KLHA KM53B87 Aluminum RS485 Wind Direction Sensor Waterproof User Manual
- June 6, 2024
- KLHA
Table of Contents
KLHA KM53B87 Aluminum RS485 Wind Direction Sensor Waterproof
Technical Parameters
Technical parameter | Parameter value |
---|---|
Brand | KLHA |
Wind direction range | 0~360° |
Wind direction resolution | 22.5° |
Interface | RS485/4-20mA/DC0-5V |
Power | DC12~24V 1A |
Running temperature | -40~80°C |
Working humidity | 5%RH~90%RH |
Product Selection
Product DesignRS485,4-20mA, DC0-5VMultiple output methods, the products are
divided into the following models depending on the output method.
Product model | output method |
---|---|
KM53B8B | RS485 总线 |
KM53B8M | 4-20mA |
KM53B8V5 | DC0-5V |
Product Size
How to wiring?
Note:
When wiring, connect the positive and negative poles of the power supply
first, and then connect the signal wire
Communication Protocol
The product uses RS485 MODBUS-RTU standard protocol format, all operation
or reply commands are hexadecimal data. The default device address is 1 when
the device is shipped, the default baud rate is 9600, 8, n, 1
Read Data (Function id 0x03)
Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the
host computer sends the command:01 03 00 00 00 01 84 0A .
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
01 | 03 | 00 00 | 00 01 | 84 0A |
For the correct query frame, the device will respond with data:01 03 02 00 79 79 A6 , the response format is parsed as follows:
Device ID | Function id | Data Length | 数据 1 | Check Code |
---|---|---|---|---|
01 | 03 | 02 | 00 79 | 79 A6 |
Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. Others and so on.
Address | Start Address | Description | Data type | Value range |
---|---|---|---|---|
40001 | 00 00 | 1#conductivityregister | Read only | 0~65535 |
40101 | 00 64 | model code | read/write | 0~65535 |
40102 | 00 65 | total points | read/write | 1~20 |
40103 | 00 66 | Device ID | read/write | 1~249 |
40104 | 00 67 | baud rate | read/write | 0~6 |
40105 | 00 68 | mode | read/write | 1~4 |
40106 | 00 69 | protocol | read/write | 1~10 |
read and modify device address Read or query device address If you don’t know the current device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
FA | 03 | 00 64 | 00 02 | 90 5F |
FA is 250 for the general address. When you don’t know the address, you can
use 250 to get the real device address, 00 64 is the device model register.
For the correct query command, the device will respond, for example the
response data is: 01 03 02 07 12 3A 79, the format of which is as shown in the
following table:
Device ID | Function id | Start Address | Model Code | CRC16 |
---|---|---|---|---|
01 | 03 | 02 | 55 3C 00 01 | 3A 79 |
The response should be in the data, the first byte 01 indicates that the real address of the current device is, 55 3C converted to decimal 20182 indicates that the current device main model is 21820, the last two bytes 00 01 Indicates that the device has a status quantity.
Change devise address
For example, if the current device address is 1, we want to change to 02, the
command is:01
Device ID | Function id | Start Address | Destination | CRC16 |
---|---|---|---|---|
01 | 06 | 00 66 | 00 02 | E8 14 |
After the change is successful, the device will return information: 02 06 00 66 00 02 E8 27 , its format is parsed as shown in the following table:
Device ID | Function id | Start Address | Destination | CRC16 |
---|---|---|---|---|
01 | 06 | 00 66 | 00 02 | E8 27 |
The response should be in the data, after the modification is successful, the first byte is the new device address. After the general device address is changed, it will take effect immediately. At this time, the user needs to change the query command of the software at the same time.
Read and Modify Baud Rate
Read baud rate The device’s default factory baud rate is 9600. If you need to
change it, you can change it according to the following table and the
corresponding communication protocol. For example, read the curren t device’s
baud rate ID, the command is:01 03 00 67 00 01 35 D5 , its format is parsed as
follows.
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
01 | 03 | 00 67 | 00 01 | 35 D5 |
Read the baud rate encoding of the current device. Baud rate encoding: 1 is
2400; 2 is 4800; 3 is 9600; 4 is 19200; 5 is 38400; 6 is 115200.
For the correct query command, the device will respond, for example, the
response data is: 01 03 02 00 03 F8 45, the format of which is as shown in the
following table:
Device ID | Function id | Data Length | Rate ID | CRC16 |
---|---|---|---|---|
01 | 03 | 02 | 00 03 | F8 45 |
coded according to baud rate, 03 is 9600, ie the current device has a baud rate of 9600.
Change the baud rate
For example, changing the baud rate from 9600 to 38400, ie changing the
code fro m 3 to 5, the command is: 01 06 00 67 00 05 F8 1601 03 00 66 00 01 64
15 .
Device ID | Function id | Start Address | Target Baud Rate | CRC16 |
---|---|---|---|---|
01 | 03 | 00 66 | 00 01 | 64 15 |
Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.
