Midea MDDF20 20L Dehumidifier Owner’s Manual

June 5, 2024
Midea

Owner’s Manual &
Installation Manual

IMPORTANT NOTE:
Read this manual carefully before installing or operating your new machine.
Make sure to save this manual for future reference.

Safety Precautions

Read Safety Precautions Before Operation and Installation
To prevent death or injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring of instructions may cause death, harm, or damage.

WARNING
This symbol indicates the possibility of personnel injury or loss of life.

CAUTION
This symbol indicates the possibility of property damage or serious consequences.

WARNING

  • Do not exceed the rating of the power outlet or connected device.
  • Do not operate or stop the unit by switching on or off the power.
  • Do not damage or use an unspecified power cord.
  • Do not modify the power cord length or share the outlet with other appliances.
  • Do not insert or pull out the plug with wet hands.
  • Do not install the appliance in a location that may be exposed to a combustible gas.
  • Do not place the unit near a heat source.
  • Disconnect the power if strange sounds, smell, or smoke comes from it.
  • You should never try to take apart or repair the unit by yourself.
  • Before cleaning, turn off the power and unplug the unit.
  • Do not use the machine near flammable gas or combustibles, such as gasoline, benzene, thinner, etc.
  • Do not drink or use the water drained from the unit.
  • Do not take the water bucket out during operation.
  • Do not use the unit in small spaces.
  • Do not put in places where water may splash onto the unit.
  • Place the unit on a level, sturdy section of the floor.
  • Do not cover the intake or exhaust openings with cloths or towels.
  • Care should be taken when using the unit in a room with the following persons: infants, children, elderly people, and people not sensitive to humidity.
  • Do not use in areas where chemicals are handled.
  • Never insert your finger or other foreign objects into grills or openings. Take special care to warn children of these dangers.
  • Do not place heavy objects on the power cord and take care so that the cord is not compressed.
  • Do not climb up on or sit on the unit.
  • Always insert the filters securely. Clean filter once every two weeks.
  • If water enters the unit, turn the unit off and disconnect the power, and contact a qualified service technician.
  • Do not place flower vases or another water container on top of the unit.
  • Do not use extension cords.

CAUTION

  • This appliance can be used by children aged 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning the use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. (be applicable for the European Countries)
  • This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. (be applicable for other countries except for the European Countries )
  • If the supply cord is damaged, it must be replaced by the manufacturer,its service agent, or similarly qualified persons in order to avoid a hazard.
  • Prior to cleaning or other maintenance, the appliance must be disconnected from the supply mains.
  • Do not install the appliance in a location that may be exposed to a combustible gas. If combustible gas accumulates around the unit, it may cause fire.
  • If the appliance is knocked over during use, turn off the unit and unplug it from the main power supply immediately. Visually inspect the unit to ensure there is no damage.
  • If you suspect the unit has been damaged, contact a technician or customer service for assistance.
  • In a thunderstorm, the power must be cut off to avoid damage to the machine due to lightning.
  • Do not run cord under carpeting. Do not cover the cord with throw rugs, runners, or similar coverings. Do not route the cord under furniture or appliances. Arrange the cord away from traffic area and where it will not be tripped over.
  • Do not operate the unit with a damaged cord or plug. Discard the unit or return it to an authorized service facility for examination and/or repair.
  • To reduce the risk of fire or electric shock, do not use this fan with any solid-state speed control device.
  • The appliance shall be installed in accordance with national wiring regulations.
  • Contact the authorized service technician for repair or maintenance of this unit.
  • Turn off the product when not in use.
  • The manufactures nameplate is located on the rear panel of the unit and contains electrical and other technical data specific to this unit.
  • Be sure the unit is properly grounded. To minimize shock and fire hazards, proper grounding is important. The power cord is equipped with a three-prong grounding plug for protection against shock hazards.
  • Your unit must be used in a properly grounded wall receptacle. If the wall receptacle you intend to use is not adequately grounded or protected by a time-delay fuse or circuit breaker(please refer to the nameplate for the electrical data), have a qualified electrician install the proper receptacle.
  • Do not operate your air conditioner in a wet room such as a bathroom or laundry room.
  • The unit s circuit board(PCB) is designed with a fuse to provide overcurrent protection.
  • The specifications of the fuse are printed on the circuit board, such as T 3.15A/250V (or 350V), etc.

