Qlima D620 Electric Dehumidifier User Manual
- June 6, 2024
- Qlima
Table of Contents
- Qlima D620 Electric Dehumidifier
- IMPORTANT COMPONENTS
- SAFETY INSTRUCTIONS
- INSTRUCTIONS FOR REPAIRING APPLIANCES CONTAINING R290 / R32
- REPAIR TO INTRINSICALLY SAFE COMPONENTS
- THE CONTROL PANEL
- AIR FILTER
- DRAINAGE OPTION
- CLEANING AND MAINTENANCE
- TROUBLESHOOTING
- CONDITIONS OF WARRANTY
- TECHNICAL SPECIFICATIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Qlima D620 Electric Dehumidifier
IMPORTANT COMPONENTS
SAFETY INSTRUCTIONS
Read this user manual carefully before using the appliance and keep it for
future reference. Install this device only when it complies with
local/national legislation, ordinances and standards. This product is intended
to be used as a dehumidi-fier in residential houses and is only suitable for
use in normal household conditions, indoors in living room, kitchen, bathroom
and garage. This unit is only suitable for earthed sockets, connec-tion
voltage 220-240 V. / ~50 Hz.
GENERAL
-
To obtain optimum performance from your dehumidifier, do not place it near a radiator or any other heat source.
-
Ensure that all windows are closed in order to achieve maximum efficiency.
-
The capacity of the dehumidifier depends on the temperature and the humidity in the room. At lower temperatures, less moisture will be removed.
-
Ensure that the screen filter is kept clean. This prevents unnecessary power consumption and guarantees optimum efficiency.
-
If the power supply has been interrupted, the dehumidifier will restart after 5 minutes. The automatic delay protects the compressor.
-
IMPORTANT
The device MUST always have an earthed connection. If the power supply is not earthed, you may not connect the unit. The plug must always be easily accessible when the unit is connected. Read these instructions carefully and follow the instructions. Before connecting the unit, check the following: -
The voltage supply must correspond with the mains voltage stated on the rating label.
-
The socket and power supply must be suitable for the current stated on the rating label.
-
The plug on the cable of the device must fit into the wall socket.
-
The device must be placed on a flat and stable surface. The electricity supply to the device must be checked by a recognised professional if you have any doubts regarding the compatibility.
-
This appliance is not intended for use by per-sons (including children) with reduced physical, sensory or mental capabilities, or lack of expe-rience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
-
This device is manufactured according to CE safety standards. Nevertheless, you must take care, as with any other electrical device.
-
Do not cover the air inlet and/or outlet.
-
Empty the water reservoir before moving the unit.
-
Never allow the device to come into contact with chemicals.
-
Never submerge the unit in water.
-
Do not insert objects into the openings of the unit.
-
Always remove the plug from the electric power supply before cleaning or replacing the unit or components of the unit.
-
Never use an extension cable to connect the device to the electric power supply. If there is no suitable, earthed wall socket available, have one installed by a recognized electrician.
-
Children should be supervised to ensure that they do not play with the appliance.
-
Have any repairs only carried out by a recognised service engineer or your supplier. Follow the instructions for use and maintenance as indicated in the user manual of this device.
-
Always remove the plug of the unit from the wall socket when it is not in use.
-
If the power cable is damaged it must be replaced by the manufacturer, its customer service department or persons with comparable qualifications in order to prevent danger.
-
This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction con-cerning use of the appliance in a safe way and understand the hazards involved.
-
Children shall not play with the appliance.
-
Cleaning and user maintenance shall not be made by children without supervision.
Specific information regarding appliances with R 290 refrigerant gas.
- Thoroughly read all of the warnings.
- When defrosting and cleaning the appliance, do not use any tools other than those recommended by the manufacturing company.
- The appliance must be placed in an area with-out any continuously sources of ignition (for example: open flames, gas or electrical appliances in operation).
- Do not puncture and do not burn.
- This appliance contains Y g (see rating label back of unit) of R290 refrigerant gas.
