beko BEHPH 120 Split Type Air Conditioner User Manual

June 5, 2024
Beko

BEHPH 120 Split Type Air Conditioner

Split Type Air Conditioner
User Manual

BEHPH 090/BEHPH 091 BEHPH 120/BEHPH 121 BEHPH 180/BEHPH 181 BEHPH 240/BEHPH 241

BEVPI 090/BEVPI 091 BEVPI 120/BEVPI 121 BEVPI 180/BEVPI 181 BEVPI 240/BEVPI 241

EN – IT – FR
10M-8505543200-4921-01

CONTENTS
ENGLISH ITALIANO FRANÇAIS

3-56 57-114 115-172

V2110002 AB UM

Please read this user manual first!
Dear Customer,
Thank you for preferring a Beko product. We hope that you get the best results from your product which has been manufactured with high quality and state-of- the-art technology. Therefore, please read this entire user manual and all other accompanying documents carefully before using the product and keep it as a reference for future use. If you handover the product to someone else, give the user manual as well. Follow all warnings and information in the user manual.
Meanings of the symbols
Following symbols are used in the various section of this manual:

C Important information or useful hints about usage.
A Warning for hazardous situations with regard to life and property.
Warning to actions that must never perform.
B Warning for electric shock.
This symbol shows that information is available such as the operating manual or installation manual.

This symbol shows that the operation manual should be read carefully.

This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.

(For R32/R290 gas type)

This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire.

Do not cover it.

This product has been manufactured at modern facilities respectful to the environment without harming nature.

Complies with the WEEE Regulation.

Does not contain PCB.

CONTENTS

1 Safety Precautions

5

2 Overview

12

2.1 Unit parts ……………………………………………………….. 13 2.2 Controls and parts…………………………………………….. 14

3 Unit specifications and features

15

3.1 Indoor unit display…………………………………………….. 15 3.2 Operating temperature ………………………………………. 16 3.3 Inverter Split type……………………………………………… 17 3.4 Fixed- speed type ……………………………………………… 17 3.5 Other features …………………………………………………. 18 3.6 Setting angle of air flow……………………………………… 19 3.6.1 Setting vertical angle of air flow ………………………… 19 3.6.2 Setting horizontal angle of air flow……………………… 19 3.7 Install the HomeWhiz kit (wireless module)……………… 19 3.8 Manual operation (without remote) ……………………….. 19

4 Installation

21

4.1 Installation summary – indoor unit ………………………… 21 4.2 Installation Instructions ­ Indoor unit …………………….. 22 4.2.1 Prior to installation …………………………………………. 22 4.2.2 Mounting plate dimensions………………………………. 23 4.2.3 Before performing any electrical work, read these
regulations…………………………………………………… 25 4.3 Outdoor Unit Installation …………………………………….. 29 4.3.1 Installation Instructions ­ Outdoor unit………………… 29

5 Refrigerant piping connection

35

5.1 Connection Instructions ­ Refrigerant Piping…………… 36 5.2 Instructions for connecting piping to indoor unit ………. 37 5.3 Instructions for connecting piping to outdoor unit …….. 38

6 Air evacuation

39

6.1 Preparations and precautions ……………………………… 39 6.1.1 Before performing evacuation …………………………… 39 6.1.2 Evacuation instructions……………………………………. 39 6.1.3 Note on adding refrigerant……………………………….. 40

7 Electrical and gas leak checks

41

7.1 Before test run…………………………………………………. 41 7.2 Electrical safety checks ……………………………………… 41 7.3 Gas leak checks……………………………………………….. 41

8 Test run

42

8.1 Test run instructions………………………………………….. 42

9 Care and maintenance

43

9.1 Cleaning your indoor unit……………………………………. 43 9.2 Cleaning your air filter ……………………………………….. 43 9.3 Maintenance ­ long periods of non-use…………………. 45 9.4 Maintenance ­ Pre-Season Inspection ………………….. 45

10 Troubleshooting

46

10.1 Common issues ……………………………………………… 46 10.2 Troubleshooting ……………………………………………… 48

11 European disposal guideline

51

12 Installation instructions

52

12.1 F-Gas instruction ……………………………………………. 52

13 Specifications

53

4 / 172 EN

Split Type Air Conditioner / User Manual

1 Safety Precautions

Warning

Warnings for product use

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental

· If an abnormal situation arises (like a burning smell), immediately turn off the unit and disconnect the power. Call your dealer for instructions to

capabilities or lack of experience avoid electric shock, fire or

and knowledge if they have been injury.

given supervision or instruction · Do not insert fingers, rods or

concerning use of the appliance other objects into the air inlet

in a safe way and understand the or outlet. This may cause injury,

hazards involved. Children shall not since the fan may be rotating

playwiththeappliance.Cleaningand at high speeds.

user maintenance shall not be made by children without supervision (European Union countries). This appliance is not intended for use by persons (including

· Do not use flammable sprays such as hair spray, lacquer or paint near the unit. This may cause fire or combustion.
· Do not operate the air conditioner in places near or

children) with reduced physical, around combustible gases.

sensory or mental capabilities, Emitted gas may collect around

or lack of experience and the unit and cause explosion.

knowledge,unless they have been · D o n o t o p e r a t e y o u r a i r

given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do

conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can cause electrical components to short circuit.

not play with the appliance.

Split Type Air Conditioner / User Manual

5 / 172 EN

1 Safety Precautions

· Do not expose your body · D o n o t c l e a n t h e a i r

directly to cool air for a conditioner with combustible

prolonged period of time.

cleaning agents. Combustible

· Do not allow children to cleaning agents can cause fire play with the air conditioner. or deformation.

Children must be supervised

around the unit at all times. Caution

· If the air conditioner is used together with burners or other heating devices, thoroughly ventilate the room to avoid

· Turn off the air conditioner and disconnect the power if you are not going to use it for a long time.

oxygen deficiency.

· Turn off and unplug the unit

· I n c e r t a i n f u n c t i o n a l during storms.

environments, such as · Make sure that water

kitchens, server rooms, etc., condensa tion can drain

the use of specially designed unhindered from the unit.

air-conditioning units is highly · D o n o t o p e r a t e t h e a i r

recommended.

conditioner with wet hands.

This may cause electric shock.

Cleaning and maintenance · Do not use device for any

warnings

other purpose than its intended

· Tu r n o f f t h e d e v i c e a n d use.

disconnect the power before cleaning. Failure to do so can cause electrical shock.

· Do not climb onto or place objects on top of the outdoor unit.

·Do not clean the air conditioner with excessive amounts of water.

· Do not allow the air conditioner to operate for long periods of time with doors or windows

open, or if the humidity is very

high.

6 / 172 EN

Split Type Air Conditioner / User Manual

1 Safety Precautions

Electrical warnings

· The product must be properly

· Only use the specified power grounded at the time of

cord. If the power cord is installation, or electrical shock

damaged, it must be replaced may occur.

by the manufacturer, its service · For all electrical work, follow

agent or similarly qualified all local and national wiring

persons in order to avoid a standards, regulations, and the

hazard.

Installation Manual. Connect

· K e e p p o w e r p l u g c l e a n . cables tightly, and clamp them

Remove any dust or grime that securely to prevent external

accumulates on or around the forces from damaging the

plug. Dirty plugs can cause fire terminal. Improper electrical

or electric shock.

connections can overheat and

· Do not pull power cord to unplug unit. Hold the plug firmly and pull it from the outlet. Pulling directly on the cord can damage it, which can lead to fire or electric shock.

cause fire, and may also cause shock. All electrical connections must be made according to the Electrical connection diagram located on the panels of the indoor and outdoor units.

· Do not modify the length of · All wiring must be properly

the power supply cord or use arranged to ensure that the

an extension cord to power the control board cover can close

unit.

properly. If the control board

· Do not share the electrical outlet with other appliances. Improper or insufficient power supply can cause fire or electrical shock.

cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire, or cause electrical shock.

Split Type Air Conditioner / User Manual

7 / 172 EN

1 Safety Precautions

· If connecting power to fixed Warnings for product

wiring, an all-pole disconnection installation

device which has at least 3mm clearances in all poles, and have a leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual operating current not exceeding 30mA, and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.

1. 2.

Installation must be performed by an authorized dealer or specialist. Defective installation can cause water leakage, electrical shock, or fire. Installation must be performed according to the installation instructions. Improper installation can cause water leakage, electrical shock, or

Take note of fuse specifications The air conditioner’s circuit board

fire. 3. Contact an authorized service
technician for repair or maintenance of this unit. This

(PCB) is designed with a fuse to appliance shall be installed

provide overcurrent protection. The in accordance with national

specifications of the fuse are printed wiring regulations.

on the circuit board, such as:

4. Only use the included

T3.15AL/250VAC, T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC, T30A/250VAC, etc.
Note: For the units using R32

accessories, parts, and specified parts for installation. Using non-standard parts can cause water leakage, electrical shock, fire, and can

C or R290 refrigerant, only the blast-proof ceramic fuse can

cause the unit to fail.

be used.

8 / 172 EN

Split Type Air Conditioner / User Manual

1 Safety Precautions

5. Install the unit in a firm location 11. How to install the appliance

that can support the unit’s to its support, please read

weight. If the chosen location the information for details in

cannot support the unit’s “indoor unit installation” and

weight, or the installation is “outdoor unit installation”

not done properly, the unit sections.

may drop and cause serious injury and damage. Install drainage piping according to the instructions in

Note about fluorinated gasses (Not applicable to the unit using R290 Refrigerant)

this manual. Improper drainage 1. This air-conditioning

may cause water damage to unit contains fluorinated

your home and property.

greenhouse gasses. For

7. For units that have an auxiliary electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.
8. Do not install the unit in a location that may be exposed to combustible gas leaks. If combustible gas accumulates around the unit, it may cause fire.
9. Do not turn on the power until all work has been completed.
10. When moving or relocating the air conditioner, consult experienced service

specific information on the type of gas and the amount, please refer to the relevant label on the unit itself or the “User Manual – Product Fiche” in the packaging of the outdoor unit. (European Union products only). 2. I n s t a l l a t i o n , s e r v i c e , maintenance and repair of this unit must be performed by a certified technician. 3. Product uninstallation and recycling must be performed by a certified technician.

technicians for disconnection

and reinstallation of the unit.

Split Type Air Conditioner / User Manual

9 / 172 EN

1 Safety Precautions

4. For equipment that contains For R290 refrigerant models,

fluorinated greenhouse gases appliance shall be installed,

in quantities of 5 tonnes of operated and stored in a room

CO2 equivalent or more, but with a floor area larger than:

of less than 50 tonnes of <=9000Btu/h units: 13m2

CO2 equivalent, If the system has a leak-detection system installed, it must be checked for leaks at least every 24 months. When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.

9000Btu/h and <=12000Btu/h units: 17m2 >12000Btu/h and <=18000Btu/h units: 26m2 >18000Btu/h and <=24000Btu/h units: 35m2 · Reusable mechanical connectors and flared joints are not allowed indoors. (EN

Warning for Using R32/R290 Standard Requirements).

Refrigerant

· Mechanical connectors used

· When flammable refrigerant indoors shall have a rate of are employed, appliance shall not more than 3g/year at 25%

be stored in a well -ventilated of the maximum allowable

area where the room size pressure. When mechanical

corresponds to the room area connectors are reused indoors,

as specific for operation.

sealing parts shall be renewed.

For R32 frigerant models: Appliance shall be installed, operated and stored in a room with a floor area larger than

When flared joints are reused indoors, the flare part shall be re-fabricated. (UL Standard Requirements)

4m2.

10 / 172 EN

Split Type Air Conditioner / User Manual

1 Safety Precautions

· When mechanical connectors When disposing of this appliance,

are reused indoors, sealing parts you have the following options:

shall be renewed. When flared · Dispose of the appliance at

joints are reused indoors, the designated municipal electronic

flare part shall be re-fabricated. waste collection facility.

(IEC Standard Requirements) · When buying a new appliance,

· Mechanical connectors used the retailer will take back the

indoors shall comply with old appliance free of charge.

ISO 14903.

· The manufacturer will take back

European disposal guidelines

the old appliance free of charge. (for some countries)

This marking shown on the product or its literature, indicates

· Sell the appliance to certified scrap metal dealers. (for some

that waste electrical and eletrical countries)

equipment should not be mixed

with general household waste.

Correct disposal of

this product (Waste

electrical & Electronic

equipment)

This

appliance

contains refrigerant and other

potentially hazardous materials.

Special notice: Disposing of this appliance in the forest or other natural surroundings
C endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.

When disposing of this appliance,

the law requires special collection

and treatment. Do not dispose of

this product as household waste

or unsorted municipal waste.

Split Type Air Conditioner / User Manual

11 / 172 EN

2 Overview

The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items are not included with the air conditioner must be purchased separately.

