TRANBALL QD3613B RS485 Bus 8-Channel SHT30 Temperature and Humidity Collector User Manual
- June 6, 2024
- TRANBALL
Table of Contents
TRANBALL QD3613B RS485 Bus 8-Channel SHT30 Temperature and Humidity
Collector User Manual
QD3613B using the standard RS485 bus MODBUS-RTU protocol,easy access to PLC,DCS and other instruments or systems for monitoring temperature,SHT30humidity@8 state quantities. The internal use of high- precision sensing core and related devices to ensure high reliability and excellent long-term tability, can be customized RS232,RS485,CAN,4-20mA,DC0~5V\10V,ZIGBEE,Lora,WIFI,GPRS and other output methods.
Technical Parameters
Technical parameter|
Parameter value
---|---
Brand| TRANBALL
Temperature measuring range| -30℃~80℃
Temperature measuring accuracy| ±0.5℃ @25℃
Support sensor| SHT30
Channels| 2
Input bus| IIC
Communication Interface| RS485
Default baud rate| 9600 8 n 1
Power| DC6~24V 1A
Display| 1.8 TFT
Running temperature| -40~80°C
Product Size
How to wiring?
Application solution
-
Upload interval display, up to 100 seconds can be set
This item is set by SET 1:0 -
When pressing enter, Stop timing on the left
When pressing enter, Start timing on the left -
Number of records: The number of records will be increased once at the end of the countdown
-
NB-10T module connection status display
When the NB-10T module is successfully connected, the status bar here is blue, when the module is not installed, it is gray
When the signal is successfully connected, the status is blue, and the unconnected signal is gray.
Press “SET” to enter the clock setting.
Use “ ” to shift, Adjust the value up and down.
Press “SET” a second time to enter the storage interval setting.
The upper limit can be set 100 seconds/time
Press the third “SET” to enter the record start point setting.
The upper limit can be set to 65101
How to use?
Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1.
Read Data (Function id 0x03)
Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host
computer sends the command:01 03 00 00 00 02 C4 0B.
Device ID| Function id| Start Address| Data Length|
CRC16
---|---|---|---|---
01| 03| 00 00| 00 02|
C4 0B
For the correct query frame, the device will respond with data:01 03 04 00 79 00 00 2B EA , the response format is parsed as follows:
Device ID| Function id| Data Length| Data 1| Data 2|
Data 3
---|---|---|---|---|---
01| 03| 04| 00 79| 00 7A|
00 7B
Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. Others and so on.
Data Address Table
Address | Start Address | Description | Data type | Value range |
---|---|---|---|---|
40001 | 00 00 | 1#temperatureregister | Read only | 0~65535 |
40002 | 00 01 | 2#SHT30humidityregister | Read only | 0~65535 |
40003 | 00 02 | 3#temperatureregister | Read only | 0~65535 |
40004 | 00 03 | 4#SHT30humidityregister | Read only | 0~65535 |
40005 | 00 04 | 5#temperatureregister | Read only | 0~65535 |
40006 | 00 05 | 6#SHT30humidityregister | Read only | 0~65535 |
… | … | … | … | … |
40015 | 00 0E | 15#temperatureregister | Read only | 0~65535 |
40016 | 00 F | 16#SHT30humidityregister | Read only | 0~65535 |
40101 | 00 64 | model code | read/write | 0~65535 |
40102 | 00 65 | total points | read/write | 1~20 |
40103 | 00 66 | Device ID | read/write | 1~249 |
40104 | 00 67 | baud rate | read/write | 0~6 |
40105 | 00 68 | mode | read/write | 1~4 |
40106 | 00 69 | protocol | read/write | 1~10 |
3 read and modify device address
(1) Read or query device address
If you don’t know the current device address and there is only one device on
the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
01 | 03 | 00 67 | 00 02 | 90 5F |
FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address, 00 64 is the device model register.
For the correct query command, the device will respond, for example the response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the following table:
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
01 | 03 | 02 | 55 3C 00 01 | 3A 79 |
Response should be in the data, the first byte 01 indicates that the real address of the current device is, 55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 00 01 Indicates that the device has a status quantity.
Change device address
For example, if the current device address is 1, we want to change to 02, the command is:01 06 00 66 00 02 E8 14.
Device ID
| Function id| Start Address| Destination| CRC16
---|---|---|---|---
01| 06| 00 66| 00 02|
E8 14
After the change is successful, the device will return information: 02 06 00
66 00 02 E8 27 , its format
is parsed as shown in the following table:
Device ID| Function id| Start Address| Destination|
CRC16
---|---|---|---|---
01| 06| 00 66| 00 02|
E8 27
Response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of the software at the same time.
4 Read and Modify Baud Rate
(1) Read baud rate
The device default factory baud rate is 9600. If you need to change it, you can change it according to the following table and the corresponding communication protocol. For example, read the current device’s baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as follows:
Device ID| Function id| Start Address| Data Length|
CRC16
---|---|---|---|---
01| 03| 00 67| 00 02|
35 D
Read the baud rate encoding of the current device. Baud rate encoding: 1 is
2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example the
response data is: 01 03 02 00 03 F8 45, the format of which is as shown in the
following table:
Device ID | Function id | Data Length | Rate ID | CRC16 |
---|---|---|---|---|
01 | 03 | 02 | 00 03 | F8 45 |
coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.
Change the baud rate
For example, changing the baud rate from 9600 to 38400, ie changing the code from 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64 15 .
Device ID
| Function id| Data Length| Target Baud Rate|
CRC16
---|---|---|---|---
01| 03| 00 66| 00 01|
64 15
Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.
Read Correction Value
When there is an error between the data and the reference standard, we can
reduce the display error by adjusting the correction value. The correction
difference can be modified to be plus or minus 1000, t hat is, the value range
is 0-1000 or 64535 -65535. For example, when the display value is too small,
we can
correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the
command 100 is hex 0x64 If you need to reduce, you can set a negative value,
such as -100, corresponding to the hexadecimal value of FF 9C, which is
calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C.
The correction value starts from 00 6B. We take the first parameter as an
example. The correction valu e is read and modified in the same way for
multiple parameters.
Device ID
| Function id| Start Address| Data Length|
CRC16
---|---|---|---|---
01| 03| 00 6B| 00 01|
F5 D6
For the correct query command, the device will respond, for example the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:
Device ID| Function id| Data Length| Data value|
CRC16
---|---|---|---|---
01| 03| 02| 00 64|
B9 AF
Change correction value
For example, the current state quantity is too small, we want to add 1 to
its true value, and the current value plus 100 correction operation command
is:01 06 00 6B 00 64 F9 FD.
Device ID | Function id | Start Address | Destination | CRC16 |
---|---|---|---|---|
FA | 03 | 00 6B | 00 64 | F9 FD |
After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after successful change.
Disclaimer
This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.
Contact Us
Company: Shanghai Sonbest Industrial Co., Ltd TRANBALL Brand Division
Address: Building 8,No.215 North east road,Baoshan
District,Shanghai,China
Web: http://www.qunbao.com
Web: http://www.tranball.com
SKYPE: soobuu
Email: sale@sonbest.com
Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>