Installation instruction

Application

The WSK 510 switch is designed to give the fireman the possibility to override the automatic smoke ventilation control and to force windows/openings closed or opened regardless of the automatic control.

Mounting

WSK 510 is to be mounted indoor on a wall through the holes in the back plate.

Configuration

WSK 510 is configured on the smoke panel (type WSC 3×0 Plus or WSC 5xx) to which they are connected.
In “View all details” “Smoke zone” the “Use Line E and F for WSK 510” must be set to “yes”.

Connection

The WSK 510 is used together with smoke panels type WSC 3×0 Plus and WSC 5xx. The WSK 510 can be connected directly to the smoke panel or to a break glass unit type WSK 50x. The WSK 50x and the WSK 510 can be connected in an arbitrary order.
Comfort keypads can be connected to WSK 510. Smoke detectors cannot be connected to WSK 510.
Note, when a WSK 510 is to be connected to a smoke control panel or a break glass unit the panel must have below listed firmware or later.

  • WSC 3×0 P ver. E1 & E5: 1.43 (not yet released)
  • WSC 3×0 P ver. E2 & E4: 2.12
  • WSC 5xx ver. E2: 1.12
  • WSC 5xx ver. E3: 1.00

Connection to smoke panel type WSC 3×0 P

**Connection to smoke panel type WSC 5xx

Connection to break glass unit type
**WSK 501/502
Please see the instruction of WSK 5xx, WSC 3×0 P or WSC 5xx for connection of WSK 501/502 to the WSC 3×0 P / WSC 5xx.

For further information please see the installation instruction of WSC 3xx, WSC 5xx or WSK 5xx.

Labels

The WSK 510 is supplied with 3 different labels in several languages.

The “SMOKE VENT“ label is placed on the door above the glass.
The “FIREMAN’S OVERRIDE” label is placed on the door below the glass.
The “OPEN” “CLOSE” label is placed on the white plastic part below the two black buttons.

Functionality

The WSK 510 is equipped with two push buttons (“OPEN” and “CLOSE”), a reset button and 4 LEDs.

Push Buttons

OPEN push button
When pushing the “OPEN” button, the smoke zone goes in “Alarm” state and opens the windows 100 %.
The “OPEN” LED is switched ON. The “CLOSE” LED is switched OFF.
CLOSE push button
When pushing the “CLOSE” the smoke zone goes in “Alarm” state and closes the windows.
The “CLOSE” LED is switched ON. The “OPEN” LED is switched OFF.
Reset push button
Pushing the “Reset” button – located inside on the right side under the plastic door – or receiving a “Reset” from any other source, puts the smoke zone back in “normal operation” state and closes all windows. The red LEDs are switched off۔

LED- and Icon explanation

On the break glass unit there are 2 icons and 4 LED.

**Ok** and green LED
When the green LED to the left of the OK icon is constantly on, the unit is connected to a smoke panel, there is 230V power supply to the smoke panel and the unit is associated with a smoke zone.
If the green LED is flashing, the smoke control panel has no 230V power supply, but the fault indication period has not occurred yet.

and yellow LED

If the yellow LED to the left of the exclamation mark icon is on, there is a fault in the smoke zone.

Red LEDs

If one of the red LEDs above one of the trigger buttons is on, the system has been triggered.

Green and yellow LED

If the green and the yellow LED flash alternately, the break glass unit is not associated with a smoke zone.

Green, yellow, and red LED

If all 4 LED are flashing, the unit does not have connection to the smoke control panel.