Name of Accessories

Q’ty(pc)

Shape

Name of Accessories

Q’ty(pc)

Manual

2-3

Remote controller

1

Drain joint

(for cooling &

1

heating models)

Seal

(for cooling &

1

heating models)

Mounting plate

1

Anchor

5~8 (depending on models)

Mounting plate fixing screw

5~8 (depending on models)

Wireless USB kit

1 (For Wifi models only)

Battery

2

Remote

controller holder

1

(optional)

Fixing screw

for remote controller holder

2

(optional)

Small Filter (Need to be installed on the back of main air filter by the authorized technician while installing the machine)

1~2 (depending on
models)

Shape

12 / 172 EN

Split Type Air Conditioner / User Manual

2 Overview

Name Connecting pipe assembly

Shape

Quantity(PC)

Liquid side Gas side

6.35 (1/4 in)

9.52 (3/8in) 9.52 (3/8in) 12.7 (1/2in) 16 (5/8in) 19 (3/4in)

Parts you must purchase separately. Consult the dealer about the proper pipe size of the unit you purchased.

1 2 3
Magnetic ring and belt (if supplied, please refer to the wiring diagram to install it on the connective cable)

Passstthheebbeeltlthtrhoruoguhgh the thhoelehoolfetohfethMeaMgangentiectircing rtoinfgixtoit foixnitthoen cthaebcleable

Varies by model

2.1 Unit parts

C

The installation must be performed in accordance with the requirement of local and national standards. The installation may be slightly different in different areas.

Split Type Air Conditioner / User Manual

13 / 172 EN

2 Overview
1
2 4
5

3 2

4 6

5 7

8

9

10

1
Air-breeaakksswwiticthch
3
6 7 8

11

11

1
2.2 Controls and parts
1. Wall mounting plate 2. Front panel 3. Power cable (some units) 4. Louver 5. Functional Filter (On Back of Main Filter –
Some Units) 6. Drainage pipe 7. Signal cable 8. Refrigerant piping 9. Remote controller 10. Remote controller holder (some units) 11. Outdoor unit power cable (some units) Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different. The actual shape shall prevail.

2

14 / 172 EN

Split Type Air Conditioner / User Manual

3 Unit specifications and features

3.1 Indoor unit display

C

Different models have different front panel and display window. Not all the indicators describing below are available for the air conditioner you purchased. Please check the indoor display window of the unit you purchased.

FFrroonntt PPaanneell

C

Illustrations in this manual are for explanatory purposes. The actual shape of your indoor unit may be slightly different. The actual shape shall prevail.

PPoowweerrCCaabblele(S(Somome eUnUitnsi)ts)

LouLvoeurver
FuFnucntcitoionnaal lFFililtteerr (O(OnnBBacakckofoMf MainaiFniltFeirlt-erSo- mSeomUneitUs)nits)

ReRmemooteteCCoonnttrrool

RReemmoottee CCoonntrtorol l HHolder ((SSoommeeUUnnitsit)s)

DDiisspplalay ywiwndinowdow

(A)

(B)

(C)

(D)

” wwhheenn EECCOO ffuunnccttiioonn iiss aaccttiivvaatteedd(s(soommeeuunnitists) )

” LiLgighhtstsuuppininddififfefererennt tccoololouurraaccccoordrdininggtotoththeeooppeerraattioionn

mmooddee((ssoommee uunniittss))::

UUnnddeerrCCOOOOLLaanndd DDRRYY mmooddee,, iitt ddiissppllaayyss aass ccooooll ccoolloouurr..

UUnnddeerrHHEEAATTmmooddee,,ititddisisppllaayyssaasswwaarrmm ccoolloouurr..

” ” wwhheennWWirireelelessssCCoonntrtorol flefaetautruereisisacatcivtaivteadte(ds(osmome eunuitnsi)ts)

” Displaayyss tetemmpepreartautruer,eo,poepreartiaotniofneafetuarteuraendanEdrrEorrcoordceosd:es:

Disppllaayy CCooddee MMeeaanniinngs

” “” “”fo”rfo3fros3rec3soesncedocsnodwnshdewsnhw:ehne:n: ·· TTIMIMEERROONN iiss set (if the unniitt iissOOFFF”F, ,” ” “”r”emfroearimn3sasionenscowonnhdewsnhwTeIhMneEnTR:IMOENRisONseits) set ) ·· FFRREESSHH,, SSWWIINNGG,,TTUURRBBOO, S,ILSEILNECNECoEr SoOrLSAORLPAVR EPCVOEfCeOatufreeaitsutruernisedtuornne””d on ” fofror 3 seconds when: ” 3 se”confdosr 3whseenc:onds when: ·· TTIMIMEERROOFFFF iiss sseett ·· FFRREESSHH,, SSWWININGG,,TTUURRBBOO, S,ILSEILNECNECoEr SoOrLSAORLPAVREPCVOEfCeOatufreeaitsutruernisedtuornffed off “”” “””wwhwehhneenannatani-ntcit-oi- clcdooladldiraafierirafetfuearateuturiseretiusisrtnuteurdnrneoedndoonn
“”” “”wwhwehnheendnedfdreoefrsfortoisnstgitnin(gcg(oc(ocoloionolgilning&g&h&ehaheteianatgitninugnguitusnn)itists))
“”” “””wwhwehhneenunnuuintniitsitissiseslsfe-elcfl-lfe-caclenleainangniningg
“”” “””wwhwehhneen8n8°8CCChheheaeataitnitnginggffeefaeatatuutrureereisisistututrunrnrenededodononn

Split Type Air Conditioner / User Manual

15 / 172 EN

3 Unit specifications and features

Front Panel

PPoowweerr CCaabbllee((SSoommeeUUnnitists) )

LouLvoeurver FuFnucnticotnioanlaFl iFltieltrer
(O(OnnBBaacckkofofMMaianinFiFltieltre-r S-oSmoemUenUitns)its)

RReemmoottee CControl

RemRoetme oCtoenCtronl trol HHooldldeer r(S(Somome eUnUintsit)s)

DiDspislpalyaywwininddooww (E)

DDiissppllaayy wwiinnddooww TThhee uunniitt hhaass aa bbuuiilldd–ininlilgighhttsseennssoor rtoto ddeetteecctt tthhee aammbbiieennttbbrrigighhtntneessss. .WWhhenenthtehe lliigghht is turned ooffff,,tthheeddisispplalayywwillillbbeeofofff aafftteer 7 secondss,,ssaavvininggeenneergrgyyaannddofoffefreinrigng yyoouu a comffoorrttaabblleesslleeeepp..

“” “”DDisipsplplaalyaysysstetmemmppepereraratautturuerre,e,,opooeppreearrtaaiottinioonfnefaefetauatruteureraenadnadnEdrErroErrorrrcoocrdoedcseo:sd:es:

“”” “”fo”frofr3o3rs3seecsceoocnnoddnssdwswhwheehnne::n: ·· TTIMIMERERONONis issets(eiftth(ifetuhneituinsitOiFsFO, FF”,”” ” “r”ermefomarina3sinsosencoownnhdweshnweTnhIeMTnIE:MREORNOisNsiests)et) ·· FFRRESEHS,HS,WSWINGIN,GT,UTRUBROB, Oor, SoIrLESNILCEENfCeEatufereastuisretsurinsetduronned on

“”” “”ff”oorrfo33r 3sseescceoocnnoddnssdwswhwhehene:nn::

·· TTIMIMEERROOFFFFis issest et

·· FFRREESSHH, S, WSWINIGN,GT,UTRUBROB,Oor, oSrILSENILCEENfCeEatfueraestuirsetsurinsetduronffed off

” when defrosting(for cooling & heating units)

” ” ” “wwhehnenddeefrfroossttiinngg((ffoorrccooolinligng&&hehaetiantginugniutsn)its)

” ” ” “”wwh”heewnnhueunnniittuniissitssiesellfsf–eccllfel- eacanleninaingng(insog(sm(sooemmueeniutusnn)iittss))

“” ” ” w” hw”ehwnehn8e8°nC8°(4C6(4°6F)°For) o1r21°C2°(C54(5°4F°) Fh)ehaetiantigngmmooddeeisisttuurrnneedd on (some units)
on(some units) “” “”wwhheenn ffrreesshh ffeeaattuurreeisistuturnrendedono(nso(msoemuenitusn) its) “” ” “””wwwhhheeennn EfErCCeOsOhfeffeeaaatuttuurerreeisiissatcuatrcivntaeivtdeadtoe(nsd(osm(osmeomeunueintsuit)ns)its) “” ” “”wwh”heewnnhwweinirreeEleCsOsfcecoaontnuttrrroeollifsefeaaatcutturiveraeitseidsa(csatoicvmtaivteeadute(nsdiotsm()seomuneitsu)nits)
” ” when wireless control feature is activated(some units)

DDiissppllaayyCCooddee MMeeaanningss

IInn FFaannmmoodde,et,hteheunuitnwitilwl dililspdliasyptlhaey rtohoemroteommpeteramtupree.rature.
IInn ootthheerrmmoodedse,st,htehuenuitnwitillwdiilslpdlaisypyloauyrytoemurpteeramtupreersaettutirneg.setting. PPrreesssstthheeLLEDEDbubtutotntoonnothnetrheemroetme cootnetrcool nwtirllotluwrnilol ftfutrhneodfifspthlaey sdcisrepelany, psrcersesetnhe, pLrEeDss the LbEutDtobnuatgtoainn adguraining d1u5rsinegco1n5dssweicllodnisdpslawy itlhl edirsopolmaytetmheperroaotumret,eifmppreesrsatituarega, iinf pafrteesrs it
a1g5asiencaonftdesr, 1it5wsilletcuornndosn,tihtewdiilslptluarynsocrneethn.e display screen.

3.2 Operating temperature
When your air conditioner is used outside of the following temperature ranges, certain safety protection features may activate and cause the unit to disable.

16 / 172 EN

Split Type Air Conditioner / User Manual

3 Unit specifications and features

3.3 Inverter Split type
COOL mode

Room Temperature

17°C – 32°C (62°F – 90°F)

Outdoor Temperature

0°C – 50°C (32°F – 122°F)
-15°C – 50°C (5°F – 122°F) (For models with low temp. cooling
systems.)
0°C – 52°C (32°F – 126°F) (For special tropical models)

C

For outdoor units with auxiliary electric heater. When outside temperature is below 0°C (32°F), we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance.

3.4 Fixed-speed type
COOL mode

Room Temperature

17°C-32°C (62°F-90°F)

Outdoor Temperature

18°C-43°C (64°F-109°F)
-7°C-43°C (19°F- 109°F) (For models with low-temp cooling
systems)
18°C-52°C (64°F -126°F) (For special tropical models)

HEAT mode
0°C – 30°C (32°F -86°F)

DRY mode
10°C – 32°C (50°F – 90°F)

-15°C – 30°C (5°F – 86°F)

0°C – 50°C (32°F – 122°F)
0°C – 52°C (32°F – 126°F) (For special tropical models)

HEAT mode 0°C-30°C (32°F-86°F)
-7°C-24°C (19°F-75°F)

DRY mode
10°C-32°C (50°F-90°F)
11°C-43°C (52°F-109°F)
18°C-43°C (64°F-109°F)
18°C-52°C (64°F – 126°F) (For special tropical
models)

Split Type Air Conditioner / User Manual

17 / 172 EN

3 Unit specifications and features

C

Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.

To further optimize the performance of your unit, do the following · Keep doors and windows closed.
· Limit energy usage by using TIMER ON and TIMER OFF functions.
· Do not block air inlets or outlets.
· Regularly inspect and clean air filters.
A guide on using the infrared remote is not included in this literature package. Not all the functions are available for the air conditioner, please check the indoor display and remote control of the unit you purchased.
3.5 Other features
· Auto-Restart (some units)
If the unit loses power, it will automatically restart with the prior settings once power has been restored. · Anti-mildew (some units)
When turning off the unit from COOL, AUTO (COOL), or DRY modes, the air conditioner will continue operate at very low power to dry up condensed water and prevent mildew growth. · Wireless Control (some units)
Wireless control allows you to control your air conditioner using your mobile phone and a wireless connection.

For the USB device access, replacement, maintenance operations must be carried out by professional staff.
· Louver Angle Memory (some units)
When turning on your unit, the louver will automatically resume its former angle.
· Refrigerant Leakage Detection (some units)
The indoor unit will automatically display “EC” or “EL0C”or flash LEDS (some units) when it detects refrigerant leakage.
· Sleep Operation
The SLEEP function is used to decrease energy use while you sleep (and don’t need the same temperature settings to stay comfortable). This function can only be activated via remote control. And the Sleep function is not available in FAN or
DRY mode.
Press the SLEEP button when you are ready to go to sleep. When in COOL mode, the unit will increase the temperature by 1°C (2°F) after 1 hour, and will increase an additional 1°C (2°F) after another hour. When in HEAT mode, the unit will decrease the temperature by 1°C (2°F) after 1 hour, and will decrease an additional 1°C (2°F) after another hour. The sleep feature will stop after 8 hours and the system will keep running with final situation.

