Midea Two-Way Cassette The 2nd Generation DC VRF Indoor Unit User Manual
- June 5, 2024
- Midea
Table of Contents
Two-Way Cassette The 2nd Generation DC VRF Indoor Unit
Installation and Operation Manual
Two-way Cassette
The 2nd generation DC VRF indoor unit
Original instructions Thank you very much for purchasing our air conditioner.
Before using your air conditioner, please read this manual carefully and keep
it for future reference.
Contents Installation Manual……………………………………………………………………1
· Make sure the power cord, communication and controller wiring are straight and level when you are working on the connections, and the
Accessories…………………………………………………………………………….3 1. Before Installation ………………………………………………………………4 2. Choosing an Installation Site ………………………………………………4 3. Indoor Unit Installation…………………………………………………………4
cover on the electric box is tight. If the electric box is not closed properly, it may lead to electric shock, fire or overheating of electrical components. · If the refrigerant leaks during installation, open the doors and windows immediately to ventilate the area. Refrigerant can produce
4. Refrigerant Piping Installation ………………………………………………8 5. Water Discharge Piping Installation ………………………………………9 6. Electrical Wiring ………………………………………………………………..9 7. On-site Configuration ……………………………………………………… 12 8. Test Run………………………………………………………………………… 13 9. Part Names …………………………………………………………………… 14 10. The Explain Of The Display Panel……………………………………….15 11. Air Conditioner Operations and Performance ……………………… 15
toxic gases when in contact with fire. · Switch off the power supply before
touching any electrical
component. · Do not touch the switch with wet hands. This is to prevent
electrical
shocks. · Do not come in direct contact with the refrigerant leaking from the
connections of refrigerant piping. Otherwise, it may lead to frostbite. · The
air conditioner must be grounded. Do not connect the earth line
(ground) to gas piping, water piping, lightning rods or telephone earth lines.
Improper grounding can lead to electric shock or fire,
12. Adjusting Air Flow Direction ……………………………………………… 16
and may cause mechanical failure due to current surges from
13. Maintenance…………………………………………………………………… 16 14. Symptoms That Are Not Faults ………………………………………… 17 15. Troubleshooting ……………………………………………………………… 17
lightning and so on. · The earth leakage circuit breaker must be installed.
There is a risk
of electric shock or fire if the earth leakage circuit breaker is not
installed.
Installation Manual
Safety Precautions Read carefully before you install the air conditioner to
make sure that the installation is correct.
· The appliance shall be installed in accordance with national wiring
regulations.
· The appliance must be installed 2,3m above floor.
· If the supply cord is damaged, it must be replaced by the manufacturer or
its service agent or a similarly qualified person in
There are two types of precautions as described below: Warning: Failure to
comply may lead to death or serious injury. Caution: Failure to comply may
lead to injury or damage of the
unit. Depending on the situation, this may also lead to serious injury. Once
the installation is completed, and the unit has been tested and
order to avoid a hazard.
· An all-pole disconnection switch having a contact separation of at least 3mm
in all poles should be connected in fixed wiring.
· The temperature of refrigerant circuit will be high, please keep the
interconnection cable away from the copper tube.
verified to be operating normally, please explain to the customer how to use and maintain the unit according to this manual. In addition, make sure that the manual is kept properly for future reference.
· The power cord type designation is H05RN-For above/H07RN-F. · Check the
power supply before installation. Ensure that the power
supply must be reliably grounded following local, state and National
Electrical Codes. If not, for example, if the ground wire is detected
Warning
charged, installation is prohibited before it is rectified. Otherwise, there is a risk of fire and electric shock, causing physical injury or
· Installation, maintenance and cleaning the filter work must be carried out
by professional installers. Refrain from doing it yourself. Improper
installation may cause water leakage, electric shock, or fire.
· Install the air conditioner according to the steps described in this manual.
Improper installation may cause water leakage, electric shock, or fire.
· For installation in smaller rooms, you must adopt the relevant measures to
prevent the refrigerant concentration from exceeding
death.
· Check the electric wire, water and gas pipeline layout inside the wall,
floor and ceiling before installation. Do not implement drilling unless
confirm safety with the user, especially for the hidden power wire. An
electroprobe can be used to test whether a wire is passing by at the drilling
location, to prevent physical injury or death caused by insulation broken
cords.
the limit. Please consult the sales agent on the relevant measures required. A high concentration of refrigerant in an airtight space can cause oxygen insufficiency (anoxia). · Make sure the required parts and accessories are installed. Using unspecified parts may cause the air conditioner to malfunction or drop, as well as water leakage, electric shock, and fire. · Mount the air conditioner in a place that is sturdy enough to bear its weight. If the base is not secured properly, the air conditioner may drop leading to damages and injuries. · Take in full consideration to the effects of strong winds, typhoons and earthquakes, and reinforce the installation. Improper installation may cause the air conditioner to drop leading to accidents. · Make sure a standalone circuit is used for the power supply. All electrical parts must comply with the local laws and regulations, and what is stated in this installation manual. The installation works must be carried out by a professional and qualified electrician. Insufficient capacity or improper electrical works can lead to electric shock or fire. · Use only electrical cables that fulfil the specifications. All wiring on site must be carried out in accordance with the connection diagram
Caution
· Install the water discharge piping according to the steps described in this
manual, and make sure that the water discharge is smooth, and the piping is
properly insulated to prevent condensation. Improper installation of the water
discharge piping may lead to water leakage, and damage the indoor furniture.
· When mounting the indoor and outdoor units, make sure the power cord is
installed at a distance of at least 1 m away from any TV or radio so as to
prevent noise or interference with the images.
· The refrigerant required for the installation is R410A. Make sure the
refrigerant is correct before installation. Incorrect refrigerant may cause
the unit to malfunction.
· Do not install the air conditioner in the following places: 1) Where there
is oil or gas, such as the kitchen. Otherwise, the plastic parts may age, fall
off or water may leak. 2) Where there are corrosive gases (such as sulphur
dioxide). Corrosion in the copper pipes or welded parts may cause the
refrigerant to leak.
attached to the product. Make sure that there are no external forces
acting on the terminals and wires. Improper wiring and installation
may cause a fire.
1
- Where there are machines emitting electromagnetic waves. Electromagnetic waves may interfere with the control system, causing the unit to malfunction.
- Where there is a high salt content in the air. When exposed to air with a high salt content, the mechanical parts will experience accelerated ageing which will severely compromise the service life of the unit.
- Where there are major voltage fluctuations. Operating the unit using a power supply system that has large voltage fluctuations will reduce the service life of the electronic components, and cause the unit’s controller system to malfunction.
- Where there is a risk of leakage of flammable gases. Examples are sites that contain carbon fibres or combustible dust in the air, or where there are volatile combustibles (such as diluent or petrol). The above gases may cause explosion and fire.
- Do not touch the fins of the heat exchanger as this may lead to injury.
- Some products use the PP packing belt. Do not pull or tug on the PP packing belt when you transport the product. It will be dangerous if the packing belt breaks.
- Note the recycling requirements for nails, wood, carton and other packaging
materials. Do not discard these materials directly as these may lead to bodily
harm.
10)Tear up the packaging bag for recycling to prevent children from playing with it, and leading to suffocation.
11)The appliance shall not be installed in the laundry.
2
Accessories
Verify that the air conditioner includes the following accessories.
