niko Swiss Garde 300 Presence Detector KNX/KLR Instructions
- June 6, 2024
- niko
Table of Contents
SWISS GARDE 300 PRESENCE DETECTOR KNX/KLR
APPLICATION DESCRIPTION
SG300P KNX/KLR
25240 / 25251CH / 25252CH
FUNCTIONAL DESCRIPTION
The SWISS GARDE 300P KNX/KLR Type No. 25240 D (CH) is a 4 channel presence
detector for wall mount indoor installation.
The SWISS GARDE 300P KNX/KLR Type No. 25241, 2542 are for outdoor wall mount
installation with enhanced temperature range. They provide IP55 protection.
The device is based on a modern 16-bit microcontroller with internal flash
memory and an integrated KNX/EIB bus coupler.
Three pyro detectors and a high-resolution lens can detect the smallest
motions.
The 3 PIR sensors can be activated individually or in groups.
An integrated light sensor with linear output measures brightness. Its built-
in optical filter has a spectral response similar to that of the human eye.
All models covered can be configured as a master or as a secondary device.
The presence detector has a 2-channel constant light controller (CLC) with a
parametrizable offset between -50% to +50%. There is an additional light
channel output for switching, dimming or scene selection.
An additional HVAC channel can be used for HVAC controls, alarm systems or
presence detection.
With the standard KNX bus, all switching and control functions can be easily
programmed and executed.
The application description is valid for devices with the program version 2.4.
Functional enhancements and changes from program version 2.7. are described in
the chapter 5
Model Overview
Description | color | E-No. | EM-Nr. | Art.-Nr |
---|---|---|---|---|
Swiss Garde 300 Presence KNX/KLR UP | white | 305401209 | 3505100252405 | 25240 CH |
Swiss Garde 300 Presence KNX/KLR UP | white | 305401209 | 3505100252405 | 25240 D |
Swiss Garde 360 Presence KNNLR IP55 UP | white | 305401309 | 3505100252412 | 25241 |
Swiss Garde 360 Presence KNX/KLR IP55 AP | white | 205401309 | 3505100252429 |
25242
Swiss Garde 300 presence detector KNX/KLR, STANDARDdue 050| white| 305401219|
3505100252511| 25251 CH
Swiss Garde 300 presence detector KNX/KLR, STANDARDdue 050| black| 305401819|
3505100252528| 25252 CH
1.2. Dimensions
COMMUNICATION OBJECTS *
input objects
output objects
Object | Function | link application with | Bit/Byte | |
---|---|---|---|---|
0 | Output – light (preset dimming) | light group actuator | 1 byte | |
0 | Output – light (switching) | light group actuator. | 1 bit | |
0 | Output – light (scene) | light group actuator | 1 bit | |
1 | Input external switch / status – light (switching) | KNX switch, touch | ||
display, logic | 1 bit | |||
2 | Input external motion – light (switching) | Output – light for secondary | ||
unit (object 0) | 1 bit | |||
3 | Input – light (forced control) | •External logic module | 2 bit | |
3 | Input – light (lock) | KNX switch, touch display, logic module | 1 bit | |
4 | Output – HVAC (switching) | •Actuators for HVAC devices such as heating, |
ventilation, and air conditioning
•Control of alarm logic modules
•Presence function| 1 bit
5| | External switch / status – HVAC (switching)| KNX switch, touch display,
logic| 1 bit
6| | External motion – HVAC (switching)| Output HVAC for the secondary unit
(output object 4).| 2 byte
7| | Input – HVAC (forced control)| External logic module| 2 bit
7| | Input – HVAC (lock)| KNX switch, touch display, logic| 1 bit
8| | Threshold switch brightness (switching)| Logic, actuator| 1 bit
9| | Brightness (lux value)| Logic, touch display| 2 byte
10| | AD calibration value| Readout and then set manually for the calibration
procedure| 2 byte
16| | Constant light control, switch on/off| KW( switch, logic| 1 bit
17| | Constant light control, dimming relative| 4 bit dimming object from KNX
switch for OWOFF, dimming up and down, touch display| 4 bit
18| | Constant light control, preset dimming| Logic module| 1 byte
20| | Constant light control, forced control| KNX button, logic| 1 bit
21| | Constant light control, scene selection| Logic module| 1 byte
22| | Constant light control, channel 1 – output| Dimming actuator for light
group 1| 1 byte
23| | Constant light control, channel 2 – output| Dimming actuator for light
group 2| 1 byte
24| | Light – standby| Switching of standby value sets| 1 bit
- Communication objects program version v2.4
PARAMETERS
To set the parameters, the SG360P KNX/KLR RA/EA motion detector should be
highlighted in the configuration or operating mode and the command Parameter
be selected from the Edit menu item or via the context menu (right mouse
click). The Edit parameter… window will open with multiple tabs.