SSeet t tteemmppeerraattuurree

SSLLEEEEPP OOppeerraattiioonn
CCooool lmmooddee((++11°CC//22°FF) )ppeerrhhoouurr ffoorrththeefifrisrtstwtwo ohohuorsurs

1hr

1hr

HHeeaattmmooddee((-1-1°CC//22°FF))ppeerr hhoouurr

ffoorrtthheefifrisrtstwtwo ohohuorsurs

KeKrueepnenrpuinnnging

SavSianvginegneenregrygydudruinringgslseleepp

18 / 172 EN

Split Type Air Conditioner / User Manual

3 Unit specifications and features

3.6 Setting angle of air flow

3.6.1 Setting vertical angle of air flow

While the unit is on, use the SWING/DIRECT button on remote control to set the direction (vertical angle) of airflow. Please refer to the Remote Control Manual for details.

C

When using COOL or DRY mode, do not set louver at too vertical an angle for long periods of time. This can cause water to condense on the louver blade, which will drop on your floor or furnishings. When using COOL or HEAT mode, setting the louver at too vertical an angle can reduce the performance of the unit due to restricted air flow.

Insert
Warning:
A This interface is only compatible with HomeWhiz kit (wireless module) provided by the manufacturer.

3.6.2 Setting horizontal angle of air flow
The horizontal angle of the airflow must be set manually. Grip the deflector rod (See Fig.B) and manually adjust it to your preferred direction. For some units, the horizontal angle of the airflow can be set by remote control. please refer to the Remote Control Manual.
3.7 Install the HomeWhiz kit (wireless module)
1. Remove the protective cap of the HomeWhiz kit (wireless module)
2. Open the front panel and insert the HomeWhiz kit (wireless module) into the reserved interface.

3.8 Manual operation (without remote)

A

CAUTION! The manual button is intended for testing purposes and emergency operation only. Please do not use this function unless the remote control is lost and it is absolutely necessary. To restore regular operation, use the remote control to activate the unit. Unit must be turned off before manual operation.

To operate your unit manually: 1. Open the front panel of the indoor unit.
2. Locate the manual control button on the righthand side of the unit.
3. Press the manual control button one time to activate forced auto mode.
4. Press the manual control button again to activate forced cooling mode.

Split Type Air Conditioner / User Manual

19 / 172 EN

3 Unit specifications and features

5. Press the manual control button a third time to turn the unit off.
6. Close the front panel.

DDeefflleeccttoorr rroodd

Fig..BB

RRaannggee

C

Do not move louver by hand. This will cause the louver to become out of sync. If this occurs, turn off the unit and unplug it for a few seconds, then restart the unit. This will reset the louver.

A

CAUTION! Do not put your fingers in or near the blower and suction side of the unit. The highspeed fan inside the unit may cause injury.

MMaannuuaal control bbuutttoonn

20 / 172 EN

Split Type Air Conditioner / User Manual

4 Installation

4.1 Installation summary – indoor unit

1

151c5mcm ((55.9.i9n)in)

2

3

121cm2c(4m.75in) (4.75in) 2.3m2(.39m0(9.50.555inin))

1122ccmm (4(.475.7in5) in)

SSeelelecctt IInnssttaallllaattiioonn LLooccaattiioonn 4

DDeetteerrmmiinneeWWaallllHHoolleePPoossiittiioonn 5

AtAtattcahchMMouonutnintigngPPlaltaete 6

DDrriillll Wallll HHole 7

CCoonnnneecctt PPiippiinngg 8

CCononnencetcWt Wiriinrigng ((nnoott aappppliliccaabblelefoforrssoommee loloccaatitoionnssininNNoorrththAAmmeerricicaa) )

PPrreeppaarree DDrraaininHHoosese

WrapWPriappinPgipaingd aCnadblCeable (n(noot tapapplpicliacbalbelfeorfosrosmoemloeclaotcioantsioinnsNionrtNhoArmtheAricmae) rica)
9 8 STEP

Split Type Air Conditioner / User Manual

Mount IInnddoooorrUUnnitit
21 / 172 EN

4 Installation

4.2 Installation Instructions ­ Indoor unit
4.2.1 Prior to installation
Before installing the indoor unit, refer to the label on the product box to make sure that the model number of the indoor unit matches the model number of the outdoor unit. Step 1: Select installation location Before installing the indoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.

C

If there is no fixed refrigerant piping: While choosing a location, be aware that you should leave ample room for a wall hole (see Drill wall hole for connective piping step) for the signal cable and refrigerant piping that connect the indoor and outdoor units. The default position for all piping is the right side of the indoor unit (while facing the unit). However, the unit can accommodate piping to both the left and right.

Proper installation locations meet the following standards: · Good air circulation · Convenient drainage · Noise from the unit will not disturb other people · Firm and solid–the location will not vibrate · Strong enough to support the weight of the unit · A location at least one meter from all other
electrical devices (e.g., TV, radio, computer)
DO NOT install unit in the following locations: · Near any source of heat, steam, or combustible
gas · Near flammable items such as curtains or
clothing · Near any obstacle that might block air circulation · Near the doorway · In a location subject to direct sunlight

Refer to the following diagram to ensure proper distance from walls and ceiling:
1155ccmm((55..99iinn)) oorr mmoorree

12cm (4.72in) oorr mmoorree

1122ccmm((44..7722iinn)) oorrmmoorree

22..33mm((900..5555iinn)) or morree
Step 2: Attach mounting plate to wall The mounting plate is the device on which you will mount the indoor unit. · Remove the screw that attaches the mounting
plate to the back of the indoor unit.

22 / 172 EN

· Secure the mounting plate to the wall with the screws provided. Make sure that mounting plate is flat against the wall.
Split Type Air Conditioner / User Manual

4 Installation

C

If the wall is made of brick, concrete, or similar material, drill 5mm- diameter (0.2in-diameter) holes in the wall and insert the sleeve anchors provided. Then secure the mounting plate to the wall by tightening the screws directly into the clip anchors.

Step 3: Drill wall hole for connective piping
1. Determine the location of the wall hole based on the position of the mounting plate. Refer to Mounting Plate Dimensions.

2. Using a 65mm (2.5in) or 90mm (3.54in) (depending on models) core drill, drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 5mm to 7mm (0.2-0.275in). This will ensure proper water drainage.
3. Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.

A

CAUTION! When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.

Indoor Waalll Outddoooorr

4.2.2 Mounting plate dimensions
Different models have different mounting plates. For the different customization requirements, the shape of the mounting plate may be slightly different. But the installation dimensions are the same for the same size of indoor unit. See Type A and Type B for example:
Correct oorriieennttaattioionnooffMMoouunntitninggPPlaltaete

TTypeeAA

TTypee BB

37mmm ((11..445i5inn))

101mmm ((44iinn))

334488..44mmmm ((1133..77inin)) 117799mmmm(7(7.0.055inin) ) 113366mmmm(5(5.3.53i5ni)n)

229900mmmm ((1111..4i4inn)) 49mm ((1..995i5inn))

LLeefftt rreeaarr wwaallll hole 6h5olme m65(m2.m5in()2.5in)

72722m2mmm(2(828.4.455inin))
MMooddeel l A

49mmmm ((11..995i5inn))

Indoor unit outline RRiigghhtt rreeaarr wwaallll hole 655mmmm((22..55inin))

2288mmmm ((88..9988inin))

40410m1mmm(1(155.7.788iinn)) 222299mmmm(9(9.0.01i1ni)n)
112266mmmm(4(4.9.69i6ni)n)

58mmmm((22..228i8inn)) 4422mmmm ((11..6655iinn))

229977mmmm ((1111..77iinn)) 47mm (1..885i5inn))

LLeefftt rreeaarr wwaallll hole 6ho5lme m65m(2m.5in(2) .5in)

80820m2mm(3(13.61i.n6)in)
MModdeel l B

Indoor unit outlinee RRiigghhtt rreeaarrwwaallll hole h6o5lme 6m5m(2m.5i(n2).5in)

5-77 mmmm (0.2-00..22775i5inn))

Split Type Air Conditioner / User Manual

23 / 172 EN

4 Installation

400mmmm((11..555i5in)n) 58mmm ((22..3i3inn))

11338mm (5.4455inin))

515177.4.4mmmm ((2200..3377inin)) 114444mmmm ((55..6655iinn))

33119mmm ((1122..555i5in)n) 57mmm ((22..225i5in)n)

IInndoor unit outtllinnee

LLeefftt rreeaarrwwaallll hole 6h5olme m65m(2m.5in(2) .5in)

3344mmmm ((11..3355iinn))

996655mmmm((3388iinn))
MMooddeel l CC

RRiigghhtt rreeaarrwwaallll hole h6o5lme 6m5m(2m.5(in2).5in)

5544mmmm (2(2.1.1inin))

2212m1mmm(8(.87.i7ni)n) 797m9mmm(3(3..11iinn))

557788mmmm ((2222.8in)

229988mmmm((1111.7.7inin))

114499mmmm ((55..99iinn))

54mm (2.11iinn)) IInnddoooorr uunit outline

336mm ((133..2i2inn)) 4499mmm (m1.(9i1.n)9in)

LLeefftt rreeaarr wwaallll hole 6ho5lme m65m(2m.5i(n2).5in)

13183m8mm(5(.54.in4)in)

11008800mm (42.5in)
MMoodedlelDD

4499mmmm ((11..99iinn)) RRight rreaarr wwaalll hole
114499mmmm((55..99inin)) h6o5lme m65m(2m.5i(n2).5in)

2. If the wall hole is behind the unit, keep the knock-out panel in place. If the wall hole is to the side of the indoor unit, remove the plastic knock-out panel from that side of the unit. This will create a slot through which your piping can exit the unit. Use needle nose pliers if the plastic panel is too difficult to remove by hand.
3. Groove has been made in the knock-out panel in order to cut it conveniently. The size of the slot is determined by the diameter of piping.

664433.6.6mmmm(2(255.3.3inin))

389mm (15..33iinn))

225577mmmm ((1100..1in))

117722mmmm((66.8.8inin))

333322mmmm((1133..0055inin))

Indoooorr uunniitt oouuttllininee

336622mmmm ((1144..2255iinn))

LLeefftt rreeaarr wwaallll hole h9o0lme m90m(3m.54(3in.)54in)

522mmmm ((2.0055iinn))
11225599mmmm((4499.5.555ini)n)
MModoedl elEE

552mm ((22.05inin)) RRiigghhtt rreeaarr wwaallll hole h9o0lme 9m0m(3m.54(3in.5) 4in)

C

When the gas side connective pipe is 16mm(5/8in) or more, the wall hole should be 90mm (3.54in).

Step 4: Prepare refrigerant piping
The refrigerant piping is inside an insulating sleeve attached to the back of the unit. You must prepare the piping before passing it through the hole in the wall.
1. Based on the position of the wall hole relative to the mounting plate, choose the side from which the piping will exit the unit.

KKnnoocckk–oouut tPPaanncel

4. If existing connective piping is already embedded in the wall, proceed directly to the Connect Drain Hose step. If there is no embedded piping, connect the indoor unit’s refrigerant piping to the connective piping that will join the indoor and outdoor units. Refer to the Refrigerant Piping Connection section of this manual for detailed instructions.

C

Refrigerant piping can exit the indoor unit from four different angles:Left- hand side, Righthand side, Left rear, Right rear.

24 / 172 EN

Split Type Air Conditioner / User Manual

4 Installation

A

CAUTION! Be extremely careful not to dent or damage the piping while bending them away from the unit. Any dents in the piping will affect the unit’s performance.

Step 5: Connect drain hose
By default, the drain hose is attached to the lefthand side of unit (when you’re facing the back of the unit). However, it can also be attached to the right-hand side. To ensure proper drainage, attach the drain hose on the same side that your refrigerant piping exits the unit. Attach drain hose extension (purchased separately) to the end of drain hose.
· Wrap the connection point firmly with Teflon tape to ensure a good seal and to prevent leaks.
· For the portion of the drain hose that will remain indoors, wrap it with foam pipe insulation to prevent condensation.
· Remove the air filter and pour a small amount of water into the drain pan to make sure that water flows from the unit smoothly.

C

Make sure to arrange the drain hose according to the follo.wing figures.

CORCROERCRTECT MMaakke sure theree aarreennookkininkkss oorrddeenntt in drain hose to ensuree pprrooppeerr ddrraaiinnaaggee..

NNOTOTCOCRORRECRTECT KKininkkssiinn the draaiinnhhoossee wwililllccrreeaattee wwaatteerrtrtraappss. .

NONTOCTOCRROERCRTECT KKininkkss in the ddrraaiinnhhoossee will cwreilal tcerewataetewratterarptrsa.ps.

NNOOTTCOCRORRERCTECT Do not ppllaacceeththeeenedndofotfhtehe ddrraaiinn hhoosseeininwwaatetrerororinin cTcTdohohranniissittnaawwaiingniilleeellr.prpssrretethvhvaeaetntncttcopoplrloelrloceptpcewrterwataert.er. drainage.