Note about Fluorinated Gasses(Not applicable to the unit using R290 Refrigerant)

  1. Fluorinated greenhouse gases are contained in hermetically sealed equipment. For specific information on the type, the amount, and the CO2 equivalent in tonnes of the fluorinated greenhouse gas(on some models), please refer to the relevant label on the unit itself.
  2. Installation, service, maintenance, and repair of this unit must be performed by a certified technician.
  3. Product uninstallation and recycling must be performed by a certified technician.

Sociable Remark

When using this dehumidifier in the European countries, the following information must be followed:

DISPOSAL: Do not dispose of this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.
It is prohibited to dispose of this appliance in domestic household waste.
For disposal, there are several possibilities:

  • The municipality has established collection systems, where electronic waste can be disposed of at least free of charge to the user.
  • When buying a new product, the retailer will take back the old product at least free of charge.
  • The manufacturer will take back the old appliance for disposal at least free of charge to the user.
  • As old products contain valuable resources, they can be sold to scrap metal dealers. Wild disposal of waste in forests and landscapes endangers your health when hazardous
    substances leak into the groundwater and find their way into the food chain.

WARNING for Using R32/R290 Refrigerant

  • Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
  • The appliance shall be stored in a room without continuously operating ignition sources (for example open flames, an operating gas appliance, or an operating electric heater).
  • Do not pierce or burn.
  • Be aware that the refrigerants may not contain an odor.
  • The appliance should be installed, operated, and stored in a room with a floor area according to the amount of refrigerant to be charged. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself.
  • The appliance should be installed, operated, and stored in a room with a floor area larger than 4 m².
  • Compliance with national gas regulations shall be observed.
  • Keep ventilation openings clear of obstruction.
  • The appliance shall be stored so as to prevent mechanical damage from occurring.
  • A warning that the appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.
  • Any person who is involved with working on or breaking into a refrigerant circuit should hold a currently valid certificate from an industry-accredited assessment authority, which authorizes their competence to handle refrigerants safely in accordance with industry-recognized assessment specifications.
  • Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of a person competent in the use of flammable refrigerants.
  • The appliance shall be stored in a room without continuously operating open flames (for example an operating gas appliance) and ignition sources (for example an operating electric heater).

Caution: Risk of fire/ flammable materials

Explanation of symbols displayed on the unit(For the unit adopts R32/R290 Refrigerant only):

**| WARNING
This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire.
---|---
|
CAUTION
This symbol shows that the operation manual should be read carefully.
|
CAUTION
This symbol shows that service personnel should be handling this equipment with reference to the installation manual.
**
| CAUTION
This symbol shows that information is available such as the operating manual or installation manual.

  1. Transport of equipment containing flammable refrigerants
    See transport regulations

  2. Marking of equipment using signs
    See local regulations

  3. Disposal of equipment using flammable refrigerants
    See national regulations.

  4. Storage of equipment/appliances
    The storage of equipment should be in accordance with the manufacturer’s instructions.

  5. Storage of packed (unsold) equipment
    Storage package protection should be constructed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be determined by local regulations.

