Loom Solar CAML 100 48 Volt 5 kWh Lithium Battery for Home Inverter User Manual

June 5, 2024
LOOM SOLAR

Loom Solar logo

CAML 100 48 Volt 5 kWh Lithium Battery for Home Inverter
User Manual

LiFePO Battery System for Solar / Power Backup

Safety and Warning

  • The CAML100Ah/48V LiFePO4 battery system installation, operation, and maintenance should follow important recommendations in this manual: The equipment shall be installed by the professional training staff.
  • Battery maintenance should be carried out by professional staff who are experienced and aware of the preventive measures on the potential harm to the battery.
  • Note: Be careful of the risk of electric shock for large current in case of battery short circuit, pay attention to the following points during operation.
  • Remove watches, rings, or other metal objects.
  • Use tools with insulated handles.
  • Do not place tools or metal objects on the battery.
  • Do not direct access to the battery system to the mains grid power outlet.
  • Do not put the battery system into fire, and do not use or store the battery near to the high-temperature source.
  • Do not use liquid or other objects placed into the battery system.
  • Do not open or cut the battery, not to hit throw, or step on the battery.
  • Using special communication iron lithium battery charging rectifier power supply module to charge the battery.
  • Be sure to be subject to charge and discharge parameters set in this manual.
  • The output interface of the system is still voltage when grid power is cut, avoid electric shock or short circuits when operating.
  • Please check if the box is damaged. If damaged, please immediately notify the supplier.
  • If you find leaking liquid or white powder residue on the product, prohibit operation.

System Introduction

2.1 System overview
CAML100Ah/48V battery system is a 48V system for communications back-up type LiFePO4 (lithium iron phosphate) battery products, the system uses the advanced LiFePO4 battery technology with the benefit of long cycle life, small size, lightweight, safety, and environmental protection, and has strong environmental adaptability, it is ideal for harsh outdoor environments.
The system also integrates smart battery management and monitoring module, support for remote centralized monitoring, and remote battery management and maintenance, to meet the requirements of unattended. Therefore, the NPFC system can fully meet the backup power supply requirements of the access network equipment, mobile communications equipment, transmission equipment, micro base stations, and microwave communication equipment.
2.2 Working principle
The CAML100Ah/48V battery system mainly includes a Fe lithium battery pack, battery protection, cell balancing unit, monitoring module, and charge- discharge management module for optional. Its schematic diagram is shown in Figure 2-1Charge-discharge management module DC Input Cell balancing unit Fc lithium battery pack Battery protection Load Monitoring module Figure 2-1Loom Solar CAML 100 48 Volt 5 kWh Lithium Battery for Home Inverter - fig
2

Figure 2-1 Schematic Diagram

Fe Lithium pack: chemical power, energy storage, and power supply components. Battery protection: protect Fe lithium batteries from overcharge, over- discharge, over-current, over-temperature, and short circuits. Battery balancing unit: Equalization of Fe lithium batteries for cells unbalanced The charge and discharge management module: discharge circuit management, and charging current limit (optional according to customer requirements).
The monitoring module: support a centralized monitoring system (optional according to customer requirements)
CAML100Ah/48V battery system working principle
DC power input charge and discharge management unit after filter, DC divided into two circuits, one circuit directly supply the load, another circuit to charge Fe lithium pack. When grid power is on, the system supplies the loads and charging inside Fe lithium batteries; When grid power fails, Fe lithium inside the system supplies DC power to the load, to ensure an uninterrupted power supply as a power system.
2.3 System feature.

  • With the latest development technology trends of international communications battery, adopt advanced Felithium battery system.
  • Advanced intelligent lithium battery management technology to ensure intelligent automatic management. With balanced patented technology, Narada Fe lithium provides high efficiency and balanced and prolonged system operation life.
  • Excellent electromagnetic compatibility. The outdoor power system with this product complies with the main equipment when they work together, not interfering with each other.
  • Complete intelligent design, centralized monitoring unit has the function of “three remote” (remote measure, remote communication, remote control), the system managed by a computer, communicates with the remote monitoring center, unattended, in line with the requirements of the development of modern communications technology.
  • Combine the power control technology and computer technology, real-time monitoring, and control of the rectifier, AC, and DC power distribution.
  • Configuration flexibility, support parallel connection expansion

2.4 Front Panel and Side panel

Loom Solar CAML 100 48 Volt 5 kWh Lithium Battery for Home Inverter - fig
1 Fig. 2-2 Panel

  1. Indicator light for Capacity (SOC): SOC means the State of Capacity
    • 4 green light indication. Each light represents 25% of its capacity. Capacity meaning is shown in table 4-1

  2. Alarm light(ALM): ALM indicates the fault condition, il fault, red light on.

  3. Run light(RUN): RUN indicates the system operation state.
    • Greenlight 0.5 seconds on and 0.5 seconds off during charge.
    • Greenlight 0.5 seconds on and 1.5 seconds off during discharge.