3.1. General
Type of detector
The function of the detector is set as a master or secondary (slave) device
Delay time for forced control mode
The value “Of” or a time of 5 min to 9 hrs can be selected in the reset time
forced control menu. This parameter defines the time delay for the detector to
reset to AUTO
mode, after an OFF or ON command, has been executed.
3.1.1. Secondary Detector Mode
Secondary Detector Mode (Slave Mode)| The secondary detector mode can be
reached in the menu General: click the type of detector as slave and the menu
slave mode appears. The delay time of the secondary unit is fixed to 30 sec.
---|---
LED green| For testing purposes, the indication LED for motions can be
activated.
Value of object| Selectable ON or OFF
Idle time after switch off| Can be set from 1 sec to 60-sec Default value is 5
sec
Cyclical transmission| We recommend retriggering the Master unit cyclically
when operating in the Master/Secondary Detector mode. The interval time for
cyclical transmission can be set from 1 second to 4 hours.
The default value is 30 sec
PIR evaluation|
Active sensors| The 3 PIR sensors can be enabled individually or in groups.
The numbers 1, 2, and 3 correspond to positions 1, 2, and 3 as shown in the
illustration (§3.6).
Sensitivity setting| The sensitivity can be adjusted from 1 to 10.( 1 = min,
10 = max) The default value is 5.
3.2. Light – Switch / Dimming / Standby values
The operating mode of the detector| Sets the operating mode to be fully or
semi-automatic.
---|---
Green LED| This LED may flash once after each motion detection or remain off
Delay time| The delay time for the light channel can be set from 1 sec to 4
hrs
Brightness below which sensor is active| Set lighting value from 10 Lux to
2000 Lux and always.
Important: If the light channel always remains active ( even with values >
2000 lux. the parameter must be always.
Brightness above which lighting is turned off| Brightness threshold (lux) for
immediate switch-off, even if delay time has not yet elapsed. The default
value is OFF.
Forced control object or disabled object| This will set object 3. See
description of object 3: force control mode — lock mode (§3.6)
2524X/2525XCH
If locked object = 0| Selects an action to be executed after reception of a 0
command
---|---
If locked object =1| Selects an action to be executed after reception of a 1
command
Object type for output – light| This will define object 0. The following
options are available: switching, dim completely, scene selection
Object value for ON when the object type is: light = switching
light = dimming
light = scene| Select ON or OFF (ON is default value) Select preset dim value
from 0% to 100% Select scenes from 1…32
Object value for OFF when object type: light = switching
light = dimming
light = scene| Select ON or OFF (OFF is default value) Select preset dim value
from 0% to 100% Select scenes from 1…32
Transmission conditions for switching object| Transmission filter for output
object 0: Output – Light – Switching Selection: ON and OFF; neither ON no OFF;
only ON; only OFF
Transmission conditions for external switch| Selection: ON and OFF; neither ON
nor OFF; ON only; OFF only
Idle time after switch off| Can be set from 1 sec to 60 secs
Applications:
Prevention off bus traffic excess
Prevention of erroneous lighting restarts if:
•light bulbs are cooling down
•room is deserted after switching off with a KNX switch.
Cyclical transmission| If the light channel is in switching mode, it is
possible to cyclically transmit the ‘ON” mode. The interval time for cyclical
transmission can be set from 1 second to 4 hours.
3.2.1. Light – Preset Dimming
Object type for output-light
Preset dimming This setting enables the standby light function. The
Standby value option appears in the Light menu.
3.2.2. Light – Standby parameters
Standby values| Toggles the orientation light function between active and
inactive
---|---
Standby time 1| Set orientation light 1 duration time (seconds, minutes,
hours).
Standby value 1| Set light intensity in % (0…100%)
Standby time 2| Set orientation light 2 duration time (seconds, minutes,
hours).
Standby value 2| Set light intensity in % (0…100%)
Standby light
If the light channel is set to preset dimming, a new menu will appear to
enable the standby functionality.
