Lindab OLC Overflow Unit Instruction Manual
- June 4, 2024
- Lindab
Table of Contents
- Lindab OLC Overflow Unit Instruction Manual
- Description
- Maintenance
- Dimensions
- Quick selection
- Materials and finish
- Overflow unit
- Order code
- OLC installed in wall
- OLC with OLCZ installed in wall
- Overflow unit OLC
- Dimensioning diagram
- Element-normalised reduction figure Dn,e
- Technical data Sample calculation
- Example:
- where:
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Lindab OLC Overflow Unit Instruction Manual
Description
OLC is a circular overflow unit for installation directly into a wall. OLC consists of two sound-attenuating baffles, which are mounted on both sides of the wall.
- Discrete design
- Sound-attenuating baffles
Maintenance
The sound attenuation baffles on both sides of the wall can be removed to
enable cleaning of internal parts.
The visible parts of the unit can be wiped with a damp cloth.
Dimensions
OLC Size (Ød)| ØD
[mm]
| *ØU| m
[kg]
---|---|---|---
100| 200| 108-110| 0.8
125| 250| 133-135| 1.0
160| 300| 168-170| 1.2
ØU = Cutout dimension in wall = Ød + 10 mm
Quick selection
OLC Size
Ød
| p t = 10 [Pa]
[l/s] [m 3/h]
| p t = 15 [Pa]
[l/s] [m 3/h]
| p t = 20 [Pa]
[l/s] [m 3/h]
| *D n,e,w [dB]
---|---|---|---|---
100| 19| 68| 24| 86| 27| 97| 49
125| 28| 101| 34| 122| 39| 140| 47
160| 40| 144| 49| 176| 56| 202| 44
- Values valid for cavity wall with 95 mm insulation.
Materials and finish
Installation bracket: Galvanised steel Front plate:
Galvanised steel
Standard finish: Powder-coated
Standard colour: RAL 9010 or 9003, Gloss 30
The OLC is available in other colours. Please contact Lindab’s sales department for further information.
Overflow unit
Accessories
OLCZ – Perforated wall sleeve
Order code
OLC installed in wall
OLC with OLCZ installed in wall
OLCZ optional accessory.
For further information, see OLC installation instruction.
Overflow unit OLC
Technical data
Capacity
Air flow rate qv [l/s] and [m3/h], total pressure loss Δpt [Pa] and sound power level LWA [dB(A)] are specified for a OLC unit on both sides of the wall.
Dimensioning diagram
Element-normalised reduction figure Dn,e
Weighted value (Dn,e,w) evaluated according to ISO 717-1
Cavity wall with 95 mm insulation
Size
[mm]
| ****
125
| Centre frequency [Hz]
250 500 1K 2K
| ****
*D n,e,w
---|---|---|---
100| 32| 46| 46| 48| 54| 49
125| 34| 43| 43| 46| 51| 47
160| 34| 40| 40| 44| 50| 44
Cavity wall with 70 mm insulation
Size
[mm]
| ****
125
| Centre frequency [Hz]
250 500 1K 2K
| ****
*D n,e,w
---|---|---|---
100| 30| 40| 38| 42| 50| 43
125| 30| 37| 37| 42| 49| 43
160| 30| 34| 34| 40| 50| 41
Solid wall without insulation
Size
[mm]
| ****
125
| Centre frequency [Hz]
250 500 1K 2K
| ****
*D n,e,w
---|---|---|---
100| 24| 24| 23| 32| 40| 31
125| 23| 24| 23| 33| 40| 31
160| 24| 24| 23| 32| 39| 30
Technical data Sample calculation
When dimensioning an overflow diffuser, calculate the decrease in the wall’s
noise-reducing properties.
For these calculations, the area of the wall and sound reduc- tion figure R
must be known.
This is adjusted in relation to the unit’s Dn,e value. Dn,e is the unit’s R
value given at a transmission area of 10 m2, as speci- fied in ISO 140-10.
The D n,e value can be converted into the R value for other transmission areas
using the table below.
A rea [m 2 ] | 10 | 2 | 1 |
---|---|---|---|
C orrection [dB] | 0 | -7 | -10 |
The diagram below indicates the decrease of the sound reduc- tion index of the
wall, for a given octave band value (D ) or weighted value ( Dn,e,w ).
As a rough estimate the calculation can be performed directly using the wall´s
Rw value and the weighted elementnormalized level difference Dn,e,w of the
unit.
Example:
(See diagram below) :
Rw (wall): 50 dB
Dn,e,w (diffuser): 44 dB Rw- Dn,e,w = 6 dB Area of
wall: 20 m2
Number of Units: 1 20 m2/1 = 20 m2
Indicated reduction of Rw (wall): 5 dB
Rw value for wall with unit: ~50-5 = 45 dB
The calculation can also be performed using the following for- mula:
where:
- Rres is the resulting reduction figure for wall and
- S is wall
- Dn,e is the unit’s Dn,e
- Rwall is the wall’s R value without unit.
Area of wall [m²] / Number of units [-]
Read More About This Manual & Download PDF:
References
Read User Manual Online (PDF format)