  6.  Information on servicing
    1)Checks the area
    Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system.
    2)Work procedure
    Work shall be undertaken under a controlled procedure so as to minimize the risk of flammable gas or vapor being present while the work is being performed.
    3)General work area
    All maintenance staff and others working in the local area shall be instructed on the nature of the work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
    4)Checking for the presence of refrigerant
    The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed, or intrinsically safe.
    5)Presence of a fire extinguisher
    If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
    6)No ignition sources
    No person carrying out work in relation to a refrigeration system that involves exposing any pipework that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removal, and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs shall be displayed.
    7)Ventilated area
    Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the atmosphere.
    8)Checks the refrigeration equipment
    Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer’s maintenance and service guidelines shall be followed. If in doubt consult the manufacturer’s technical department for assistance. The following checks shall be applied to installations using flammable refrigerants:
    The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
    The ventilation machinery and outlets are operating adequately and are not obstructed;
    If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;
    Refrigeration pipes or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant- containing components unless the components are constructed of materials that are inherently resistant to being corroded or are suitably protected against being so corroded.
    9)Checks to electrical devices
    Repair and maintenance of electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise the safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.
    Initial safety checks shall include:
    That capacitor is discharged: this shall be done in a safe manner to avoid the possibility of sparking;
    That there no live electrical components and wiring are exposed while charging, recovering, or purging the system; That there is continuity of earth bonding.

  7. Repairs to sealed components
    1)During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
    2)Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, an excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that apparatus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications.
    NOTE: The use of silicone sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.

  8. Repair intrinsically safe components
    Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and currently permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while living in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

  9. Cabling
    Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

  10. Detection of flammable refrigerants
    Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used.

  11. Leak detection methods
    The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/ extinguished.
    If leakage of refrigerant is found which requires brazing, all of the refrigerants shall be recovered from the system, or isolated (by means of shut-off valves) in a part of the system remote from the leak.
    Oxygen-free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

  12. Removal and evacuation
    When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:
    Remove refrigerant; Purge the circuit with inert gas; Evacuate; Purge again with inert gas; Open the circuit by cutting or brazing.
    The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working pressure is achieved, then venting to the atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system.
    When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.

  13. Charging procedures
    In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.
    Cylinders shall be kept upright.
    Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
    Label the system when charging is complete (if not already).
    Extreme care shall be taken not to overfill the refrigeration system. Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging prior to commissioning. A follow-up leak test shall be carried out prior to leaving the site.

  14. Decommissioning
    Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely.
    Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
    a) Become familiar with the equipment and its operation. b) Isolate system electrically. c) Before attempting the procedure ensure that: Mechanical handling equipment is available, if required, for handling refrigerant cylinders; All personal protective equipment is available and being used correctly;
    The recovery process is supervised at all times by a competent person; Recovery equipment and cylinders conform to the appropriate standards. d) Pump down the refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system. f) Make sure that the cylinder is situated on the scales before recovery takes place. g) Start the recovery machine and operate in accordance with the manufacturer’s instructions. h) Do not overfill cylinders. (No more than 80 % volume liquid charge). i) Do not exceed the maximum working pressure of the cylinder, even temporarily. j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from the site promptly and all isolation valves on the equipment are closed off. k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

  15. Labeling
    Equipment shall be labeled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

  16. Recovery
    When removing refrigerants from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labeled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with a pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.
    In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained, and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release.
    Consult the manufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

Preparation

Identification of parts

NOTE:
All the illustrations in the manual are for explanation purposes only. Your machine may be slightly different.
The actual shape shall prevail. The unit can be controlled by the unit control panel alone or with the remote controller. This manual does not include Remote Controller Operations, see the <> packed with the unit for details.

Design Notice
In order to ensure the optimal performance of our products, the design specifications of the unit are subject to change without prior notice.

Positioning the unit

Casters(At four points on the bottom of the unit)

  • Casters can move freely.
  • Do not force casters to move over the carpet, nor move the unit with water in the bucket.
    (The unit may tip over and spill water.)

A dehumidifier operating in a basement will have little or no effect in drying an adjacent enclosed storage area, such as a closet unless there is adequate circulation of air in and out of the area.

  • Do not use outdoors.

  • This dehumidifier is intended for indoor residential applications only. This dehumidifier should not be used for commercial or industrial applications.

  • Place the dehumidifier on a smooth, level floor strong enough to support the unit with a full bucket of water.

  • Allow at least 20cm of air space on all sides of the unit for good air circulation (at least 40cm of air space on the air outlet).