There are 2 parameters for both the duration time and the light intensity (%)
of the standby operation.
After the regular duration time has elapsed the standby light will turn on.
With object 24 the user will then be able to select one of two presentable
parameter pairs. If the object value is 0 or there was no command received
yet, value pair 1 is enabled. A 1 command value will trigger pair 2.
After standby has elapsed, an OFF command will be sent on the light channel.
The motion detector will return to regular mode and standby mode will be
reset.
Lock commands and forced control commands will always reset standby mode
immediately.
3.3. HV AC
| All parameters are identical to those of the light channel with the
exception of:
---|---
Number of monitoring time windows| The number of monitoring time intervals can
be set from 1 to 32.
Duration of the monitoring time window| Adjustable from 1 s to 30,000 s
(8.33h)
Note!| The correct setting for the fastest response of the HVAC channel is:
Number of monitoring time windows: 1
Duration of monitoring time window: 1 second
Presence function with HVAC channel| I the above parameters should be used for
the presence function (the presence signal is independent from the ambient
lighting brightness!)
3.4. Brightness/threshold switch / Value calibration
2524X/2525XCH
| The parameters for object 8 (Brightness threshold switch, 1 bit) and object
9 (Brightness value, 2 bytes) can be set in the Brightness / Threshold menu.
---|---
Transmission of the lux value in case of change of| This parameter allows the
lux value + change to be sent via object 9 (brightness value) ft the set
threshold is exceeded. Values from 10 lux up to 1800 ha and “OFF” can be set.
The set value of change refers to the set threshold.
Cyclical transmission of the light value| Values from 5 seconds to 30 minutes
and,, OFF” can be set.
Lux value of the threshold for switching| Can be set from 10 lux to 2000 lux
Hysteresis| Can be set from 5 lux to 200 lux
Object value for ON| Selection: “ON’ or “OFF’
Object value for OFF| Selection: “OFF” or “ON”
Transmission filter| Selections: “ON and OFF”; “neither ON nor OFF”; “ON
only”; “OFF only”
3.5. Brightness value calibration
Calibration| ‘NO”: Factory calibration is enabled (default value)
Reset to factory calibration: This is possible at any time with the setting
110″ and thereafter the reprogramming of the detector. ‘YES’: This option
opens the following two additional windows:
---|---
Al) calibration value| Head AU calibration value (at <— object 1 U) in the EIS
and enter it in the window.
Attention: use type 7.001 unsigned 2 byte counter in the read/send value menu!
The AD value read-out then appears in the Value received menu (e.g. 739
pulses).
Lux value| Measure reference brightness with lux meter and enter a
corresponding value.
| See also a description of “AD calibration value” on §4.4 for further
details.
3.6. PIR evaluation
Active sensors| The 3 RR sensors can be enabled individually or in groups. The
numbers 1, 2, and 3 correspond to positions 1, 2, and 3 as shown in the
illustration below.
---|---
Sensitivity setting| The sensitivity can be adjusted from 1 to 10. (1 = min,
10 = mmg The default value is 5.
Numbering of the PIR sensors
The PIR sensors 1, 2 and 3 can be enabled individually or in groups of two.
The 3 positions of the pyro detectors are visible in the above illustration.
3.7. Constant light control
3.7.1. Constant light scenes
3.8. Constant light parameters
Constant light controller| This parameter enables or disables the constant
light controller.
---|---
Channel 2 for constant light control| Channel 2 can be enabled for constant
light control
Active/inactive Via the output object 23 a configurable value with a fixed
offset can be transmitted
Preset setpoint| The preset setpoint in lux for constant light control can be
preset in the ETS. It can also be changed via objects 17 and 18 (constant
light – dimming relative and constant light – dim completely).
Transmit difference| This parameter (from 1% to 100%) defines the tolerance
window to be exceeded in order to send a new brightness control value.
Switching constant light control with| Switching constant light control ON/OFF
can be done using three different sources:
By object 16, presence detection on the light channel or presence detection on
the HVAC channel.
The time interval for cyclical transmission| Defines the cycle time interval
with which the last brightness value is repeated, even if it has not exceeded
the tolerance window. Cyclical transmission can also be disabled.
Switch on the brightness value| The switch-on value for the lighting can be
set from 1% to 100 %.
Switch on timeout| This parameter defines the initial time delay before
constant light control is started.