Plug the unused drain hole. To prevent unwanted leaks you must plug the unused drain hole with the rubber plug provided.

4.2.3 Before performing any electrical work, read these regulations
1. All wiring must comply with local and national electrical codes, regulations and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.

Split Type Air Conditioner / User Manual

25 / 172 EN

4 Installation

4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause malfunction, electrical shock, or fire.
5. If connecting power to fixed wiring, a surge protector and main power switch should be installed.
6. If connecting power to fixed wiring, a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring. The qualified technician must use an approved circuit breaker or switch.
7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that outlet.
8. Make sure to properly ground the air conditioner.
9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
10. Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.
11. If the unit has an auxiliary electric heater, it must be installed at least 1 meter (40in) away from any combustible materials.
12. To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 10 minutes or more before you touch the electrical components.
A WARNING! Before performing any electrical Or wiring work, turn off the Main power to the system.

Step 6: Connect signal and power cables The signal cable enables communication between the indoor and outdoor units. You must first choose the right cable size before preparing it for connection. Cable Types · Indoor Power Cable (if applicable): H05VV-F or
H05V2V2-F
· Outdoor Power Cable: H07RN-F or H05RN-F
· Signal Cable: H07RN-F

C

In North America, choose the cable type according to the local electrical codes and regulations.

Minimum Cross-Sectional Area of Power and Signal Cables (For reference) (Not applicable for North America)

Rated Current of Appliance (A)

Nominal CrossSectional Area (mm²)

3 and 6

0.75

6 and 10

1

10 and 16

1.5

16 and 25

2.5

25 and 32

4

32 and 40

6

The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch.

26 / 172 EN

Split Type Air Conditioner / User Manual

4 Installation

C

In North America, please choose the right cable size according to the Minimum Circuit Ampacity indicated on the nameplate of the unit.

A

CAUTION! Do not mix up live and null wires. This is dangerous, and can cause the air conditioning unit to malfunction.

1. Open front panel of the indoor unit. 2. Using a screwdriver, open the wire box cover
on the right side of the unit. This will reveal the terminal block.
TTeerrmmiinnaal lbblolcokck WWiirreeccoovevrer
SSccrreeww CCaabblleecclalammp p

7. After checking to make sure every connection is secure, use the cable clamp to fasten the signal cable to the unit. Screw the cable clamp down tightly.
8. Replace the wire cover on the front of the unit, and the plastic panel on the back.

C

The wiring connection process may differ slightly between units and regions.

A

WARNING! All wiring must be performed strictly in accordance with the wiring diagram located on the back of the indoor units front panel.

3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Facing the back of the unit, remove the plastic panel on the bottom left- hand side.
5. Feed the signal wire through this slot, from the back of the unit to the front.
6. Facing the front of the unit, connect the wire according to the indoor unit’s wiring diagram, connect the u-lug and firmly screw each wire to its corresponding terminal.

Step 7: Wrappiping and cables Before passing the piping, drain hose, and the signal cable through the wall hole, you must bundle them together to save space, protect them, and insulate them (Not applicable in North America). 1. Bundle the drain hose, refrigerant pipes, and
signal cable as shown below:
InInddoooorrUUnniitt

SiSginganlawl iwreire DDrraaiinn hhoossee

SSppaaccee bbeehhinindduunnitit
RRefrigeraannttppipipiningg IInnssuullaattiioonntatappee

Split Type Air Conditioner / User Manual

27 / 172 EN

4 Installation

Make sure that the drain hose
C is at the bottom of the bundle. Putting the drain hose at the top of the bundle can cause the drain pan to overflow, which can lead to fire or water damage.

A

CAUTION! While bundling these items together, do not intertwine or cross the signal cable with any other wiring.

2. Using adhesive vinyl tape, attach the drain hose to the underside of the refrigerant pipes.
3. Using insulation tape, wrap the signal wire, refrigerant pipes, and drain hose tightly together. Double-check that all items are bundled.

A

CAUTION! When wrapping the bundle, keep the ends of the piping unwrapped. You need to access them to test for leaks at the end of the installation process (refer to Electrical Checks and Leak Checks section of this manual).

4. Hook the top of the indoor unit on the upper hook of the mounting plate.
5. Check that unit is hooked firmly on mounting by applying slight pressure to the left and righthand sides of the unit. The unit should not jiggle or shift.
6. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.
7. Again, check that the unit is firmly mounted by applying slight pressure to the left and the righthand sides of the unit.
If refrigerant piping is already embedded in the wall, do the following: 1. Hook the top of the indoor unit on the upper
hook of the mounting plate. 2. Use a bracket or wedge to prop up the unit,
giving you enough room to connect the refrigerant piping, signal cable, and drain hose.
Wedge

Step 8: Mount indoor unit
If you installed new connective piping to the outdoor unit, do the following:
1. If you have already passed the refrigerant piping through the hole in the wall, proceed to Step 4.
2. Otherwise, double-check that the ends of the refrigerant pipes are sealed to prevent dirt or foreign materials from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant pipes, drain hose, and signal wire through the hole in the wall.

3. Connect drain hose and refrigerant piping (refer to Refrigerant Piping Connection section of this manual for instructions).
4. Keep pipe connection point exposed to perform the leak test (refer to Electrical Checks and Leak Checks section of this manual).
5. After the leak test, wrap the connection point with insulation tape.
6. Remove the bracket or wedge that is propping up the unit.

28 / 172 EN

Split Type Air Conditioner / User Manual

4 Installation

7. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.

C

Keep in mind that the hooks on the mounting plate are smaller than the holes on the back of the unit. If you find that you don’t have ample room to connect embedded pipes to the indoor unit, the unit can be adjusted left or right by about 30-50 mm (1.18-1.95in), depending on the model.

3300–5500mmmm (1(1.1.188–11.9.966iinn))

3300–5500mmmm ((11..118-1.966iinn))

MMoovveetotolelefftt oorr rriigghhtt

4.3 Outdoor Unit Installation
Install the unit by following local codes and regulations, there may be differ slightly between different regions.

6600ccmm ((2244iinn)) aabboovvee

3300ococnmmnllee((1ff1tt22inin) ) 20200c0cminmin(f(7of7rr9o9nniinntt))

33ff0rr0ooccmmmmb(ba1(1ca2k2icnwik)na)wll all 660oo0cnncmrmirg(i2gh(4ht2itn4)in)

4.3.1 Installation Instructions ­ Outdoor unit
Step 1: Select installation location Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.
Proper installation locations meet the following standards: · Meets all spatial requirements shown in
Installation Space Requirements above.
· Good air circulation and ventilation
· Firm and solid–the location can support the unit and will not vibrate
· Noise from the unit will not disturb others
· Protected from prolonged periods of direct sunlight or rain
· Where snowfall is anticipated, raise the unit above the base pad to prevent ice buildup and coil damage. Mount the unit high enough to be above the average accumulated area snowfall. The minimum height must be 18 inches.
DO NOT install unit in the following locations: · Near an obstacle that will block air inlets and
outlets
· Near a public street, crowded areas, or where noise from the unit will disturb others
· Near animals or plants that will be harmed by hot air discharge
· Near any source of combustible gas
· In a location that is exposed to large amounts of dust.
· In a location exposed to a excessive amounts of salty air.

Split Type Air Conditioner / User Manual

29 / 172 EN

4 Installation

C

If the unit is exposed to heavy wind: Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds. See Figures below.

SStrtornogngwiwndind

SSttrroonngg wwinindd

Wind Bafffllee

SSttrroonngg wwiinndd

C

If the unit is frequently exposed to heavy rain or snow: Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow around the unit. If the unit is frequently exposed to salty air (seaside): Use outdoor unit that is specially designed to resist corrosion.

Step 2: Install drain joint (Heat pump unit only)
Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. Note that there are two different types of drain joints depending on the type of outdoor unit.
If the drain joint comes with a rubber seal (see Fig. A), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. B), do the following:
1. Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
2. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

BBaasseeppaannhhooleleofof oouuttddoooorruunnitit
SSeeaall
SSeeaall

DDrraaiinn jjooiinntt

(A)

(B)

30 / 172 EN

Split Type Air Conditioner / User Manual

4 Installation

A

CAUTION! In cold climates, make sure that the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit.

AAiirr iinnlleett

A AAiririinnlleett

AAiirr oouuttlleett

D B

Step 3: Anchor outdoor unit
The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolt(M10). Prepare the installation base of the unit according to the dimensions below.

C

The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions below.

H W

Outdoor Unit Dimensions (mm) W x H x D
681x434x285 (26.8″x 17.1″x 11.2″) 700x550x270 (27.5″x 21.6″x 10.6″) 700x550x275 (27.5″x 21.6″x 10.8″) 720x495x270 (28.3″x 19.5″x 10.6″) 728x555x300 (28.7″x 21.8″x 11.8″) 765x555x303 (30.1″x 21.8″x 11.9″) 770x555x300 (30.3″x 21.8″x 11.8″) 805x554x330 (31.7″x 21.8″x 12.9″) 800x554x333 (31.5″x 21.8″x 13.1″) 845x702x363 (33.3″x 27.6″x 14.3″) 890x673x342 (35.0″x 26.5″x 13.5″) 946x810x420 (37.2″x 31.9″x 16.5″) 946x810x410 (37.2″x 31.9″x 16.1″)

Mounting Dimensions

Distance A (mm)

Distance B (mm)

460 (18.1″)

292 (11.5″)

450 (17.7″)

260 (10.2″)

450 (17.7″)

260 (10.2″)

452 (17.8″)

255 (10.0″)

452 (17.8″)

302(11.9″)

452 (17.8″)

286(11.3″)

487 (19.2″)

298 (11.7″)

511 (20.1″)

317 (12.5″)

514 (20.2″)

340 (13.4″)

540 (21.3″)

350 (13.8″)

663 (26.1″)

354 (13.9″)

673 (26.5″)

403 (15.9″)

673 (26.5″)

403 (15.9”)

Split Type Air Conditioner / User Manual

31 / 172 EN

4 Installation

If you will install the unit on the ground or on a concrete mounting platform, do the following: 1. Mark the positions for four expansion bolts
based on dimensions chart.
2. Pre-drill holes for expansion bolts.
3. Place a nut on the end of each expansion bolt.
4. Hammer expansion bolts into the pre-drilled holes.
5. Remove the nuts from expansion bolts, and place outdoor unit on bolts.
6. Put washer on each expansion bolt, then replace the nuts.
7. Using a wrench, tighten each nut until snug.
A WARNING! When drilling into concrete, eye protection is recommended at all times.

If you will install the unit on a wall-mounted bracket, do the following:

A

CAUTION! Make sure that the wall is made of solid brick, concrete, or of similarly strong material. The wall must be able to support at least four times the weight of the unit.

1. Mark the position of bracket holes based on dimensions chart.
2. Pre-drill the holes for the expansion bolts.
3. Place a washer and nut on the end of each expansion bolt.
4. Thread expansion bolts through holes in mounting brackets, put mounting brackets in position, and hammer expansion bolts into the wall.
5. Check that the mounting brackets are level.

6. Carefully lift unit and place its mounting feet on brackets.
7. Bolt the unit firmly to the brackets. 8. If allowed, install the unit with rubber gaskets to
reduce vibrations and noise. Step 4: Connect signal and power cables The outside unit’s terminal block is protected by an electrical wiring cover on the side of the unit. A comprehensive wiring diagram is printed on the inside of the wiring cover.
A WARNING! Before performing any electrical or wiring work, turn off the main power to the system.

1. Prepare the cable for connection: Please choose the right cable refer to “Cable types” in page 24.

C

The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit.

C

In North America, please choose the right cable size according to the minimum circuit ampacity indicated on the nameplate of the unit.

· Using wire strippers, strip the rubber jacket from both ends of cable to reveal about 40mm (1.57in) of the wires inside.
· Strip the insulation from the ends of the wires.
· Using a wire crimper, crimp u-lugs on the ends of the wires.

32 / 172 EN

Split Type Air Conditioner / User Manual

4 Installation

C

While crimping wires, make sure you clearly distinguish the Live (“L”) Wire from other wires.

C

If the cable clamp looks like the following, please select the appropriate through-hole according to the diameter of the wire.

A

WARNING! All wiring work must be performed strictly in accordance with the wiring diagram located inside of wire cover of the outdoor unit.