- R290 is a refrigerant gas that complies with the European directives on the environment. Do not puncture any part of the refrigerant circuit. Be aware the refrigerants may not contain an odour.
- If the appliance is installed, operated or stored in a nonventilated area, the room must be designed to prevent to the accumulation of refrigerant leaks resulting in a risk of fire or explosion due to ignition of the refrigerant caused by electric heaters, stoves, or other sources of ignition.
- The appliance must be stored in such a way as to prevent mechanical failure.
- Individuals who operate or work on the refrig-erant circuit must have the appropriate certifi-cation issued by an accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry.
- Repairs must be performed based on the recommendation from the manufacturing company.
Maintenance and repairs that require
Maintenance and repairs that require the assistance of other qualified
personnel must be performed under the supervision of an individual specified
in the use of flammable refrigerants.
Appliances shall be installed,operated and stored in a room with a floor area
larger than 4 m² (D620) / 12 m² (D625). The appliance shall be stored in a
well-ventilated area where the room size corre-sponds to the room area as
specified for operation.
Specific information regarding appliances with R290 / R32 refrigerant gas.
- Thoroughly read all of the warnings.
- When defrosting and cleaning the appliance, do not use any tools other than those recommended by the manufacturing company.
- The appliance must be placed in an area with-out any continuous sources of ignition (for example: open flames, gas or electrical appliances in operation).
- Do not puncture and do not burn.
- This appliance contains Y g (see rating label back of unit) of R290 / R32 refrigerant gas.
- R290 / R32 is a refrigerant gas that complies with the European directives on the environment. Do not puncture any part of the refrigerant circuit. Be aware the refrigerants may not contain an odour.
- If the appliance is installed, operated or stored in a nonventilated area, the room must be designed to prevent to the accumulation of refrigerant leaks resulting in a risk of fire or explosion due to ignition of the refrigerant caused by electric heaters, stoves, or other sources of ignition.
- The appliance must be stored in such a way as to prevent mechanical failure.
- Individuals who operate or work on the refrigerant circuit must have the appropriate certification issued by an accredited organization that ensures competence in handling refrigerants according to a specific evaluation recognized by associations in the industry.
- Repairs must be performed based on the recommendation from the manufacturing company.
Maintenance and repairs that require the assistance of other qualified
personnel must be performed under the supervision of an individual specified
in the use of flammable refrigerants.
Appliances shall be installed,operated and stored
in a room with a floor area larger than 4 m2. The
appliance shall be stored in a well-ventilated area where the room size
corresponds to the room area as specified for operation.
INSTRUCTIONS FOR REPAIRING APPLIANCES CONTAINING R290 / R32
GENERAL INSTRUCTIONS
This instruction manual is intended for use by individuals possessing adequate backgrounds of electrical, electronic, refrigerant and mechanical experience.
-
Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. -
Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being present while the work is being performed. -
General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material. -
Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe. -
Presence of fire extinguisher
lf any hotwork is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry
powder or CO2 fire extinguisher adjacent to the charging area. -
No ignition sources
No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to thesurrounding space. Prior to worktaking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking” signs shall be displayed. -
Ventilated area
Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it extemally into the atmosphere. -
Checks to the refrigeration equipment
Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. lf in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants: – the charge size is in accordance with the room size within which the refrigerant containing parts are installed; the ventilation machinery and outlets are operating adequately and are not obstructed; if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected; refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components unless the components are constructed of materials that are inherently resistant to being corroded or are suitably protected against being so corroded.
Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. lf a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. lf the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. lnitial safety checks shall include:
- that capacitor are discharged: this shall be done in a safe manner to avoid the possibility of sparking;
- that there no live electrical components and wiring are exposed while charging, recovering or purging the system;
- that there is continuity of earth bonding.
REPAIRS TO SEALED COMPONENTS
During repairs to sealed components, all electrical supplies shall be
disconnected from the equipment being worked upon prior to any removal of
sealed covers, etc. lf it is absolutely necessary to have an electrical supply
to equipment during servicing, then a permanently operating form of leak
detection shall be located at the most critical point to warn of a potentially
hazardous situation.