  • Place the unit in an area where the temperature will not fall below 5 C(41 F). The coils can become covered with frost at temperatures below 5 C(41 F), which may reduce performance.

  • Place the unit away from the clothes dryer, heater, or radiator.

  • Use the unit to prevent moisture damage anywhere books or valuables are stored.

  • Use the dehumidifier in a basement to help prevent moisture damage.
    The dehumidifier must be operated in an enclosed area to be most effective.

  • Close all doors, windows, and other outside openings to the room.

When using the unit
  • When first using the dehumidifier, operate the unit continuously for 24 hours. Make sure the plastic cover on the continuous drain hose outlet install slightly properly so there are no leaks.
  • This unit is designed to operate in a working environment between 5 C/41 F and 32 C/90 F, and between 30%(RH) and 80%(RH).
  • If the unit has been switched off and needs to be switched on again quickly, allowing approximately three minutes for the correct operation to resume.
  • Do not connect the dehumidifier to a multiple sockets outlet, which is also being used for other electrical appliances.
  • Select a suitable location, making sure you have easy access to an electrical outlet.
  • Plug the unit into an electrical socket-outlet with an earth connection.
  • Make sure the Water bucket is correctly fitted otherwise the unit will not operate properly.

NOTE: When the water in the bucket reaches a certain level, please be careful to move the machine to avoid it falling down.

Operating Instructions

Control Panel Features

NOTE: The following control panels are for explanation purposes only. The control panel of the unit you purchased may be slightly different according to the models. Your machine may not contain some indicators or buttons. The actual shape shall prevail.

Indicator Function Indicator Function
Air purifier light Timer ON light
Anti-mold light Timer OFF light
Low fan speed light Dehumidifying mode light
Med fan speed light Dryer mode light
High fan speed light Continuous Dehumidifying light
Bucket full light Smart Dehumidifying light

Note: When the lights are dark, press any pad(except the power pad) the first time, and light up the lights. Then press a pad to operate the desired settings. ( For panel H )

When you push the button to change operation modes, the unit will make a beep sound to indicate that it is changing modes.
Power / button
Press to turn the dehumidifier on and off.
Note: When the compressor startups or stops running, the unit may make a loud voice, it is normal.

Mode button
Press to select the desired operation mode from
Dehumidifying, Dryer, Continuous dehumidifying, and Smart dehumidifying.
Note: Dryer and Smart dehumidifying modes are optional.
(For control panel H)Press the MODE pad for 3
(For control panel K)Press the ION pad for 3 seconds to initiate the Wireless connection mode.
The LED DISPLAY shows the app(at this time the unit shuts off all other functions) to indicate you can set
Wireless connection. If the connection (router) is successful within 8 minutes, the unit will exit Wireless connection mode automatically and the unit reverts to the previous state.
If the connection is a failure within 8 minutes, the unit exits the Wireless connection mode automatically.

Fan button (On some models)
(For control panel C&D&J&E&K&L&F)Control the fan speed. Press to select fan speed in three steps-low, med, and high. The fan speed indicator light illuminates under different fan speed settings. But when selecting high fan speed, both the low and med fan speed lights illuminate.

Turbo button (On some models)
(For control panel A&B&I&M&G)Control the fan speed.
Press to select either High or Normal fan speed. Set the fan control to High for maximum moisture removal. When the humidity has been reduced and quiet operation is
preferred, set the fan control to Normal.
(For control panel I)Control the fan speed. Press to select fan speed in three steps-low, med, and high. The fan speed indicator light illuminates under different fan speed settings. But when selecting high fan speed, both the low and med fan speed lights illuminate.
Note: The turbo button is disabled in Dryer mode, the Self-clean, Air purifier, or Anti-mould functions. Pressing the turbo button for more than 3 seconds enables the Self-clean function and the LED DISPLAY shows ‘SC’ for 5 seconds. Press this button for 3 seconds again to cancel the Self-clean function, the LED DISPLAY flashes ‘SC’ for 5 seconds.

Timer button
Press to initiate the Autostart and Auto-stop feature, in conjunction with the buttons.

