operation of the control cabinet, a set of specifications, an installation guide and a guide to setting the voltage adjustments.
SPS48D150 – SPECIFICATIONS
SPS48D150|
---|---
Nominal Voltage| 48| Volt
Wire entry size maximum (multistrand)| 70| mm²
Regulator| |
Array input voltage maximum| 100| Volt
Solar charge current maximum per bank| 40| Amp
Solar charge current total maximum| 150| Amp
Boost Max. adjustment range| 54~ 68| Volt
Boost cut in voltage range| 48~ 54| Volt
Float voltage adjustment range| 48~ 60| Volt
Supply current maximum| 170| mA
Supply current typical| 60| mA
Array cable entry size maximum| 35| mm²
Output Voltage Control| |
Continuous output current max| 50| Amp
Current overload limit| 70| Amp
Load cable entry size maximum| 35| mm²
Alarm (See section 3.7)| |
Relay contact current (@24V)| 1| Amp
Relay contact voltage| 60| Volt (DC)
Wire entry size maximum| 1| mm²
Alarm Input sense current| 0.5| mA
Alarm Input open contact voltage| 5| V
Environment| |
Operating temperature range (for sealed enclosure)| -15 to +55| °C
Non-failure conditions for short term exposure Altitude
Weight (in c binet)
| -20 to +70
16
| °C
metres kilograms
OPERATION
This section contains a description of the functions of each section in the block diagram.
CHARGE REGULATOR
Charge regulators are used to protect the storage batteries from overcharging.
This particular regulator uses a two-state boost/float type control scheme.
The photovoltaic panels are divided into banks (or sub-arrays). In the boost
mode, all banks are connected so that the full charge current flows into the
battery until it’s voltage reaches the taper voltage (adjustable 52 ~ 68V). As
the battery voltage continues to rise, banks are progressively disconnected
(beginning with bank D) until only one bank is charging. A time delay occurs
between changes in bank connection (adjustable 0 ~ 6 minutes). This is
necessary to allow the new conditions to stabilise and prevent oscillation.
Banks A and B can be paralleled and the unit used as a three-bank regulator by
selecting the 3 bank option in the control set menu. Similarily, in 2 bank
mode A,B & C are paralleled and in 1 bank mode, all four are paralleled. This
tapered charging results in less corrosion of the plates and allows better
charging of batteries in poor condition.
When the battery will sustain the boost maximum voltage (adjustable 54 ~ 68V),
the regulator will switch into float mode. In this mode, the charge current is
reduced to that level which is necessary to keep the battery voltage within a
preset float range (float high and float low adjustable 48 ~ 60V). Floating
the batteries in this voltage range helps to keep them fully charged and
prolongs their life. To eliminate audio interference, the bank switching in
the float mode can be no faster than 1 change per second. When the battery
voltage remains below the boost cut-in voltage (adjustable 48 ~ 54V) for 10
minutes, the regulator will switch back into boost mode and will remain in
boost until the voltage rises again to the boost maximum. The charge current
switching is done with rugged power MOSFET devices. These devices result in a
very low voltage drop across the bank switches when on and enable the unit to
achieve very low operating power dissipation. They are also arranged to as to
block reverse current flow due to panel wiring shorts and solar night loss
currents. This design eliminates the need for reverse-blocking diodes. The
optional temperature sensor is able to compensate for battery temperature
variations over the range 0 ~ 60ºC.
CONTROL PANEL
An 8051 series microcontroller is used to control the unit. Voltages are
measured using a 10-bit A to D converter and the processor compares these
readings against those settings stored in an EEPROM memory chip. (Because the
EEPROM is non-volatile, the settings will not be lost if there is a break in
power.) The controller uses a 16 x 2 line liquid crystal display to show its
information and a 12-key keypad to select which information is displayed or to
alter the settings. (The display is a special extended temperature range
version.). To reduce the effects of noise and transients (or spikes), the
voltage and current measurements are processed through a digital smoothing
filter with a time constant of 0.5 sec.