Particular attention shall be paid to the following to ensure that by working
on electrical components, the casing is not altered in such a way that the
level of protection is affected. This shall include damage to cables,
excessive number of connections, terminals not made to original specification,
damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is
mounted securely.
Ensure that seals or sealing materials have not degraded such that they no
longer serve the purpose of preventing the ingress of flammable atmospheres.
Replacement parts shall be in accordance with the manufacturer’s
specifications.
NOTE The use of silicon sealant may inhibit the effectiveness of some
types of leak detection equipment. lntrinsically safe components do not have
to be isolated prior to working on them.
REPAIR TO INTRINSICALLY SAFE COMPONENTS
Do not apply any permanent inductive or capacitance loads to the circuit
without ensuring that this will not exceed the permissible voltage and current
permitted tor the equipment in use.
lntrinsically safe components are the only types that can be worked on while
live in the presence of a flammable atmosphere. The test apparatus shall be at
the correct rating.
Replace components only with parts specified by the manufacturer. Other parts
may result in the ignition of refrigerant in the atmosphere from a leak.
CABLING
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continua! vibration from sources such as compressors or fans.
DETECTION OF FLAMMABLE REFRIGERANTS
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame} shall not be used.
LEAK DETECTION METHODS
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be calibrated in a refrigerant- free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum} is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipework. lf a leak is suspected, all open flames shall be removed/extinguished. lf a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves} in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.
REMOVAL AND EVACUATION
When breaking into the refrigerant circuit to make repairs – or for any other
purpose – conventional procedures shall be used. However, it is important that
best practice is followed since flammability is a consideration. The following
procedure shall be adhered to: remove refrigerant; purge the circuit with
inert gas; evacuate; purge again with inert gas; open the circuit by cutting
or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders.
The system shall be “flushed” with OFN to render the unit safe. This process
may need to be repeated several times. Compressed air or oxygen shall not be
used for this task. Flushing shall be achieved by breaking the vacuum in the
system with OFN and continuing to fill until the working pressure is achieved,
then venting to atmosphere, and finally pulling down to a vacuum. This process
shall be repeated until no refrigerant is within the system. When the final
OFN charge is used, the system shall be vented down to atmospheric pressure to
enable work to take place. This operation is absolutely vital if brazing
operations on the pipework are to take place. Ensure that the outlet tor the
vacuum pump is not close to any ignition sources and !here is ventilation
available.
CHARGING PROCEDURES
In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. Cylinders shall be kept upright. Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. Label the system when charging is complete (if not already). Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.
DECOMMISSIONING
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. lt is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. lt is essential that 4 GB electrical power is available before the task is commenced.
- Become familiar with the equipment and its operation.
- lsolate system electrically.
- Before attempting the procedure ensure that: mechanical handling equipment is available, if required, for handling refrigerant cylinders;
- All personal protective equipment is available and being used correctly; the recovery process is supervised at all times by a competent person;
- recovery equipment and cylinders conform to the appropriate standards.
- Pump down refrigerant system, if possible.
- lf a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
- Make sure that cylinder is situated on the scales before recovery takes place.
- Start the recovery machine and operate in accordance with manufacturer’s instructions.
- Do not overfill cylinders. (No more than 80 % volume liquid charge).
- Do not exceed the maximum working pressure of the cylinder, even temporarily.
- When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
- Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
LABELLING
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.
RECOVERY
When removing refrigerant from a system, either for servicing or
decommissioning, il is recommended good practice that all refrigerants are
removed safely. When transferring refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed. Ensure that the
correct number of cylinders for holding the total system charge are available.