Ion button(On some models)
Press to activate the ionizer. Anions are automatically generated by ionization. The anions deactivate the airborne chemical vapors and dust particles. Press it again to stop the function.
Fresh button(On some models)
Press to activate the ionizer. The ion generator is energized and will help to purify the air inside. Press it again to stop the function.

Wireless button(On some models)
Press this button for 3 seconds to initiate the Wireless connection mode. The LED DISPLAY shows the app (at this time the unit shuts off all other functions) to indicate you can set a Wireless connection. If the connection (router) is successful within 8 minutes, the unit will exit Wireless connection mode automatically and the Wireless indicator illuminates and the unit enters the previous function. If the connection is a failure within 8 minutes, the unit exits the Wireless connection mode automatically.

Pure/Anti-mould button(On some models)
Press this button to select the Air purifier function which uses the included HEPA(High Efficiency
Particulate Air) filter to reduce the dust, bacteria, and allergen content in the room.
Press the button for 3 seconds to enable the Anti-mould function. Press this button for 3 seconds again to cancel the Anti-mould function and the unit prevents the previous state.

UP( )/DOWN( ) buttons(On some models)

  • Humidity Set Control buttons
    The humidity level can be set within a range of 35% RH(Relative Humidity) to 85%RH(Relative Humidity) in 5% increments.
    For drier air, press the button and set it to a lower percent value(%).
    For damper air, press the button and set a higher percent value(%).

  • TIMER Set Control buttons
    Use the Up/Down buttons to set the Autostart and Auto stop time from 0.0 to

  1. (For control panel E ) Note: Press the button for 3 seconds to show the room temperature and quit to showroom temperature after 10 seconds.

Display
Shows the set % humidity level from 35% to 85% or auto start/stop time (0~24) while setting, then shows the actual(±5% accuracy) room % humidity level in a range of 30% RH(Relative Humidity) to 90%RH(Relative Humidity).
Error Codes:
AS-Humidity sensor error–Unplug the unit and plug it back in. If the error repeats, call for service;
ES-Temperature sensor error– Unplug the unit and plug it back in. If the error repeats, call for service;
P2-Bucket is full or bucket is not in right position–
Empty the bucket and replace it in the right position.
P1-Unit is defrosting–Allow the unit time to automatically service. The protection will clear after the unit self defrosts. (On some models)
E4-Display panel communication error–Unplug the unit and plug it back in. If the error repeats, call for service. (On some models)

Other features

Bucket Full Light
Glows when the bucket is ready to be emptied, or when the bucket is removed or not replaced in the proper position.
Auto Defrost
When the frost builds up on the evaporator coils, the compressor will cycle off and the fan will continue to run until the frost disappears.
Note: When Auto defrosting operation, the unit may make a voice of refrigerant flowing, it is normal.
Auto Shut Off
The dehumidifier shuts off when the bucket is full, or when the bucket is removed or not replaced in the proper position. For some models, the fan motor will continue to run for 30 seconds.
Wait 3 minutes before resuming the operation
After the unit has stopped, it can not be restart operation in the first 3 minutes. This is to protect the unit. The operation will automatically start after 3 minutes.
Auto-Restart
If the unit breaks off unexpectedly due to the power cut, it will restart with the previous function setting automatically when the power resumes.

Smart dehumidifying mode(On some models)
In smart dehumidifying mode, the unit will automatically control room humidity in a comfortable range of 45%~55% according to the room temperature.
The humidity setting function will be invalid.
Anti-mold function(On some models)
Press the Pure pad for 3 seconds to enable this function. This maximizes occupant comfort while reducing the risk of mold and bacterial growth. To disable the function, press the Pure pad for 3 seconds or select an operating mode with the Mode pad.

Self-clean(On some models)
Press the Turbo pad for 3 seconds to enable this function. This function initiates as soon as the unit is switched off, and runs for 15 minutes under high fan speed.