BBuucckklele
TThhrreeee ssiizzeehhoolele::SSmmaall,ll,LaLragreg,eM, Medeiudmium

2. Unscrew the electrical wiring cover and remove it.
3. Unscrew the cable clamp below the terminal block and place it to the side.
4. Connect the wire according to the wiring diagram, and firmly screw the u-lug of each wire to its corresponding terminal.
5. After checking to make sure every connection is secure, loop the wires around to prevent rain water from flowing into the terminal.
6. Using the cable clamp, fasten the cable to the unit. Screw the cable clamp down tightly.
7. Insulate unused wires with PVC electrical tape. Arrange them so that they do not touch any electrical or metal parts.
8. Replace the wire cover on the side of the unit, and screw it in place.
CCoovveerr
SSccrreeww

Whheenntthheeccaalblbeeisisnnoot tfafastsetneneneonuoguhg,hu,suestehethbeuckle tboupcrkolep titouppr,ospoititucpan, sboeict lcaamnpbeed ctilgahmtlpy.ed tightly.
In North America 1. Remove the wire cover from the unit by
loosening the 3 screws.
2. Dismount caps on the conduit panel.
3. Temperarily mount the conduit tubes (not included) on the conduit panel.
4. Properly connect both the power supply and low voltage lines to the corresponding terminals on the terminal block.
5. Ground the unit in accordance with local codes.
6. Be sure to size each wire allowing several inches longer than the required length for wiring.
7. Use lock nuts to secure the conduit tubes.

Split Type Air Conditioner / User Manual

33 / 172 EN

4 Installation

TTeerrmmiinnaall bblolocckk OOvever r1.15.75i7ni.n(4.0(4m0mm) m)

CCoonnnneeccttininggccaabblele

G

PPoowweerr ssuupppplylyccoordrd

CCoonndduuititppaanneel l

WWiirree CCoovveerr
PPlleeaasseesesleecltetchte athpperoparpiapterotphrroiautgeh-htholreouacgcho- rhdionlge atoccthoerddiinamg etoterthoef tdheiawmireet.er of the wire.

34 / 172 EN

Split Type Air Conditioner / User Manual

5 Refrigerant piping connection

When connecting refrigerant piping, do not let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.

C

The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal efficiency is tested on units with a pipe length of 5 meters (16.5ft) (In North America, the standard pipe length is 7.5m (25′). A minimum pipe run of 3 metres is required to minimise vibration & excessive noise. In special tropical area, for the R290 refrigerant models, no refrigerant can be added and the maximum length of refrigerant pipe should not exceed 10 meters (32.8ft).

Refer to the table below for specifications on the maximum length and drop height of piping. Maximum Length and Drop Height of Refrigerant Piping per Unit Model

Model

Capacity (BTU/h)

R410A,R32 Inverter Split < 15,000

Air Conditioner

15,000 and < 24,000

24,000 and < 36,000

R22 Fixed-speed Split Air < 18,000

Conditioner

18,000 and < 21,000

21,000 and < 35,000

R410A, R32 Fixed-speed < 18,000

Split Air Conditioner

18,000 and < 36,000

Max. Length (m) 25 (82ft) 30 (98.5ft) 50 (164ft) 10 (33ft) 15 (49ft) 20 (66ft) 20 (66ft) 25 (82ft)

Max. Drop Height (m) 10 (33ft) 20 (66ft) 25 (82ft) 5 (16ft) 8 (26ft) 10 (33ft) 8 (26ft) 10 (33ft)

Split Type Air Conditioner / User Manual

35 / 172 EN

5 Refrigerant piping connection

5.1 Connection Instructions ­ Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.
1. Measure the distance between the indoor and outdoor units.
2. Using a pipe cutter, cut the pipe a little longer than the measured distance.
3. Make sure that the pipe is cut at a perfect 90° angle.

90°

OObblliiqquuee Rough Warped

PPooiinntt ddoowwnn

PPiippee RReeaammeerr

Step 3: Flare pipe ends Proper flaring is essential to achieve an airtight seal. 1. After removing burrs from cut pipe, seal the
ends with PVC tape to prevent foreign materials from entering the pipe.
2. Sheath the pipe with insulating material.
3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can’t put them on or change their direction after flaring.
FFllaarree nnuutt

WARNING! Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.

CCooppppeerrppipipee

Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.
1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.

4. Remove PVC tape from ends of pipe when ready to perform flaring work.
5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the edge of the flare form in accordance with the dimensions shown in the table below.

36 / 172 EN

Split Type Air Conditioner / User Manual

5 Refrigerant piping connection

C

When bending connective refrigerant piping, the minimum bending radius is 10cm.

Piping extension beyond flare form

Outer Diameter of Pipe (mm)

A (mm)

Min.

Max.

Ø 6.35 (Ø 0.25″) 0.7 (0.0275″) 1.3 (0.05″)

Ø 9.52 (Ø 0.375″) 1.0 (0.04″)

1.6 (0.063″)

Ø12.7 (Ø 0.5″) 1.0 (0.04″)

1.8 (0.07″)

Ø 16 (Ø 0.63″) 2.0 (0.078″) 2.2 (0.086″)

Ø 19 (Ø 0.75″) 2.0 (0.078″) 2.4 (0.094″)

RRaaddiiuuss 1100ccmm((44iinn))
5.2 Instructions for connecting piping to indoor unit
1. Align the center of the two pipes that you will connect.

FFllaarree ffoorrmm

A
IInnddoooorruunnitittutbuibnging

FFllaarree nnuutt PPiippee

PPiippe
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared.
8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.
Step 4: Connect pipes When connecting refrigerant pipes, be careful not to use excessive torque or to deform the piping in any way. You should first connect the low-pressure pipe, then the high-pressure pipe.

2. Tighten the flare nut as tightly as possible by hand.
3. Using a spanner, grip the nut on the unit tubing.
4. While firmly gripping the nut on the unit tubing, use a torque wrench to tighten the flare nut according to the torque values in the Torque Requirements table below. Loosen the flaring nut slightly, then tighten again.

Split Type Air Conditioner / User Manual

37 / 172 EN

5 Refrigerant piping connection

Torque requirements

Outer Diameter of Pipe (mm)

Tightening Torque (N·m) Flare dimension(B) (mm) Flare shape

Ø 6.35 (Ø 0.25″) 18~20 (180~200kgf.cm) 8.4~8.7 (0.33~0.34″)

Ø 9.52 (Ø 0.375″) 32~39 (320~390kgf.cm) 13.2~13.5 (0.52~0.53″)

Ø 12.7 (Ø 0.5″)

49~59 (490~590kgf.cm) 16.2~16.5 (0.64~0.65″)

Ø 16 (Ø 0.63″)

57~71 (570~710kgf.cm) 19.2~19.7 (0.76~0.78″)

Ø 19 (Ø 0.75″) 67~101 (670~1010kgf.cm) 23.2~23.7 (0.91~0.93″)

WARNING! Excessive force can break the nut or damage the refrigerant piping. You must not exceed torque requirements shown in the table above.
5.3 Instructions for connecting piping to outdoor unit
1. Unscrew the cover from the packed valve on the side of the outdoor unit.
2. Remove protective caps from ends of valves. 3. Align flared pipe end with each valve, and
tighten the flare nut as tightly as possible by hand. 4. Using a spanner, grip the body of the valve. Do not grip the nut that seals the service valve.

6. Loosen the flaring nut slightly, then tighten again.
7. Repeat Steps 3 to 6 for the remaining pipe.
A CAUTION! Torque from tightening the flare nut can snap off other parts of valve.

VVaalvlveecocvoevrer

5. While firmly gripping the body of the valve, use a torque wrench to tighten the flare nut according to the correct torque values.

38 / 172 EN

Split Type Air Conditioner / User Manual

6 Air evacuation

6.1 Preparations and precautions
Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can damage the air conditioner, reduce its efficiency, and cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant circuit, removing any non-condensable gas and moisture from the system.
Evacuation should be performed upon initial installation and when unit is relocated.

6.1.1 Before performing evacuation
· Check to make sure the connective pipes between the indoor and outdoor units are connected properly.
· Check to make sure all wiring is connected properly.

6.1.2 Evacuation instructions

1. connect the charge hose of the manifold gauge to service port on the outdoor unit’s low pressure valve.

2. Connect another charge hose from the manifold gauge to the vacuum pump.

3. Open the Low Pressure side of the manifold gauge. Keep the High Pressure side closed.

4. Turn on the vacuum pump to evacuate the system.

5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-105Pa).

MMaanniiffoolldd GGaauuggee

CCoommppoouunndd ggaauuggee –7766ccmmHHgg
LLooww pprreessssuurree vvaallvvee PPrreessssuurree hhoossee / CChhaargrgeehhoossee

PPrreessssuurree ggaauuggee
High presssuurree vvaallvvee CChhaarrggee hhoossee
VVacuum ppuummpp

LLoowwpprreessssuurree vvaallvvee

6. Close the Low Pressure side of the manifold gauge, and turn off the vacuum pump.
7. Wait for 5 minutes, then check that there has been no change in system pressure.
8. If there is a change in system pressure, refer to Gas Leak Check section for information on how to check for leaks. If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve).
9. Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench in a 1/4 counterclockwise turn. Listen for gas to exit the system, then close the valve after 5 seconds.
10. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. The Pressure Gauge should read slightly higher than atmospheric pressure.
11. Remove the charge hose from the service port.
Flaree nnuutt

CCaapp vavlavlevebbooddyy vvaallvvee sstteemm

12. Using hexagonal wrench, fully open both the high pressure and low pressure valves.

13. Tighten valve caps on all three valves (service port, high pressure, low pressure) by hand. You may tighten it further using a torque wrench if needed.

A

CAUTION! When opening valve stems, turn the hexagonal wrench until it hits against the stopper. Do not try to force the valve to open further.

Split Type Air Conditioner / User Manual

39 / 172 EN

6 Air evacuation

6.1.3 Note on adding refrigerant Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe
Additional refrigerant per pipe length

length is 7.5m (25′). In other areas, the standard pipe length is 5m (16`). The refrigerant should be charged from the service port on the outdoor unit’s low pressure valve. The additional refrigerant to be charged can be calculated using the following formula:

Connective Air Pipe Length Purging
(m) Method

Additional Refrigerant

< Standard pipe length

Vacuum Pump

N/A

Standard pipe length

Vacuum Pump

Liquid Side: Ø 6.35 (ø 0.25″) R32:
(Pipe length ­ standard length) x 12g/m (Pipe length ­ standard length) x 0.13oZ/ft
R290: (Pipe length ­ standard length) x 10g/m (Pipe length ­ standard length) x 0.10oZ/ft
R410A: (Pipe length ­ standard length) x 15g/m (Pipe length ­ standard length) x 0.16oZ/ft
R22: (Pipe length ­ standard length) x 20g/m (Pipe length ­ standard length) x 0.21oZ/ft

Liquid Side: Ø 9.52 (ø 0.375″) R32:
(Pipe length ­ standard length) x 24g/m (Pipe length ­ standard length) x 0.26oZ/ft (Pipe length ­ standard length) x 18g/m (Pipe length ­ standard length) x 0.19oZ/ft
R410A: (Pipe length ­ standard length) x 30g/m (Pipe length ­ standard length) x 0.32oZ/ft
R22: (Pipe length ­ standard length) x 40g/m (Pipe length ­ standard length) x 0.42oZ/ft

For R290 refrigerant unit, the total amount of refrigerant to be charged is no more than: 387g (<=9000Btu/h), 447g (>9000Btu/h and <=12000Btu/h), 547g (>12000Btu/h and <=18000Btu/h), 632g (>18000Btu/h and <=24000Btu/h).

A CAUTION! DO NOT mix refrigerant types.

40 / 172 EN

Split Type Air Conditioner / User Manual

7 Electrical and gas leak checks

7.1 Before test run
Only perform test run after you have completed the following steps: · Electrical Safety Checks ­ Confirm that the
unit’s electrical system is safe and operating properly
· Gas Leak Checks ­ Check all flare nut connections and confirm that the system is not leaking
· Confirm that gas and liquid (high and low pressure) valves are fully open
7.2 Electrical safety checks
After installation, confirm that all electrical wiring is installed in accordance with local and national regulations, and according to the Installation Manual.
Before test run Check Grounding Work Measure grounding resistance by visual detection and with grounding resistance tester. Grounding resistance must be less than 0.1. Note: This may not be required for some locations in North America.
During test run Check for Electrical Leakage During the Test Run, use an electroprobe and multimeter to perform a comprehensive electrical leakage test. If electrical leakage is detected, turn off the unit immediately and call a licensed electrician to find and resolve the cause of the leakage.

All wiring must comply with local and national electrical codes, and must be installed by a licensed electrician.

7.3 Gas leak checks

There are two different methods to check for gasleaks.
Soap and Water Method
Using a soft brush, apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit. The presence of bubbles indicates a leak.
Leak Detector Method
If using leak detector, refer to the device’s operation manual for proper usage instructions.

C

After confirming that the all pipe connection points do not leak, replace the valve cover on the outside unit.

CChheecckk–ppooininttooffiinnddoooorr uunniitt

Check-point of outtddoooorruunniitt
D

B

C

A

AA::LLoowwpprersessusruerestsotpovpavlvaelve BB::HHigighhpprersessusruerestosptovpavlvaelve
CC&&D:DI:ndInodoorournuitnfiltarfelanreutnsuts

C

This may not be required for some locations in North America.