Code
Name
1
Installation Manual
2
Nut
3
Washer
4
Insulation casing for copper pipe
5
Bolt (M6)
6
Connecting wire group
7
Insulation casing for copper pipe
8
Foam (250x250x10)
9
Foam (60x100x5)
10
Insulation casing for water discharge piping
11
Ring clamp for water discharge pipe
12
Tie for water discharge piping
13
Soft flexible hose for water discharge
14
Brass nut
Appearance
Qty
1
8
8
1
4 1 1
1 1 1
1 5 1 1
Accessories to purchase locally
Code Name
Appearance
1
Copper pipe
2
PVC pipe for water discharge
Insulation
3
casing for
piping
4
Expansion hook anchor
5
Mounting hooks
Dimensions
Choose and purchase copper pipes that correspond to the length and size
calculated for the selected model in the installation manual of the outdoor
unit and your actual project requirements.
Qty
To purchase based on actual project requirements.
Outer diameter: 37-39 mm, inner diameter: 32 mm
The inner diameter is based on the diameter of the copper and PVC pipes. The
thickness of the pipe casing is 10 mm or more. Increase the thickness of the
casing (20 mm or thicker) when the temperature exceeds 30°C or the humidity
exceeds RH80%.
To purchase based on actual project requirements.
To purchase based on actual project requirements.
Note
Use to connect indoor refrigerant piping.
Use to discharge condensed water from the indoor unit.
Protect piping from condensation.
For installation
M10
4
of indoor unit
M10
4
For installation
of indoor unit
3
1. Before Installation
1. Determine the route to move the unit to the installation site. 2. First
unseal and unpack the unit. Then hold on to the seats of the
hanger (4 pcs) to move the unit. Refrain from exerting force on other parts of
the unit, especially the refrigerant piping, water discharge piping, and
plastic parts.
2. Choosing an Installation Site
1. Choose a site that fully complies with the following conditions and user
requirements to install the air conditioning unit.
Well ventilated. Unobstructed airflow. Strong enough to bear the weight of the
indoor unit. Ceiling has no obvious slant. There is sufficient space for
repair and maintenance work to be
carried out. No leakage of flammable gas. The length of the piping between the
indoor and outdoor units is
within the permitted range (refer to the manual on installation of the outdoor
unit). 2. Mounting height Mounting height is 2.5 ~ 3.5 metres. 3. Mount using
the mounting screws. 4. Space required for installation (unit (mm)):
100
100
Figure 2.1
5. Based on the shape of the room, determine the airflow directions for the
installation site. See Figure 2.3 for the schematic on the direction of
airflow.
Figure 2.3
3. Indoor Unit Installation
Make sure that only specified components are used for the installation works.
3.1 Installation with lifting bolts Use different bolts for the installation
depending on the installation environment.
Wooden structure Secure the square rod on the beam to set
the lifting bolts. Square bar material
Beam
Lifting bolt
Ceiling
Figure 3.1
Ceiling
Original concrete slab structure
1500
1500
Use embedded bolts, and pull bolts.
2500mm 1000 350
Floor
Figure 2.2
4
Figure 3.2
Steel framework Directly set and use an angled steel rod for support.
Suspension bolt
Suspension bolt
Angled rod for support
Figure 3.3
Newly set concrete slab structure
Set using embedded appliances, and embedded type of bolts.
2. Install the hooks in four corners based on the layout for the hooks
outlined in the installation board (accessory 4).
Determine the location on the ceiling of the room or building roof for
mounting, and drill four 12 mm X 50-55 mm holes. Then embed and set up the
expansion hook anchors (purchased accessory 4) in these holes. See Figure 3.2.
During the installation of the hooks (purchased accessory 5), make sure that
the concave portion of the hanger corresponds to that of the expansion hook
anchors. Determine the appropriate hook length for installation based on the
ceiling’s height. Remove any excess.
Use M10 or W3/8/ bolts for the screws of the mounting hooks. Take
approximately 1/2 of the screw length for the installed hooks
as the excess length.
Top
Knife-type insertion piece
Sliding-type insertion piece
Reinforced bar
Embedded bolt (hanging and embedded
bolt for piping)
Figure 3.4
Caution
· All bolts should be made from high quality carbon steel (with galvanized
surface or other rust prevention treatment) or stainless steel.
· How the ceiling should be handled will differ with the type of building. For
specific measures, please consult the building and renovation engineers.
· How the lifting bolt should be secured depends on the specific situation,
and it must be secure and reliable.
3.2. Indoor Unit Installation
3.2.1 Installation sequence for existing ceiling: Must maintain the ceiling at
a level position.
1. Drill 1390 mm x 640 mm holes into the ceiling based on the layout of the
installation board (accessory 4). See Figure 3.5.
The centre of the ceiling opening should match the centre of the body of the
indoor unit.
Determine the length and outlets of the connecting pipes, water discharge
piping and the electrical wiring.
In order to keep the ceiling level and prevent vibrations, reinforce the
strength of the ceiling when necessary.
The panel contour dimension 1430
20
The ceiling opening dimension 1390
20
The ceiling opening (1390*640)
Hanging screw bolts distance 1207 Machine body size 1172
Figure 3.6
3. Use the hex nuts on the four mounting hooks to adjust and make sure that
the unit body is level.
If the water discharge pipe is slanted, it may cause the water level switch to
malfunction, and water may leak.
Adjust the position of the unit body, and make sure that the gap with the
ceiling is evenly spaced on all four sides of the ceiling, and the base of the
unit body is 24-26 mm into the base of the ceiling.
Once the position of the unit body is adjusted, use the nuts on the mounting
hooks to secure the unit.
Air conditioner body
Air conditioner frame
Air conditioner body
Ceiling
10~12mm
Figure 3.7
3.2.2 Installation sequence for new ceiling:
1. Refer to Step 2 of the “Installation sequence for existing ceiling”. Pre-
bury the hooks in the new ceiling, and make sure that they are strong enough
to bear the weight of the indoor unit, and that the unit will not become loose
when the concrete shrinks.
2. Once you have lifted and mounted the unit, use M6x12 screws (accessory 5)
to secure the installation board (accessory 4) on the unit body. Make sure you
verify the size and positions of the opening in the ceiling before you do so.
See Figure 3.8.
Before you mount the unit onto the ceiling, make sure the ceiling is level.
The rest of the procedures are the same as Step 2 of the “Installation
sequence for existing ceiling”.
3. Refer to Step 3 of the “Installation sequence for existing ceiling”. 4.
Remove the installation board (accessory 4).
The panel contour dimension 680
The ceiling opening dimension 640 20 Machine body size 591 Hanging screw bolts
distance 520
Figure 3.5
5
Pattern paper
Panel fixing screw (M4X16) Figure 3.8
Caution
· Make sure that the unit body is level; otherwise, it may cause water to
leak. Calibrate the levelness of the unit using a spirit level or polyethylene
tube filled with water.
· The unit is equipped with a built-in water discharge pump and float switch.
Do not tilt the unit in the direction of the drain pan; otherwise, the float
switch may malfunction and cause water leakages.
Dimensions of unit 57
1172 701
129 129
3.3 Panel Installation 3.3.1 Remove the stickup foam from the air inlet
grille. 3.3.2 Remove the air inlet grille (1) Lift one side of the air inlet
grille (no directionality), and
press the other side down. Then slide in the direction of the arrow as shown
in Figure 3.12. Inhalation grating
Figure 3.12 (2) Take and press down one side of the suspension buckle
as shown in Figure 3.13.
Figure 3.13 (3) Open the air inlet grille to about 45°, and then open the
other
side of the suspension buckle as shown in Figure 3.14.
32
45
151 44 192 299
32
1430 Top view Figure 3.9
591
436
241
185
44
120 104 91
299 176 171 91 51
42~45
680
Side view Figure 3.10
Mounting hooks
Hex nut (to adjust level)
Panel
Master air conditioner
Surface of the opening ceiling
Figure 3.11
150mm
Figure 3.14
Caution
· Do not place the panel such that it faces downwards or leans against the
wall. Do not place it on a protruding object either.
