niko 25050 Swiss Garde 360 Premium AP Instruction Manual

June 6, 2024
niko

niko 25050 Swiss Garde 360 Premium AP LOGO

niko 25050 Swiss Garde 360 Premium AP

niko 25050 Swiss Garde 360 Premium
AP 1

Product description

The device detects the movements using a passive infrared sensor (PIR). It reacts most sensitively to movements that are tangential to the monitored area (1a). Movements directly towards the detector have a reduced sensitivity of approx. -50% (1b). The detector does not switch until the brightness drops below the set value (twilight threshold). The switching duration is extended as long as movements are detected (1d). Products that are indicated as accessories are not included in the scope of delivery.

Application

The detector is suitable for indoor or protected outdoor use to control lamps. Adhere to the following during installation:

  • Install only on stable ceilings.
  • Mask moving objects in the monitored area by covering up the lens.
  • Do not place any lamps underneath or next to the detector at a distance of fewer than 1 m away (2a).
  • Do not install in the direct cold (2b) or hot air flows (2c).

Safety notes

Ensure that the electrical lines are de-energized before installation.

**Installation

niko 25050 Swiss Garde 360 Premium AP
2**

H max. Ø 30 m
2 m 20 m
3 m 26 m
4 m 28 m
5 m 30 m
6 m 30 m
7 m 30 m
8 m 30 m

niko 25050 Swiss Garde 360 Premium AP 3
niko 25050 Swiss Garde 360 Premium AP 3 niko
25050 Swiss Garde 360 Premium AP 4 niko
25050 Swiss Garde 360 Premium AP 5

The detector is intended for ceiling installation at a height of 2 to 8 m. The diameter Ø of the monitored area depends on the installation height (1c). Install the detector as follows:

  • Remove the front cover by turning counter-clockwise (4c).
  • Mark and drill holes at the desired mounting site.
  • Pull the cable through the grommet (4a).
  • Attach the detector with the screw/dowel set (4b).
  • Wire the detector according to item 5.

Wiring

The electrical circuit must be protected with a circuit breaker.

Current conduction line L
Neutral conductor N
Switching output relay L’

Connection of loads
High inrush currents shorten the service life of the relay which is integrated in the detector. Adhere to the technical specifications provided by the manufacturer of the lamps and lighting equipment to avoid overloading the relay
(3a–b). To keep the circuit well-arranged, we recommend switching no more than 3–4 detectors in parallel. If there is an above-average number of switching cycles or in case of increased loads, we recommend switching the load via an external contactor.
Configuration
The detector is ready for operation about 1min after mains connection. Parameter changes must be made during operation eighter by adjusting the device’s potentiometers or using the remote control (accessory).

  • Time: TIME determines the delay after the last movement (5b). If the relay
  • output is wired to an automatic staircase switch, set TIME to pulse mode ( ).
  • Twilight threshold: LUX gradually sets the trigger threshold of the
  • twilight sensor between Z day mode and 4-night mode (5a).
  • Range: SENS sets the detection range of the PIR sensor (5c).

Note: The values can be increased by turning the knob clockwise.

Display

Status LED indication Duration
Start-up approx. 1 min, short flashes
Parameter change 3x short flashes
Movement detection 1x long flash

The following statuses are indicated by the LED. Parameter changes can be made at the detector’s potentiometers or by using the remote control (accessory). When a parameter change is confirmed, the detector briefly switches off the relay output.

Troubleshooting

The switching output does not switch: The switching output switches too frequently:

  • Twilight threshold too high
  • Check the lamp/fuse protection
  • Reduce the range
  • Cover the lens
  • Twilight threshold too low

Technical data

Supply voltage 230 V ~ 50 Hz

Switching power

| max. 2300 W, 10 A (cos j = 1.0)

max. 1150 VA, 5 A (cos j = 0.5)

LED 350 W

Detection area| 360°
Detection range| max. 26 m at 3 m height
Installation height| 2–8 m
Lux level control| 5–2000 lx
Timer control| Pulse, 10 s to 20 min
Protection class| II
Protection type| IP55
Temperature range| -20 to +55 °C
Dimensions (L x W x H)| Ø 125×75 mm
Connection terminal| Ø 1.5 mm