novus N1200 Controller Instruction Manual

June 6, 2024
Novus

N1200 Controller

N1200 Controller
UNIVERSAL CONTROLLER ­ INSTRUCTIONS MANUAL ­ V2.0x J

SAFETY ALERTS
The symbols below are used on the equipment and throughout this document to draw the user’s attention to important operational and safety information.

CAUTION:
Read the manual thoroughly before installing and operating the
equipment.

CAUTION OR DANGER: Electrical Shock Hazard

All safety related instructions that appear in the manual must be observed to ensure personal safety and to prevent damage to either the instrument or the system. If the instrument is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

INTRODUCTION
The N1200 is an extraordinarily versatile process controller. It holds in one single instrument all the main features needed for the vast majority of industrial processes. It accepts in a single model virtually all the sensors and signals used in the industry and provides the main output types required for the operation of diverse processes.
Configuration can be performed either directly on the controller or via the USB interface once QuickTune software has been installed on the computer to be used. Once connected to USB, the device will be recognized as a serial communication (COM) port operating with Modbus RTU protocol.
Through the USB interface, even if disconnected from the power supply, the configuration performed in a piece of equipment can be can be saved in a file and repeated in other pieces of equipment that require the same configuration.
It is important that the users read carefully this manual before using the controller. Verify if the release of this manual matches the instrument version (the firmware version is shown when the controller is energized). The N1200 main characteristics are:
· Multi-sensor universal input; · Protection for open sensor in any condition; · Relay, 4-20 mA and logic pulse control outputs all available in
the standard model; · Self-tuning of PID parameters; · Automatic / Manual function with “bumpless” transfer; · Four modes of independents alarms, with functions of minimum,
maximum, differential (deviation), open sensor and event; · Timer functions that can be associated to the alarms; · Retransmission of PV or SP in 0-20 mA or 4-20 mA; · Input for remote setpoint; · Digital input with 5 functions; · Programmable soft-start; · 20 setpoint profile programs with 9 segments each, with the
ability to be linked together for a total of 180 segments; · Password for parameters protection; · Universal power supply.
NOVUS AUTOMATION

CONFIGURATION / FEATURES

INPUT TYPE SELECTION Select the input type (in parameter “tYPE”) from Table 1 below.

TYPE J K T N R S B E
Pt100 0-20 mA 4-20 mA 0­50 mV 0-5 Vdc 0-10 Vdc

CODE
Tc j Tc k Tc t Tc n Tc r Tc s Tc b Tc e
Pt L0.20 L4.20 L0.50 L0.5 L0.10 ln j

RANGE OF MEASUREMENT Range: -110 to 950 °C (-166 to 1742 °F) Range: -150 to 1370 °C (-238 to 2498 °F) Range: -160 to 400 °C (-256 to 752 °F) Range: -270 to 1300 °C (-454 to 2372 °F) Range: -50 to 1760 °C (-58 to 3200 °F) Range: -50 to 1760 °C (-58 to 3200 °F) Range: 400 to 1800 °C (752 to 3272 °F) Range: -90 to 730 °C (-130 to 1346 °F) Range: -200 to 850 °C (-328 to 1562 °F)
Linear Signals Programmable indication from -1999 to 9999.

4-20 mA
NON LINEAR

Ln k ln t ln n ln r ln s ln b ln E Ln.Pt

Non Linear Analog Signals Indication range depends on the selected sensor

Table 1 – Input types
Note: All input types are factory calibrated.

CONFIGURATION OF OUTPUTS, ALARMS AND DIGITAL INPUTS
The controller input and output channels (I / O) can assume multiple functions: control output, digital input, digital output, alarm output, retransmission of PV and SP. These channels are identified as I / O 1, I / O 2, I / O 3, I / O 4 and I / O 5.
The basic controller model comes loaded with the following features:
I / O 1 output to Relay SPST-NA; I / O 2 output to Relay SPST-NA; I / O 5 current output, digital output, digital input;
Optionally, other features can be added, as shown under the item “Identification” in this manual:
– 3R: I / O3 with output to SPDT relay;
– DIO: I / O3 and I / O4 as digital input and output channels;
– HBD: Heater break detect;
– 485: Serial Communication;

1 / 12

The function to be used in each channel of I/O is defined by the user in accordance with the options shown in the Table 2.

FUNCTION OF I/O Without Function Output of Alarm 1 Output of Alarm 2 Output of Alarm 3 Output of Alarm 4 LBD – Loop break detection Control Output (Relay or Digital Pulse) Automatic / Manual mode selection Run / Stop mode selection Remote SP selection Setpoint profile program HOLD (Freezes program execution) Setpoint Profile Program 1 selection 0 to 20 mA control output selection 4 to 20 mA control output selection Retransmission of PV in 0 to 20 mA Retransmission of PV in 4 to 20 mA Retransmission of SP in 0 to 20 mA Retransmission of SP in 4 to 20 mA

CODE
OFF A1 A2 A3 A4 Lbd CTRL
mAN RVN RSP

TYPE OF I/O Output Output Output Output Output Output Output
Digital Input Digital Input Digital Input

KPRG

Digital Input

PR 1 (.0.20 (.4.20 P.0.20 P.4.20 S.0.20 S.4.20

Digital Input Analogical Output Analogical Output Analogical Output Analogical Output Analogical Output Analogical Output

Table 2 – Types of functions for the I/O channels

During the configuration of the I/O channels, only the valid options for each channel will be shown on the display. These functions are described below: · off – Without function
The I/O channel programmed with code off will not be used by the controller. Although without function, this channel is available through the serial communication as digital I/O (command 5 MODBUS).
· a1, a2, a3, a4 ­ Alarm Outputs
The selected channel can be used as output to Alarms 1 to 4. Defines that the programmed I/O channel acts as alarm outputs. Available for all the I/O channels.
· Lbd ­Loop Break Detector function.
Assigns the output of the Loop Break Detector alarm to an I/O channel. Available to all I/O channels.
· (trL ­ PWM Control Output
Defines the I/O channel to be used as the PWM control output (relay or digital pulse). Available for all the I/O channels. The digital pulse is available on I/O5 (standard) or on I/O3 and I/O4 (when the DIO optional is installed). Check the specifications of each channel.
· mAn – Digital Input with Auto/Manual function
Defines the I/O channel as Digital Input with the function of switching the control mode between Automatic and Manual. Available on I/O5 (standard) or on I/O3 and I/O4 (when the DIO optional is installed).
Closed = Manual control; Open = Automatic control · rvn – Digital Input with RUN function
Defines channel as Digital Input with the function of enabling/disabling the control and alarm outputs (“RvN”: YES / no). Available for I/O5 or I/O3 and I/O4, when installed.
Closed = outputs enabled Open = control and alarms output shut off
· rsp – Digital Input with Remote SP function
Defines channel as Digital Input with the function of selecting the remote SP as the control setpoint. Available for I/O5 or I/O3 and I/O4, when available.
Closed = remote SP Open = uses main SP
· kprg – Digital Input with Hold Program function
Defines channel as Digital Input with the function of commanding the execution of the selected setpoint profile program. Available for I/O5 or I/O3 and I/O4, when available.

NOVUS AUTOMATION

Controller N1200
Closed = Enables execution of the program Open = Interrupts (freezes) execution of the program
Note: Even when the execution of the program is interrupted, the control output remains active and controlling the process at the point (Setpoint) of interruption. The program will resume its normal execution starting from this same point when the digital input is closed.
· Pr 1 – Digital Input with function to Execute Program 1 Defines the IO channel as Digital Input with the function of commanding the execution of the setpoint profile program 1. Available for I/O5 or I/O3 and I/O4, when available. Useful function for switching between the main setpoint and a secondary one defined by the program 1.
Closed = selects program 1; Open = selects main setpoint · (.0.20 ­0-20 mA Control Output Available for I/O 5 only, defines the channel as a 0-20 mA control output. · (.4.20 – 4-20 mA Control Output Defines the channel as a 4-20 mA control output. · P.0.20 ­ 0-20 mA PV retransmission Available for I/O 5 only, configures the channel to retransmit the values of PV in 0-20 mA. · P.4.20 – 4-20 mA PV retransmission Available for I/O 5 only, configures the channel to retransmit the values of PV in 4-20 mA. · s.0.20 ­ 0-20 mA SP (Setpoint) retransmission Available for I/O 5 only, configures the channel to retransmit the values of SP in 0-20 mA. · s.4.20 ­ 4-20 mA SP (Setpoint) retransmission Available for I/O 5 only, configures the channel to retransmit the values of SP in 0-20 mA.
CONFIGURATION OF ALARMS The controller has 4 independent alarms. These alarms can be configured to operate with nine different functions, as shown in Table 3. · off ­ Alarms turned off. · ierr ­ Open Sensor alarms – (Loop Break) The open sensor alarm acts whenever the input sensor is broken or badly connected. · rs ­ Program Event Alarm Configures the alarm to act in (a) specific segment(s) of the programs of ramps and baselines to be created by the user. · Rfai1 ­ Burnt-out Resistance Alarm – (Heat Break) Signals that the heating element has broken up. This alarm function requires the accessory Current transformer CT1. Details for use of the option “burnt-out resistance” are found in the specific documentation that accompanies the product whenever this option is requested. · lo ­ Alarm of Absolute Minimum Value Triggers when the value of measured PV is below the value defined for alarm Setpoint. · ki ­ alarm of Absolute Maximum Value Triggers when the value of measured PV is above the value defined for alarm Setpoint. · dif ­ Alarm of Differential Value In this function the parameters “SPA1”, “SPA2″,” SPA3″ and “SPA4” represent the Deviation of PV in relation to the SP. Using the Alarm 1 as example: for Positive SPA1 values, the Differential alarm triggers when the value of PV is out of the range defined for:
(SP ­ SPA1) to (SP + SPA1) For a negative SPA1 value, the Differential alarm triggers when the value of PV is within the range defined above:
2 / 12

· difl ­ Alarm of Minimum Differential Value It triggers when the value of PV is below the defined point by:
(SP ­ SPA1)

Using the Alarm 1 as example.

· difk ­ Alarm of Maximum Differential Value Triggers when the value of PV is above the defined point by:
(SP + SPA1)

Using the Alarm 1 as example.

SCREEN TYPE

ACTUATION

Off Inoperative Output is not used as alarm.

Ierr

Open sensor (input Error)

Activated when the input signal of PV is interrupted, out of the range limits or Pt100 in short-circuit.

Rs Event (ramp and Activated in a specific segment of program.
Soak)

rfail Resist. burnt out Signals a failure in the heating element.
(resistance fail)

Lo Ki Dif
Difl Difk

Minimum value (Low)
Maximum value (High)
Differential (differential)

PV

SPAn PV

SPAn

PV

PV

SV – SPAn SV SV + SPAn

SV + SPAn SV SV – SPAn

Positive SPAn

Negative SPAn

Minimum Differential (differential Low)

Positive SPAn
PV

SV – SPAn

SV

Maximum

differential

PV

(differential High) SV SV + SPAn

Positive SPAn

Negative SPAn
PV

SV

SV – SPAn

PV SV + SPAn SV
Negative SPAn

Table 3 ­ Alarm Functions
Where SPAn refers to Setpoints of Alarm “SPA1”, “SPA2”, “SPA3” and “SPA4”.
Important note: Alarms configured with the ki, dif, and difk functions also trigger their associated output when a sensor fault is identified and signaled by the controller. A relay output, for example, configured to act as a High Alarm (ki), will operate when the SPAL value is exceeded and also when the sensor connected to the controller input is broken.

ALARM TIMER MODES
The controller alarms can be configured to perform 3 timer modes:
· One pulse with defined duration;
· Delayed activation;
· Repetitive pulses; The illustrations in Table 4 show the behavior of the alarm output for various combinations of times t1 and t2. The timer functions can be configured in parameters A1t1, A1t2, A2t1, A2t2, A3t1, A3t2, A4t1 and A4t2.

OPERATION T 1

T 2

ACTION

Normal Operation

0

Alarm

0

Output

Alarm Event

Activation for a defined time

1

to

6500

s

0

Alarm

Output

T1

Alarm Event

Activation with delay

0

Alarm
1 to 6500 s Output

T2

Alarm Event

Intermittent Activation

1 to 6500 s 1 to 6500 s

Alarm Output

T1

T2

T1

Alarm Event

Table 4 ­ Temporization Functions for the Alarms

NOVUS AUTOMATION

Controller N1200
The LEDs associated to the alarms will light when the alarm condition is recognized, not following the actual state of the output, which may be temporarily OFF because of the temporization.
INITIAL BLOCKING OF ALARM The initial blocking option inhibits the alarm from being recognized if an alarm condition is present when the controller is first energized (or after a transition from run YES NO). The alarm will be enabled only after the occurrence of a non-alarm condition followed by a new occurrence for the alarm. The initial blocking is useful, for instance, when one of the alarms is configured as a minimum value alarm, causing the activation of the alarm soon upon the process start-up, an occurrence that may be undesirable. The initial blocking is disabled for the sensor break alarm function.
EXTRACTION OF THE SQUARE ROOT With this feature enabled the controller uses for display and control a value that corresponds to the square root of the applied input signal. Available only for the inputs belonging to the group of linear analogic signals: 0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V.
ANALOG RETRANSMISSION OF PV AND SP The analog output, when not used for control purposes, is available for retransmitting the PV and SP values in 0-20 or 4-20 mA. This analog output is electrically isolated from other inputs and outputs. The analog output signal is scalable, with the output range defined by the values programmed in the parameters “rtLL” and “rtkL”. To obtain a voltage output, the user must install a resistor shunt (550 max.) to the current output terminals (terminals 7 and 8). The actual resistor value depends on the desired output voltage span. There is no electrical isolation between serial communication (RS485) and channel I/O5.
SOFT START The soft-start feature avoids abrupt variations in the power delivered to the load regardless of the system power demand. . This is accomplished by defining a limiting ramp for the control output. The output is allowed to reach maximum value (100 %) only after the time programmed in the soft-start parameter has elapsed. The Soft-start function is generally used in processes that require slow start-up, where the instantaneous application of 100 % of the available power to the load may cause damages to parts of the system. Notes: 1- Function only valid when in PID control mode. 2- Setting 0 (zero) in the time interval, the function is disabled.
REMOTE SETPOINT The controller can have its Setpoint value defined by an analog, remotely generated signal. This feature is enabled through the channels I/O3, I/O4 or I/O5 when configured as digital inputs and configured with the function rsp (Remote SP selection) or through the parameter E.rsp. The remote setpoint input accepts the signals 0-20 mA, 4-20 mA, 0-5 V and 0-10 V. For the signals of 0-20 and 4-20 mA, a shunt resistor of 100 is required between terminals 9 and 10, as shown in Figure 4c.
CONTROL MODE The controller can operate in two different manners: Automatic mode or Manual mode. In automatic mode the controller defines the amount of power to be applied on the process, based on defined parameters (SP, PID, etc.). In the manual mode the user himself defines this amount of power. The parameter “(trl” defines the control mode to be adopted.
3 / 12

PID AUTOMATIC MODE
For the Automatic mode, there are two different strategies of control: PID control and ON/OFF control.
PID control has its action based on a control algorithm that takes into account the deviation of PV with respect to SP, the rate of change of PV and the steady state error.
On the other hand, the ON/OFF control (obtained when Pb=0) operates with 0 % or 100 % of power, when PV deviates from SP.
The determination of the PID parameters (Pb, Ir and Dt) is described in the item DETERMINATION OF PID PARAMETERS of this manual.
LBD – LOOP BREAK DETECTION ALARM
The parameter defines a time interval, in minutes, within which the PV is expect to react to a control output signal. If the PV does not react properly within the time interval configured in lbd.t, the controller interprets this as a control loop break and signals this occurrence in the display.
A LBD event may be sent to any I/O channel. Simply configure the LDB function to the desired I/O channel: the selected output will be activated when a LDB condition is detected. When the lbd.t parameter is programmed with 0 (zero), the LDB function is disabled.
The LDB is useful in system supervision and troubleshooting, allowing early detection of problems in the actuator, power source or load.
HBD – HEATER BREAK DETECTION
Available in the products identified with the suffix HBD. Visit our website for further information www.novusautomation.com.
SAFE OUTPUT VALUE WITH SENSOR FAILURE
This function defines an output value (user defined) to be assigned to the control output in the event of a sensor failure.
When the input sensor is identified as broken, the controller forcing MV to assume the user configured value in the 1E.ov parameter.
When the parameter 1E.ov is configured with 0.0 (zero) value, this function is disabled and the control output is simply turned off upon input sensor error.
USB INTERFACE
The USB interface is used to CONFIGURE, MONITOR or UPDATE the controller FIRMWARE. The user should use QuickTune software, which offers features to create, view, save and open settings from the device or files on the computer. The tool for saving and opening configurations in files allows the user to transfer settings between devices and perform backup copies.
For specific models, QuickTune allows to update the firmware (internal software) of the controller via the USB interface.
For MONITORING purposes, the user can use any supervisory software (SCADA) or laboratory software that supports the MODBUS RTU communication over a serial communication port. When connected to a computer’s USB, the controller is recognized as a conventional serial port (COM x).
The user must use QuickTune software or consult the DEVICE MANAGER on the Windows Control Panel to identify the COM port assigned to the controller.
The user should consult the mapping of the MODBUS memory in the controller’s communication manual and the documentation of the supervision software to start the MONITORING process.
Follow the procedure below to use the USB communication of the device:
1. Download QuickTune software from our website and install it on the computer. The USB drivers necessary for operating the communication will be installed with the software.
2. Connect the USB cable between the device and the computer. The controller does not have to be connected to a power supply. The USB will provide enough power to operate the communication (other device functions may not operate).
3. Run the QuickTune software, configure the communication and start the device recognition.

Controller N1200
The USB interface IS NOT SEPARATE from the signal input (PV) or the controller’s/indicator’s digital inputs and outputs. It is intended for temporary use during CONFIGURATION and MONITORING periods. For the safety of people and equipment, it must only be used when the piece of equipment is completely disconnected from the input/output signals. Using the USB in any other type of connection is possible but requires a careful analysis by the person responsible for installing it. When MONITORING for long periods of time and with connected inputs and outputs, we recommend using the RS485 interface, which is available or optional in most of our products.
INSTALLATION / CONNECTIONS
The controller must be fastened on a panel, following the sequence of steps described below: · Prepare a panel cut-out according Specifications; · Remove the mounting clamps from the controller; · Insert the controller into the panel cut-out; · Slide the mounting clamp from the rear to a firm grip at the
panel.
RECOMMENDATIONS FOR THE INSTALLATION · All electrical connections are made to the screw terminals at the
rear of the controller. They accept wire sizes from 0.5 to 1.5 mm2 (16 to 22 AWG). The terminals should be tightened to a torque of 0.4 Nm (3.5 lb in) · To minimize the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power conductors. If this is impractical, use shielded cables. In general, keep cable lengths to a minimum. · All electronic instruments must be powered by a clean mains supply, proper for instrumentation. · It is strongly recommended to apply RC’S FILTERS (noise suppressor) to contactor coils, solenoids, etc. · In any application it is essential to consider what can happen when any part of the system fails. The controller features by themselves cannot assure total protection.
ELECTRICAL CONNECTIONS The controller’s internal circuits can be removed without undoing the connections on the back panel. The controller complete set of features is drawn in Figure 1. The features loaded in a particular unit are shown on its label
Figure 1 – Connections of the back panel

NOVUS AUTOMATION

4 / 12

Power Supply Connections

Controller N1200
Digital Input Connections Figures 5a and 5b show switches driving I/O 3 and I/O 5. The same scheme applies to I/O 4

Observe the power requirement for the unit. of required power
supply

Figure 2 ­ Power supply connections

Input Connections
· Thermocouple (T/C) and 0-50 mV
The Figure 3a indicates the wiring for the thermocouple and 0-50 mV signals. If the thermocouple wires need to be extended, use appropriate compensation cables.
· RTD (Pt100):
Figure 3b shows the Pt100 wiring, for 3 conductors. For proper cable length compensation, use conductors of same gauge and length). For 4-wires Pt100, leave one conductor disconnected at the controller. For 2-wire Pt100, short- circuit terminals 11 and 12.

T/C, 0-50mV

Pt100

Figure 3a – Connection of T/C, Figure 3b – Connection of three

0-50 mV

wire Pt100-3

· 4-20 mA:
The connections for current signals 4-20 mA must be carried-out according to Figure 4a.

Figure 5a ­ I/ O3 a Digital Input Figure 5b ­ I/O5 a Digital Input
Connection of Alarms and Outputs The I/O channels, when configured as outputs, must have their load limit capacities observed, according to the product specifications.

Figure 6a ­ I/ O3 or I/O4 with output pulse for SSR.

Figure 6b ­ I/O5 with output pulse for SSR.

I/O3, I/O4 and I/O5 can also be configured as digital outputs (I/O3 and I/O4 provide a 5 Vdc output signal whereas I/O5 a 12 Vdc signal). An example of usage is shown in Figure 6a for the I/O3 and in Figure 6b for the I/O5. I/O5 is electrically isolated from the sensor input

OPERATION
The controller’s front panel, with its parts, can be seen in the Figure 7:

4-20mA

Figure 4a – Current connection Figure 4b – Connection for 5 V

4-20 mA

and 10 V

· 5 V and 10 V Refer to Figure 4b for connecting voltage signals.

Remote Setpoint
Feature available in the controller’s terminals 9 and 10. When the Remote SP input signal is 0-20 mA or 4-20 mA, an external 100 shunt resistor of must be connected to terminals 9 and 10 as indicated in Figure 4c.

Figure 4c – Connection for remote SP

NOVUS AUTOMATION

Figure 7 – Identification of the parts referring to the front panel
Display of PV/Programming: Displays the current value of PV (Process Variable). When in configuration mode, it shows the parameters names. Display of SP/Parameters: Displays the value of SP (Setpoint). When in configuration mode, it shows the parameters values. COM indicator: Flashes to indicate communication activity in the RS485 interface. TUNE indicator: Stays ON while the controller is in tuning process. MAN indicator: Signals that the controller is in the manual control mode. RUN indicator: Indicates that the controller is active, with the control output and alarms enabled. OUT indicator: For relay or pulse control output; it reflects the actual state of the output. If an analog output is assigned for control, the OUT indicator lights continuously. A1, A2, A3 and A4 indicators: signalize the occurrence of alarm situation. P P Key (Program key): used to walk through the menu parameters.
Back Key: used to retrocede parameters. Increment key and – Decrement key: allow altering the values of the parameters. When the controller is powered on, its firmware version is presented for 3 seconds, after which the controller starts normal operation. The values of PV and SP are displayed and the outputs are enabled.
5 / 12

In order to operate appropriately, the controller needs a configuration that is the definition of each one of the several parameters presented by the controller. The user must be aware of the importance of each parameter and for each one determine a valid condition or a valid value.
Note: Since many parameters depend on the input type chosen, it is recommended that the parameter TYPE be the first one to be configured.

The parameters are grouped in levels according to their functionality and operation easiness. The 7 levels of parameters are:

LEVEL 1 – Operation 2 – Tuning 3 – R&S Programs 4 – Alarms 5 – Scale 6 – I/Os 7 – Calibration

ACCESS Free access
Reserved access

Table 5 ­ Cycles of Parameters

The parameters in the operation level have easy access through the key P . The access deeper levels use the combination of keys:

(BACK) and P (PROG) pressed simultaneously

Press P to advance or to retrocede parameters within a level. At the end of each level, the controller returns to the operation level. Keep pressing the P key to move fast forward in the level.
Alternatively, the controller returns to the operation level after pressing the key for 3 seconds
All configuration parameters are stored in protected memory. The values are saved when the keys P or are pressed after changing a parameter value. The value of SP is saved upon pressing the P key or every 25 seconds.
Note: It is recommended to disable/suspend the control (rvn = NO)
whenever it is necessary to change the device settings.

DESCRIPTION OF THE PARAMETERS

CYCLE OF OPERATION
To access the operation level parameters, press P until the desired parameter is displays.

PV Indication (Red Screen)
SP Indication (Green Screen)

PV and SP indication ­ The upper display shows the current value of PV. The lower display shows the control SP value.

(trl
Control

Control Mode:
avto – Means automatic control mode. Man ­ Means manual control mode.
(bumpless transfer between automatic and manual control modes).

PV Indication (Red Screen)
MV Indication (Green Screen)

MANIPULATED VARIABLE VALUE (MV): The upper display shows PV value and the lower display shows the percentage of MV applied to the control output. When in manual control, the MV value can be manually changed by the and keys. When in auto mode the MV value can only be viewed.
To distinguish the MV display from the SP display, the MV is shown flashing intermittently.

E pr
Enable Program

Execution of Program – Selects the ramp and soak profile program to be executed.
0 – does not execute program 1 to 20 number of the program to be executed
With enabled outputs (RUN = YES), the program starts right after the program is selected.

NOVUS AUTOMATION

Controller N1200

p.seg t.seg rvn

Screen for indication only. When a ramp and soak program is active, this parameter shows the number of the segment under execution, from 1 to 9.
Screen for indication only. When a ramp and soak program is in execution, it shows the remaining time to the end of the current segment, in units of time configured in the Pr.tb parameter.
Enables control outputs and alarms.
YES – Outputs enables. NO – Outputs not enabled.

CYCLE OF TUNING

Atvn
Auto-tune
pb
Proportional Band

Defines the control strategy to be taken:
off ­ Turned off. (no PID tuning) Fast ­ Fast automatic tuning. Full ­More accurate automatic tuning. self ­ Precise + auto – adaptive tuning Ralf ­ Forces one new precise automatic precise + auto – adaptive tuning. T9kt – Forces one new precise automatic + auto – adaptive tuning when Run = YES or controller is turned on.
PROPORTIONAL BAND – Value of the term P of the control mode PID, in percentage of the maximum span of the input type. Adjust of between 0 and 500.0 %. Select zero for ON/OFF control.

ir INTEGRAL RATE – Value of the term I of the PID
Integral Rate algorithm, in repetitions per minute (Reset). Adjustable between 0 and 99.99.
Displayed only if proportional band 0.

dt DERIVATIVE TIME – Value of the term D of the
Derivative Time control mode PID, in seconds. Adjustable between 0 and 300.0 seconds.
Displayed only if proportional band 0.

(t
Cycle Time

Pulse Width Modulation (PWM) period in seconds. Adjustable between 0.5 and 100.0 seconds.
Displayed only if proportional band 0.

kyst
Hysteresis

CONTROL HYSTERESIS (in engineering. units): This parameter is only shown for ON / OFF control (Pb=0). Adjustable between 0 and the measurement input type span.

ACt
Action

CONTROL ACTION: For Auto Mode only.
re Control with reverse Action. Appropriate for heating. Turns control output on when PV is below SP.
dir Control with direct Action. Appropriate for cooling. Turns control output on when PV is above SP.

Lbd.t
Loop break detection time.
bias

Time interval for the LBD function. Defines the maximum interval of time for the PV to react to a control command. In minutes
BIAS: Offset for MV (manual reset). Range: -100 % to +100 %.
Allows adding a percentage value between -100 % and +100 %. to the MV control output
The value 0 (zero) disables the function.

ovll
Output Low Limit

Lower limit for the control output – Minimum percentage value assumed by the control output when in automatic mode and in PID.
Typically configured with 0 %. Default value: 0 %

6 / 12

ovkl
Output High Limit

Upper limit for the control output – Maximum percentage for the control output when in automatic mode and in PID. Typically configured with 100 %. Default value: 100 %

sfst
Soft Start

Soft Start Function ­ Time in seconds during which the controller limits the MV value progressively from 0 to 100 %. It is enabled at power up or when the control output is activated. If in doubt set zero (zero value disables the Soft start function).

Sp.a1 Sp.a2 Sp.a3 Sp.a4

ALARM SETPOINT: Tripping point for alarm 1, 2, 3 and 4. Value that defines the point of activation for the programmed alarms with the functions “Lo” or “ki”.
For the alarms configured with Differential type functions, this parameter defines deviation (band).
Not used for the other alarm functions.

CYCLE OF PROGRAMS

Pr.tb Defines the time base that will be used by all Ramp

Program time & Soak programs.

base

Se(- Time basis in seconds;

Min – Time basis in minutes;

Pr n
Program number

Selects the ramp and soak profile program to be edited/viewed. The sequence of parameters that follows refer to this selected program. Total of 20 programs possible.

Ptol
Program Tolerance

Maximum admitted deviation of PV with respect to SP. If exceeded, the program execution is suspended (the internal timer freezes) until the deviation be returns back within the defined tolerance.
The value 0 (zero) disables the function (the program progresses regardless of the difference between PV and SP).

Psp0 Program SP’s, 0 to 9: Group of 10 values of SP that Psp9 define the Ramp and Soak profile segments.

Pt1 Pt9

Segments durations, 1 to 9: Defines the time of duration, in second or minutes, of the segments of the program being edited.

Pe1 Alarms of Event, 1 to 9: Parameters that define Pe9 which alarms are to be activated during the
Program event execution of a certain program segment. The alarms chosen must have its function configured as “rS.”
(See Table 3)

Lp
Link Program

Link Programs: Number of the next profile program to be linked following the current program. Profiles can be linked together to produce larger programs of up to 180 segments.

0 ­ do not link to any other program.

CYCLE OF ALARMS

Fva1 Fva2 Fva3 Fva4

FUNCTIONS OF ALARMS 1 to 4. Defines the functions for the alarms among the options of the Table 3.

bla1 bla2 bla3 bla4

BLOCK ALARM 1 TO 4: This function blocks the alarms when the controller is energized.
YES – enables initial blocking NO – inhibits initial blocking
When enabled, the alarm will not be active at power-up, waiting for PV (Process Variable) to reach a non-alarm situation. From this point on the alarm will be free to actuate should a new alarm situation occur.

NOVUS AUTOMATION

Controller N1200

xya1 xya2 xya3 xya4

ALARM HYSTERESIS: Defines the difference between the value of PV at which the alarm is triggered and the value at which it is turned off (in engineering units).

A1t1 Defines the temporization time t1, in seconds, for

A2t1 the alarms. Defines the temporization time t1, in

A3t1 A4t1

seconds, for the alarms time functions. The value 0 (zero) disables the function.

Refer to Table 4 for configuring this parameter

Alarm Time t1 timed functions. The value 0 (zero) disables the

function.

Refer to Table 4 for configuring this parameter.

A1t2 A2t2 A3t2 A4t2

Alarm Time t2. Defines the temporization time t2, in seconds, for the alarms time functions. The value 0 (zero) disables the function. Refer to Table 4 for configuring this parameter

flsh
Flash

Allows visual signalization of an alarm occurrence by flashing the indication of PV in the operation level.
To enable, the user chooses which alarms are to be associated with this feature: 1, 2, 3, 4.

CYCLE OF SCALE

Type
Type
fltr
Filter

INPUT TYPE: Selects the input signal type to be connected to the process variable input. Refer to Table 1 for the available options.
Digital Input Filter – Used to improve the stability of the measured signal (PV). Adjustable between 0 and 20. In 0 (zero) it means filter turned off and 20 means maximum filter. The higher the filter value, the slower is the response of the measured value.

Dppo Selects the decimal point position to be viewed in
Decimal Point both PV and SP.

vnI t Unit. Temperature indication in ºC or ºF:

root
Square Root

Square Root Function. Applies the quadratic function on the input signal, within the limits programmed in “SPLl” and “spkL.”
YES Enables the Function no Does not enable the Function
The indication assumes the lower limit value when the input signal is below 1 % of programmed span.
Parameter available for lineal inputs only.

0ffs
Offset

SENSOR OFFSET: Offset value to be added to the PV reading to compensate sensor error.
Default value: zero.

e.rsp Enables remote SP.

Enable Remote SP

YES Enables the Function no Does not enable the Function

This parameter is not displayed when the remote SP selection is defined by a Digital Input.

rsp
Remote SP type

Defines the signal type for the remote SP.

0-20 4-20 0-5 0-10

current of 0-20 mA current of 4-20 mA voltage of 0-5 V voltage of 0-10 V

Parameter displayed when remote SP is enabled.

rsll
Remote SP Low Limit

REMOTE SETPOINT LOW LIMIT: used in
conjunction with the rSxL, scales the remote SP
input defining the initial value in the remote SP indication range.
Parameter displayed when remote SP is enabled.

7 / 12

rskl REMOTE SETPOINT HIGH LIMIT: defines the full
Remote SP scale indication of the Remote Setpoint.
High Limit Parameter displayed when remote SP is enabled.

Spll
Setpoint Low Limit

Defines the SP lower limit of SP.
For the linear analog input types available (0-20 mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V), defines the minimum PV indication range, besides limiting the SP adjustment.

Spxl Defines the upper limit for adjustment of SP.
Setpoint High For the linear analog input types available (0-20 Limit mA, 4-20 mA, 0-50 mV, 0-5 V and 0-10 V), defines the maximum PV indication range, besides limiting the SP adjustment.

rtll In association with the rtxl parameter, it defines
Retransmission the analog retransmission scale for PV or SP. The
Low Limit rtll represents the. minimum scale value for
the analog output

This parameter is displayed only if the analog retransmission is selected in the I/O 5 parameter (I/O level).

rtkl Defines the full scale value for the analog

retransmission of PV or SP.

Retransmission High Limit

This

parameter

is

displayed

only

when

the

analog

retransmission is selected in the I/O 5 parameter

(I/O level).

1eov

Percentage output value that will be transfer to MV when the SAFE output function is enabled. If
1eov = 0, the SAFE output function is disabled
and the outputs are turned off in the occurrence of a sensor fail.

bavd Digital communication Baud Rate selection, in
Baud Rate kbps: 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2

prty
Parity

Parity of the serial communication.
none Without parity Ewem Even parity 0dd Odd parity

Addr
Address

SLAVE ADDRESS SELECTION: Identifies the controller in the network. The possible address numbers are from 1 to 247.

CYCLE OF I/OS (INPUTS AND OUTPUTS)
Io 1 Function of the channel I/O 1: Selection of the
function used in the channel I/O 1, according to the Table 2.
Io 2 Function of the channel I/O 2: Selection of the
function used in the channel I/O 2, according to the Table 2.
Io 3 Function of the channel I/O 3: Selection of the
function used in the channel I/O 3, according to the Table 2.
Io 4 Function of the channel I/O 4: Selection of the
function used in the channel I/O 4, according to the Table 2.

Controller N1200

Io 5 Function of the channel I/O 5: Selection of the
function used in the channel I/O 5, according to the Table 2.

CYCLE OF CALIBRATION
All of the input and output types are calibrated in the factory. If a recalibration is required, this should be carried out by an experienced personnel. If this cycle is accidentally accessed, pass through all the parameters without pressing the or keys

pass Input of the Access Password.

Password This parameter is presented before the protected cycles. See item Protection of Configuration.

inL(
Input Low Calibration

See section MAINTENANCE / Input Calibration. Enter the value corresponding to the low scale signal applied to the analog input.

ink(
Input High Calibration

See section MAINTENANCE / Input Calibration. Enter the value corresponding to the full scale signal applied to the analog input.

rsL( See section: MAINTENANCE / Input Calibration

Remote SP Low Calibration

Enter the value corresponding to the signal applied to the remote SP input.

low

scale

rsk( See section: MAINTENANCE / Input Calibration.

Remote SP High Calibration

Enter the value corresponding to the signal applied to the remote SP input.

full

scale

0vL(
Output Low Calibration

See section MAINTENANCE / Analog output Calibration. Enter the analog low value as measured at the analog output.

0vk( See section MAINTENANCE / Analog output

Calibration. Enter the analog high value as

Output High Calibration

measured at the analog output.

rstr
Restore
(j

Restores the factory calibration for all inputs and outputs, disregarding modifications carried out by the user.
Adjusts the of cold junction temperature value.

ktyp Parameter that informs the controller about the
hardware optional installed. It should not be altered Hardware Type by the user, except when an accessory is introduced
or removed. 0 ­ Basic model. Without optional items 1 ­ 485 2 ­ 3R 3 ­ 3R + 485 4 ­ DIO 5 ­ DIO + 485 8 ­ HBD 9 ­ HDB + 485
Note: The options 6 and 7 not are used.

Pas.( Allows defining a new access password, always
different from zero.

Prot Sets up the Level of Protection. See Table 7.

Freq Mains frequency. This parameter is important for
proper noise filtering.

NOVUS AUTOMATION

8 / 12

OPERATION CYCLE TUNING CYCLE

PV and SP (trl
PV and MV Epr p.seg t.seg Rvn

atvn pb ir dt (t
Kyst a(t Lbd.t bias ovll ovkl sfst Spa1 – spa4

PROGRAM CYCLE
PR.tb pr n Ptol psp0 ­ psp9 pt1 ­ pt9 pe1 ­ pe9
Lp

ALARM CYCLE CONFIGURATION CYCLE I/O CYCLE

fva1 – fva4

type

io1

bla1 – bla4

fltr

io2

kya1 – kya4

dppo

io3

a1t1

vnit

Io4

a1t2

Root

Io5

a2t1

Offs

a2t2

e.rsp

flsh

Rsp

Rsll

Rskl

Spll

Spkl

Ieov

Rtll

rtkl

Bavd

Prty

addr

CALIBRATION CYCLE
pass Inl( Ink( Rsl( Rsk( 0vl( 0vk( rstr
(j ktyp Pas.( prot freq.

Table 6 ­ All the Controller’s Parameters

PROTECTION OF CONFIGURATION

The controller provides means for protecting the parameters configurations, not allowing modifications to the parameters values, avoiding tampering or improper manipulation.
The parameter Protection (PROt), in the Calibration level, determines the protection strategy, limiting the access to particular levels, as shown by the table below.

PROTECTION LEVEL

PROTECTED CYCLES

1

Only the Calibration level is protected.

2

I/Os and Calibration levels.

3

Tuning, I/Os and Calibration levels.

4

Alarm, Tuning, I/Os and Calibration levels.

5

Programs, Alarm, Tuning, I/Os and Calibration levels.

6

Tuning, Programs, Alarm, Input, I/Os and Calibration levels.

7

Operation (except SP), Tuning, Programs, Alarm, input, I/Os and Calibration levels.

8

Operation, Tuning, Programs, Alarm, Input, I/Os and Calibration levels.

Table 7 ­ Levels of Protection for the Configuration

Access Password:
The protected levels, when accessed, request the user to provide the Access Password for granting permission to change the configuration of the parameters on these cycles.
The prompt PASS precedes the parameters on the protected levels. If no password is entered, the parameters of the protected cycles can only be visualized.
The Access Code is defined by the user in the parameter Password Change (PAS.(), present in the Calibration level. The factory default for the password code is 1111.

Protection of the access code
The protection system built into the controller blocks for 10 minutes the access to protected parameters after 5 consecutive frustrated attempts of guessing the correct password.

Master Password
The Master Password is intended for allowing the user to define a new password in the event of it being forgotten. The Master Password doesn’t grant access to all parameters, only to the Password Change parameter (PAS(). After defining the new password, the protected parameters may be accessed (and modified) using this new password.
The master password is made up by the last three digits of the serial number of the controller added to the number 9000.
As an example, for the equipment with serial number 07154321, the master password is 9 3 2 1.
RAMPS AND SOAKS PROGRAMS
This feature allows the creation of Ramp and Soak Setpoint Profiles (Programs). Up to 20 different profiles with 9 segments each can be programmed. Longer profiles of up to 180 segments can be created by linking 2 or more profiles together.
The figure below displays a profile model:

Figure 8 – Example of a Ramp and Soak
Once a profile is defined and selected for execution (parameter EPr in the operating level), the controller starts to generate the SP profile automatically in accordance with the elaborated program.
To execute a profile with fewer segments just program 0 (zero) for the time intervals that follow the last segment to be executed.

SV SP1
SP0 T1

SP2 SP3
T2 T3 T4=0 Time

Figure 9 – Program example with few segments

NOVUS AUTOMATION

9 / 12

The program tolerance defines the maximum deviation between PV and SP for the execution of the profile. If this deviation is exceeded, the program will be halted until the deviation falls to within the tolerance band.
Programming 0 (zero) in the “Ptol” parameter disables the program tolerance and the profile execution will continue regardless of the PV value (time priority as opposed to SP priority).
The configured time limit for each segment is 9999 and can be displayed in seconds or minutes, depending on the time base configured.

LINK OF PROGRAMS
It is possible to create a more complex program, with up to 180 segments, joining the 20 programs. This way, at the end of a program execution the controller immediately starts to run the next one, as indicated in the “LP”.
To force the controller to run a given program or many programs continuously, it is only necessary to link a program to itself or the last program to the first.

SV

Program 1

Program 2

SP3 SP4 SP1 SP2

SP5 / SP0

SP3

SP1 SP2

SP0 T1 T2 T3 T4 T5 T1

T2 T3

SP4 T4

Time

Figure 10 – Example of interlinked programs

EVENT ALARM
The Event Alarm function associates the alarms to specific segments of a program. The information of which alarms are to be activated or deactivated is given in parameters ” PE1″ to ” PE9. Press the and keys until the desired alarm numbers are displayed.
The Event Alarm requires that the Alarm function be configured as “rS “.
Notes:
1. If PtoL is different than zero, the controller will wait for the PV to reach the first program set point SP0 in order to start the program execution. Otherwise, it will start promptly.
2. Should any power failure occur, the controller resumes the program execution at the beginning of the segment that was interrupted.

DETERMINATION OF PID PARAMETERS
The determination (or tuning) of the PID control parameters in the controller can be carried out in an automatic way and auto-adaptive mode. The automatic tuning is always initiated under request of the operator, while the auto- adaptive tuning is initiated by the controller itself whenever the control performance becomes poor.
Automatic tuning: In the beginning of the automatic tuning the controller has the same behavior of an ON/OFF controller, applying minimum and maximum performance to the process. Along the tuning process the controller’s performance is refined until its conclusion, already under optimized PID control. It begins immediately after the selection of the options FAST, FULL, RSLF or TGHT, defined by the operator in the parameter ATUN.
Auto-adaptive tuning: Is initiated by the controller whenever the control performance is worse than the one found after the previous tuning. In order to activate the performance supervision and autoadaptive tuning, the parameter ATUN must be adjusted for SELF, RSLF or TGHT. The controller’s behavior during the auto-adaptive tuning will depend on the worsening of the present performance. If the maladjustment is small, the tuning is practically imperceptible for the user. If the maladjustment is big, the auto-adaptive tuning is similar to the method of automatic tuning, applying minimum and maximum performance to the process in ON/OFF control.

NOVUS AUTOMATION

Controller N1200
Figure 11 ­ Example of auto tuning
Figure 12 – Example of auto-adaptive tuning
The operator may select, through the ATUN parameter, the desired tuning type among the following options: · OFF: The controller does not carry through automatic tuning or
auto-adaptive tuning. The PID parameters will not be automatically determined nor optimized by the controller. · FAST: The controller will accomplish the process of automatic tuning one single time, returning to the OFF mode after finishing. The tuning in this mode is completed in less time, but not as precise as in the FULL mode. · FULL: The same as the FAST mode, but the tuning is more precise and slower, resulting in better performance of the P.I.D. control. · SELF: The performance of the process is monitored and the auto- adaptive tuning is automatically initiated by the controller whenever the performance becomes poorer. After a tuning cycle, the controller starts collecting data from the process for determining the performance benchmark that will allow evaluate the need for future tunings. This phase is proportional to the process response time and is signaled by the flashing TUNE indication on the display. It is recommended not to turn the controller off neither change the SP during this learning period. · rSLF: Accomplishes the automatic tuning and returns into the SELF mode. Typically used to force an immediate automatic tuning of a controller that was operating in the SELF mode, returning to this mode at the end. · TGHT: Similar to the SELF mode, but in addition to the autoadaptive tuning it also executes the automatic tuning whenever the controller is set in RUN=YES or when the controller is turned on. Whenever the parameter ATUN is altered by the operator into a value different from OFF, an automatic tuning is immediately initiated by the controller (if the controller is not in RUN=YES, the tuning will begin when it passes into this condition). The accomplishment of this automatic tuning is essential for the correct operation of the autoadaptative tuning. The methods of automatic tuning and auto-adaptative tuning are appropriate for most of the industrial processes. However, there may be processes or even specific situations where the methods are not capable to determine the controller’s parameters in a satisfactory way, resulting in undesired oscillations or even taking the process to extreme conditions. The oscillations themselves imposed by the tuning methods may be intolerable for certain processes. These
10 / 12

possible undesirable effects must be considered before beginning the controller’s use, and preventive measures must be adopted in order to assure the integrity of the process and users.
The “TUNE” signaling device will stay on during the tuning process.
In the case of PWM or pulse output, the quality of tuning will also depend on the cycle time adjusted previously by the user.
If the tuning does not result in a satisfactory control, refer to Table 8 for guidelines on how to correct the behavior of the process.

PARAMETER

VERIFIED PROBLEM SOLUTION

Proportional Band

Slow answer Great oscillation

Decrease Increase

Rate of Integration

Slow answer Great oscillation

Increase Decrease

Derivative Time

Slow answer or instability Great oscillation

Decrease Increase

Table 8 – Guidance for manual adjustment of the PID parameters

MAINTENANCE

PROBLEMS WITH THE CONTROLLER
Connection errors and inadequate programming are the most common errors found during the controller operation. A final revision may avoid loss of time and damages.
The controller displays some messages to help the user identify problems.

MESSAGE —Err1 Err6

DESCRIPTION OF THE PROBLEM
Open input. No sensor or signal.
Connection and/or configuration errors. Check the wiring and the configuration.

Other error messages may indicate hardware problems requiring maintenance service. When contacting the manufacturer, inform the instrument serial number, obtained by pressing the key for more than 3 seconds.

CALIBRATION OF THE INPUT
All inputs are factory calibrated and recalibration should only be done by qualified personnel. If you are not familiar with these procedures do not attempt to calibrate this instrument.
The calibration steps are:
a) Configure the type of input to be calibrated.
b) Configure the lower and upper limits of indication for the maximum span of the selected input type.
c) At the input terminals inject a signal corresponding to a known indication value a little above the lower display limit.
d) Access the parameter “inLC”. With the keys and adjust the display reading such as to match the applied signal. Then press the P key.
e) Inject a signal that corresponds to a value a little lower than the upper limit of indication.
f) Access the parameter “inLC”. With the keys and adjust the display reading such as to match the applied signal. Then press the P key.
Note: When checking the controller calibration with a Pt100 simulator, pay attention to the simulator minimum excitation current requirement, which may not be compatible with the 0.170 mA excitation current provided by the controller.

ANALOG OUTPUT CALIBRATION · Configure I/O 5 for the current output to be calibrated, be it
control or retransmission. · In the screen “Ctrl”, program manual mode (man). · Connect a current meter to the analog output.
NOVUS AUTOMATION

Controller N1200

· Enter the calibration cycle with the correct password.
· Select the screen “ovLC”. Press the keys and for the controller to recognize the calibration process of the current output.
· Read the current indicated on the current meter and adjust the parameter “ovLC” to indicate this current value (use the keys and )
· Select the screen “ovxC”. Press the keys and for the controller to recognize the calibration process of the current output.
· Read the current indicated on the current meter and adjust the parameter “ovkC” to indicate this current value
· Press the key P in order to confirm the calibration procedure and return to the operating level.

SERIAL COMMUNICATION
The controller can be supplied with an asynchronous RS-485 digital communication interface for master-slave connection to a host computer (master).
The controller works as a slave only and all commands are started by the computer which sends a request to the slave address. The addressed unit sends back the requested reply.
Broadcast commands (addressed to all indicator units in a multidrop network) are accepted but no reply is sent back in this case.

CHARACTERISTICS
· Signals compatible with RS-485 standard. MODBUS (RTU) Protocol. Two wire connection between 1 master and up to 31 (addressing up to 247 possible) instruments in bus topology. The communication signals are electrically insulated from the rest of the device;
· Maximum connection distance: 1000 meters.
· Time of disconnection for the controller: Maximum 2 ms after last byte.
· Selectable speed; 8 data bits; 1 stop bit; selectable parity (no parity, pair or odd);
· Time at the beginning of response transmission: maximum 100 ms after receiving the command.
· There is no electrical isolation between serial communication (RS485) and channel I/O5.
The RS-485 signals are:

D1 D D + B Bi-directional data line.

Terminal 16

D0 D: D – A Bi-directional inverted data line.

Terminal 17

C

Optional connection that improves the Terminal 18

performance of the communication. GND

CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION

Two parameters must be configured for using the serial type: bavd: Communication speed. prty: Parity of the communication. addr: Communication address for the controller.

REDUCED REGISTERS TABLE FOR SERIAL COMMUNICATION

COMMUNICATION PROTOCOL

The MOSBUS RTU slave is implemented. All configurable parameters can be accessed for reading or writing through the communication port. Broadcast commands are supported as well (address 0).
The available Modbus commands are:

03 – Read Holding Register 05 – Force Single Coil

06 – Preset Single Register 16 – Preset Multiple Register

11 / 12

HOLDING REGISTERS TABLE

Follows a description of the usual communication registers. For full documentation download the Registers Table for Serial Communication in the N1200 section of our website ­ www.novusautomation.com.

All registers are 16 bit signed integers.

Address Parameter

Register Description

0000 Active SP Read: Active control SP (main SP, from ramp and soak or from remote SP). Write: to main SP. Range: from spll to spkl.

0001

PV Read: Process Variable.

Write: Not allowed.

Range: Minimum value is the one

configured in spll and the maximum value

is the one configured in spkl. Decimal

point position depends on dppo value.

In case of temperature reading, the value

read is always multiplied by 10,

independently of dppo value.

0002

MV Read: Output Power in automatic or manual

mode.

Write: Not allowed. See address 28.

Range: 0 to 1000 (0.0 to 100.0 %).

SPECIFICATIONS
DIMENSIONS:…………………………………. 48 x 48 x 110 mm (1/16 DIN) Cutout in the Panel: …………………45.5 x 45.5 mm (+0.5 -0.0 mm) Approximate Weight: …………………………………………………… 150 g
POWER SUPPLY………………..100 to 240 Vac/dc (±10 %), 50 / 60 Hz Optionally 24V: ………………12 to 24 Vdc / 24 Vac (-10 % / +20 %) Maximum consumption:………………………………………………… 9 VA
ENVIRONMENTAL CONDITIONS: Operation Temperature: ……………………………………….. 5 to 50 °C Relative Humidity: ……………………………………80 % max. @ 30 ºC For temperatures above 30 ºC, reduce 3 % for each ºC Internal Use; Category of installation II, Degree of pollution 2; altitude < 2000 m
INPUT………….T/C, Pt100, voltage and current (according to Table 1) Internal Resolution: ……………………………. 32767 levels (15 bits) Resolution of Display: …. 12000 levels (from – 1999 up to 9999) Rate of input reading: ……………………………up to 55 per second Accuracy: .Thermocouples J, K, T, E: 0.25 % of the span ±1 ºC ……………….Thermocouples N, R, S, B: 0.25 % of the span ±3 ºC ……………………………………………………….Pt100: 0.2 % of the span …………. 4-20 mA, 0-50 mV, 0-5 Vdc, 0-10 Vdc: 0.2 % of the span Input Impedance: 0-50 mV, Pt100 and Thermocouples: >10 M ……………………………………………………………………… 0-5 V: >1 M ………………………………………… 4-20 mA: 15 (+2 Vdc @ 20 mA) Measurement of Pt100: …………… Three wire type, (=0.00385) with compensation for cable length, excitation current of 0.170 mA.
All input and output types are factory-calibrated. Thermocouples according to standard NBR 12771 / 99, RTD’s NBR 13773 / 97;
ANALOGICAL OUTPUT (I/O5): …..0-20 mA or 4-20 mA, 550 max. 31000 levels, insulated, for control or retransmission of PV and SP
CONTROL OUTPUT: 2 Relays SPST-NA (I/O1 and I/O2): 1.5 A / 240 Vac, general use ……………………..1 Relay SPDT (I/O3): 3 A / 250 Vac, general use ……………………..Voltage pulse for SSR (I/O5): 10 V max. / 20 mA …………. Voltage pulse for SSR (I/O3 and I/O4): 5 V max. / 20 mA
ELECTROMAGNETIC COMPATIBILITY:…………… EN 61326-1:1997
and EN 61326-1 / A1:1998
SAFETY: …………………… EN61010-1:1993 and EN61010-1 / A2:1995
USB INTERFACE 2.0, CDC CLASS (VIRTUAL COMMUNICATIONS PORT), MODBUS RTU PROTOCOL.

NOVUS AUTOMATION

Controller N1200

SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6.3 MM;
FRONT PANEL: …………………………..IP65, polycarbonate – UL94 V-2 CASE: ………………………………………………… IP20, ABS+PC UL94 V-0 STARTS UP OPERATION: after 3 seconds connected to the power supply;
CERTIFICATIONS: ………………………………….CE / UL (FILE: 300526)

IDENTIFICATION

N1200 –

3R –

485 –

24V

A

B

C

D

A: Controller Model: N1200;
B: Optional I/Os: Blank (basic version, without I/O3 nor I/O4); 3R (SPDT Relay in I/O3); DIO (Digital I/Os in I/O3 and I/O4); HBD (Burnt-Out Resistance detection);
C: Digital Communication: Blank (basic version, without serial communication); 485 (RS485, Modbus protocol)
D: Power Supply: Blank (basic version, 100 to 240 Vac/dc input); 24V (12 to 24 Vdc / 24 Vac input voltage);

WARRANTY
Warranty conditions are available on our website www.novusautomation.com/warranty.

12 / 12

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Novus User Manuals

Related Manuals