· Do not hit or squeeze the air deflector.
3.3.3 Panel installation (1) Align the air deflector at the swing motor with
the
corresponding copper pipe connection and water discharge connection of the
unit body. (2) Place two positioning bolts (from panel accessories) and
install them at the corresponding positions of the unit body, as shown in
Figure 3-15 (tighten in the bolts by about 10 cm). (3) Hang the frame setting
plates on the panel on the two bolts described in step (2) above (it will be
easier to start with the water discharge side). (4) Reverse to remove the
positioning bolts installed in step (2), and take out the other two bolts from
the panel accessories. (5) Turn to tighten the four bolts. The mounting
position is as shown in Figure 3.16. Secure the panel to the unit body, and
make sure that there is no gap between the panel and ceiling.
6
Piping side Bolt
Air deflector for swing motor
Bolt
Figure 3.15
Bolt
Edge setting plates
3.3.4 Remove the lid from the electric control box, and connect the swing
motor and display panel to the electric control box. Cover the lid, and
tighten the two screws. 3.3.5 Reinstall the air inlet grille by performing the
steps used to remove the air inlet grille in the reverse order. Adjust to the
appropriate position. 3.3.6 If you need to adjust the air deflector, use the
following steps to remove and install the air deflector:
(1) Remove the air deflector. Make sure that the air deflector is level, press
one end of the air deflector at where the buckle is, and the buckles in the
middle and at the other side will also fall off. Remove the air deflector as
shown in Figure 3-19.
(2) Install the air deflector. Repeat the steps used to remove the air
deflector (1) in reverse order to install the air deflector. As shown in
Figure 3-20.
Wind leading strip
Press
Bolt
Figure 3.16
Caution · To prevent air and water leakages, make sure there is no gap
between the ceiling, panel, and unit body. See Figure 3.17 and Figure 3.18. ·
As long as it does not affect the lifting and lowering of the indoor unit and
the water discharge piping, you can use the hex nuts on the four corners of
the panel boom to adjust the height of the indoor unit.
Figure 3.19
Pot-head Drive retainer
Interval
Droplets of condensed water, dripping water. Figure 3.17
Interval
Droplets of condensed water, dripping water. Figure 3.18
7
Figure 3.20
4. Refrigerant Piping Installation
4.1 Length and Level Difference Requirements for the Piping Connections to the
Indoor and Outdoor Units The length and level difference requirements for the
refrigerant piping are different for different indoor and outdoor units. Refer
to the installation manual of the outdoor unit.
4.2 Piping Material and Size 1. Piping material: Copper pipes for air
handling. 2. Piping size: Choose and purchase copper pipes that correspond to
the
length and size calculated for the selected model in the installation manual
of the outdoor unit and your actual project requirements.
4.3 Piping Layout 1. Seal the two ends of the piping properly before you
connect the indoor and
outdoor piping. Once unsealed, connect the piping of the indoor and outdoor
units as quickly as possible to prevent dust or other debris from entering the
piping system via the unsealed ends, as this may cause the system to
malfunction. 2. If the piping needs to go through walls, drill the opening in
the wall, and place accessories like casings and covers for the opening
properly. 3. Place the refrigerant connecting piping and the communication
wiring for the indoor and outdoor units together, and bundle them tightly to
make sure air does not enter and condensate to form water that may leak from
the system. 4. Insert the bundled piping and wiring from outside the room
through the wall opening into the room. Be careful when you lay out the
piping. Do not damage the piping.
4.4 Piping Installation · Refer to the installation manual attached with the
outdoor unit on installation
of the refrigerant piping for the outdoor unit. · All gas and liquid piping
must be properly insulated; otherwise, this may cause
water to leak. Use heat insulation materials that can withstand high
temperatures above 120°C to insulate the gas pipes. In addition, the
insulation of the refrigerant piping should be reinforced (20 mm or thicker)
in situations where there is high temperature and/or high humidity (when part
of refrigerant piping part is higher than 30°C or when the humidity exceeds
RH80%). Otherwise, the surface of the heat insulation material may be exposed.
· Before the works are carried out, verify that the refrigerant is R410A. If
the wrong refrigerant is used, the unit may malfunction. · Other than the
specified refrigerant, do not let air or other gases enter the refrigeration
circuit. · If the refrigerant leaks during installation, make sure you fully
ventilate the room. · Use two wrenches when you install or dismantle the
piping, a common wrench and a torque wrench. See Figure 4.1.
Normal wrench Torque wrench Pipe socket cap
Pipe fittings Figure 4.1
Slot the refrigerant piping into the brass nut (accessory 14), and expand the
pipe socket. Refer to the following table for the size of the pipe socket and
the appropriate tightening torque.
External diameter (mm)
Tightening torque
Flared opening diameter (A)
6.35
14.2-17.2N·m
8.3-8.7mm
9.53
32.7-39.9N·m
12-12.4mm
12.7
49.5-60.3N·m 15.4-15.8mm
15.9
61.8-75.4N·m
18.6-19mm
19.1
97.2-118.6N·m 22.9-23.3mm
Flared opening
90°±4 A 45°±2 R0.4 ~ 0.8
Figure 4.2
Caution
· Apply the appropriate tightening torque according to the installation
conditions. Excessive torque will damage the socket cap, and the cap will not
be tight if you apply insufficient torque, leading to leakages.
Before the socket cap is installed on the pipe socket, apply some refrigerant oil on the socket (both inside and outside), and then rotate it three or four times before you tighten the cap. See Figure 4.3. Apply refrigerant oil
Figure 4.3
Precautions to take when welding the refrigerant pipes
· Before you weld the refrigerant pipes, fill the pipes with nitrogen first to
discharge the air in the pipes. If no nitrogen is filled during welding, a
large amount of oxide film will form inside the piping which may cause the air
conditioning system to malfunction.
· Welding can be carried out on the refrigerant pipes when the nitrogen gas
has been replaced or refilled.
· When the pipe is filled with nitrogen during welding, the nitrogen must be
reduced to 0.02 MPa using the pressure release valve. See Figure 4.4.
1 Copper piping
2 Section being brazed
3 Nitrogen connection
4 Hand valve
Figure 4.4
5 Pressure-reducing valve 6 Nitrogen
4.5 Air Tightness Test Carry out the air tightness test on the system
according to the instructions in the installation manual of the outdoor unit.
Caution
· The Air Tightness Test helps to ensure that the air and liquid cut-off
valves of the outdoor unit are all closed (maintain the factory defaults).
4.6 Heat Insulation Treatment for Gas-Liquid Piping Connections
for the Indoor Unit The heat insulation treatment is carried out on the piping at the gas and
liquid sides of the indoor unit respectively.
a. The piping on the gas side must use heat insulation material that can
withstand temperatures of 120°C and more.
b. For the piping connections of the indoor unit, use the insulation casing
for copper pipes (accessory 7) to carry out the insulation treatment,
and close all gaps.
Face upwards
Unit body
On-site piping Attached insulation side heat pump belt
Figure 4.5
4.7 Vacuum Create a vacuum in the system according to the instructions in the installation manual of the outdoor unit.
Caution
· For the vacuum, make sure that the air and liquid cut-off valves of the
outdoor unit are all closed (maintain the factory status).
4.8 Refrigerant Charge the system with refrigerant according to the instructions in the installation manual of the outdoor unit.
8
5. Water Discharge Piping Installation
5.1. Water Discharge Piping Installation for Indoor Unit
1. Use PVC pipes for the water discharge pipes (outer diameter: 37~39 mm,
inner diameter: 32 mm). Based on the actual installation circumstance, users
can purchase the appropriate piping length from sales agent or local after-
sales service centre, or purchase directly from the local market.
