TRANBALL QR3613B Networking 8-Channel SHT30 Temperature and Humidity Logger User Manual

June 6, 2024
TRANBALL

QR3613B
User Ma nual
File Version: V22.1.14

QR3613B using the standard RS485 bus MODBUS-RTU protocol,easy access to PLCDCS and other instruments or systems for monitoring temperature,humidity@8 state quantities.The internal use of high-precision sensing core and related devices to ensure high reliability and excellent long-term stability can be customized RS232, RS485, CAN,4-20mA, DC0~5V10V, ZIGBEE, Lora, WIFI, GPRS and other output methods.

Technical Parameters

Technical parameter Parameter value
Brand TRANBALL
Communication Interface RS485
Power DC5~24V 1A
Display 1.8 TFT
Storage 8M
Max Records 65000
Running temperature -40~80°C
Working humidity 5%RH~90%RH

Product Size

How to wiring?

Application solution

A: After opening the software, enter the main interface, select the corresponding product model at the time of purchase, and save the settings after selection, in case you need to reselect it after opening it next time.

B: Use the USB converter to insert the computer’s USB2.0 interface, the driver will be installed automatically, If the installation fails, you can install it in the driver wizard software. After connecting to the computer, Select the serial port number: USB-SERIAL CH340 (COM5), set the baud rate Click to open the serial port to complete the connection.

C D: After opening the serial port, click online collection (C) to see the real-time measurement data (D).

E: Enter the parameter setting interface
F: A variety of parameters can be set in the parameter setting, such as temperature and humidity correction, baud rate, upload time, and other parameters. For the parameters on the right, you can click on “read all” to set the parameters on the recorder.

G: Enter the record operation interface
H: Click “Read Data’ to start transferring the data on the recorder to the software.

I: After the step (H), the number of read data, the total number of data, and the number of pages will be displayed at the top of the reading.
J: The read data will be displayed on it
K: You can export the read data in Excel or txt format

How to use?

KEY POSITION & SCREEN DISPLAY DESCRIPTION

SET: Set time & storage parameters
 : Up and down
 : Shift/start & stop timing

  1. Upload interval display, up to 100 seconds can be set
    This item is set by SET

  2. When the 4J button is pressed, when the icon becomes , the timing stops on the left
    When the 4.1 button is pressed, when the icon becomes , the timing starts on the left

  3. Number of records: The number of records will be increased once at the end of the countdown on the left

Press “SET” to enter the clock setting
USe to shift, adjust the value up and down

Press the second “SET” to enter the storage interval setting
The upper limit can be set to 100 seconds/time
Press the third “SET” to enter the record Start point setting
The upper limit can be set to 65101

Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1

  1. Read Data (Function id 0x03)
    Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the command:01 03 00 00 00 02 C4 0B. Device ID| Function id| Start Address| Data Length| CRC16
    ---|---|---|---|---
    1| 3| 0| 2| C4 OB

For the correct query frame, the device will respond with data:01 03 04 00 79 00 00 2B EA, the response format is parsed as follows:

Device ID| Function id| Data Length| Data 1| Data 2| Data 3
---|---|---|---|---|---
1| 3| 4| 79| 00 7A| 00 7B

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. Others and so on.

  1. Data Address Table
    Address| Start Address| Description| Data type| Value range
    ---|---|---|---|---
    40001| 0| 1#temperature register| Read Only| 65535
    40002| 1| 2#humidity register| Read Only| 65535
    40003| 2| 3#temperature register| Read Only| 65535
    40004| 3| 4#humidity register| Read Only| 65535
    40005| 4| 5#temperature register| Read Only| 65535
    40006| 5| 6#humidity register| Read Only| 65535
    | …| …| …| …
    40015| 00 OE| 15#temperature register| Read Only| 65535
    40016| 0 F| 16#humidity register| Read Only| 65535
    40101| 64| model code| read/write| 65535
    40102| 65| total points| read/write| 1-20
    40103| 66| Device ID| read/write| 1-249
    40104| 67| baud rate| read/write| 0-6
    40105| 68| mode| read/write| 1-4
    40106| 69| protocol| read/write| 1-10
  2. read and modify device address
    (1) Read or query device address
    If you don’t know the current device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.

Device ID| Function id| Start Address| Data Length| CRC16
---|---|---|---|---
FA| 3| 00 64| 00 02| 90 5F

FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address, 00 64 is the device model register.
For the correct query command, the device will respond, for example the response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the following table:

Device ID| Function id| Start Address| Model Code| CRC16
---|---|---|---|---
1| 3| 2| 55 3C 00 01| 3A 79

Response should be in the data, the first byte 01 indicates that the real address of the curr ent device is, 55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 00 01 Indicates that the device has a status quantity.

Device ID| Function id| Start Address| Destination| CRC16
---|---|---|---|---
1| 6| 66| 2| E8 14

(2)Change device address
For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 00 02 E8 14 .

Device ID| Function id| Start Address| Destination| CRC16
---|---|---|---|---
1| 6| 66| 2| E8 27

After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27, its format is parsed as shown in the following table:
Response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of the software at the same time.

  1. Read and Modify Baud Rate (1) Read baud rate
    The device default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol. For example, read the current device’s baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows. Device ID| Function id| Start Address| Data Length| CRC16
    ---|---|---|---|---
    1| 3| 67| 1| 35 D5

Read the baud rate encoding of the current device. Baud rate encoding: 1 is 2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example the response data is: 01 03 02 00 03 F8 45, the format of which is as shown in the following table:

Device ID Function id Data Length Rate ID CRC16
1 3 2 00 03 F8 45

coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.
(2)Change the baud rate
For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15.

Device ID Function id Start Address Target Baud Rate CRC16
1 3 66 1 6415

Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.

  1. Read Correction Value
    (1) Read Correction Value
    When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If  you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction valu e is read and modified in the same way for multiple parameters. Device ID| Function id| Start Address| Data Length| CRC16
    ---|---|---|---|---
    1| 3| 00 6B| 1| F5 D6

For the correct query command, the device will respond, for example the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:

Device ID| Function id| Data Length| Data value| CRC16
---|---|---|---|---
1| 3| 2| 64| B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperature, humidity have this parameter, the light generally does not have this item.
(2) Change correction value
For example, the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD.

Device ID| Function id| Start Address| Destination| CRC16
---|---|---|---|---
1| 6| 00 6B| 64| F9 FD

After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after successful change.
Disclaimer
This document provides all information about the product, does not gran t any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us
Company:
Shanghai Sonbest Industrial Co., Ltd TRANBALL Brand Division
Address: Building 8, No.215 North east road, Baoshan District, Shanghai, China
Web: http://www.qunbao.com
Web: http://www.tranball.com
SKYPE: soobuu Email: [email protected]
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
Shanghaihitdo IndustrialCo., Ltd TRANBALL Brand Division

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

TRANBALL User Manuals

Related Manuals