Split Type Air Conditioner / User Manual

41 / 172 EN

8 Test run

8.1 Test run instructions
You should perform the Test Run for at least 30 minutes. 1. Connect power to the unit.
2. Press the ON/OFF button on the remote controller to turn it on.
3. Press the MODE button to scroll through the following functions, one at a time:
· COOL ­ Select lowest possible temperature
· HEAT ­ Select highest possible temperature
4. Let each function run for 5 minutes, and perform the following checks:

List of Checks to Perform PASS/FAIL

No electrical leakage

Unit is properly grounded

All electrical terminals properly covered

Indoor and outdoor units are solidly installed

All pipe connection points do not Outdoor Indoor

leak

(2):

(2):

Water drains properly from drain hose

All piping is properly insulated

Unit performs COOL function properly

Unit performs HEAT function properly

Indoor unit louvers rotate properly

Indoor unit responds to remote controller

C

During operation, the pressure of the refrigerant circuit will increase. This may reveal leaks that were not present during your initial leak check. Take time during the Test Run to doublecheck that all refrigerant pipe connection points do not have leaks. Refer to Gas Leak Check section for instructions.

5. After the Test Run is successfully completed, and you confirm that all checks points in List of Checks to Perform have PASSED, do the following:
­ Using remote control, return unit to normal operating temperature.
­ Using insulation tape, wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process.
If ambient temperature is below 17°c (62°f)
You can’t use the remote controller to turn on the cool function when the ambient temperature is below 17°c. In this instance, you can use the manual control button to test the cool function.
1. lift the front panel of the indoor unit, and raise it until it clicks in place.
2. The MANUAL CONTROL button is located on the right-hand side of the unit. Press it 2 times to select the COOL function.
3. Perform Test Run as normal.

42 / 172 EN

MMaannuuaal lcconotnrotrloblubttuotnton
Split Type Air Conditioner / User Manual

9 Care and maintenance

9.1 Cleaning your indoor unit

A

CAUTION! Always turn off your air conditioner system and disconnect its power supply before cleaning or maintenance.

C

Only use a soft, dry cloth to wipe the unit clean. If the unit is especially dirty, you can use a cloth soaked in warm water to wipe it clean.

A CAUTION! Do not use chemicals or chemically treated cloths to clean the unit.

5. Clean the large air filter with warm, soapy water. Be sure to use a mild detergent.
6. Rinse the filter with fresh water, then shake off excess water.
7. Dry it in a cool, dry place, and refrain from exposing it to direct sunlight.
8. When dry, re-clip the air freshening filter to the larger filter, then slide it back into the indoor unit.
9. Close the front panel of the indoor unit.

A

CAUTION! Do not use benzene, paint thinner, polishing powder or other solvents to clean the unit. They can cause the plastic surface to crack or deform.

A

CAUTION! Do not use water hotter than 40°C (104°F) to clean the front panel. This can cause the panel to deform or become discolored.

9.2 Cleaning your air filter
A clogged air conditioner can reduce the cooling efficiency of your unit, and can also be bad for your health. Make sure to clean the filter once every two weeks.
1. Lift the front panel of the indoor unit.
2. Grip the tab on the end of the filter, lift it up,then pull it towards yourself.
3. Now pull the filter out.
4. If your filter has a small air freshening filter, unclip it from the larger filter. Clean this air freshening filter with a hand-held vacuum.

Split Type Air Conditioner / User Manual

43 / 172 EN

9 Care and maintenance
FilteFriltTearbTsabs

A

CAUTION! · Before changing the filter or
cleaning, turn off the unit and disconnect its power supply.
· When removing filter, do not touch metal parts in the unit. The sharp metal edges can cut you.
· Do not use water to clean the inside of the indoor unit. This can destroy insulation and cause electrical shock.
· Do not expose filter to direct sunlight when drying. This can shrink the filter.

Remove air freshening filter from back of llaarrggeerr ffiillteerr ((some units)

A

CAUTION! Do not touch air freshening (Plasma) filter for at least 10 minutes after turning off the unit.

44 / 172 EN

Split Type Air Conditioner / User Manual

9 Care and maintenance

9.3 Maintenance ­ long periods of non-use
If you plan not to use your air conditioner for an extended period of time, do the following:

9.4 Maintenance ­ Pre-Season Inspection
After long periods of non-use, or before periods of frequent use, do the following:

Cleaann aalll ffiillteerrs

TTuurnrnoonnFFAANNfufunncctitoionnuunntitlil uunnititddrriieessoouuttccoommpplleetteelyly

CChheecckkfoforrddaammagaegdedwwireirses CCleleaannaallllfiflitletersrs

TTuurrn off tthhee uunniitt aanndd ddiisconnecctt tthhee ppoowweerr

ReRmeomvoevbeabttaetrteiersiefsrom fromrermemotoetecocnotnrotrlol

CChheecckkfoforrleleaaksks

Replace bbaattteerriieess

MMaakkeessuurree nothing is blockiinngg aallll aaiirriinnlleettssaannddoouutlteletsts

Split Type Air Conditioner / User Manual

45 / 172 EN

10 Troubleshooting

A

CAUTION! If any of the following conditions occurs, turn off your unit immediately! · The power cord is damaged or abnormally warm.
· You smell a burning odor.
· The unit emits loud or abnormal sounds.
· A power fuse blows or the circuit breaker frequently trips.
· Water or other objects fall into or out of the unit.
· Do not attempt to fix these yourself! Contact an authorized Service provider immediately!

10.1 Common issues

The following problems are not a malfunction and in most situations will not require repairs.

Issue

Possible Causes

Unit does not turn on when pressing The Unit has a 3-minute protection feature that prevents the unit from

ON/OFF button

overloading. The unit cannot be restarted within three minutes of being

turned off.

The unit changes from COOL/HEAT The unit may change its setting to prevent frost from forming on the

mode to FAN mode

unit. Once the temperature increases, the unit will start operating in the

previously selected mode again.

The set temperature has been reached, at which point the unit turns off the compressor. The unit will continue operating when the temperature fluctuates again.

The indoor unit emits white mist

In humid regions, a large temperature difference between the room’s air and the conditioned air can cause white mist.

Both the indoor and outdoor units emit When the unit restarts in HEAT mode after defrosting, white mist may be

white mist

emitted due to moisture generated from the defrosting process.

The indoor unit makes noises

A rushing air sound may occur when the louver resets its position.

A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit’s plastic parts.

Both the indoor unit and outdoor unit Low hissing sound during operation: This is normal and is caused by

make noises

refrigerant gas flowing through both indoor and outdoor units.

Low hissing sound when the system starts, has just stopped running, or is defrosting: This noise is normal and is caused by the refrigerant gas stopping or changing direction.

Squeaking sound: Normal expansion and contraction of plastic and metal parts caused by temperature changes during operation can cause squeaking noises.

46 / 172 EN

Split Type Air Conditioner / User Manual

10 Troubleshooting

Issue

Possible Causes

The outdoor unit makes noises

The unit will make different sounds based on its current operating mode.

Dust is emitted from either the indoor The unit may accumulate dust during extended periods of non-use,

or outdoor unit

which will be emitted when the unit is turned on. This can be mitigated

by covering the unit during long periods of inactivity.

The unit emits a bad odor

The unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be emitted during operations.

The unit’s filters have become moldy and should be cleaned.

The fan of the outdoor unit does not During operation, the fan speed is controlled to optimize product

operate

operation.

Operation is erratic, unpredictable, or unit is unresponsive

Interference from cell phone towers and remote boosters may cause the unit to malfunction. In this case, try the following: · Disconnect the power, then reconnect. · Press ON/OFF button on remote control to restart operation.

C

If problem persists, contact a local dealer or your nearest customer service center. Provide them with a detailed description of the unit malfunction as well as your model number.

Split Type Air Conditioner / User Manual

47 / 172 EN

10 Troubleshooting

10.2 Troubleshooting

When troubles occur, please check the following points before contacting a repair company.

Problem

Possible Causes

Solution

Temperature setting may be higher than ambient room temperature

Lower the temperature setting

The heat exchanger on the indoor or outdoor unit is dirty

Clean the affected heat exchanger

The air filter is dirty

Remove the filter and clean it according to instructions

The air inlet or outlet of either unit is Turn the unit off, remove the obstruction and turn it

blocked

back on

Poor Cooling Performance

Doors and windows are open
Excessive heat is generated by sunlight

Make sure that all doors and windows are closed while operating the unit
Close windows and curtains during periods of high heat or bright sunshine

Too many sources of heat in the room (people, computers, electronics, etc.)

Reduce amount of heat sources

Low refrigerant due to leak or long- Check for leaks, re-seal if necessary and top off

term use

refrigerant

SILENCE function is activated (optional function)

SILENCE function can lower product performance by reducing operating frequency. Turn off SILENCE function.

48 / 172 EN

Split Type Air Conditioner / User Manual

10 Troubleshooting

Problem
The unit is not working
The unit starts and stops frequently
Poor heating performance
Indicator lamps continue
flashing Error code appears and begins with the letters as the following in the window display of indoor unit: E(x), P(x), F(x) EH(xx), EL(xx), EC(xx) PH(xx), PL(xx), PC(xx)

Possible Causes
Power failure
The power is turned off
The fuse is burned out
Remote control batteries are dead
The Unit’s 3-minute protection has been activated
Timer is activated
There’s too much or too little refrigerant in the system
Incompressible gas or moisture has entered the system.
The compressor is broken
The voltage is too high or too low
The outdoor temperature is extremely low
Cold air is entering through doors and windows
Low refrigerant due to leak or longterm use

Solution Wait for the power to be restored Turn on the power Replace the fuse Replace batteries
Wait three minutes after restarting the unit
Turn timer off Check for leaks and recharge the system with refrigerant.
Evacuate and recharge the system with refrigerant
Replace the compressor Install a manostat to regulate the voltage
Use auxiliary heating device
Make sure that all doors and windows are closed during use Check for leaks, re-seal if necessary and top off refrigerant

The unit may stop operation or continue to run safely. If the indicator lamps continue to flash or error codes appear, wait for about 10 minutes. The problem may resolve itself. If not, disconnect the power, then connect it again. Turn the unit on. If the problem persists,
disconnect the power and contact your nearest customer service center.

Split Type Air Conditioner / User Manual

49 / 172 EN

10 Troubleshooting

C

If your problem persists after performing the checks and diagnostics above, turn off your unit immediately and contact an authorized service center.

50 / 172 EN

Split Type Air Conditioner / User Manual

11 European disposal guideline

This appliance contains refrigerant and other potentially hazardous materials, When disposing of this appliance, the law requires special collection and treatment, Do not dispose of this product as household waste or unsorted municipal waste,
When disposing of this appliance, you have the following options:
· Dispose of the appliance at designated municipal electronic waste collection facility.
· When buying a new appliance, the retailer will take back the old appliance free of charge.
· The manufacturer will take back the old appliance free of charge.
· Sell the appliance to certified scrap metal dealers.

This symbol indicates that this product shall not be disposed with other household wastes at the end of its service life. Used device must be returned to official collection point for recycling of electrical and electronic devices. To find these collection systems please contact to your local authorities or retailer where the product was purchased. Each household performs important role in recovering and recycling of old appliance. Appropriate disposal of used appliance helps prevent potential negative consequences for the environment and human health.

Special notice Disposing of this appliance in the forest
C or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.

Split Type Air Conditioner / User Manual

51 / 172 EN

12 Installation instructions

12.1 F-Gas instruction
This product contains fluorinated greenhouse gases.

The fluorinated greehouse gases are contained in hermetically sealed equipment.

Installs, services, maintains, repairs, checks for leaks or decommissions equipment and product recycling should be carried out by natural persons that hold relevant certificates.

If the system has a leakage detection system installed, leakage checks should be performed at least every 12 months, make sure system operate properly.

If product must be performed leakage checks, it should specify Inspection cycle, establish and save records of leakage checks.

C

Note: For hermetically sealed equipment, local air conditioner, window air conditioner and dehumidifier, if CO2 equivalent of fluorinated greenhouse gases is less than 10 tonnes, it should not perform leakage checks.