2. Insert the water discharge pipe into the end of the water suction
connecting pipe of the unit body, and use the ring clamp (accessory 11) to
clamp the water discharge pipes with the insulation casing for the water
outlet piping securely.
3. Use the insulation casing for water discharge piping (accessory 10) to
bundle the water suction and discharge pipes of the indoor unit (especially
the indoor portion), and use the tie for the water discharge piping (accessory
12) to bind them firmly to make sure air does not enter and condense.
4. In order to prevent the back-flow of water into the interior of the air
conditioner when the operation stops, the water discharge pipe should slope
downwards towards the outside (drainage side) at a slope of more than 1/100.
Make sure that the water discharge pipe does not swell or store water;
otherwise, it will cause strange noises. See Figure 5.1.
5. When connecting the water discharge piping, do not use force to pull the
pipes to prevent the water suction pipe connections from coming loose. At the
same time, set a supporting point at every 0.8~1 m to prevent the water
discharge pipes from bending. See Figure 5.1.
5.2 Water Discharge Test
Before the test, make sure that the water discharge pipeline is smooth, and
check that each connection is sealed properly.
Conduct the water discharge test in the new room before the ceiling is paved.
1. Remove the test water cap to connect to the test water outlet, and use the
water injection pipe to inject 2000 ml of water into the drain pan.
Drainage outlet for water pump
Opening for test water injection and water level switch check Water injection
pipe
Maintenance plug for water discharge
Figure 5.3
0.8 ~ 1.0 m
Slope of 1/100 or more
1.0 m
Figure 5.1
2. Connect the power supply, and set the air conditioner to operate in the
cool mode. Check the running sound of the drainage pump, as well as whether
water is properly drained from the drainage outlet.
3. Stop the air conditioner. Wait for three minutes, and then check if there
is anything unusual. If the water discharge piping layout is not correct, the
excessive water flow will cause the water level error and “EE” error code will
be displayed on the display panel. There may even be water overflowing from
the water pan.
4. Continue to add water until the alarm for excessive water levels is
triggered. Check if the drainage pump drains water immediately. After three
minutes, if the water level does not fall below the warning level, the unit
will shut down. At this time, you need to turn off the power supply, and drain
away the accumulated water before you can turn on the unit normally.
5. Turn off the power supply, remove the water manually using the drainage
plug, and put the test cap back to the original place.
6. When connecting to a long water discharge pipe, the connections must be
covered with the insulation casing to prevent the long pipe from coming loose.
7. When the outlet of the water discharge pipe is higher than the pipe
connection for water suction, try to keep the water discharge pipe as vertical
as possible, and the water outlet connecting fittings will bend so that the
height of the water discharge pipe should be within 1000 mm away from the base
of the drain pan. Otherwise, there will be excessive water flow when the
operation stops. See Figure 5.2.
Water discharge pipes from multiple units are connected to the main water discharge pipe to be discharged through the sewage pipe.
Below 200 mm
Below 200 mm 50 ~ 100 mm
50 ~ 100 mm Below 200 mm
50 ~ 100 mm
Water outlet pipe fittings
Main water outlet pipe
Slope of 1/100 or more
Figure 5.2
All are below 1000 mm
8. The end of the water discharge pipe must be more than 50 mm above the ground or from the base of the water discharge slot. Besides, do not put it in the water.
Caution
· Make sure all the connections in the piping system are properly sealed to
prevent water leakages.
Caution
· The drainage plug at the bottom of the unit body is used to discharge
accumulated water from the drain pan when the air conditioner malfunctions.
When the air conditioner is operating normally, make sure the drainage plug is
properly plugged to prevent water from leaking.
6 Electrical Wiring
Warning
· All the supplied parts, materials and electrical works must comply with
local regulations.
· Use only copper wires. · Use a dedicated power supply for the air-
conditioners. The power voltage
must be in line with the rated voltage. · The electrical wiring works must be
carried out by a professional technician,
and must comply with the labels stated in the circuit diagram. · Before the
electrical connection works are carried out, turn off the power
supply to prevent injuries caused by electric shock. · The external power
supply circuit of the air conditioner must include an
earth line, and the earth line of the power cord connecting to the indoor unit
must be securely connected to the earth line of the external power supply. ·
Leakage protective devices must be configured according to the local technical
standards and requirements for electrical and electronic devices. · The fixed
wiring connected must be equipped with an all-pole disconnection device with a
minimum 3 mm contact separation. · The distance between the power cord and
signalling line must be at least 300 mm to prevent the occurrences of
electrical interference, malfunction or damage to electrical components. At
the same time, these line must not come in contact with the piping and valves.
· Choose electrical wiring that conforms to the corresponding electrical
requirements. · Connect to the power supply only after all the wiring and
connection works have been completed, and carefully checked to be correct.
9
6.1 Power Cord Connection
Use a dedicated power supply for the indoor unit that is different from the
power supply for the outdoor unit. Use the same power supply, circuit breaker and leakage protective device
for the indoor units connected to the same outdoor unit.
Outdoor power supply
RCCB Grounding line
Grounding line
Wire slot
Indoor power supply
RCCB
Indoor unit
Communication wire between indoor and outdoor units
Figure 6.1 Figure 6.2 shows the power supply terminal of the indoor unit.
LN
POWER INPUT Figure 6.2
When connecting to the power supply terminal, use the circular wiring terminal with the insulation casing (see Figure 6.3).
Use power cord that conforms to the specifications and connect the power cord firmly. To prevent the cord from being pulled out by external force, make sure it is fixed securely.
If circular wiring terminal with the insulation casing cannot be used,
please make sure that:
· Do not connect two power cords with different diameters to the
same power supply terminal (may cause overheating of wires due
to loose wiring) (See Figure 6.4).
: Copper wire
Circular wiring terminal
Proper power wiring connections Insulation tube
Power cord
Figure 6.3
6.2 Electrical Wiring Specifications
220-240V~50/60Hz 220-240V~50Hz Power supply
Indoor unit
LN
Breakers with current leakage
Figure 6.4 Indoor unit
Table 6.1
Model
Power supply
Phase Volt and frequency
Communication wire between indoor and outdoor units
Communication wire between indoor unit and wired controller *
2.2-7.1kW 1-phase 220-240V~50Hz 220-240V~50/60Hz
Shielded 3×AWG16-AWG18
Shielded AWG16-AWG20
Field fuses
15A
- Please refer to the corresponding wired controller manual for the wired controller wiring.
Table 6.2 Indoor units electrical characteristics
Capacity
Power supply
IFM
Hz
Volts MCA MFA kW FLA
2.2KW
0.47 15 0.1 0.38
2.8KW 3.6KW 4.5KW 5.6KW 7.1KW
0.47 15
50 50/60
0.52 220-240
0.59
15 15
0.9 15
1.3 15
0.1 0.38 0.1 0.42 0.1 0.47 0.1 0.72 0.1 1.04
Abbreviations: MCA: Minimum Circuit Amps MFA: Maximum Fuse Amps IFM: Indoor Fan Motor kW: Rated motor output FLA: Full Load Amps
1. Select the wire diameters( minimum value) individually for each unit based
on the table 6.3.