All cylinders to be used are designated for the recovered refrigerant and
labeled for that refrigerant (i.e. special cylinders for the recovery of
refrigerant). Cylinders shall be complete with pressure relief valve and
associated shut-off valves in good working order. Empty recovery cylinders are
evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of
instructions concerning the equipment that is at hand and shall be suitable
for the recovery of flammable refrigerants. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be
complete with leak-free disconnect couplings and in good condition. Before
using the recovery machine, check that il is in satisfactory working order,
has been properly maintained and that any associated electrical components are
sealed to prevent ignition in the event of a refrigerant release. Consult the
manufacturer if in doubt. The recovered refrigerant shall be returned to the
refrigerant supplier in the correct recovery cylinder, and the relevant Waste
Transfer Note arranged. Do not mix refrigerants in recovery units and
especially not in cylinders. lf compressors or compressor oils are to be
removed, ensure that they have been evacuated to an acceptable level to make
certain that flammable refrigerant does not remain within the lubricant. The
evacuation process shall be carried out prior to returning the compressor to
the suppliers. Only electric healing to the compressor body shall be employed
to accelerate this process. When oil is drained from a system, il shall be
carried out safely.
ATTENTION!
Never use the device with a damaged power cord, plug, cabinet or control panel. Never trap the power cord or allow it to come into contact with sharp edges.
ATTENTION!
Failing to follow the instructions may lead to nullification of the guarantee on this device.
THE CONTROL PANEL
- Lowest ambient working condition: 5°C / 40% relative humidity
- Highest ambient working condition: 35°C / 90% relative humidity
NOTE!
- Water bucket must be correctly installed for the dehumidifier to operate.
- Do not remove the bucket while unit is in operation.
- If you want to use drain hose to drain water away, please install the hose according to section “Drainage method”.
- Each time pressing the effective button on the control panel will give out a “beep” sound.
- When tuning on the unit, the running indicator is ON. Running indicator is OFF under standby status.
FUNCTIONS & NAME OF KEY PADS
- (On/Off): Switch on/off the power
- Mode: Press the button to set automatic drying (Dry) or dehumidification (Dehu).
- Lock: Press to lock the keys
- Set: To set CO (continuous operation) or desired h idity leve
- Press the “Night ode” button to t indicatio light off. cept the CHILD lock light
- Swing: Press to control the lo er
- Speed: Press to set fan speed Timer: On/Off timer setting
OPERATION OF KEY PADS
-
When the unit is plugged into a power socket, 2 beep signals can be heard. The display will remain blank until the On/Off power button is pressed.
-
Press “ MODE” to set humidistat (Dehu) or dry mode (Dry)
-
In Dry mode the Dry symbol appears along with CO (continuous) on the display. The fan speed will increase to the highest fourth fan speed (only available in Laundry Mode). Having this higher fan speed is key to drying things faster. We recommend also activating the swing louvre mode to help move the air across the item to be dried.
-
When selected “Dehu” mode. You can press the SET to select a target relative humidity (40%~50%~60%~70%~CO). There is also the option of CO which stands for continuous and means that the machine will not stop at a particular relative humidity but will continue to dry regardless of the room relative humidity.
-
CHILD LOCK Press the button of “LOCK” for 3 second to activate lock function then fall function keys are locked. To release this feature. Press LOCK key again 3
seconds. -
Press the “SET” to set desired humidity 40%~50%~60%~70%~CO.
Recommend to set humidity value in 50%. For example, when the appliance
detects that the current environment humidity is higher than or equal to 55%RH, the appliance start and fan runs at high speed; when the appliance detects that
the current environment humidity is less than or equal to 49%RH, compressor
stop and fan runs at low speed, the power indicator light will illuminate. -
SWING: Press the button to switch on/off swing performance.
Press “SWING” to turn the air outlet louver move or stop. -
SPEED
Press “SPEED” to select the fan working at “High speed” or “Low speed”. -
TIMER (On or Off)
The appliance must be connected to the mains socket outlet and power provided to the appliance.
With the appliance switched OFF at the control panel (the display and all LEDs will be OFF), press the TIMER button repeatedly to select the number of hours (1H/2H/4H/8H) that will pass before the appliance switches ON.