52 / 172 EN

Split Type Air Conditioner / User Manual

13 Specifications

BEHPH

Model name
Refrigerant Total Refrigerant Amount (g) GWP CO2 equivalent (tonnes) Anti- Electric Climate Class Heating Type Power Supply Connection Pdesign C (kW)

Indoor unit Outdoor unit

Pdesign H (kW)

SEER/AEER/Weight EER (W/W)

SCOP/ACOP/Weight EER (W/W)

Energy Level-Cooling

Energy Level-Heating

Annual Energy Consumption-Cooling (kWh)
Annual Energy Consumption-Heating (kWh)
The declared capacity for calculation of SCOP at reference design condition (kW)
The back up heating capacity assumed for calculation of SCOP at reference design condition (kW)
Power of Electric Heater (W)
Cooling Power Input (W)
Heating Power Input (W)

Voltage/Frequency (V/Hz)

Cooling Running Current (A)

BEHPH 090 BEHPH 091
R32 550 675 0.37 Class I T1 Heat Pump Outdoor 2.7 2.7 (EU Average Season) 6.9 (SEER, EU) 4.0 (SCOP, EU Average) A++ (EU) A+ (EU Average Season) 137 945
2.63
0.07
/ / / 220-240V~ 50Hz, 1Ph /

BEHPH 120 BEHPH 121
R32 550 675 0.37 Class I T1 Heat Pump Outdoor 3.5 2.9 (EU Average Season) 7.0 (SEER, EU) 4.0 (SCOP, EU Average) A++ (EU) A+ (EU Average Season) 175 990
2.69

BEHPH 180 BEHPH 181
R32 1100 675 0.74 Class I T1 Heat Pump Outdoor 5.2 4.1 (EU Average Season) 7.0 (SEER, EU) 4.0 (SCOP, EU Average) A++ (EU) A+ (EU Average Season) 260 1435
3.39

BEHPH 240 BEHPH 241
R32 1450 675 0.98 Class I T1 Heat Pump Outdoor 7.0 4.9 (EU Average Season) 6.5 (SEER, EU) 4.0 (SCOP, EU Average) A++ (EU) A+ (EU Average Season) 377 1730
3.69

0.21

0.71

1.21

/
/
/ 220-240V~ 50Hz, 1Ph
/

/

/

/

/

/

/

220-240V, 1Ph, 50Hz 220-240V, 1Ph, 50Hz

/

/

Split Type Air Conditioner / User Manual

53 / 172 EN

13 Specifications

Model name

Indoor unit Outdoor unit

Heating Running Current (A)

Noise Pressure Level – Indoor Unit (dBA)

Noise Pressure Level – Outdoor Unit (dBA)

Air flow volume (m3/h)

Rated Power Input-EN 60335(W)

Rated Current Input-EN 60335(A)

Indoor unit Resistance Class

Outdoor unit Resistance Class

High Pressure Pipe Diameter (mm)

Low Pressure Pipe Diameter (mm)

Power Supply Cord specification (mm2)

Indoor & Outdoor Connection Cord (mm2)

Max. elevation (m)

Max. pipe length (m)

Additional Gas Quantity (g/m)

Indoor Unit (WxHxD) mm

Outdoor Unit (WxHxD) mm

Indoor Unit Net Weight (kg)

Outdoor Unit Net Weight (kg)

BEHPH 090 BEHPH 091
/ 56 63 416/309/230 2150 10 IPX0 IP24 6.35mm (1/4in) 9.52mm (3/8in) 1.5×3 1.5×5 10 25 12 752×290×219 720x495x270 8.5 23

BEHPH 120 BEHPH 121
/ 55 63 584/477/395 2150 10 IPX0 IP24 6.35mm (1/4in) 9.52mm (3/8in) 1.5×3 1.5×5 10 25 12 832×297×223 720x495x270 9.5 23

BEHPH 180 BEHPH 181
/ 57 65 730/500/420 2500 13 IPX0 IP24 6.35mm (1/4in) 12.7mm (1/2in) 1.5×3 1.5×5 20 30 12 995×319×251 805x554x330 12 32

BEHPH 240 BEHPH 241
/ 63 67 1020/830/640 3700 19 IPX0 IP24 9.52mm (3/8in) 15.9mm (5/8in) 2.5×3 2.5×5 25 50 24 1119×336×259 890x673x342 15 43

Note:
1. Specifications are standard values calculated based on rated operating conditions, They will vary in difference work condition.
2. Our company has quick technical imporvments. There will be prior notice for any change of technical data. Please read nameplate on the air- conditioner.
Please refer to detail product information required in Regulation No 206/2012 from leaflet of Product Fiche.

54 / 172 EN

Split Type Air Conditioner / User Manual

13 Specifications

BEVPI

Model name
Refrigerant Total Refrigerant Amount (g) GWP CO2 equivalent (tonnes) Anti- Electric Climate Class Heating Type Power Supply Connection Pdesign C (kW)

Indoor unit Outdoor unit

Pdesign H (kW)

SEER/AEER/Weight EER (W/W)

SCOP/ACOP/Weight EER (W/W)

Energy Level-Cooling

Energy Level-Heating

Annual Energy Consumption-Cooling (kWh)
Annual Energy Consumption-Heating (kWh)
The declared capacity for calculation of SCOP at reference design condition (kW)
The back up heating capacity assumed for calculation of SCOP at reference design condition (kW)
Power of Electric Heater (W)
Cooling Power Input (W)
Heating Power Input (W)

Voltage/Frequency (V/Hz)

Cooling Running Current (A) Heating Running Current (A)

BEVPI 090 BEVPI 091
R32 550 675 0.37 Class I T1 Heat Pump Outdoor 2.7 2.7 (EU Average Season) 6.9 (SEER, EU) 4.0 (SCOP, EU Average) A++ (EU) A+ (EU Average Season) 137 945
2.63
0.07
/ / / 220-240V~ 50Hz, 1Ph / /

BEVPI 120 BEVPI 121
R32 550 675 0.37 Class I T1 Heat Pump Outdoor 3.5 2.9 (EU Average Season) 7.0 (SEER, EU) 4.0 (SCOP, EU Average) A++ (EU) A+ (EU Average Season) 175 990
2.69

BEVPI 180 BEVPI 181
R32 1100 675 0.74 Class I T1 Heat Pump Outdoor 5.2 4.1 (EU Average Season) 7.0 (SEER, EU) 4.0 (SCOP, EU Average) A++ (EU) A+ (EU Average Season) 260 1435
3.39

BEVPI 240 BEVPI 241
R32 1450 675 0.98 Class I T1 Heat Pump Outdoor 7.0 4.9 (EU Average Season) 6.5 (SEER, EU) 4.0 (SCOP, EU Average) A++ (EU) A+ (EU Average Season) 377 1730
3.69

0.21

0.71

1.21

/

/

/

/

/

/

/

/

/

220-240V~ 50Hz, 1Ph

220-240V, 1Ph, 50Hz 220-240V, 1Ph, 50Hz

/

/

/

/

/

/

Split Type Air Conditioner / User Manual

55 / 172 EN

13 Specifications

Model name

Indoor unit Outdoor unit

Noise Pressure Level – Indoor Unit (dBA)

Noise Pressure Level – Outdoor Unit (dBA)

Air flow volume (m3/h)

Rated Power Input-EN 60335(W)

Rated Current Input-EN 60335(A)

Indoor unit Resistance Class

Outdoor unit Resistance Class

High Pressure Pipe Diameter (mm)

Low Pressure Pipe Diameter (mm)

Power Supply Cord specification (mm2)

Indoor & Outdoor Connection Cord (mm2)

Max. elevation (m)

Max. pipe length (m)

Additional Gas Quantity (g/m)

Indoor Unit (WxHxD) mm

Outdoor Unit (WxHxD) mm

Indoor Unit Net Weight (kg)

Outdoor Unit Net Weight (kg)

BEVPI 090 BEVPI 091
56 63 416/309/230 2150 10 IPX0 IP24 6.35mm (1/4in) 9.52mm (3/8in) 1.5×3 1.5×5 10 25 12 752×290×219 720x495x270 8.5 23

BEVPI 120 BEVPI 121
55 63 584/477/395 2150 10 IPX0 IP24 6.35mm (1/4in) 9.52mm (3/8in) 1.5×3 1.5×5 10 25 12 832×297×223 720x495x270 9.5 23

BEVPI 180 BEVPI 181
57 65 730/500/420 2500 13 IPX0 IP24 6.35mm (1/4in) 12.7mm (1/2in) 1.5×3 1.5×5 20 30 12 995×319×251 805x554x330 12 32

BEVPI 240 BEVPI 241
63 67 1020/830/640 3700 19 IPX0 IP24 9.52mm (3/8in) 15.9mm (5/8in) 2.5×3 2.5×5 25 50 24 1119×336×259 890x673x342 15 43

Note:
1. Specifications are standard values calculated based on rated operating conditions, They will vary in difference work condition.
2. Our company has quick technical imporvments. There will be prior notice for any change of technical data. Please read nameplate on the air- conditioner.
Please refer to detail product information required in Regulation No 206/2012 from leaflet of Product Fiche.

56 / 172 EN

Split Type Air Conditioner / User Manual

Prima dell’utilizzo, leggere il presente manuale.
Gentile Cliente,
grazie per aver scelto un prodotto Beko. Ci auguriamo che possa essere soddisfatto del prodotto che è stato realizzato secondo elevati standard di qualità e con una tecnologia all’avanguardia. Pertanto, prima di utilizzare il prodotto, legga attentamente tutto il manuale e i documenti che lo accompagnano avendo cura di conservarli per un riferimento futuro. Se cede il prodotto a terzi, fornisca anche il manuale utente. Segua tutte le avvertenze e le informazioni riportate nel presente manuale.
Significato dei simboli
I seguenti simboli sono utilizzati in diverse sezioni del presente manuale:

C Informazioni importanti o suggerimenti pratici sull’utilizzo.

Questo simbolo indica che il manuale operativo deve essere letto con attenzione.

A Avvertenza: situazioni che mettono a rischio l’incolumità di persone o cose.
Avvertenza: operazioni da non eseguire mai.
B Attenzione: rischio di scosse elettriche.
Questo simbolo indica che sono disponibili informazioni quali il manuale operativo o il manuale di installazione.
Non coprirlo.

Questo simbolo indica che il personale addetto all’assistenza deve maneggiare questo dispositivo con riferimento al manuale di installazione.

Questo simbolo indica

che questo dispositivo

usa un refrigerante

infiammabile. Se il

refrigerante perde ed

è esposto a una fonte

di ignizione esterna,

(Per

il

tipo

con

gas

R32/R290)

c’è un rischio incendio.

di

Questo prodotto è stato fabbricato in impianti moderni rispettando l’ambiente e senza nuocere alla natura.

Conforme alla Direttiva RAEE.

Non contiene PCB.

SOMMARIO

1 Misure di sicurezza

59

2 Presentazione

67

2.1 Componenti dell’unità ……………………………………….. 68 2.2 Dispositivi di controllo e componenti……………………… 69

3 Specifiche e caratteristiche dell’unità

70

3.1 Display dell’unità interna ……………………………………. 70 3.2 Temperatura di funzionamento…………………………….. 71 3.3 Modelli split inverter………………………………………….. 72 3.4 Modelli a velocità fissa ………………………………………. 72 3.5 Altre caratteristiche …………………………………………… 73 3.6 Impostazione dell’angolazione del flusso d’aria ……….. 74 3.6.1 Impostazione dell’angolazione verticale del flusso d’aria
…………………………………………………………………. 74 3.6.2 Impostazione dell’angolazione orizzontale del flusso
d’aria …………………………………………………………. 74 3.7 Installazione del Kit HomeWhiz (Modulo Wireless)…….. 74 3.8 Funzionamento manuale (senza telecomando) ………… 75

4 Installazione

76

4.1 Riepilogo dell’installazione ­ Unità interna ……………… 76 4.2 Istruzioni di installazione ­ Unità interna ………………… 77 4.2.1 Prima dell’installazione……………………………………. 77 4.2.2 Dimensioni della piastra di montaggio ………………… 78 4.2.3 Prima di effettuare qualsiasi collegamento elettrico,
leggere le seguenti avvertenze …………………………. 80 4.3 Installazione dell’unità esterna …………………………….. 84 4.3.1 Istruzioni per l’installazione ­ Unità esterna …………. 85

5 Collegamento delle tubature del refrigerante 91

5.1 Istruzioni di collegamento ­ Tubatura del refrigerante .. 92 5.2 Istruzioni per il collegamento dei tubi all’unità interna.. 93 5.3 Istruzioni per il collegamento del tubo all’unità esterna 94

6 Scarico dell’aria

95

6.1 Preparazione e avvertenze ………………………………….. 95 6.1.1 Prima di eseguire lo scarico……………………………… 95 6.1.2 Istruzioni per lo scarico……………………………………. 95 6.1.3 Note sull’aggiunta di refrigerante ………………………. 96

7 Verifiche elettriche e delle perdite di gas

98

7.1 Prima di eseguire il test……………………………………… 98 7.2 Verifiche sulla sicurezza elettrica ………………………….. 98 7.3 Verifica della presenza di fughe di gas…………………… 98

8 Esecuzione del test

99

8.1 Istruzioni per l’esecuzione del test………………………… 99

9 Cura e manutenzione

101

9.1 Pulizia dell’unità interna……………………………………. 101 9.2 Pulizia del filtro dell’aria……………………………………. 101 9.3 Manutenzione ­ Mancato utilizzo per lunghi periodi di
tempo ………………………………………………………….. 103 9.4 Manutenzione ­ Controllo prima dell’inizio della stagione
………………………………………………………………….. 103

10 Risoluzione dei problemi

104

10.1 Problemi comuni…………………………………………… 104 10.2 Risoluzione dei problemi…………………………………. 106

11 Normative europee per lo smaltimento

109

12 Istruzioni per l’installazione

110

12.1 Istruzioni per i gas fluorurati…………………………….. 110

13 Specifiche tecniche

111

58 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

1 Misure di sicurezza

Attenzione

sicurezza. I bambini devono essere

Questo elettrodomestico può sorvegliati per assicurarsi che non essere utilizzato dai bambini dagli giochino con l’elettrodomestico.