  4. Address Dial Number(ADD): ADD indicates the system telecom address
    •  Add adopt four Dial numbers as to set up the telecom address when parallel connect system. Table 2-1 is the table of the setup number of band switches add
    Table 2-2 Panel Band -Switch Address Number Set Up
    ** Dial Number| ADD| PACK
    Definition| Description**
    ---|---|---|---
    1| 2| 3| 4| 5| 6| | |
    ON| OFF| OFF| OFF| OFF| OFF| 000001| PACK 1| As Slave Pack 1
    OFF| ON| OFF| OFF| OFF| OFF| 000010| PACK 2| As Slave Pack 2
    ON| ON| OFF| OFF| OFF| OFF| 000011| PACK 3| As Slave Pack 3
    OFF| OFF| ON| OFF| OFF| OFF| 000100| PACK 4| As Slave Pack 4
    ON| OFF| ON| OFF| OFF| OFF| 000101| PACK 5| As Slave Pack 5
    OFF| ON| ON| OFF| OFF| OFF| 000110| PACK 6| As Slave Pack 6
    ON| ON| ON| OFF| OFF| OFF| 000111| PACK 7| As Slave Pack 7
    OFF| OFF| OFF| ON| OFF| OFF| 001000| PACK 8| As Slave Pack 8
    ON| OFF| OFF| ON| OFF| OFF| 001001| PACK 9| As Slave Pack 9
    OFF| ON| OFF| ON| OFF| OFF| 001010| PACK 10| As Slave Pack 10
    ON| ON| OFF| ON| OFF| OFF| 001011| PACK 11| As Slave Pack 11
    OFF| OFF| ON| ON| OFF| OFF| 001100| PACK 12| As Slave Pack 12
    ON| OFF| ON| ON| OFF| OFF| 001101| PACK 13| As Slave Pack 13
    OFF| ON| ON| ON| OFF| OFF| 001110| PACK 14| As Slave Pack 14
    ON| ON| ON| ON| OFF| OFF| 001111| PACK 15| As Slave Pack 15
    OFF| OFF| OFF| OFF| ON| OFF| 010000| PACK 16| As Slave Pack 16

  5. Up-link communication(RS-232): an RS-232 communication interface
    • It adopts an RS-232 series port communication pattern with the system to upload data. Content of data transmitting includes system parameters, system status, and alarm messages. Normally, the speed rate of RS-232 is 9600bps.RS-232 is effective only in the system dial number switch is set as Pack (Master Pack) pattern, so as well to communicate with the upper computer/machine.

  6. Cascading Telecommunication (RS-485): an RS-485 communication interface
    • When cascading connects, adopt the RS-485 series port communication pattern to transfer data, RS-485 is adopted to be the internal communication pattern of the after-cascading pack system, the superior system through Master Pack to obtain data from each Slave Pack

  7. Reset Button
    • When performance is unusual with the system, press this button to reset the system, to assure stability of system performance.

  8. Circuit Breaker: 125A rated Miniature circuit breaker

  9. System DC output (Battery Output): Positive terminal and Negative terminal.
    • Use 2 core connecting terminal, mainly for connecting between battery module cascading, connecting terminal device pins are on the front

  10. Maintenance Interface

  11. GND

System Installation

3.1 Unboxing and Check

  • Please study this manual before installing the system
  • Please inspect the package before unboxing, if any destroy with appearance, contact the supplier immediately
    – This device should be operated by a professionally trained person
    – This device should be installed by a professional service person

3.2 Preparing Installation

  • To prevent the battery from being placed in direct sunshine or close to a heat source
  • Put your battery in ventilated place to assure enough dissipation
  • To assure the battery is in a clean and low humidity area
  • Please don’t put heavy goods on cable or power source cable.

3.3 System Installation
Note:

  • Output socket or cable of the terminal block should not exceed 2 meters
  • The essential of electric connection is safe and reliable
  • The battery system provides a terminal block for site connection and installation, the terminal block should be tightened by 13.8pound/inch(1.554newton/meter)
  • Break, damage, and scratch of cable are forbidden.
  • The internal circuit of the battery system provides protection for over current and short-circuit of DC output
  • Concerning the charging voltage of the battery system, the surrounding temperature, and other specification, please refer to the technology specification section of this manual
  • Battery installation and replacement should be implemented by a professional who is familiar with batteries and precautions.