To switch OFF the appliance:
With the appliance switched ON at a the control panel, press the TIMER button repeatedly to select the number of hours (1H/2H/4H/8H) that will pass before the appliance switches OFF. -
INDICATION LIGHT BAR
-
When the machine is running, the blue light is on.
-
When the water tank is full, the orange light is on and tank “Full” indication light on
-
NIGHT MODE
Pressing the light button when the machine is working makes the buzzer bleep for one time. Digital display, LED light and blue decoration light are off but the power light is on. (Note: the child lock light is on if the machine is at child lock mode.) When pressing the light button again the buzzer bleeps one time. Digital display works normally, corresponding mode or function lights show normally.
WATER FULL
When tank is full, device will automatically shut off and buzzer will alarm 10
times. The indication light of “power” and “tank full” will illuminate.
The dehumidifying process will only restart once the condensate tank has been
emptied and re-installed. Once re-installed correctly the LED will turn off.
DO NOT attempt to modify or remove the float mechanism; this could result in
the tank overflowing.
AUTO RESTART
- If the unit is turned off unit and is in stand-by, the device will recall the last setting when turned on again.
- In the event of a power failure, the machine will restart automatically at the settings selected prior to the power interruption.
- If user sets the “child lock” and “timer” functions, the device will shut off when time is up, but the child lock function will be turned off when the unit restarts.
time is up, but the child lock function will be turned off when the unit restarts.
AUTOMATIC DEFROSTING
When the machine is working in low temperatures the evaporator may frost. In order to protect cooling system, this device is provided with an automatic defrosting function.
COMPRESSOR PROTECTION FUNCTION
This device is equipped with a compressor protection function so the fan will run for 3 minutes before the compressor kicks in.
REFRIGERANT LEAKAGE DETECTION FUNCTION
The refrigerant leakage function will shut off the device automatically if any leak is detected. The digital display will flash and the buttons will be unresponsive until the unit has been restarted.
CONTINUOUS DRAINAGE
Drainage hose 15mm is included. Insert drainage hose to drain outlet and extend the hose to a suitable drainage facility.
AIR FILTER
The dehumidifiers are equipped with a 3-layer filter package to clean the circulated room air. The 3-layer filter package consists of a screen filter and (separately packed) Apollo and active carbon filter. These filters must be placed according to the instructions before operating the dehumidifiers.
- Screen filter; to remove bigger dust particles.
- Apollo filter; to remove unhealthy particles from the air such as pollen, bacteria, animal dander and dust.
- Active carbon filter sheet; to remove odours.
TO CLEAN, INSPECT OR EXCHANGE THE FILTERS TAKING OUT THE FILTERS:
- Take out the water container (see chapter ‘DRAINAGE OPTION’).
- Take out the screen filter by firmly pressing down the top of the screen filter with 2 or 3 fingers. The screen filter will bend and the two securing hooks at the top side of the screen filter will be releasable from its dedicated holes. The screen filter is now disconnected and can be easily removed.
- Take out the now visible Apollo filter and the active carbon filter
The screen filter has to be cleaned regularly with a vacuum cleaner to avoid blocking of the air flow. It does not need periodically replacement. New filter Recommended change of filter The active carbon sheet can be cleaned with a vacuum cleaner when dusty but has to be changed at the same time as the Apollo filter.
NOTE!
-
Never use the dehumidifier without the screen filter!
-
To run the unit without active carbon sheet and/or Apollo filter package does not bring any harm to the dehumidifier. In that case unhealthy dust is not removed.
-
Replacement filters are available at your dealer. / www.qlima.com
REPOSITIONING THE FILTERS:
- Reposition the new Apollo filter and new active carbon filter. The active carbon filter at the most inner side of the machine, the Apollo filter at the most outer side of the machine.
- Place the lower end 2 hooks in the dedicated holes, reposition the top end two hooks into the dedicated 2 holes. The screen filter will need to be bend a little, this must be done by pressing on the top of the screen filter with 2 or 3 fingers.
If the green filter light stays on despite cleaning, reset the service time of 168 hours of use indicating the cleaning of the filter. Simply press the “timer” button for 5 seconds while the unit is in operation. The indicator light will flash 5 times, thus resetting the filter service time. The green light goes out.
