DESCO ASIA CTC065-5-WW Ground Master Monitor Installation Guide
- June 5, 2024
- DESCO ASIA
Table of Contents
TECHNICAL BULLETIN TB-9114
Ground Master Monitor
Installation, Operation and Maintenance
Figure 1. SCS CTC065-5-WW Ground Master Monitor
Description
The SCS Ground Master Monitor is an equipment ground continuous monitor for
metal tools. It continuously monitors the path-to-ground impedance and
electromagnetic integrity of eight metal ground connections of process tools
in work areas. This includes semiconductor, disk drive, flat panel, and
electronic equipment manufacturing environments. The monitor provides both
visual and audible alarms and includes fuse protection for each channel.
The Ground Master Monitor continuously monitors eight metal tools for
electromagnetic interference (EMI). EMI can cause equipment lockups and
malfunction. The Ground Master Monitor will alarm if EMI is detected. Each
Ground Master Monitor is calibrated with accepted procedures and standards
traceable to the National Institute of Standards and Technology (NIST) and
includes a certificate of calibration.
The Ground Master Monitor meets the Continuous Monitor requirements of
ANSI/ESD S20.20 in accordance with ESD TR53. It meets the recommendations of
ESD Handbook ESD TR20.20 which includes “if the products that are being
produced are of such value that knowledge of a continuous, reliable ground is
needed, and then continuous monitoring should be considered or even required”.
The Ground Master Monitor and its accessories are available as the following
item numbers:
Item | Description |
---|---|
CTC065-5-WW | Ground Master Monitor, with Modbus Connectivity |
CTA212 | Power Adapter, 100-240 VAC Input, 12 VDC 1.5 A Output, All Plugs |
CTC065-C | Ground Master Extension Cable Unit |
CTE701 | Workstation Monitor Checker |
Packaging
1 Ground Master Monitor
1 Monitor Ground Cord (Green and Yellow)
4 Replacement Fuses (250 VAC, 125 mA)
1 Ring Terminal 1 Screw, Pan-Head, 6-32 x 1/4″
1 Star Washer
1 Power Adapter, 12 VDC, with interchangeable plugs (North America, UK/Asia,
Europe, China)
1 Certificate of Calibration
Features and Components
Figure 2. CTC065-5-WW Ground Master Monitor features and components
A. Power LED: Illuminates yellow when the monitor is powered.
B. Tool LEDs: Illuminates green when its respective tool is within the
impedance and electromagnetic interference (EMI) voltage test limits. Blinks
red when its respective tool exceeds the EMI voltage limit. Illuminates solid
red and audible alarm sounds when its respective tool exceeds the impedence
test limit.
C. Tool Monitor Switches: Slide the switch up to enable its respective
tool monitor circuit. Slide the switch down to disable its respective tool
monitor circuit.
D. Test Limit Rotary Switch (top-side): Sets the test limit of the tool
monitor circuits from 1 to 20 ohms.
Setting | Test Limit | Setting | Test Limit |
---|---|---|---|
1 | 1 ohm | 9 | 9 ohms |
2 | 2 ohms | A | 10 ohms* |
3 | 3 ohms | B | 12 ohms |
4 | 4 ohms | C | 14 ohms |
5 | 5 ohms | D | 16 ohms |
6 | 6 ohms | E | 18 ohms |
7 | 7 ohms | F | 20 ohms |
8 | 8 ohms |
*default setting
E. Audible Alarm Switch: Enables and disables the monitor’s audible
alarm.
F. Protective Fuses: Protects the spread of harmful voltage to other
tools via the Ground Master Monitor should one of the tools become exposed to
excessive voltage. The appropriate fuse will disconnect the faulty tool from
the Ground Master Monitor and from the other connected tools.
G. Communication LEDs: Blinks when the monitor is powered and
communicating to SMP Server.
H. Ext. Jack: Slave port for serial daisy-chaining.
I. Modbus Output Jack: Provides Modbus connectivity to a data acquisition
system and accepts 12-24 VDC power.