Offset for channel 2 *| The offset range for channel 2 can be set from -50%,
0% to +50%.
Force control during switch-on| This parameter allows the constant light
controller function to be set to no reaction, minimum brightness, maximum
brightness
Force control during switch-off| This parameter allows the constant light
controller function to be set to no reaction, minimum brightness, maximum
brightness
Time for relative dimming| This parameter allows the relative dimming time to
be set. This will influence the dimming soft control.
Take over set point after| This parameter allows setting the time delay after
which a new setpoint will be recognized and stored in the RAM memory.
Changed setpoint to flash memory| This parameter allows a new set point to be
written to the flash memory.
Keep the changed set point| Here at Yes the changed value is stored in the
RAM.
Attention: now corresponds to the new nominal value of the last new dimmed
brightness!
Scene| Various lux values can be set as light scenes (light moods). These can
be enabled through object 21 as well.
Dead zone| The dead zone is an area within which the actual light value can
change without generating new control commands. The default value for the dead
zone is 2. The lux value tolerance of the dead zone can be extracted from the
table below.
Example:
Dead zone value = 2
Brightness = 500 lux
The resulting tolerance is: +/- 24 ha
This means that the actual value can change from 476 lux to 524 lux without
sending new control inputs to the actuator.
- In addition to the previous constant light control channel 1 (Object 22 ) there is a second constant light control channel 2 (Object 23 ). The control signal of channel 1 ± offset value is sent to the dimming actuator for light channel 2. Internally, the control range has been extended to ± 150% in order to maintain a reasonable control range at the limits.
That means: Offset at -50%, darkness: FF (=100%) is sent to both objects. Internally, object 1 is at 150% and object 2 at 100%. If the ambient brightness now increases, object 1 remains at 100% (150% – x), and object 2 is regulated downwards (150% – 50% – x). If the regulation now drops below 100%, object 1 will also be visibly smaller on the bus, e.g. 73%, object 2 23%. Object 1 is then regulated down to 0 and object 2 is set to the minimum value of 50%. The values for transmission difference and cyclical transmission are taken from the once-off available parameters.
3.9. Dead zone/Brightness correlation
Brightness in lux, +/- lux tolerance (dead band)
| Dead zone r I
---|---
1| 2| 3| 4| 5| 6| 7| 8| 9| 10
Brightness| 100| 2| 5| 7| 10| 12| 15| 17| 20| 23| 26
200| 5| 9| 14| 19| 24| 30| 35| 40| 46| 52
300| 7| 14| 21| 29| 37| 44| 52| 61| 69| 78
400| 9| 19| 29| 39| 49| 59| 70| 81| 92| 104
500| 12| 24| 36| 48| 61| 74| 87| 101| 115| 129
600| 14| 28| 43| 58| /3| 89| 105| 121| 138| 155
700| 16| 33| 50| 68| 85| 104| 122| 142| 161| 181
800| 19| 38| 57| 77| 98| 119| 140| 162| 184| 207
900| 21| 42| 64| 87| 110| 133| 157| 182| 207| 233
1000| 23| 47| 72| 96| 122| 148| 175| 202| 230| 259
1100| 26| 52| 79| 106| 134| 163| 192| 222| 253| 285
1200| 28| 57| 86| 116| 146| 178| 210| 243| 276| 311
1300| 30| 61| 93| 125| 159| 193| 227| 263| 299| 337
1400| 33| 66| 100| 135| 171| 207| 245| 283| 322| 362
1500| 35| 71| 107| 145| 183| 222| 262| 303| 345| 388
1600| 37| 75| 114| 154| 195| 237| 280| 324| 368| 414
1700| 40| 80| 122| 164| 207| 252| 297| 344| 391| 440
1800| 42| 85| 129| 174| 220| 267| 315| 364| 414| 466
1900| 44| 90| 136| 183| 232| 281| 332| 384| 438| 492
2000| 47| 94| 143| 193| 244| 296| 350| 405| 461| 518
FUNCTIONAL BLOCKS
The functionality of the presence detector can be split up into the following blocks:
- Motion detection
- Brightness measuring
- Light control channel Switching
- Light control channel preset dimming with optional standby light function
- The HVAC control channel (with presence function)
- Lighting dependent threshold switch
- 2 channel constant light control
The motion detector and the brightness sensor (lux) each work independently on
the light channel and the HVAC channel.