DISPLAY
The keypad of the SPS charge regulator is as shown in Figure 0-1:
-
DISPLAY ON/OFF
To prevent the display being accidentally left on, the display will turn off if no key has been pressed for more than 10 minutes. To reactivate the display, press any key. -
DISPLAY SELECTION
The functions of the various keys are: -
VOLTAGE DISPLAY
To display the battery or load voltage, press the corresponding key. Because of the smoothing filter, the meters have a settling time of about 1 second. Voltage range 0 ~ 100V, resolution 0.1V. -
CURRENT DISPLAY
To display the charge or load current press the corresponding key. The current is measured by using the built-in current shunts. Display values are filtered as above. The range is 0 ~ 102A, resolution 0.1A. -
SOLAR DISPLAY
The solar display first shows the current from each bank and ‘ON’ if that bank is connected. By pushing the INC button the display will now show the open circuit voltage of the bank. By using the INC and DEC buttons, the user can select which bank is displayed. This feature can be used to check the performance of each bank.
The number in the lower left-hand corner is the regulator state. (See the state transition diagram for an explanation of regulator state numbers) -
REMOTE MONITOR
The remote monitor key allows the user to select the communication speed for the serial remote monitor and control facility and the site number of the controller for use in multistation systems. Use INC and DEC to adjust the site number and the REMOTE MONITOR key to adjust the baud rate. -
VIEW DATA
The view data key allows the user to read the performance data logged by the controller. Each day, the controller measures the total charge amp hours, the total discharge amp hours and records the minimum and maximum battery voltages. These readings are stored in the EEPROM and can be viewed using the VIEW DATA button or via the remote monitor link. 32 days data can be stored. To view the data, press the VIEW DATA button. The first display that appears is the information for the current day in progress. It shows the data collected during that day from midnight on. On the lower line of the display, the first number is the number of the day for which the information is being displayed (0 is the current day). The next number is the minimum battery voltage and then the maximum battery voltage. On the top line, the first number is the charge amp hours and the second the discharge amp hours. By pressing the INC button, the data from the previous day will be displayed (day 1). Pushing INC again will move to the day before (day 2). Further pushes of INC will continue back until day 32 after which it will return to day 0. The DEC button, will move the other way. To leave the status display just press another function key. -
CONTROL SET
This key allows the regulation levels to be set. Each press of the key will access a different setting. Adjust each variable using the INC (increase) or DEC (decrease) keys. Holding down the INC or DEC key will provide the fastest rate of change.
1. Maximum boost voltage. This is the maximum voltage that the regulator will allow the battery to charge to before it changes to the float mode.
2. Taper voltage setting. This is the maximum voltage that the regulator will allow the battery to charge to, before it begins to reduce the charging current. The taper voltage will be less than the boost maximum voltage.
3. Number of banks. Select number of separate banks in use.
4. Float maximum voltage.
5. Float minimum voltage. The regulator will try to keep the battery voltage between these levels. The smaller the gap between the maximum and minimum, the faster the float bank switching will be. For minimum bank switching noise, a gap of 1 ~ 1.5 volts is suggested.
6. Return to boost setting. When the battery voltage drops below this level, the unit will switch from float back into boost mode. (After a delay of about 10 minutes)
7. Temperature Compensation setting. If a temperature sensor is attached, the temperature compensation feature can be enabled. About -5mV/oC/cell is normal. If no temperature sensor is connected, the setting MUST be 0 (zero) otherwise the regulator will assume that the battery is at 0ºC and correct accordingly.
8. Absolute Maximum Battery Voltage setting. Due to the time delays involved in changing from one regulator state to the next, it is possible for the battery voltage to overshoot the boost maximum voltage setting briefly. In some situations, this is not acceptable (e.g. over voltage cut-outs on some inverters) To deal with this problem, the SPSD has an absolute maximum voltage limit. If the battery voltage rises to this limit, each bank turns off within 80 msec.