DRAINAGE OPTION
OPTION 1 EMPTYING MANUALLY
Notes:
- Do not remove the bucket when unit is in operation or has just stopped. Otherwise it may cause some water to drip on the floor.
- Do not use the hose if using water bucket to collect water. When the hose is connected, water will be drained out through it instead of into the bucket.
- the handle at the bottom of the water bucket and pull it out folllowing the arrow direction.
- Empty the bucket by grasping the handle on the bottom of bucket with one hand and grasping the top of bucket with the other hand.
- Replace bucket in the dehumidifier according to the arrow direction.
OPTION 2 GRAVITY DRAIN HOSE
- Use the hose included in the packaging.
- Remove bucket from the unit as instructed.
- Thread the drain hose onto the nozzle and make sure it’s securely locked.
- Replace the bucket. Make sure the drain hose goes through the buckets drain hole and is placed downward. Lead the hose to the floor drain and then cover the hole with a lid. Note that drain hose should not be pressed, otherwise water can not be drained out.
NOTE!
When you want to take off the drain hose, prepare a receptacle to collect
water from the nozzle.
CLEANING AND MAINTENANCE
WARNING:
- Before cleaning, turn off the dehumidifier and disconnect power. Otherwise it may lead to electric shock.
- Do not wash the dehumidifier with water, or it may lead to electric shock.
- Do not use volatile liquid(such as thinner or gasoline) to clean dehumidifier. Otherwise it will damage unit’s appearance.
GRILLE AND CASE
To clean the case: When there is dust on the case, use soft towel to dust it off; When the case is very dirty(greasy), use mild detergent to clean it. To clean the grille: Use a dust catcher or brush.
CARE AFTER USE-SEASON
- Disconnect power.
- Clean air filter and case.
- Clean dust and obstacle of the dehumidifier.
- Empty the water bucket.
TROUBLESHOOTING
Check the following before contacting technical support.
Problem | Ursache | Abhilfe |
---|---|---|
Das Gerät funktioniert nicht. | Der Stecker steckt nicht in der Steckdose. |
Stecken Sie den Stecker in die Steckdose.
Das Gerät entfeuchtet nicht.| Der Wasserbehälter ist voll.| Entleeren Sie den
Wasserbe- hälter.
Der Wasserbehälter wurde nicht richtig eingesetzt.| Setzen Sie den
Wasserbehäl- ter richtig ein.
Der Luftfilter ist verschmutzt.| Reinigen Sie den Luftfilter.
Die Temperatur bzw. die relati- ve Luftfeuchtigkeit des Raums, in dem das
Gerät steht, ist zu niedrig.| Unter diesen Umständen ist es normal, dass das
Gerät nicht entfeuchtet.
Der Entfeuchter ist in Betrieb, er senkt die re- lative Luftfeuchtigkeit
jedoch nicht genügend.| Der Raum ist zu groß.| Es empfiehlt sich, einen Ent-
feuchter mit größerer Kapazi- tät aufzustellen.
Es gibt zu viele Feuchtigkeits- quellen.| Es empfiehlt sich, einen Ent-
feuchter mit größerer Kapazi- tät aufzustellen.
Es wird zu viel belüftet.| Schränken Sie bitte die Be- lüftung ein (z.B. Türen
und Fenster schließen).
Service-Licht brennt.| Wenn die Wartungszeit 168 Stunden erreicht, leuchtet
die Filterreinigungsanzeige auf.| Reinigen Sie den Filter und setzen Sie den
Service-Timer zurück.
Filter wurde bereinigt, aber der Service-Timer wurde nicht zurückgesetzt|
Drücken Sie bei laufendem Gerät die Timer-Taste für 5 Sekunden. Der Summer
ertönt einmal und die Filteranzeige blinkt 5 Mal.
CONDITIONS OF WARRANTY
There is a two-year warranty on your dehumidifier from the date of purchase.
All material or manufacturing defects will be repaired free of charge.
The following applies:
- All claims for compensation, including consequential damage, will not be entertained.
- Any repairs or replacement of components during the warranty period will not result in an extension of the warranty period.
- The warranty will expire if any alterations have been made, not genuine components have been fitted or if the dehumidifier has been repaired by a third party.
- Components subject to normal wear and tear, such as the air filter, are not covered by the warranty.
- The warranty is only valid on presentation of the original, unaltered, and date-stamped purchase receipt.
- The warranty does not cover damage caused by actions that deviate from those as described in the user’s manual or by neglect.
- Transportation costs and the risks involved during the transportation of the dehumidifier or components shall always be for the account of the purchaser.
To prevent unnecessary expenses, we recommend that you always carefully read
the user’s manual first. If this does not provide a solution, take the
dehumidifier to your distributor for repair.
Do not dispose of electrical appliances as unsorted municipal waste, use
separate collection facilities. Contact your local government for information
regarding the collection systems available. If electrical appliances are
disposed of in landfills or dumps, hazardous substances can leak into the
groundwater and get into the food chain, damaging your health and well-being.
When replacing old appliances with new once, the retailer is legally obligated
to take back your old appliance for disposal at least for free of charge. Do
not throw batteries into the fire, where they can explode or release dangerous
liquids. If you replace or destroy the remote control, remove the batteries
and throw them away in accordance with the applicable regulations because they
are harmful to the environment.
Environmental information: This equipment contains fluorinated greenhouse
gases covered by the Kyoto Protocol. It should only be serviced or dismantled
by professional trained personnel.
This equipment contains R290 refrigerant in the amount as stated in the table
above. Do not vent R290 into atmosphere: R290, is a fluorinated greenhouse gas
with a Global Warming Potential (GWP) = 3
TECHNICAL SPECIFICATIONS
Problem | Ursache | Abhilfe |
---|---|---|
Das Gerät funktioniert nicht. | Der Stecker steckt nicht in der Steckdose. |
Stecken Sie den Stecker in die Steckdose.
Das Gerät entfeuchtet nicht.| Der Wasserbehälter ist voll.| Entleeren Sie den
Wasserbe- hälter.
Der Wasserbehälter wurde nicht richtig eingesetzt.| Setzen Sie den
Wasserbehäl- ter richtig ein.
Der Luftfilter ist verschmutzt.| Reinigen Sie den Luftfilter.
Die Temperatur bzw. die relati- ve Luftfeuchtigkeit des Raums, in dem das
Gerät steht, ist zu niedrig.| Unter diesen Umständen ist es normal, dass das
Gerät nicht entfeuchtet.
Der Entfeuchter ist in Betrieb, er senkt die re- lative Luftfeuchtigkeit
jedoch nicht genügend.| Der Raum ist zu groß.| Es empfiehlt sich, einen Ent-
feuchter mit größerer Kapazi- tät aufzustellen.
Es gibt zu viele Feuchtigkeits- quellen.| Es empfiehlt sich, einen Ent-
feuchter mit größerer Kapazi- tät aufzustellen.
Es wird zu viel belüftet.| Schränken Sie bitte die Be- lüftung ein (z.B. Türen
und Fenster schließen).
Service-Licht brennt.| Wenn die Wartungszeit 168 Stunden erreicht, leuchtet
die Filterreinigungsanzeige auf.| Reinigen Sie den Filter und setzen Sie den
Service-Timer zurück.
Filter wurde bereinigt, aber der Service-Timer wurde nicht zurückgesetzt|
Drücken Sie bei laufendem Gerät die Timer-Taste für 5 Sekunden. Der Summer
ertönt einmal und die Filteranzeige blinkt 5 Mal.
- To be used as indication
Subject to change without prior notice.
References
- Qlima homepage
- Welcome to Comfortable Living: Explore Qlima's Home Page for Innovative Heating and Cooling Solutions
- Page d'accueil Qlima
- Qlima, esperti del comfort domestico
- Qlima homepage
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>