The constant light controller receives the actual brightness value from the
Lux sensor. The controller can be switched on/off by a command via object 16
or triggered by motion detection on the light or HVAC channel. After switching
or recovery of the KNX bus voltage, the presence detector usually generates a
switch-on procedure.
4.1. Light control channel
The light control channel has two operating modes that can be selected via the
detector operating mode parameters.
The possible settings are:
- fully-automatic
- semi-automatic
The differences between the fully-automatic and semi-automatic modes are:
- the fully-automatic mode has three operating conditions: ready, active, and passive
- the semi-automatic mode has two operating conditions: ready and active
- the semi-automatic mode does not switch the light on after motion has been detected.
Lighting can only be switched on manually by an external KNX switch.
4.1.1. OBJECT 0 OUTPUT – LIGHT – SWITCH
Output 1 bit
After each detected motion this output sends an “ON” command and starts the
delay timer
The delay time can be set with a parameter delay time from 1 second to 4
hours.
At the end of the programmed time interval, an “OFF” command is sent to the
output (object 0).
4.1.2. OBJECT 0 OUTPUT – LIGHT – COMPLETE DIMMING
Output 1 byte
This mode sends preselected dim values (0% to 100%) to the output for
objective value for ON and for objective value for OFF respectively.
4.1.3. OBJECT 0 OUTPUT – LIGHT – SCENE
Output 1 byte
For the Objective value for ON or Objective value for OFF, one of 32 scenes
can be selected respectively.
4.1.4. OBJECT 1 EXTERNAL SWITCHING / STATUS – LIGHT – SWITCH
Input 1 Bit
Input object 1 external switch/status can be used in two different ways:
- As input for an external push button that directly switches on the light
- As input for monitoring the status or the input of an actuator
In both cases, a received telegram „ON“ sets the detector to the ON state and
an „OFF“ telegram to the ready state.
Whether commands for ON or OFF will be sent during the transitions depends on
the parameter sending conditions for the external push button.
After having received an ON command, the follow-up timer starts as if a motion
had been detected.
Lighting is subsequently switched off again.
After having received an OFF command the detector remains in its passive
status during which it will not detect any motion. After having passed the
idle time after switching off, the detector is ready again.
The idle time after switch-off can be programmed in the light menu.
4.1.5. OBJECT 2 EXTERNAL MOVEMENT – LIGHT – SWITCH
Input 1 Bit
Additional (secondary) detectors can be connected through Object 2 “external
movement – light – switching”.
The received signal from external presence detectors is processed the same as
if from its own detector and works in parallel.
Object 2 is used to set up a Master-Secondary detector configuration as
follows:
Secondary devices: Connect all outputs of the secondary devices ( object 0 )
to the input external movement-light-switching (object 2 ) of the master
device.
4.1.6. OBJECT 3 INPUT – LIGHT – FORCED CONTROL / LOCK
Input 2 Bit
The meaning of this object is defined by the Light forced control object or
disabling object parameter.
Forced control object:
Object 3 when used as a forced control object has 3 values that can be
received by a 2-bit command:
1. Forced control object ON (control = 1, value = 1)
An ON command is sent unconditionally to the output – light (object 0).
The follow-up timer is disabled and the timer release time starts.
If after having terminated the release time and no further command is sent to
the forced control object, normal operation is resumed.
2. Forced control object OFF (control = 1, value = 0)
An OFF command is sent unconditionally to the output – light (object 0).
The delay timer is disabled and the timer release time starts.
If after having terminated the release time and no further command is sent to
the forced control object, normal operation is resumed.
3. Forced control object auto (control = 0, value = 0)
Normal operation is resumed immediately.
Locked object:
Object 3 when used as a locked object has 2 values which can be received by a
1-bit command 0 and 1:
The response to a switch command on this object is controlled by two more
parameters:
Light if locked object = 0, and Light if locked object = 1,
Both parameters can specify one of the following commands:
- forced control ON
- forced control OFF
- automatic
- lock (actual state)
- do nothing
Note: Incorrect settings of parameters such as: locked object, lock at 0
and no action at 1 and release time restraint OFF can completely inactivate
the correct function of the presence detector.
4.2. HVAC channel
Output 1 bit
The HVAC channel has the same objects and the same operating modes as the
light channel. It works the same way as the light channel as well.
The motion detection function, however, has been expanded and substituted by a
“longer presence detection”. This is done by setting several equally long
monitoring time windows. At least one motion
detection must occur during each time slot.