2. Maximum allowable voltage range variation between phases is 2%.
3. Select circuit breaker that having a contact separation in all poles not
less than 3 mm providing full disconnectionwhere MFA is used to select the
current circuit breakers and residual current operation breakers:
Table 6.3
Rated current of appliancecA
3 >3 and 6 >6 and 10 >10 and 16 >16 and 25 >25 and 32 >32 and 50 >50 and 63
Nominal cross-sectional area (mm2 )
Flexible cords 0.5 and 0.75 0.75 and 1
1 and 1.5 1.5 and 2.5 2.5 and 4 4 and 6 6 and 10 10 and 16
Cable for fixed wiring
1
to 2.5
1
to 2.5
1
to 2.5
1.5 to
4
2.5 to
6
4
to 10
6
to 16
10 to 25
All-pole disconnection device with leakage protector
Pull box
Pull box Pull box
Warning
Refer to local laws and regulations when deciding on the dimensions for the
power cords and wiring. Get a professional to select and install the wiring.
Indoor unit
Indoor unit
Indoor unit
Figure 6.5
Refer to Tables 6.1 and 6.2 for the specifications of the power cord and communication wire. A wiring capacity that is too small will cause the electrical wiring to become too hot, and lead to accidents when the unit burns and becomes damaged.
6.3 Communication Wiring Use only shielded wires for the communication wiring.
Any other type of wires
may produce a signal interference that will cause the units to malfunction. Do
not carry out electrical works like welding with the power on. Do not bind the
refrigerant piping, power cords and communication wiring
together. When the power cord and communication wiring are parallel, the
distance between the two lines must be 300 mm or more in order to prevent
signal source interference. Communication wiring must not form a closed loop.
6.3.1 Communication wiring between the indoor and outdoor units The indoor and
outdoor units communicate via the RS485 serial port.
10
Build-out resistor
The communication wiring between the indoor and outdoor units should connect
one unit after another in a daisy chain from the outdoor unit to the
final indoor unit, and the shielded layer must be properly grounded, and a
build-out resistor must be added to the last indoor unit to enhance the
stability of the communication system (see Figure 6.6). Incorrect wiring such
as a star connection or a closed ring will cause instability of the
communication system and system control anomalies. Use a three core shielded
wire (greater than or equal to 0.75 mm2) for the communication wiring between
the indoor and outdoor units. Make sure the wiring is connected correctly. The
connecting lead for this communication wire must come from the master outdoor
unit. All shielded wiring in the network are interconnected, and will
eventually
connect to earth at the same point” “.
Outdoor unit
(Connect the shielded end of the shielded wire to the electronic controller box sheet metal ” ” here)
- For a unidirectional communication mode: Use 1 wired controller to control 1 indoor unit (see Figure 6.9).
Indoor unit 1
A B C D
Display board
A B C D
P Q E
P Q E Communication line between indoor and outdoor units
Signalling line between outdoor units
Connecting the shielded layer of the shielded wire
Only the last indoor unit requires adding
P
the build-out resistor at P and Q.
Q (open)
Figure 6.6
6.3.2 Communication wiring between the indoor unit and wired controller
The wired controller and the indoor unit can be connected in different
manners, depending on the forms of communication. 1) For a bidirectional
communication mode: Use 1 wired controller to control 1 indoor unit or 2 wired
controllers
(one master and one slave controller) to control 1 indoor unit (see Figure
6.7); Use 1 wired controller to control multiple indoor units or 2 wired
controllers (one master and one slave controller) to control multiple indoor
units (see Figure 6.8);
Wired controller 1
Figure 6.9
The X1/X2, D1/D2 ports on the sides of the main control board and the
unidirectional communication port (display board side) are for different types
of wired controllers (see Figure 6.10).
Use the connecting wires (accessory) to connect the D1/D2 ports.
To wired controller COMM. BUS
X1 X2
To outdoor/ indoor units COMM. BUS
E Q P
To wired controller COMM. BUS
D2 D1
X2 X1 E Q P
A B C D
Wired controller
XP4 XS4
Display board
Yellow Grey Black
White Blue
CN17
ON ON ON ON ON ON ON POWER_S
ON ON ON ON ON ON ON
12 12 12 12 12 12 12
SW6 SW5 SW4 SW3 SW2SW1 SW7 ENC1
CN9 CN15
Main control panel
Figure 6.10
P Q E X1 X2
Indoor unit 1
Caution
· For the specific connection method, refer to the instructions in the
corresponding wired controller manual to carry out the wiring and connections.
X1 X2
Wired controller 1
Wired controller 2
Master wired controller
Slave wired controller
Figure 6.7
Indoor unit 1
Indoor unit 2
Indoor unit n(n<=16)
X1 X2
6.4 Handling the Electrical Wiring Connection Points
Once the wiring and connections are done, use tie straps to secure the wiring
properly so that the connection joint cannot be pulled apart by external
force. The connection wiring must be straight out so that the cover of the
electrical box is level and can be closed tightly.
Use professional insulation and sealing materials to seal and protect the
perforated wires. Poor sealing may lead to condensation, and entry of small
animals and insects that may cause short circuits in parts of the electrical
system, causing the system to fail.
6.5 Panel Wiring
Refer to the panel instructions to connect the docking terminals of the
display board and the swing motor.
D2
D1
D1 D2
P Q E X1 X2
P Q E X1 X2
P Q E X1 X2
D1
X2 X1 D2 D1 D2
X2 X1 D2 D1
Wired controller 1 Master wired controller
Wired controller 2 Slave wired controller
Figure 6.8
11
7. On-site Configuration
7.1 Capacity Settings
Set up the PCB DIP switch on the indoor electric control box to cater to
different uses. Once the settings are done, make sure you cut off the main
power switch again, and then switch the power on. If the power is not cut off
and switched on again, the settings will not be executed.
POWER_S
ENC1
ENC1 Settings for Capacity DIP Switch:
DIP Switch Code 0 1 2 3 4 5
Capacity 2200W 2800W 3600W 4500W 5600W 7100W
Caution
· The capacity DIP switches have been configured before delivery. Only a
professional maintenance personnel should change these settings.
SW2
SW2
Factory settings
[ 00 ]
SW3_1
SW3
Reserved
[ 0]
SW3 [ 1] SW3_2
Clear indoor unit address
SW3 [ 0]
Reserved
SW4
SW4 [ 00 ] SW4 [ 01 ] SW4 [ 10 ] SW4 [ 11 ]
In heating mode when the set temperature has been reached, the fan operates in
a 4 minutes off / 1 minute on repeating cycle
In heating mode when the set temperature has been reached, the fan operates in
an 8 minutes off / 1 minute on repeating cycle
In heating mode when the set temperature has been reached, the fan operates in
a 12 minutes off / 1 minute on repeating cycle
In heating mode when the set temperature has been reached, the fan operates in
a 16 minutes off / 1 minute on repeating cycle
7.2 Address Settings
When this indoor unit is connected to the outdoor unit, the outdoor unit will
automatically allocate the address to the indoor unit. Alternatively, you may
use the controller to manually set the address. The addresses of any two
indoor units in the same system cannot be the same. The network address and
the indoor unit address are the same, and does
not have to be configured separately. Once the address settings are completed,
mark the address of each indoor
unit to facilitate after-sales maintenance. The centralized control of the
indoor unit is completed on the outdoor unit.
For details, refer to the manual on the outdoor unit.
SW5
SW5 [ 00 ] SW5 [ 01 ] SW5 [ 10 ] SW5 [ 11 ]
In heating mode fan does not run when indoor heat exchanger mid-point
temperature is 15°C or below
In heating mode fan does not run when indoor heat exchanger mid-point
temperature is 20°C or below
In heating mode fan does not run when indoor heat exchanger mid-point
temperature is 24°C or below
In heating mode fan does not run when indoor heat exchanger mid-point
temperature is 26°C or below
Caution
· Once the centralized control function for the indoor unit has been completed
on the outdoor unit, the DIP switch on main control panel of the outdoor unit
must be set to auto addressing; otherwise, the indoor unit in the system are
not controlled by the centralized controller.