Chart 3-1 CAML100Ah/48V Construction Dimension

No. Type Code Dimension LWH (mm) Remark
7 CAML100Ah/48V 439400222 (without hanger) Height 5U
  1. Installation and Fasten
    • Have system insert 19-inch cabinet, fix system with 4pcs screws on the shelf at both side mounting ears of the cabinet
    • Hanging installation also can be adopted, fix the system with 4pcs screw on lamp stand at both sides installing ears of the cabinet.

  2. Earth connection
    • Connect earth by flexible cable above 16AWG through earth connecting hole on right side of the cabinet back, assure well connection.

  3. Battery output connecting
    Connect the output terminal “+” “-” of LiFePO4 battery system cabinet to battery connecting terminal of DC switch power source modules with/by the black & red flexible cable
    • If need multi system connected in parallel, please connect output terminal”+”and” +” to busbar directly.

  4. System power on
    • When system installation is completed, battery should be in dormant state,and will get into normal operation
    state after power-on can be charged or discharged.

  5. Connect the RS-232 communication port
    • If necessary, the COM1 and COM2 of the PC can be connected to RS- 232communication port of the battery system front panel with/ by a communication cable
    • Can connect RS232 to monitor section according to different communication software

System Operation

4.1 Start System
After installation, the system is in a dormant & inactive state, when connect charging power source or loaded to the positive and negative electrodes, the system will be opened to a normal working state automatically
4.2 Close system
Disconnect power source and load, after a certain period, the battery system will get into a dormant inactive state initiatively.
4.3 Charge
When charging, the charging module parameters should be set in accordance with the following table.
Table 4-1 Charge parameter setting

No. Item Parameter Note
1 Float Voltage See Annex1 Float Charge Available
2 Max. Charge current See Annex1
3 Charge temperature range -10°C~50°C

Note
The charging voltage should be adjusted and set by an engineer from the manufacturer, once adjusting is complete, it usually does not need to more adjust, unless replacing the charging module.
4.4 Discharge
To ensure that the load current does not exceed the max continuous operation current when connect to the load, disconnect the voltage set to >40.5V
Note:
Increasing load under DC electrification requires a strict tool and human insulation measurement, prevent from an accident or short circuit in operation.
The specification of cable (cross-sectional area) can be selected according to the following formula, which is determined by permit voltage drop, A=EIxL/ ( Kx AU )
In formula:
A is across a sectional area of wire ( mm2); EI is the total current through the wire ( A ) ;
L is the return circuit length of wire ( m ); AU is the permit voltage drop on wire ( V ) ;
K is the electrical conductivity of wire, For example, for copper, K = 570
Recommend using color code to distinguish the polarity of wire: positive is black, negative is blue
4.5 Information Instruction
The information indicated by the six LED indicators on the front panel is in Tables 4-2 and table 4-5
Table 4-2 Status of Capacity

| | | | State of Charge (SOC)
---|---|---|---|---
| | | | 75% ≥ SOC ≥ 100%
| | | | 50% ≥ SOC ≥ 75%
| | | | 25% ≥ SOC ≥ 50%
| | | | 0% ≥ SOC ≥ 25%

Note: mean light on, mean light off
Table 4-3 RUN LED Indicator Description

Flash 1 Activation state, but neither charge nor discharge
Flash 2 Charging state
Continue Light Discharging state
Extinguish  Dormant state

Table 4-4 ALM LED Indicator State

Extinguish Minor Alarm (Various Alarm Status)
Flash 2 Fail (Various fails)
Flash 3 Major Alarm (Various protection status)
Extinguish Normal, no alarm
Light Extinguish
--- ---
Flash 1 0.25S
Flash 2 0.5S
Flash 3 0.5S

Maintenance

  • The battery should be recharged every 3 months if in long time storage
  • Please clean the dust with the dust collector when the dust is accumulated on the vent.
  • Please turn off the charging input if the system is not in use for a long time.
  • Please use a clean dry cloth/fabric to clean up the cabinet, if need further cleaning, please use a neutral un-corrode cleanser. Alcohol or ammonia synthesis is forbidden.
  • Carrying should be handled gently, to prevent it from being severely compact.
  • Prevent the battery from splashing liquid.
  • Installation and maintenance of the battery system should be implemented by trained professionals.
  • Suggestion to inspect the tighten of output screw every two years.

Annex Technical Parameter

Technical Parameter
Ambient Condition

  1. Working Temperature range: -10°C— +55°C
  2. Storage Temperature range: 0°C— +40°C
  3. Relative Humidity: 5% —95%, without condensation
  4. Altitude: 0-2000m. Above 2000m demand decease apply.

The working temperature should be reduced to 1°C every 200m rises, the max altitude is 4000m.

Loom Solar Pvt. Ltd.
CAML100Ah/48V

Read User Manual Online (PDF format)

Loading......