The parameters are:
- number of monitoring time windows
- length of the monitoring time window (s)
Presence function
The HVAC output can be used as presence detection. To activate this, the
number of observation time windows must be set to 1 and the length of the
observation time window set to 1 second. The presence the signal is
independent of the ambient light level.
4.2.1. OBJECT 4 OUTPUT – HVAC – SWITCH
Output 1 bit
Object 4 “Output – HVAC – Switch” is similar to object 0 “Output – light –
switch” but has additional functions (see HVAC parameters, page 10).
4.2.2. OBJECT 5 EXTERNAL SWITCHING / STATUS – HVAC
Input 1 Bit
Object 5 “External switching / status – HVAC” is identical to object 1
“External switching / status – light”.
4.2.3. OBJECT 6 EXTERNAL MOVEMENT – HVAC
Input 1 Bit
Object 6 “External movement – HVAC – switch” is identical to object 2
“External movement – light – switch”.
4.2.4. OBJECT 7 INPUT – HVAC – FORCED CONTROL
Input 2 Bit
Object 7 “Input – HVAC – forced control” is identical to object 3 “Input –
light – forced control”.
4.2.5. OBJECT 7 INPUT – HVAC – DISABLE
Input 1 Bit
Object 7 “Input – HVAC – disable” is identical to object 3 “Input – light –
disable”.
4.3. BRIGHTNESS THRESHOLD SWITCH
This block has two output objects: Threshold switch and brightness value
4.3.1. OBJECT 8 THRESHOLD SWITCH BRIGHTNESS – SWITCHING
Output 1 bit
Output object 8 sends an “ON” if the measured brightness is greater than the
Value for switching the threshold value switch parameter. If the measured
brightness drops below the Switch-on threshold value – (minus) the
Hysteresis parameter, an “OFF” is transmitted.
4.3.2. OBJECT 9 BRIGHTNESS VALUE
Output 2 bytes
Output object 9 sends the current measured brightness value in lux. The
transmission is triggered by changes that are greater than the parameter
Transmission of the light value in case of a change of or cyclically with the
time stipulated for Cyclical transmission of the light value.
If the cycle time is set to “OFF” there will be no cyclical transmission.
4.4. AD calibration value
Output 2 bytes
Object 10 is not transmitted autonomously. It can only be read. Its unsigned
16-bit value represents the momentary value of the AD converter for the
brightness measurement.
The brightness measurement can be calibrated as follows:
-
Measure the incident light – on a desktop for example – with an external lux meter. This represents the reference lux value.
-
Read out the AD calibration value (communication object 10) in the ETS.
Note: In the menu Read/send value, use type 7.001 unsigned 2 byte counter! The AD value read then appears in the Value received menu as 739 pulses, for example. -
With full access, enter the two values Lux value and AD calibration value as parameters.
4.5. OBJECTS FOR CONSTANT LIGHT CONTROL
4.5.1. OBJECT 16 CONSTANT LIGHT – SWITCH ON/OFF
Input 1 bit
This input allows the constant light controller to be switched ON and OFF
(Object).
Alternatively, the constant light controller can be activated by motion
detection on the light or the HVAC channel.
4.5.2. OBJECT 17 CONSTANT LIGHT – RELATIVE DIMMING
Input 4 bit
Using this object, the current value is changed with relative dimming steps of
1%. Using a KNX push-button, the light can be dimmed and set to a new
brightness level.
The new light value can then be displayed in Lux on a KNX touch panel through
object 9: brightness value.
Important: In the menu, constant light takes over the setpoint after you
can define the period during which the controller will remain switched off.
After this interval, the new value is written to the RAM (not to the flash
memory)!
Note: This new target value remains stored in RAM as long as there are
people present in the scanned area. After switching the light channel off and
back on again, the setpoint stored in ETS is adopted once again. If the newly
changed set point are definitely taken over, set the parameter Keep changed
set point to YES (see also section 3.8 Constant light parameter page 18)
4.5.3. OBJECT 18 CONSTANT LIGHT – PRESET DIMMING
Input 1 Byte
With this object the user can define a new dim set point in % over the bus.
4.5.4. OBJECT 20 CONSTANT LIGHT – FORCE CONTROL
Input 1 bit
In accordance to the parameters force output at ON and force output at OFF,
various options can be selected: no reaction, minimum brightness, maximum
brightness
4.5.5. OBJECT 21 CONSTANT LIGHT – SCENE
Input 1 byte
Scene selection input. 8 adjustable scenes can be selected via ETS.