9. State Change Delay setting. Set time between bank connection changes in boost mode. Adjustable 0 ~ 6 minutes.
10. LCD temperature setting. This is a device to aid in protecting the control unit against condensation due to rapid cooling after a hot day in humid conditions. By using the display backlighting control, it is possible, with the aid of insulation in the top half of the enclosure, keep the display warm enough to keep above the dew point and so keep the display dry. By leaving the bottom section of the control board uninsulated, condensation will occur first in this area, and tend to dry the air inside the enclosure. The control board senses the temperature in the top section of the enclosure and tries to keep it at the set temperature. Because of the limited power available, this will not be possible under very cold conditions, and the facility should be disabled by setting the temperature to 0. This facility should be used ONLY in areas subject to extreme humidity, and only during the wet season. A setting of 35 should be adequate for most conditions.
11. Viewing Contrast. Adjust for best display contrast. (varies with temperature).
12. Time (of day). Set present time of day. The daily data is saved at 0:0 hours each day.
Pushing the control set button again will cause the display to return to the
start of the menu.
Note: The new values entered for controls will not be stored until you
exit from the control set mode. (This is done by pressing any display select
key).
LOAD DISCONNECT SET
This key allows the user to adjust the battery voltages at which the load is disconnected and reconnected and the generator is started.
Load disconnect
When the battery voltage drops below the disconnect setting, the time delay
counter begins. If the battery voltage stays low for the whole time delay then
the load is disconnected. The Load voltage screen indicates that the load is
disconnected. When the battery voltage rises above the reconnect voltage, for
the length of the time delay, then the load will reconnect. As a guide, the
low battery load disconnect voltage should be in the range 44 ~ 47V and the
reconnect level between 50 ~ 54V. The time delay before disconnection is to
prevent false disconnects due to transient loads. Range is 1 to 250 seconds.
As a safety feature, if the load current exceeds the current limit,
disconnection will occur after only 0.3 seconds. The load will also be
disconnected if the battery voltage is too high. The high battery disconnect
voltage is set to be 0.4 Volt above the absolute maximum voltage. It will
reconnect when the battery voltage drops below the boost max voltage.
Generator Start
When the battery voltage drops to the generator start voltage setting, the
time delay counter begins. If the battery voltage stays low for the whole time
delay then the generator start relay contacts will open, indicating that the
generator should start. The generator relay led indicates that the generator
is enabled. When the battery voltage rises above the load reconnect voltage+
0.4V, for the length of the time delay, then the generator relay contacts will
close to indicate that the generator should stop. As a guide, the generator
start voltage should be in the range 44,8 ~ 48V. The time delay before start
and stop is to prevent false operation due to transient loads.
Battery Voltage Alarms
Two battery voltage alarm outputs are provided. These are low battery voltage and high battery voltage. The low battery alarm activates when the battery voltage falls below the generator start voltage – 0.2V. It will turn off again at generator start + 0.2V. The The high battery alarm activates when the battery voltage exceeds the absolute maximum voltage+0.2V. It deactivates below the boost maximum voltage. The high and low alarms are available as voltage free normally closed relay contacts and via the serial port.
METER ADJUST
This allows the various meter scale factors and offsets to be adjusted. The
correction range is limited to ±12%. These are adjusted in the factory and
should not be adjusted without proper measuring equipment. The INC and DEC
keys are used to adjust the value. There are slope and offset adjustments. INC
and DEC control the offset directly. To adjust the slope or gain, hold SOLAR
button down while using INC and DEC. Pushing the METER ADJUST button moves
through the list. At the start of the list, it is possible to enter the two
test modes. TEST MODE A can be selected by pressing the INC button and TEST
MODE B by pushing the INC button twice. Pushing the METER ADJUST key then
starts the test mode. Test mode A is useful for testing correct operation of
the control system. In this mode, the controller works normally, except that
all time delays are reduced to 2 seconds so that changes in state can be
observed without wasting large amounts of time. Test mode B is used for
testing the switchboard hardware. The controller does not operate normally,
but turns the charge switch on, then the load, performs a test write and read
to the EEPROM, cycles regulator through each operating state, sends data to
the serial output and then repeats this. Pressing the INC button will pause
the cycle until the INC button is pressed again. Pressing the DEC button will
terminate the test mode.
LIGHTNING PROTECTION
The lightning protection circuitry consists of transient absorption diodes across the charge switch FETs. Zener diodes are also installed from the gate to the source of each FET to protect the gate oxide. The logic board has a 1.5kW transorb on the input and series resistance on each of the sense leads to protect the ADC.