Air purifier function(On some models)
This function significantly reduces the dust, bacterial, and allergen content of the room, using the HEPA(High
Efficiency Particulate Air) filter supplied with the unit.
Press the Pure pad to activate the Air purifier function, all other modes and special functions are inhibited while it is running. Make sure you have fitted the HEPAfilter as indicated in fig.A.

Setting the Timer(With 1 indicator light)

  • Press to initiate the Autostart or Auto-stop feature, in conjunction with the UP and DOWN buttons.
  • When the unit is on, press the Timer button to actieve the Auto-Stop feature. When the unit is off, press this button to activate the Autostart feature.
  • Press or hold the UP or DOWN button to change the Auto time by 0.5-hour increments, up to 10 hours, then at 1-hour increments, up to 24 hours. The control will count down the time remaining until the start.
  • The selected time will register in 5 seconds and the system will automatically revert back to displaying the previous humidity setting.
  • Turning the unit On or Off at any time or adjusting the timer setting to 0.0 will cancel the Auto Start/Stop function.
  • When the LED display window plays the code of P2, the Auto Start/Stop function will also be canceled.

Setting the Timer(With 2 indicator lights)

  • When the unit is on, first press the Timer button, the Timer Off indicator light illuminates. It indicates the
    Auto Stop program is initiated. Press it again the
    Timer On indicator light illuminates. It indicates the
    Auto Start is initiated.

  • When the unit is off, first press the Timer button, and the Timer On indicator light illuminates. It indicates the Auto Start program is initiated. Press it again the Timer Off indicator light illuminates. It indicates the Auto Stop is initiated.

  • Press or hold the UP or DOWN button to change the Auto time by 0.5-hour increments, up to 10 hours, then at 1-hour increments, up to 24 hours. The control will count down the time remaining until the start.

  • The selected time will register in 5 seconds and the system will automatically revert back to displaying the previous humidity setting.

  • When the Autostart & Auto-stop times are set, within the same program sequence, Timer On Off indicator lights illuminate identifying both On and Off times are now programmed.

  • Turning the unit On or Off at any time or adjusting the timer setting to 0.0 will cancel the Auto Start/Stop function.

  • When the LED display window plays the code of P2, the Auto Start/Stop function will also be canceled.

Dryer mode(On some models)
The unit can make the MAX dehumidification function when it is under Dryer mode. The fan speed is fixed at high fan speed. For some models, The unit will quit dryer mode after a maximum of 10 hours of operation.

Note:

  1. The dryer mode must be operated in a closed room, do not open the door and window.
  2. To make the best effective dehumidification, please first dehydrate the wet clothes.
  3. Make sure to direct airflow at the wet clothes.
  4. Thick and heavy wet clothes may not get the best effective dehumidification.
Removing the collected water

There are two ways to remove collected water.

Use the bucket

  • When the unit is off if the bucket is full, the unit will beep 8 times(on some models) and the Full Water indicator light will flash.

  • (For some models)When the unit is on, if the bucket is full, the compressor turns off and the fan turns off after 30 seconds for drying the water of the condenser, then the unit will beep 8 times, and the Full Water indicator light will flash.

  • Slowly pull out the bucket. Grip the left and right handles securely, and carefully pull out straight so water does not spill. Do not put the bucket on the floor because the bottom of the bucket is uneven.
    Otherwise, the bucket will fall and cause the water to spill.

  • Throw away the water from the water outlet and replace the bucket. The bucket must be in place and securely seated for the dehumidifier to operate.

  • The machine will re-start when the bucket is restored to its correct position.

1. Pull out the bucket a little.

Hold both sides of the bucket with even strength, and pull it out from the unit.

Pour the water out.

Note:

  • When you remove the bucket, do not touch any parts inside of the unit. Doing so may damage the product.
  • Be sure to push the bucket gently all the way into the unit. Banging the bucket against anything or failing to push it in securely may cause the unit not to operate.
  • When you remove the bucket, if there is some water in the unit you must dry it.

Continuous draining

  • Water can be automatically emptied into a floor drain by attaching the unit with a water hose(not included).