This object has no switch function but only changes the brightness setpoint
values.
4.5.6. OBJECT 22 CONSTANT LIGHT – OUTPUT CHANNEL 1
Output 1 byte
This is the constant light control signal (% brightness) for the dimming
actuator of lighting 1
4.5.7. OBJECT 23 CONSTANT LIGHT – OUTPUT CHANNEL 2
OUTPUT 1 byte
This is the constant light control signal for the dimming actuator of lighting
2.
The lux value is equal to channel 1 +/- offset.
PROGRAMMVERSION 2.7
With the program version 2.7, the functional possibilities of the presence
detector – series Swiss Guard 360P KNX / KLR RA / EA expanded and existing
features of program version 2.4, have been supplemented respectively adapted.
The standard values (default values) of the parameters compared to the
settings in version 2.4 are partially modified.
These settings allow a simple and safe functionally check (initial start-up )
of the presence detector.
Older devices of software version 2.4 can also be programmed with the program
version 2.7 ( backward compatibility ) .
However, supplemented functions and the additional communication objects are
not all supported.
5.1. Overview of the changes:
- Forced control Secondary detector-Mode……………………………………see 5.2.0
- Parameter changes via communication objects……………………..see 5.2.1
- Dimming function with constant light control (clc)……………………………………………see 5.2.2
- Power on characteristics……………………….see 5.3.1
- Automatic lighting OFF threshold……………………………..see 5.3.2
- Delay time in semi-automatic mode……………………………………see 5.3.3
- Standby-function………………………..see 5.3.4
- Light sensor adaption………………………….see 5.3.5
5.2. Communication objects
input objects
output objects
Object | Function | link application with | Bit/Byte | |
---|---|---|---|---|
0 | Output – light (preset dimming) | light group actuator | 1 byte | |
0 | Output – light (switching) | light group actuator. | 1 bit | |
0 | Output – light (scene) | light group actuator | 1 bit | |
1 | Input external switch / status – light (switching) | Kaka switch, touch | ||
display, logic | 1 bit | |||
2 | Input external motion – light (switching) | Output – light for secondary | ||
unit (object 0) | 1 bit | |||
3 | Input – light (faced control) | •External logic module | 2 bit | |
3 | Input – light (lock) | KNX switch, touch display, logic module | 1 bit | |
4 | Output -HVAC (switching) | •Actuators for HVAC devices such as heating, |
ventilation, and air conditioning
•Control of alarm logic modules
•Presence function| 1 bit
5| | External switch / status – HVAC (switching)| KNX switch, touch display,
logic| 1 bit
6| | External motion – HVAC (switching)| Output HVAC for the secondary unit
(output object 4).| 2 byte
7| | Input – HVAC (forced control)| External logic module| 2 bit
7| | Input – HVAC (lock)| Da switch, touch display, logic| 1 bit
8| | Threshold switch brightness (switching)| Logic, actuator| 1 bit
9| | Brightness (lux value)| Logic, touch display| 2 byte
10| | Al) calibration value| Readout and then set manually for the calibration
procedure| 2 byte
16| | Constant light control, switch on/off| KW switch, logic| 1 bit
17| | Constant light control, dimming relative| 4 bit dimming object from KNX
switch for OWOFF, dimming up and down, touch display| 4 bit
18| | Constant light control, preset dimming| Logic module| 1 byte
20| | Constant light control, forced control| KIV button, logic| 1 bit
21| | Constant light control, scene selection| Logic module| 1 byte
22| | Constant light control, channel 1 – output| Dimming actuator for light
group 1| 1 byte
23| | Constant light control, channel 2 – output| Dimming actuator tor light
group 2| 1 byte
24| | Light – standby| Switching of standby value sets| 1 bit
5.2.1. COMMUNICATION OBJECTS with Secondary Detector- Mode
Object | Function | link application with | Bit/Byte | |
---|---|---|---|---|
0 | Output (switching) | Master presence -detector | ||
3 | Input (forced control) | KM switch, touch display, logic module |
Object forced control:
Object 3 as a forced control object knows 2 values (1-bit command ) that can
be received :
If object forced control = 1: output ( Obj.0 ) remains locked when motion is
detected, no telegrams are sent
If object forced control = 0: output ( Obj.0 ) AUTO ( normal operation )
5.2.2. OBJECTS FOR DYNAMIC PARAMETER CHANGES
Input 2 byte
Output 2 byte
Via object 11 (delay time) and via object 12 (brightness below which sensor is
active) may be changed or read the related parameter- values directly without
to re-programming the presence- detector.