· The system can connect up to 64 indoor units (address 0~63) at the same
time. Each indoor unit can only have one address DIP switch in the system. The
addresses of any two indoor units in the same system cannot be the same. Units
that have the same address may malfunction.
7.3 DIP Switch Settings on Main Board
0/1 definition of each dial code switch: means 0
means 1
SW6
SW6 [ 00 ]
Heating mode temperature compensation is 6°C
SW6 [ 01 ]
Heating mode temperature compensation is 2°C
SW6
Heating mode temperature compensation is 4°C
[ 10 ]
SW6
Heating mode temperature compensation is 0°C
[ 11 ]
(use follow me function)
SW7: reserved J1
SW1_1
SW1
Cooling mode temperature compensation is 0°C
[ 0]
Auto restart function enabled Auto restart function disabled
SW1 [ 1] SW1_2
Cooling mode temperature compensation is 2°C
SW1
EEV at position 96 (steps) in standby in heating mode
[ 0]
SW1
EEV at position 72 (steps) in standby in heating mode
[ 1]
Caution
· All DIP switches (including the capacity DIP switch) have been configured
before delivery. Only a professional maintenance personnel should change these
settings.
· Improper DIP switch settings may cause condensation, noise, or unexpected
system malfunction.
12
7.4 Error Codes and Definitions
Operation manual
Error code Content
There are two types of precautions as described below: Warning: Failure to comply may lead to death or serious injury. Caution: Failure to comply may lead to injury or damage of the
E0 Mode conflict
unit. Depending on the situation, this may also lead to serious injury.
E1 Communication error between indoor and outdoor units
E2 Indoor ambient temperature sensor (T1) error E3 Indoor heat exchanger mid-
point temperature sensor
(T2) error
E4 Indoor heat exchanger outlet temperature sensor (T2B) error
E6 Fan error
Once the installation is completed, please keep the manual properly for future
reference. When this air conditioner is handed over to other users, make sure
that the manual is included with the handover.
Warning · Do not use this unit in locations where flammable gas may exist. If
flammable gas comes into contact with the unit, a fire may occur, which could
result in serious injury or death.
E7 EEPROM error
· If this unit exhibits any abnormal behavior (such as emitting
Eb Indoor EEV coil error Ed Outdoor unit error
smoke) there is a danger of serious injury. Disconnect the power supply and contact your supplier or service engineer immediately. · The refrigerant in this unit is safe and should not leak if the system
EE Water level error
is designed and installed properly. However, if a large amount of
FE Indoor unit has not been assigned an address
refrigerant leaks into a room, the oxygen concentration will decrease rapidly, which can cause serious injury or death. The
8. Test Run
8.1 Things to Note Before Test Run
Indoor and outdoor units are properly installed; Piping and wiring are
correct; No leakage from the refrigerant piping system; Water discharge is
smooth; Insulation is complete; Grounding line has been properly connected;
Piping length, and amount of refrigerant filled have been recorded; The
voltage of the power supply is the same as the rated voltage
refrigerant used in this unit is heavier than air, so the danger is greater in basements or other underground spaces. In the event of a refrigerant leak, turn off any devices that produce a naked flame and any heating devices, ventilate the room, and contact your supplier or service engineer immediately. · Toxic fumes may be produced if the refrigerant in this unit comes into contact with naked flames (such as from a heater, gas stove/burners, or electric appliances). · If this unit is used in the same room as a cooker, stove, hob, or burner, ventilation for sufficient fresh air must be ensured, otherwise the oxygen concentration will fall, which may cause
of the air conditioner; No obstacles at the air inlet and outlet of the indoor
and outdoor
units; Cut-off valves for the gas and liquid ends of the outdoor unit are
injury. · Dispose of this unit’s packaging carefully, so children cannot play
with it. Packaging, especially plastic packaging, can be dangerous, can cause
serious injury or death. Screws, staples
opened;
and other metal packaging components can be sharp and should
8.2. Test Run
When the wired/remote controller is used to set the cooling operations of the
air conditioner, check the following items one by one. If there is a fault,
troubleshoot according to the manual.
be disposed of carefully to avoid injury. · Do not attempt to inspect or
repair this unit yourself. This unit
should only be serviced and maintained by a professional air conditioning
service engineer. Incorrect servicing or maintenance can cause electric
shocks, fire or water leaks.
Function keys of the wired/remote controller are operating
· This unit should only be re-positioned or re-installed by a
normally;
professional technician. Incorrect installation can lead to electric
Room temperature regulation is normal;
shocks, fire or water leaks. The installation and grounding of
LED indicator is on;
electrical appliances should only be carried out by licensed
Water discharge is normal;
professionals. Ask your supplier or installation engineer for further
No vibration and strange sounds during operation;
information.
Note: Once the power is connected, when the unit is turned on or started immediately after the unit is turned off, the air conditioner has a protective function which delays the start of the compressor.
· Do not allow this unit or its remote controller to come into contact with
water, as this can lead to electric shocks or fire.
· Turn off the unit before cleaning it to avoid electric shocks. Otherwise, an
electric shock and injury may result.
· To avoid electric shocks and fires, install an earth leakage detector.
· Do not use paint, varnish, hair spray, other flammable sprays or
other liquids that may give off flammable fumes/vapor near this
unit, as doing so can cause fires.
· When replacing a fuse, ensure that the new fuse to be installed
completely complies with requirements.
· Do not open or remove the unit’s panel when the unit is powered
on. Touching the unit’s internal components while the unit is
powered on can lead to electric shocks or injuries caused by
moving parts such as the unit’s fan.
· Ensure that the power supply is disconnected before any servicing
13 or maintenance is carried out.
· Do not touch the unit or its remote controller with wet hands, as doing so
can lead to electric shocks.
· Do not allow children to play near this unit, as doing so risks injury. · Do
not insert your fingers or other objects into the unit’s air inlet or
air outlet to avoid injury or damage to the equipment. · Do not spray any
liquids onto the unit or allow any liquids to drip
onto the unit. · Do not place vases or other liquid containers on the unit or
in
places where liquid could drip onto it. Water or other liquids that come into
contact with the unit can lead to electric shocks or fires. · Do not remove
the remote controller’s front or back overs and do not touch the remote
controller’s internal components, as doing so can cause injury. If the remote
controller stops working, contact your supplier or service engineer. · Ensure
that the unit is properly grounded, otherwise electric shocks or a fire may
result. Electrical surges (such as those that can be caused by lightning) can
damage electrical equipment. Ensure that suitable surge protectors and circuit
breakers are properly installed, otherwise electric shocks or a fire may
result. · Dispose of this unit properly and in accordance with regulations. If
electrical appliances are disposed of in landfills or dumps, hazardous
substances can leak into the groundwater and thus enter the food chain. · Do
not use the unit until the qualified technician instructs you that it is safe
to do so. · Do not place appliances that produce naked flames in the path of
the airflow from the unit. The airflow from the unit may increase the rate of
combustion, which may cause a fire and cause serious injury or death.
Alternatively, the airflow may cause incomplete combustion which can lead to
reduced oxygen concentration in the room, which can cause serious injury or
death.
· To avoid damaging the remote controller, exercise caution when using it and
replacing its batteries. Do not place objects on top of it.
· Do not place appliances that have naked flames under or near the unit, as
heat from the appliance can damage the unit.
· Do not place the unit’s remote controller in direct sunlight. Direct
sunlight can damage the remote controller’s display.
· Do not use strong chemical cleaners to clean the unit, as doing so can
damage the unit’s display or other surfaces. If the unit is dirty
or dusty, use a slightly damp cloth with very diluted and mild
detergent to wipe the unit. Then, dry it with a dry cloth. · Children shall
not play with the appliance.