  • Remove the rubber plug or cut the cover down from the back drain hose outlet. Attach a drain hose and lead it to the floor drain or a suitable drainage facility.

  • Make sure the hose is secure so there are no leaks.

  • Direct the hose toward the drain, making sure that there are no kinks that will stop the water from flowing.

  • Place the end of the hose into the drain and make sure the end of the hose is level or down to let the water flow smoothly. Do never let it up.

  • Make sure the water hose is lower than the drain hose.

  • Select the desired humidity setting and fan speed on the unit for continuous draining to start.

Note: When the continuous drain feature is not being used, remove the drain hose from the outlet and reinstall the rubber plug.

Care and Maintenance

Care and cleaning of the dehumidifier
Turn the dehumidifier off and remove the plug from the wall outlet before cleaning.

Clean the Grille and Case
  • Use water and a mild detergent. Do not use bleach or abrasives.
  • Do not splash water directly onto the main unit. Doing so may cause an electrical shock, cause the insulation to deteriorate, or cause the unit to rust.
  • The air intake and outlet grilles get soiled easily, so use a vacuum attachment or brush to clean.
Clean the bucket

Every few weeks, clean the bucket to prevent the growth of mold, mildew, and bacteria. Partially fill the bucket with clean water and add a little mild detergent. Swish it around in the bucket, empty, and rinse.
Note: Do not use a dishwasher to clean the bucket. After cleaning, the bucket must be in place and securely seated for the dehumidifier to operate.

Clean the air filter

The air filter behind the front grille should be checked and cleaned at least every two weeks or more often if necessary.
NOTE: DO NOT RINSE OR PUT THE FILTER IN AN AUTOMATIC DISHWASHER.

To remove:

  • Grip the tab on the filter and pull it outward, then pull it up.

  • Clean the filter with warm, soapy water. Rinse and let the filter dry before replacing it. Do not clean the filter in a dishwasher.
    To attach:

  • Insert the air filter into the unit from the underside to the upside.

CAUTION
DO NOT operate the dehumidifier without a filter because dirt and lint will clog it and reduce performance.

Note: The cabinet and front may be dusted with an oil-free cloth or washed with a cloth dampened in a solution of warm water and mild liquid dishwashing detergent.
Rinse thoroughly and wipe dry. Never use harsh cleansers, wax, or polish on the cabinet front. Be sure to wring excess water from the cloth before wiping around the controls. Excess water in or around the controls may cause damage to the unit.

When not using the unit for long time periods

  • After turning off the unit, wait one day before emptying the bucket.
  • Clean the main unit, water bucket, and air filter.
  • Cover the unit with a plastic bag.
  • Store the unit upright in a dry, well-ventilated place.

Troubleshooting Tips

Before calling for service, review the chart below first yourself.

Problem What to check
The unit does not start
  • Make sure the dehumidifier s plug is pushed completely into the outlet.
  • Check the house fuse/circuit breaker box.
  • The dehumidifier has reached its present level or the bucket is full.
  • The water bucket is not in the proper position.

The dehumidifier does not
dry the air as it should|

  • Did not allow enough time to remove the moisture.
  • Make sure there are no curtains, blinds, or furniture blocking the front or back of the dehumidifier.
  • The humidity control may not be set low enough.
  • Check that all doors, windows, and other openings are securely closed.
  • Room temperature is too low, below 5  C(41  F).
  • There is a kerosene heater or something giving off water vapor in the room.

The unit makes a loud
noise when operating|

  • The air filter is clogged.
  • The unit is tilted instead of the upright as it should be.
  • The floor surface is not level.

Frost appears on the coils|

  • This is normal. The dehumidifier has an auto-defrost feature.

Water on floor|

  • The hose to connector or hose connection may be loose.
  • Intend to use the bucket to collect water, but the back drain plug is removed.

ES, AS, E4, P1 or P2
appear in the display|

  • These are error codes and protection codes. See the CONTROL PADS ON THE DEHUMIDIFIER section.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals