Altronix LPS5C24X220 Linear Power Supply Charger Owner’s Manual

June 3, 2024
Altronix

LPS5C24X220 Linear Power Supply Charger
Owner’s Manual

Overview:

Altronix LPS5C24X220 linear power supply/charger converts a 220VAC 50/60Hz input to a 24VDC @ 3.5A continuous supply current. The output stays regulated until the batteries discharge to 25% capacity.

Specifications:

Input:

  • 220VAC 50/60Hz, 0.8A.

Output:

  • 24VDC @ 3.5A.
  • Filtered and electronically regulated.
  • Thermal and overload protection with auto reset.

Battery Backup:

  • Built-in charger for sealed lead acid batteries.
  • Automatic switchover to stand-by battery when AC Fails.
  • PTC battery protection.
  • Maximum charge current 0.3A.
  • Battery leads included.

Visual Indicators:

  • AC input and DC output LED indicators.

Supervision:

  • Low battery and AC fail supervision (dry relay outputs 1A @ 28VDC).

Enclosure Dimensions:
13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)

Power Supply Voltage Output Specifications:

Output VDC Maximum Load DC
24VDC 3.5A

Installation Instructions:

The LPS5C24X220 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.

  1. Mount the LPS5C24X220 in the desired location.
  2. Connect the unswitched AC circuit (220VAC, 50/60Hz) as follows: Green branch wire (ground) connects to the terminal marked ****, Line connects to the terminal marked [L], and Neutral connects to the terminal marked [N] of the Inlet Appliance Connector. Use 18 AWG or larger for all power connections (Battery, DC output).
  3. Measure output voltage before connecting devices. This helps avoid potential damage.
  4. Connect devices to be powered to the terminals marked [+ DC —] (Fig. 1).
  5. Connect the battery to the terminals marked [+ BAT —] on the unit (battery leads included) (Fig. 1).

Note: When batteries are not used, a loss of AC will result in a loss of output voltage.

Terminal Identification:

Terminal Legend Function/Description
AC/AC Low voltage AC input (24VAC 150VA).
+ BAT – Stand-by battery connections.
+ DC – 24VDC @ 3.5A continuous output.

LED Diagnostics:

Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. The standby battery is supplying power.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or missing standby battery. No DC output.

Enclosure Dimensions (H x W x D approximate): 13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)Altronix LPS5C24X220 Linear Power Supply
Charger - Dimensions

Altronix is not responsible for any typographical errors.
Product specifications are subject to change without notice.
140 58th Street, Brooklyn,
New York 11220 USA
Phone: 718-567-8181
Fax: 718-567-9056
Website: www.altronix.com
E-mail: info@altronix.com
Lifetime Warranty
IILPS5C24X220 Rev. 051105 L09U

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Altronix User Manuals

Related Manuals