DAIKIN IM 1314 High Duct Pressure Limit Switch Instruction Manual

June 6, 2024
Daikin

Daikin logo

Installation and Maintenance Manual                   IM 1314

Group: WSHP
Part Number: 910339000
Date: January 2021

High Duct Pressure Limit Switch

DAIKIN IM 1314 High Duct Pressure Limit Switch

High Duct Pressure Limit Switch
Included Parts:
  • High Duct Limit Pressure Switch
  • (2) 120″ Black Wires with connectors
Installation
  • Locate the field provided duct pressure tap downstream static pressure.
  • Mount sensor on the supply duct near the location selected for the duct pressure. See Figure 2
  • Connect the field provided tube between the tap and the high pressure (H) port on the sensor.
  • Run the wires provided from the sensor location to the unit.
  • Refer to Figure 3 and Figure 4 on page 3 and connect the first wire from the Normally Open terminal on the sensor to pin 13 on the unit terminal strip. Connect the second wire from the Common terminal on the sensor to pin 26 on the unit terminal strip.

Figure 1: Mounting Holes Locations

DAIKIN IM 1314 High Duct Pressure Limit Switch figure
1

Figure 2: Sensing Tube Location

DAIKIN IM 1314 High Duct Pressure Limit Switch figure
2

Figure 3: Unit Terminal Connections
DAIKIN IM 1314 High Duct Pressure Limit Switch figure
3

Figure 4: Unit Terminals to Switch Terminals

DAIKIN IM 1314 High Duct Pressure Limit Switch figure
4

Programming:

This High Duct Pressure Limit is automatically enabled and the factory programmed for a Normally Open configuration. If the connected switch closes the High Duct Limit fault occurs and the unit will initiate an immediate shutdown. The input can be reconfigured for a Normally Closed state. Changes can be made through the local user interface or through the ServiceTools software for Microtech® Unit Controllers program on a connected PC. For information on how to use the ServiceTools software, refer to OM 732. The local user interface menu path is shown below.

  • To change the polarity of the Duct High Limit Switch input, go to Service > Serv-BinIn > Serv-BinIn-Config > CfgRevBI4 and change the value from Reverse to Direct.

If using the ServiceTools software change the unit configuration as follows:

  • To change the polarity of the Duct High Limit Switch input, go to the Configuration’ menu and under theInputs’ drop down change DI 4 Polarity’ toDirect’.

Click the Save button after making changes so they take effect. ServiceTools prompts you to save if you are switching to another screen without saving.

Daikin logo

Daikin Applied Training and Development

Now that you have made an investment in modern, efficient Daikin equipment, its care should be a high priority. For training information on all Daikin HVAC products, please visit us at www.DaikinApplied.com and click on Training, or call 540-248-9646 and ask for the Training Department.

Warranty

All Daikin equipment is sold pursuant to its standard terms and conditions of sale, including Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. Refer to Form 933-430285Y. To find your local Daikin Applied representative, go to www.DaikinApplied.com.

Aftermarket Services

To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.

This document contains the most current product information as of this printing. For the most up-to-date product information, please go to www.DaikinApplied.com.

Products manufactured in an ISO Certified Facility.

IM 1314

©2021 Daikin Applied (01/21) | (800) 432­1342 | www.DaikinApplied.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Daikin User Manuals

Related Manuals