MANUAL RESET
A manual reset of the controller can be performed from the keypad. Push the METER ADJUST key once. While holding down the SOLAR ARRAY key, press the CONTROL SET key. The controller will now reset.
Clearing The Data Memory
It is possible to clear the 32 day data memory from the keypad. While in the VIEW DATA mode, press the CONTROL SET button and hold down for 1 second. The display now asks if you want to clear the data memory. To clear press the INC button. To not clear, press any other key.
ALARMS
Alarm Inputs
The controller has seven general-purpose alarm inputs. These expect to have
normally closed voltage-free contacts connected to them. When the contacts
open, indicating an alarm, the alarm led will light indicating that alarm is
active and the alarm will be available to be read via the serial port. The
alarm contacts are connected between the common and the alarm input. The alarm
inputs have a 10Kohm pull-up resistor to 5V. The alarm inputs have a 10Kohm
pull-up resistor to 5V. See alarm circuit p16.
Warning: the alarm common is connected to battery negative. It has a
resettable fuse in series with it to prevent damage if it is accidentally
connected to battery positive.
Alarm Outputs
There are six internally derived alarms which are available as voltage-free
relay contacts. The contacts are normally closed and open when the alarm
condition is active. This allows ‘fail safe’ operation because a break in the
cable will cause an alarm. They are also available via the serial port.
These are:
- Low battery voltage alarm (see above for details)
- High battery alarm (see above for details)
- Generator control (see above for details)
- Logic fail alarm. This alarm indicates that the logic power supply has failed or that the logic has not sent the correct information to the alarm. This will give an alarm in many cases of logic failure but it is impossible to detect all forms of logic failure. The logic fail alarm relay is normally energised, so it will give an alarm even if the power supply fails. Please note: the logic fail alarm led (green) is normally ON – this indicates that the logic is OK. If the logic alarm led is OFF then it indicates that the logic fail alarm is active. This is the reverse of the other alarms.
- Load alarm. If the load voltage is more than 1V below the battery voltage and if the battery voltage is less than 50V, then the load alarm will activate. This alarm will also activate if load disconnect has occured (i.e. if Load voltage is less than 16V).
- Solar bank switch fail. This alarm detects the failure of the bank switch blocks. If any bank switch block fails open circuit or permanently on, then this alarm will activate. The failure condition is tested for each 16 minutes. The result of the test is held until the next test is done. Permanently on is detected by switching all banks off and testing for charge current greater than 0.6A. If there is more than 10 amp of total charge current, then the open circuit failure is tested. This is done by by turning each bank on in turn and testing for charge current greater than 0.6A. This will also indicate broken or missing/stolen arrays and damaged wiring.
SERIAL PORTS
The controller has a serial port for connecting to remote monitoring and
control equipment. This serial port is available in two forms – RS232 and
RS485. RS232 communication is done using separate transmit and receive lines
and is unbalanced. The RS232 port has only transmit (TX) and receive (RX) and
Signal Ground connections available. No handshake lines (e.g. CTS,RTS,DSR,DTR)
are used because flow control is done in software. The port has 15kV ESD
protection. RS485 communication is balanced and oriented toward bus operation.
The same pair of wires is used for transmit and receive. The connection has an
inverted and non inverted output. The port is normally high impedance and only
becomes low impedance when it is transmitting. Because many devices can be on
the same bus, there must be a control protocol to prevent two devices talking
at the same time. The SPSD controller uses a master slave protocol – it will
only speak when it is spoken to. To get data from the SPSD controller the
master computer sends a command to the SPSD which includes a site number. If
the received command matches the site number of the controller (set in the
remote monitor screen) then the controller will respond with the data
requested.
The two ports are operated in parallel. It is not necessary to switch between
ports. Connect only the port being used. Both ports transmit the same data and
the received data is logically or-ed. i.e. data can be received on either port
but not at the same time because they will interfer.
To prevent grounding conflicts, the serial ports are optically isolated. The
isolation can withstand 500V.