Pin | Signal | Pin | Signal |
---|---|---|---|
1 | 12-24 VDC | 5 | TXD0/D0 |
2 | Ground | 6 | Ground |
3 | 12-24 VDC | 7 | 12-24 VDC |
4 | TXD1/D1 | 8 | Ground |
J. Power Jack: Connect the included 12VDC power adapter here.
K. Monitored Tool Terminals: Monitors metal tools for proper conductive
impedance and electromagnetic interference (EMI) voltage. Use 18 AWG wire to
connect the metal tools to these terminals.
L. Ground Terminal: Common ground point for the monitor.
Installation
- Remove the Ground Master Monitor from the carton, and inspect for damage.
- Determine the mounting location of the Ground Master Monitor, and use its mounting tabs to secure it. Its display should be visible to the operator(s).
- Bond the Ground Master Monitor to equipment ground by using the ground terminal screw located on its bottom-side.
- Insert stripped terminations of 18 AWG wires (not included) into the monitored tool terminals located on the bottom side of the Ground Master Monitor. Ensure that the tool monitor switches are enabled if using these monitored tool terminals.
- Route the tool monitor wires from the bottom side of the Ground Master Monitor to their respective grounded metal tools, and secure them. Keep the wires as short as possible. Do not loop or coil them as it may affect the measured impedance.
- Connect a powered Modbus cable to the Modbus output jack located on the bottom side of the Ground Master Monitor. The Ground Master Monitor is now powered.
Operation
Use the table below to interpret the behavior of the Ground Master Monitor’s tool LED’s and audible buzzer (if enabled).
Green LED | Red LED | Buzzer | Status |
---|---|---|---|
ON | OFF | OFF | No failures |
OFF | ON | ON | Impedance failure |
ON | BLINK | OFF | EMI voltage failure |
OFF | OFF | OFF | Monitor channel disabled |
Maintenance
Cleaning
Disconnect the power adapter from the device. Clean the Ground Master
Monitor using a dry brush or vacuum cleaner. Clean its contacts using a
contact cleaner or brush, and tighten all connections. Do not reconnect the
power adapter until cleaning is finished.
Replacing the Fuses
The monitored equipment may become prone to excessive voltage and significant
damage should it lose its connection to ground or be bonded to an improperly
wired ground point. In order to prevent the spread of this excessive voltage
to other equipment via the Ground Master Monitor, fuses are implemented for
each individual ground connection. In the case of excessive voltage on the
equipment, the appropriate fuse will disconnect the equipment from the Ground
Master Monitor and from the other connected equipment. Ground failure on that
particular ground will be immediately indicated.
Before replacing the fuse, always investigate the reason for the fuse blowing,
and correct the problem. The fuse should never blow under normal
circumstances.
NOTE: Never use wire jumpers in place of fuses. Use only factory-
authorized fuses. Disconnect power before replacing any fuses. The fuses are
manufactured by Littelfuse®, and its part number is 37301250410.
Calibration
Frequency of recalibration should be based on the critical nature of those
ESD-sensitive items handled and the risk of failure for the ESD protective
equipment and materials. In general, SCS recommends that calibration be
performed annually.
Use the SCS CTE701 Workstation Monitor Checker to perform periodic
verification (once every 6-12 months) of the Ground Master Monitor. The
Workstation Monitor Checker can be used to check the test limits of the Ground
Master Monitor without removing it from the factory floor.
See TB-9031 for more information.
Figure 3. SCS CTE701 Workstation Monitor Checker
Specifications
Power
Power Adapter| Output: 12 VDC @ 1.5 A
100-240 VAC| Output Plug Polarization: Center Positive
50-60 Hz| Output Plug: 5.5 mm O.D. x 2.1 mm I.D. x 9.5 mm L
Metal Tool
Amount Monitored| 8
Impedance Limit| 10 ohms (default)
EMI Voltage Limit| 223 mV average amplitude (@ 1.5 MHz)
Test Voltage| 80 mV square pulse @ open circuit (80 Hz)
Test Current| <5 mA @ short circuit
Connectivity
Input| 18 AWG wire terminal blocks for metal tools
General
Alarm| LEDs and buzzer
Dimensions| 3.54″ x 5.52″ x 1.18″ (90 mm x 140 mm x 30 mm)
Weight| 0.4 lbs. (0.18 kg)