· Do not dispose of this product as unsorted waste. It must be separately
collected and processed. Ensure that all applicable legislation regarding the
disposal of refrigerant, oil and other materials is adhered to. Contact your
local waste disposal authority for information about disposal procedures.
· This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
· This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
9. Part Names
The figure shown above is for reference only and may be slightly different from the actual product.
Caution
· Only use the air conditioner for its intended purpose. This unit
should not be used to provide refrigeration or cooling for food,
plants, animals, machinery, equipment or art.
· Do not insert your fingers or other objects into the unit’s air inlet or
air outlet to avoid injury or damage to the equipment.
· The fins on the unit’s heat exchanger are sharp and can cause
injury if touched. To prevent injury, when the unit is being serviced,
gloves should be worn or the heat exchanger should be covered.
· Do not place items which might be damaged by moisture under
the unit. When the humidity is greater than 80% or if the drain pipe
is blocked or the air filter is dirty, water could drip from the unit and
damage objects placed under the unit.
· Ensure that the drain pipe functions properly. If the drain pipe is
blocked by dirt or dust, water leaks may occur when the unit is
running in cooling mode. If this happens, turn the unit off and
contact your supplier or service engineer.
· Do not touch the internal parts of the controller. Do not remove the
front panel. Some internal parts may cause injury or be damaged.
· Ensure that children, plants and animals are not directly exposed
to the airflow from the unit.
· When fumigating a room with insecticide or other chemicals, cover
the unit well and do not run it. Failure to observe this caution could
lead to chemicals getting deposited inside the unit and later
emitted from the unit when it running, endangering the health of
any room occupants.
· Do not dispose of this product as unsortedwaste. It must be
separately collectedand processed. Ensure that allapplicable
legislation regarding thedisposal of refrigerant, oil and
othermaterials is adhered to. Contact your local waste disposal
authority forinformation about disposal procedures.
14
Air Outlet Louver (adjustable) For in-situ adjustment to three-direction or
two-direction,please contact the local dealer.
Air inlet grille
Figure 9.1
10. The Explain Of The Display Panel
Digital LED display Infrared signal receiver
Check Operation Timer Anti-cold air /
ALARM
button indicator indicator defrosting indicator
Table: Display panel output under normal operating conditions.
Unit state Standby
Unit state
Operation indicator flashes slowly
Display output Digital display panels
Digital display
Shutting-down
All indicators off
Operation
Normal operation
Operation indicator Cooling and heating modes: set temperature
on
Fan only mode: indoor ambient temperature
Cold draft prevention Operation and
or outdoor unit
Anti-cold / defrosting
defrosting operation indicators on
Set temperature
A timer has been set
Timer indicator on
Note: Flashing slowly means flashing once per second.
11. Air Conditioner Operations and Performance
The operating temperature range under which the unit runs stablyare
given in below table.
Cooling mode
Heating mode
Indoor temperature
17j32°C(DB)
15j27°C(DB)
Indoor humidity
80%(a)
(a) Condensation will form on the unit surface and water dripping out of the unit when the indoor humidity is beyond 80%
Caution
· The unit performs stably in the temperature range given in above table. If
the indoor temperature is outside the unit’s normal operating range, it may
stop running and display an error code.
To ensure the desired temperature is achievedefficiently, ensure that: All
windows and door are closed. The airflow direction is adjusted to work in
running mode.
The air filter is clean. Please note how you can best save energy and achieve
the best cooling/heating effect. Regularly clean air filters inside indoor
units.
15
Check regularly
Figure 11.1 Avoid too much outdoor air coming into air-conditioned spaces.
Close doors and windows.
Caution · During heating operation, horizontal airflow will aggravate the
uneven distribution of room temperature. · The louver direction: horizontal
airflow is recommended
during cooling operation. Note the downward air flow will cause condensation
on the air outlet and louver surface.
Adjust the air direction up and down a. Auto-swing: Press SWING for the louver
to swing up and down. b. Manual swing: Adjust the louver to improve the
cooling or heating effect. c. When cooling adjust the louver horizontally.
Figure 11.2
Note that outlet air is cooler or heater than set room temperature. Avoid
direct exposure to outlet air as it may be too cool or hot.
Figure 12.1 d. When heating adjust the louver downward.
Do not set the temperature too
low
Figure 11.3 Maintain a proper air distribution.Air outlet louvers should be
used
to adjust the direction of outlet airflow, as doing so might ensure more
efficient operation.
13. Maintenance
Figure 12.2
Caution
· Please release pressure before disassembly. · Before you clean the air
conditioner, ensure it is powered off. · Check that the wiring is undamaged
and connected. · Use a dry cloth to wipe the indoor unit and remote
controller. · A wet cloth may be used to clean the indoor unit if it is very
dirty. · Never use a damp cloth on the remote controller. · Do not use a
chemically treated duster on the unit or leave this
type of material on the unit to avoid damaging the finish. · Do not use
benzene, thinner, polishing powder, or similar
solvents for cleaning. These may cause the plastic surface to crack or warp.
Figure 11.4
12. Adjusting Air Flow Direction
Since warmer air rises and cooler air falls, the distribution of warmed/cooled
air around a room can be improved by positioning the unit’s louvers. The
louver angle can be adjusted by pressing the [SWING] button on the remote
controller.
Method for cleaning the air filter a. The air filter can prevent the dust or
other particles from entering the unit. If the filter is blocked, the unit
will not work well. Clean the filter every two weeks when you use it
regularly. b. If the air conditioner is positioned in a dusty place, clean the
filter often. c. Replace the filter if it is too dusty to clean (the
replaceable air filter is an optional fitting).
1. Take out the air intake grille Push the grille switches simultaneously.
Then pull down the air
intake grille (together with the air). Pull the air intake grille down to 45°,
and lift it up to remove the grille.
Caution
· The control box cables originally connected to the electrical terminals on
the main body must be removed, as indicated above.
16
2. Dismantle the air filter. 3. Clean the air filter Dusts will accumulate on
the filter along with the unit operation,
and need to be removed from the filter,or the unit would not function
effectively. Clean the filter every two weeks when you use the unit regularly.
Clean the air filter with a vacuum cleaner or water. a. The air intake side
should face up when using a vacuum
cleaner. (Refer to Figure 13.1) b. The air intake side should face down when
using clean water.
(Refer to Figure 13.2) For excessive dusts, use a soft brush and natural
detergent to
clean it and dry in a cool place.
Figure 13.1
Figure 13.2
Caution · Do not dry out the air filter under direct sunshine or with fire. ·
The air filter should be installed before the unit body installation.
4. Re-install the air filter. 5. Install and close the air inlet grille by
reversing steps 1 and 2, and
connect the control box cables to the corresponding terminals in the main
body. Maintenance before stopping using the unit for a long time (e.g., at the
end of a season) a. Let the indoor units run in fan only mode for about half a
day to
dry the interior of the unit. b. Clean the air filter and indoor unit casing.
c. Refer to “Cleaning the air filter” for details. Install cleaned air
filters back in their original positions. d. Turn off the unit with the ON/OFF
button on the remote
controller, and then unplug it.
Caution · When the power switch is connected, some energy will be
consumed even if the unit is not running. Disconnect the power to save energy.
· A degree of dirt will accumulate when the unit has been used several times,
which will require cleaning. · Take of the batteries from the remote
controller.
Maintenance after a long period of non-use a. Check for and remove anything
that might be blocking the inlet and outlet vents of the indoor units and
outdoor units. b. Clean the unit casing and clean the filter. Refer to
[Cleaning the filter] and “Cleaning the filter” for instructions. Re-install
the filter before running the unit. c. Turn on the power at least 12 hours
before you want to use the unit to ensure it works properly. As soon as the
power is turned on, the remote control display appears.
14. Symptoms That Are Not Faults
The following symptoms may be experienced during the normal operation of the
unit and are not considered faults. Note: If you are not sure whether a fault
has occurred, contact your supplier or service engineer immediately.
Symptom 1: The unit will not run Symptom: When the ON/OFF button on the remote
controller is
pressed, the unit does not immediately start running. Cause: to protect
certain system components, system start-up or re-start is intentionally
delayed for up to 12 minutes under some operating conditions. If the OPERATION
LED on the unit’s panel is lighting, the system is working normally and the
unit will start after the intentional delay is complete.
Heating mode is running when the following panel lights are on:operation and
the “DEF./FAN LED indicator. Cause: the indoor unitactivates protective
measures because of the low outlettemperature.
Symptom 2: The unit emits white mist White mist is generated and emitted when
the unit starts to
operate in a very humid environment. This phenomenon will stop once the
humidity in the room is reduced to normal levels. The unit occasionally emits
white mist when it runs in heating mode. This occurs when the system finishes
periodic defrosting. Moisture that may accumulate on the unit’s heat exchanger
coil during defrosting becomes mist and is emitted from the unit.
Symptom 4: Dust is emitted from the unit This can occur when the unit first
runs after a long idle period.
Symptom 5: The unit gives off a strange odor If smells such as those of
strong-smelling food or tobacco smoke are
present in the room, they can enter the unit, leave trace deposits on the
unit’s internal components, and later be emitted from the unit.
15. Troubleshooting
15.1 General Sections 14.2 and 14.3 describe some initial troubleshooting
steps that
can be taken when an error occurs. If these steps do not resolve the issue,
arrange for a professional technician to investigate the problem. Do not
attempt further investigations or troubleshooting yourself. If any of the
following errors occur, power the unit off, contact a professional technician
immediately and do not attempt troubleshooting yourself: a. A safety device
such as a fuse or circuit breaker frequently
blows/trips. b. An object or water enters the unit. c. Water is leaking from
the unit.
Caution · Do not attempt to inspect or repair this unit by yourself. Arrange
for
a qualified technician to carry out all servicing and maintenance.
17
15.2 Unit Troubleshooting
Symptom
Possible causes
Troubleshooting steps
A power cut has occurred (the power to the
premises has been cut-off).
Wait for the power to come back on.
The unit does not start
The unit is powered off.
Power on the unit. This indoor unit forms part of an air conditioning system that has multiple indoor units that are all connected. The indoor units cannot be powered on individually – they are all connected to one, single power switch. Ask a professional technician for advice regarding how to safely power on the units.
Air flows normally butdoesn’t cool The unit starts or stopsfrequently
Low cooling effect
The power switch fuse may haveburned out. The remote controller’s batteries aredead.
Replace the fuse. Replace the batteries.
The temperature setting is not correct.
Set the desired temperature on theremote controller.
Arrange for a professional technician to check the following: Too much or too little refrigerant. No gas in the refrigerant circuit. The outdoor unit comp ressors have malfunctioned.
The power supply voltage is too high or too low.
There is a blockage in the piping system.
Doors or windows are open.
Close the doors and windows.
Sunlight is shining directly onto theunit.
Close shutters/blinds to shield the unitfrom direct sunlight.
The room contains many heat sourcessuch as Turn off some of the computers duringthe hottest part
computers or refrigerators.
of the day.
The unit’s air filter is dirty.
Clean the filter.
The outside temperature is unusuallyhigh.
The cooling capacity of the system reduces as the outdoor temperature rises and the system may not provide sufficient cooling if the local climate conditions are not considered when the system’s outdoor units were selected.
Low heating effect
Engage a professional air conditioning engineer to check the following: The unit’s heat exchanger is dirty. The unit’s air inlet or outlet is blocked. A refrigerant leak has occurred.
Doors or windows are not completelyclosed.
Close doors and windows.
Arrange for a professional technician to check the following:
A refrigerant leak has occurred.
18
15.3 Remote Controller Troubleshooting
Warning:
Certain troubleshooting steps that a professional technician may perform when
investigating an error are described in this owner’s manual for reference
only. Do not attempt to undertake these steps yourself arrange for a
professional technician to investigate the problem.
If any of the following errors occur, power the unit off and contact a
professional technician immediately. Do not attempt troubleshooting yourself:
A safety device such as a fuse or circuit breaker frequently blows/trips. An
object or water enters the unit. Water is leaking from the unit.
Symptom
Possible causes
Troubleshooting steps
Check whether the MODEindicated on the display is “AUTO”.
In automatic mode, the air conditioner will automatically change the fan’sspeed.
The fan speed cannot beadjusted
Check whether the MODEindicated on the display is “DRY”.
When dry mode is selected, theair conditioner automatically adjuststhe fan speed. (The fan speed can beselected during “COOL”, “FAN ONLY”,and “HEAT”.)
The remote controller signalis not transmitted even whenthe ON/OFF button is pushed
A power cut has occurred (the powerto the premises has been cut-off).
The remote controller’s batteries are
Wait for the power to come back on. Replace the batteries.
The indication on the displaydisappears after a certain time
Check whether the timer operation has come to an end when TIMER OFF is indicated on the display.
The air conditioner operation will stopup to the set time.
The TIMER ON indicator goesoff after a certain time
Check whether the timer operation has come to an end when TIMER ON is indicated on the display.
Up to the set time, the airconditioner will automatically startand the appropriate indicator will gooff.
No receiving soundfrom the indoor unit whenthe ON/OFF button is pressed
Check whether the signal transmitterof the remote controller is properlydirected to the infrared signal receiverof the indoor unit when the ON/OFFbutton is pressed.
Directly transmit the signal transmitterof the remote controller to the infraredsignal receiver of the indoor unit, andthen press the ON/OFF button twice.
19
15.4 Error Codes
With the exception of a mode conflict error, contact your supplier or service
engineer if any of the error codes listed in the following table are displayed
on the unit’s display panel. If the mode conflict error is displayed and
persists, contact your supplier or service engineer. These errors should only
be investigated by a professional technician. The descriptions are provided in
this manual for reference only.
Content
Digital display output
Possible causes
Mode conflict
E0
Communication error
betweenindoor and
E1
outdoor units
Indoor ambient temperature
sensor (T1) error
E2
Indoor heat exchanger
mid-point temperature
E3
sensor (T2) error
Indoor heat exchanger
outlet temperature sensor
E4
(T2B) error
Fan error
E6
EEPROM error
E7
Indoor EEV coil error
Eb
Outdoor unit error
Ed
Water level error
EE
indoor unit has not
been assigned an
FE
address
The indoor unit’s operating mode conflicts with that of the outdoor units.
Communication wires betweenindoor and outdoor units not connected properly.
Interference from high voltage wires or other sources of electromagnetic
radiation.
Communication wire too long. Damaged main PCB.
Temperature sensor not connected properly or has malfunctioned. Damaged main
PCB.
Fan stuck or blocked. Fan motor not connected properlyor has malfunctioned.
Power supply abnormal. Damaged main PCB.
Damaged main PCB.
Line loosened or broken. The electronic expansion valve in stuck. Damaged main
PCB. Outdoor unit error. Water level float stuck. Water level switch not
connected properly. Damaged main PCB. Drain pump has malfunctioned.
Indoor unit has not been assigned an address.
Notes: Flashing rapidly means flashing twice per second; flashing slowly means flashing once per second.
20
16126000002968 V.N
80g 210*297() /
)
2021.01.04 80
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>