Read Correction Value
Read Correction Value When there is an error between the data and the
reference standard, we can reduce the display error by adjusting the
correction value. The correction difference can be modified to be plus or
minus 1000, that is, the value range is 0-1000 or 64535 -65535. For example,
when the display value is too small, we can correct it by adding 100. The
command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you
need to reduce, you can set a negative value, such as -100, corresponding to
the hexadecimal value of FF 9C, which is calculated as 100-65535=65435, and
then converted to hexadecimal to 0x FF 9C. The correction value starts from 00
6B. We take the first parameter as an example. The correction value is read
and modified in the same way for multiple parameters.
Device ID | Function id | Start Address | Data Length | CRC16 |
---|---|---|---|---|
01 | 03 | 00 6B | 00 01 | F5 D6 |
For the correct query command, the device will respond, for example the response data is: 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:
Device ID | Function id | Data Length | Data value | CRC16 |
---|---|---|---|---|
01 | 03 | 02 | 00 64 | B9 AF |
In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperature, and humidity have this parameter, the light generally does not have this item.
Change correction value
For example, the current state quantity is too small, we want to add 1 to
its true value, and the current
Device ID | Function id | Start Address | Destination | CRC16 |
---|---|---|---|---|
01 | 06 | 00 6B | 00 64 | F9 FD |
After the operation is successful, the device will return information: 01 06
00 6B 00 64 F9 FD, the parameters take effect immediately after a successful
change.
For example, the range is 0~360°, the analog output is 4~20mA current signal,
conductivity and current The calculation relationship is as shown in the
formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is conductivity range
upper limit, A1 is the lower limit of the range, B2 is current output range
upper limit, B1 is the lower limit, X is the currently read conductivity
value, and C is the calculated current value. The list of commonly used values
is as follows:
current(mA) | conductivityValue (°) | Calculation Process |
---|---|---|
4 | 0.0 | (360-0)*(4-4)÷(20-4)+0 |
5 | 22.5 | (360-0)*(5-4)÷(20-4)+0 |
6 | 45.0 | (360-0)*(6-4)÷(20-4)+0 |
7 | 67.5 | (360-0)*(7-4)÷(20-4)+0 |
8 | 90.0 | (360-0)*(8-4)÷(20-4)+0 |
9 | 112.5 | (360-0)*(9-4)÷(20-4)+0 |
10 | 135.0 | (360-0)*(10-4)÷(20-4)+0 |
11 | 157.5 | (360-0)*(11-4)÷(20-4)+0 |
--- | --- | --- |
12 | 180.0 | (360-0)*(12-4)÷(20-4)+0 |
13 | 202.5 | (360-0)*(13-4)÷(20-4)+0 |
14 | 225.0 | (360-0)*(14-4)÷(20-4)+0 |
15 | 247.5 | (360-0)*(15-4)÷(20-4)+0 |
16 | 270.0 | (360-0)*(16-4)÷(20-4)+0 |
17 | 292.5 | (360-0)*(17-4)÷(20-4)+0 |
18 | 315.0 | (360-0)*(18-4)÷(20-4)+0 |
19 | 337.5 | (360-0)*(19-4)÷(20-4)+0 |
20 | 360.0 | (360-0)*(20-4)÷(20-4)+0 |
As shown in the above formula, when measuring 8mA, current is 94°。 For example, the range is 0~360°, the analog output is 0~5V DC0-5Vvoltage signal, conductivity and DC0-5Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is conductivity range upper limit, A1 is the lower limit of the range, B2 is DC0-5Vvoltage output range upper limit, B1 is the lower limit, X is the currently read conductivity value, and C is the calculated DC0-5Vvoltage value. The list of commonly used values is as follows:
DC0-5Vvoltage(V) | conductivityValue (°) | Calculation Process |
---|---|---|
0 | 0.0 | (360-0)*(0-0)÷(5-0)+0 |
1 | 72.0 | (360-0)*(1-0)÷(5-0)+0 |
2 | 144.0 | (360-0)*(2-0)÷(5-0)+0 |
3 | 216.0 | (360-0)*(3-0)÷(5-0)+0 |
4 | 288.0 | (360-0)*(4-0)÷(5-0)+0 |
5 | 360.0 | (360-0)*(5-0)÷(5-0)+0 |
As shown in the above formula, when measuring 2.5V, current DC0-5Vvoltage is 180°。
Disclaimer
This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability or the infringement liability for any patent, copyright or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.
Contact Us
Company: Shanghai Sonbest Industrial Co., Ltd KLHA Brand Division Address:
Building 8,No.215 Northeast road, Baoshan District, Shanghai, China Web:
http://www.klha.com
Web: http://www.klha.com
SKYPE: soobuu Email: sale@sonbest.com Tel: 86-021-51083595
/ 66862055 / 66862075 / 66861077
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>