INSTALLATION
This section provides some notes on installation.
MOUNTING
The cabinet is sealed to IP66 standard and so can be installed outside if necessary. However, it is best if it is under cover and out of direct sunlight.
TEMPERATURE SENSOR
If the temperature sensor is to be used, plug it into the two-pin terminal on the left-hand side of the interface board. The sensor is polarised, but the connecter will not allow the sensor to be connected back to front. so take care to connect the wire with the stripe on it to the T-input as shown. The sensor acts as a current source which is proportional to temperature. This means that the cabling to the sensor can be extended without having to worry about voltage drops along the wire. The sensor must be installed in good thermal contact with the battery case. Do not place the sensor near but out of contact with the batteries. This will give false correction because the air temperature will not be the same as the battery temperature. Good thermal contact can be achieved in the following ways:
- Glue the sensor to the battery case as shown in diagram Figure 0-2.
- Wedge the sensor in the gap between two batteries in the bank with a piece of foam rubber. The foam rubber will hold it against the battery as well as sealing around it.
- Place the sensor against the battery and cover it with a duct tape strip which goes all the way round the battery and wraps back on itself a couple of times. This will prevent it coming undone easily.
- Sit one of the batteries on top of it. A space can be cut in the support shelf and a piece of foam rubber used to hold it against the battery.
- Wedge between the battery and the wall using foam rubber to insulate it from the wall.
Notes:
- It is very important to get the polarity of the battery connection correct! If in doubt, check before connection with a meter or use a current limiting resistor in series with the battery lead until the battery polarity has been shown to be correct.
START UP
Install the regulator with all the circuit breaker switches and the logic board switched off. Turn on the logic board switch first. The small yellow LED should come on indicating logic power is good. The alphanumeric display should also light up and display an identifying logo, the battery voltage. If this does not happen, then check the battery polarity or look for loose connections. Check the plug between the logic board and the control board. When the logic control is O.K., turn on the load/limiter circuit breaker, check that the load current and voltage are correct via the keypad. Finally, turn on the charge circuit breakers. Check each bank in turn using the SOLAR button on the keypad.
BASIC FIELD SERVICE
The SPSD was designed for fast easy field servicing. It uses four standardized circuit boards: the switch block, interface,power supply and control boards. By keeping spares of these boards, repair can be done by replacing the faulty board with a spare and returning the faulty board for base or factory repair. This reduces the need for staff training. The basic field repair procedure is:
-
Step 1
Using the spare control board and keypad, unplug the existing control board ribbon cable and plug in the spare. -
Step 2
Put the controller into test mode B and verify the operation of each bank on the switch block and the interface board. -
Step 3.
If switches are O.K., replace the control board. If not, then install spare interface board and retest. If the switching is now O.K., the interface board was faulty. -
Step 4.
Send the faulty boards back for testing or repair.
SWITCH BOARD TEST PROCEDURE
- Put controller into TEST MODE B by pressing the METER ADJUST button,pressing INC twice then pressing METER ADJUST again.
- Using the INC key, pause the test in Solar Chr. Check that Gen LED is off. Check that the displayed charge current is what should be expected from the bank under the light levels at the time.
- Check that the battery voltage is about the same as the bank voltage.
- Remove pause by pressing INC again, and wait until bank B is being tested. Pause again (by pressing INC) and repeat the current and voltage comparisons for bank B. Check that all LEDs are off.
- Repeat for banks C and D.
- Check that the load current shown is appropriate. Check that the load voltage reading is the same as the limiter output voltage. The additional number at the left of the lower line is the alarm input byte. This shows the values of the alarm inputs that the processor is reading. It is displayed in hex. Alarm 1 is bit 0 and Alarm 7 is bit 6. The bit is 1 when the alarm is active.
- Check the result of the EEPROM test.
- Pause the test in state 0. All banks should have a charge current flowing. The total charge current should equal the sum of the individual bank charge currents.
- Continue to state 4. The banks should switch off starting with bank D until no banks are on (state 4). Current should decrease as each bank is switched off.
- Connect SI to SO to test serial port.
To terminate the test mode press the DEC button.