This mode allows external devices (BMS, touch screen, logic ) to influence the
functioning of the presence- detector directly.
For example, dependent on user needs, the light-ON switching
characteristic/delay time can be dynamically adapted during certain day times
to optimize the application.
Changed values via object remain stored temporarily. After bus voltage
interruption/return, after a reset or after a re-programming, the originally
parameterized values are active again.
5.2.3. Object 14 CONSTANT LIGHT CONTROL – FORCED DIMMING
Input 4 bit
If the constant light control of the Presence detector is activated by a
presence detection or by an external “ON”- command (obj1) , dimming values
(brighter or darker ) transmitted to object 14 interrupt the function
Constant-light-control immediately and remains inactive during motion
detection and or the delay- time.
At that moment, the constant-light-control output-value ( Obj 22) can with
relative dimming ( brighter / darker ) by a KNX push button – to be changed.
After the delay- time or after an external “ OFF “ switching command, the
constant-light- control is active again and operates (when motion-detection)
with the stored parameter- values.
Parameters
5.3.1. Operating mode during power- on
After power-on/ bus voltage return or bus voltage interruption, the presence-
detector is for the first 60sec inactive. During this stabilization period of
the electronic device, the detector doesn´t send any telegrams too.
Dependent on the application, in the operating mode “Automatic” ,the light
output (obj1/obj22) can be activated during the start-up phase.
In this mode, two options with ”75s light on after restart” or “no reaction
after restart” can be selected.
5.3.2. Automatic adaptation of the “light-off“ threshold
With the setting „Automatic“ in the parameter Brightness above which lighting
is turned off, the detector calculates automatically the light-off threshold
with the following rule:
If the effective brightness with switched light-channel (after 1min.) is
greater than the parameterized value „Brightness below which sensor is
active“, the light-off threshold is 10% increased above this value plus
200LUX.
If the effective brightness with switched light-channel (after 1min.) is below
the parameterized value „Brightness below which sensor is active“, the light-
off threshold is 10% increased above the actual brightness-value (obj9) plus
200LUX.
The light-off threshold is recalculated after each expired delay-time and a
renewed motion detection or an “ON” switching command.
If the parameter Brightness switch–off level is selected with a fixed value,
this value needs to be higher or the same as the parameter Brightness below
sensor is active.
5.3.3. Delay-time, mode semi- automatic
If the brightness is increasing during the delay-time and passes over the
threshold “Brightness switch off level”, the light-channel (obj0/obj22) is
switching off but the delay-time is continuing either. If the brightness
reduces below the value “Brightness below sensor is active”, the light channel
is switching ”ON” again, till the delay-time is expired.
5.3.4. Standby-functionality
When the light-channel is used as “dim completely”, a standby-light can be
activated optionally.
Two pairs of values are available and can select with obj24.
The delay-time for the Standby-functionality can also parameterize as
“Unlimited “ too. Emergency light with permanent minimum brightness.
If the brightness during standby increases over “Brightness switches off
level”, the light-channel (obj0) is switching off.
If the brightness reduces below the value “Brightness below sensor is active”,
the light channel is switching ”ON” with the standby settings again till the
delay-time (standby) is expired.
5.3.5. Adjustment brightness sensor
Brightness value calibration| ![niko Swiss Garde 300 Presence Detector KNX KLR
- fig 21](https://manuals.plus/wp-content/uploads/2022/03/niko-Swiss-Garde-300
-Presence-Detector-KNX-KLR-fig-21-550x255.png)
---|---
Factory calibration| This setting is possible at any time with the reprogramming of the presence-detector.
Custom calibration| This option opens two additional windows. AD calibration value and Lux value
AD calibration value| Read out the AD calibration value (communication object
- in the ETS and submit it in the window AD calibration value.
Note: In the menu Read/send value, use type 7.001 unsigned 2 byte counter!
The AD value read then appears in the Value received menu as 739 pulses, for example.
Lux value| Measure with Luxmeter the reference brightness and submit it in the Lux window.
Keep internal value| This setting is selected after a recalibration was made.