8 anni in su e dalle persone con Avvertenze sull’uso del

capacità fisiche, sensoriali o prodotto

mentali ridotte, anche in caso di · Se si verifica una situazione

mancata esperienza o conoscenza, solo se controllati e istruiti all’uso sicuro dell’elettrodomestico e informati sui possibili rischi. Non consentire ai bambini di giocare con l’apparecchio. La pulizia e la manutenzione a carico dell’utente

anomala (ad es. un odore di bruciato), spegnere immediatamente l’apparecchio e scollegare l’alimentazione. Rivolgersi al proprio rivenditore per istruzioni in modo da scongiurare scosse elettriche, incendi o infortuni.

non devono essere eseguite da · Non inserire dita, oggetti

bambini senza la supervisione oblunghi o altri oggetti nelle

di un adulto (Paesi dell’Unione prese o nelle uscite d’aria. In

Europea).

quanto la ventola può ruotare

Questo elettrodomestico non è destinato all’utilizzo da parte di persone (compresi i bambini) con capacità fisiche, sensoriali o mentali ridotte o che non

ad alta velocità e causare infortuni. ·Non utilizzare spray infiammabili, come spray e lacca per capelli o vernici, in prossimità dell’unità. in quanto

posseggono la dovuta esperienza potrebbero causare incendi o

e conoscenza, a meno che non esplosioni.

siano controllate o istruite all’uso

dell’elettrodomestico da una

persona responsabile della loro

Condizionatore d’aria di tipo split / Manuale utente

59 / 172 IT

1 Misure di sicurezza

· Non utilizzare il condizionatore di utilizzare climatizzatori

d ‘ a r i a n e i p r e s s i d i g a s appositamente progettati.

combustibili. I gas emessi

potrebbero raccogliersi attorno Avvertenze sulla pulizia e la

all’unità e provocare esplosioni. manutenzione

· Non mettere in funzione il · Spegnere l’apparecchio e climatizzatore in una stanza scollegare la spina prima umida come il bagno o la della pulizia. In caso contrario

lavanderia. Un’eccessiva potrebbero verificarsi scosse esposizione all’acqua potrebbe elettriche.

provocare cortocircuiti nei · Non pulire il condizionatore

componenti elettrici.

d’aria con quantità eccessive

· Non esporre direttamente il d’acqua.

proprio corpo al flusso d’aria · Non pulire il condizionatore

fredda per lunghi periodi di tempo. d ‘ a r i a c o n d e t e r g e n t i

· Non consentire ai bambini di giocare con il climatizzatore. I bambini devono essere

combustibili. I detergenti combustibili possono provocare incendi o deformazioni.

costantemente controllati se si trovano nei pressi dell’unità.

Attenzione

· Se il condizionatore d’aria viene utilizzato in concomitanza con fornelli o altri dispositivi che producono calore, areare bene il locale per evitare carenza

· Spegnere il condizionatore d’aria e scollegare l’alimentazione se si prevede di non utilizzarlo per un lungo periodo di tempo.

d’ossigeno.

· Spegnere e scollegare l’unità

· In determinate condizioni di durante i temporali.

funzionamento, ad esempio · Accertarsi che la condensa

all’interno di cucine, sale server dell’acqua sia scaricata senza

e altro, si consiglia vivamente ostacoli dall’unità.

60 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

1 Misure di sicurezza

· Non utilizzare il condizionatore provocare incendi o scosse

con le mani bagnate. In questo elettriche.

modo potrebbero verificarsi · N o n t i r a r e i l c a v o d i

scosse elettriche.

alimentazione per scollegare

· Non utilizzare il dispositivo per l ‘ u n i t à . E s t r a r r e l a s p i n a

scopi diversi da quelli a cui è d a l l a p r e s a d i c o r r e n t e

destinato.

tenendola saldamente. Tirando

· Non salire sull’unità esterna o direttamente il cavo è possibile

collocarvi oggetti.

danneggiarlo, provocando

· N o n l a s c i a r e a c c e s o i l incendi o scosse elettriche.

condizionatore d’aria per lunghi · Non modificare la lunghezza

periodi di tempo con porte o del cavo dell’alimentatore né

finestre aperte oppure se il utilizzare una prolunga per

tasso di umidità è molto elevato. alimentare l’unità.

· Non collegare la presa elettrica

Avvertenze sulla sicurezza

ad altre apparecchiature.

elettrica

Un’alimentazione inadeguata

· Utilizzare solo il cavo di o insufficiente potrebbe

alimentazione specificato. provocare incendi o scosse

Se il cavo di alimentazione elettriche.

è danneggiato, deve essere · Il prodotto deve essere

sostituito dal produttore, dal correttamente collegato a

servizio di assistenza o da terra durante l’installazione o

personale qualificato al fine di potrebbero provocare scosse

evitare rischi.

elettriche.

· Te n e r e p u l i t a l a s p i n a d i · Per tutti i collegamenti elettrici, alimentazione. Rimuovere la attenersi a tutti gli standard polvere o la sporcizia che si e a tutte le normative locali e accumulano su o intorno alla nazionali in materia di impianti spina. Spine sporche possono

Condizionatore d’aria di tipo split / Manuale utente

61 / 172 IT

1 Misure di sicurezza

elettrici nonché al Manuale · Nel caso di collegamento

di installazione. Collegare i d e l l ‘ a l i m e n t a z i o n e a

cavi saldamente e fissarli in installazioni elettriche fisse,

modo sicuro per impedire è necessario integrarvi un

a sollecitazioni esterne di interruttore che scolleghi

danneggiare il terminale. tutti i poli e che presenti una

Collegamenti elettrici non separazione fra i contatti di

corretti potrebbero provocare almeno 3 mm e abbia una

surriscaldamenti, incendi corrente di dispersione che

e scosse elettriche. Tutti i possa superare i 10 mA e

collegamenti elettrici devono un dispositivo di corrente

essere effettuati secondo il residua (RCD) con una corrente

Diagramma dei collegamenti nominale di esercizio residua

elettrici posto sui pannelli non superiore a 30 mA. La

dell’unità interna ed esterna. disconnessione deve essere

· Tutti i collegamenti elettrici integrata nell’installazione

devono essere effettuati elettrica fissa in conformità in modo a ppropria to per con le normative in materia di

assicurarsi che il coperchio cablaggio.

del quadro di comando possa chiudersi correttamente. Se il coperchio del quadro

Prendere nota delle specifiche del fusibile

di comando non si chiude Il circuito (PCB) del climatizzatore

correttamente, potrebbero è progettato con un fusibile

verificarsi corrosioni, il surriscaldamento dei punti di collegamento sul terminale e incendi o scosse elettriche.

per fornire protezione da sovratensioni. Le specifiche del fusibile sono riportate sul circuito,

ad esempio:

62 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

1 Misure di sicurezza

T3.15AL/250VAC, T5AL/250VAC, unità. L’elettrodomestico deve

T3.15A/250VAC, T5A/250VAC, essere installato in conformità

C T20A/250VAC, T30A/250VAC ecc. Nota: Per le unità che utilizzano refrigerante R32

con le normative di cablaggio nazionali. 4. Utilizzare solo gli accessori, i componenti e i componenti

o R290 è possibile utilizzare specifici per l’installazione.

solo il fusibile in ceramica a L’utilizzo di componenti

prova di cortocircuito.

non standard potrebbe

provocare perdite d’acqua,

Avvertenze in merito

scosse elettriche, incendi e

all’installazione del prodotto

malfunzionamenti dell’unità.

1. L’installazione deve essere 5. Installare l’unità in una

effettuata da un rivenditore o un tecnico specializzato

posizione stabile in grado di sostenerne il peso. Qualora

autorizzato. Un’installazione la posizione prescelta non

errata potrebbe provocare perdite d’acqua, scosse

potesse sostenere il peso dell’unità o l’installazione

elettriche o incendi.

non fosse effettuata

2. L’installazione deve essere effettuata attenendosi alle relative istruzioni di

correttamente, l’unità potrebbe cadere e provocare lesioni e danni gravi.

installazione. Un’installazione inappropriata potrebbe provocare perdite d’acqua,

6. Installare le tubature di scarico attenendosi alle istruzioni contenute nel presente

scosse elettriche o incendi. 3. Contattare il tecnico
autorizzato al servizio di assistenza per la riparazione o la manutenzione di questa

manuale. Un impianto di scarico non opportunamente predisposto potrebbe provocare allagamenti alla casa o all’immobile.

Condizionatore d’aria di tipo split / Manuale utente

63 / 172 IT

1 Misure di sicurezza

7. Per le unità che dispongono di Nota sui gas fluorurati (non

un impianto di riscaldamento applicabile all’unità che

elettrico ausiliario, non utilizza il refrigerante R290)

installare l’unità entro 1 metro di distanza da qualsiasi materiale combustibile.

1. Questo climatizzatore contiene gas fluorurati ad effetto serra. Per informazioni specifiche

8. Non installare l’unità in sul tipo di gas e sulla quantità,

una posizione che potrebbe fare riferimento all’etichetta

essere esposta a perdite pertinente sull’unità stessa o

di gas combustibile. Se un al “Manuale utente – Scheda

gas combustibile dovesse prodotto” nella confezione

accumularsi intorno all’unità, dell’unità esterna. (Solo

potrebbe provocare incendi.

prodotti nell’Unione Europea).

9. Accendere l’apparecchio solo 2. L’installazione, l’assistenza, la

dopo aver completato tutto il manutenzione e la riparazione

lavoro.

di questa unità devono essere

10. Quando il condizionatore d’aria viene spostato o riposizionato,

effettuate da un tecnico certificato.

consultare un tecnico 3. La disinstallazione e lo

dell’assistenza qualificato smaltimento del prodotto

per la disconnessione e la devono essere effettuati da

reinstallazione dell’unità.

un tecnico certificato.

11. Per le modalità di 4. Nel caso di apparecchiature installazione dell’apparecchio che contengono gas fluorurati sul suo supporto, leggere ad effetto serra in quantità le informazioni dettagliate pari o superiori a 5 tonnellate nei capitoli “Installazione di CO2 equivalente, ma dell’unità interna” e inferiori a 50 tonnellate di “Installazione dell’unità CO2 equivalente, se il sistema esterna”.

64 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

1 Misure di sicurezza

è dotato di un dispositivo di Per i modelli con refrigerante rilevamento delle perdite, R290, l’apparecchio deve

quest’ultimo deve essere essere installato, messo in

controllato almeno ogni funzione e conservato in una

24 mesi per individuare stanza con una superficie del

eventuali perdite.

suolo maggiore di:

5. Quando viene effettuata la verifica di perdite nell’unità, si consiglia vivamente di conservare una documentazione adeguata di tutte le verifiche effettuate.

unità <=9000 Btu/h: 13 m2 unità >9000 Btu/h e <=12000 Btu/h: 17 m2 unità

12000Btu/h e <=18000Btu/h: 26 m2 unità >18000Btu/h e

Avvertenze per l’utilizzo del <=24000Btu/h: 35 m2

refrigerante R32/R290

· Connettori meccanici riutilizzabili e

· Quando si utilizza un refrigerante infiammabile, l’apparecchio deve essere

giunti svasati non sono consentiti per installazioni interne. (Requisiti della norma EN).

tenuto in un’area ben ventilata · I connettori meccanici utilizzati

dove la dimensione della stanza al chiuso devono avere un tasso

corrisponde a quella specificata non superiore a 3 g/anno al

per il funzionamento.

25% della pressione massima

Per modelli con refrigerante R32: l’apparecchio deve essere installato, messo in funzione e conservato in una stanza con una superficie del suolo maggiore di 4 m2.

consentita. Se i connettori meccanici vengono riutilizzati all’interno al chiuso, occorre sostituire gli elementi di tenuta. Se i giunti svasati vengono riutilizzati al chiuso, occorre rifare la parte svasata. (Requisiti della norma UL)

Condizionatore d’aria di tipo split / Manuale utente

65 / 172 IT

1 Misure di sicurezza

· Se i connettori meccanici vengono legge stabilisce una raccolta e un

riutilizzati all’interno al chiuso, trattamento speciali. Non smaltire

occorre sostituire gli elementi di questo prodotto nei rifiuti domestici

tenuta. Se i giunti svasati vengono riutilizzati al chiuso, occorre rifare la parte svasata. (Requisiti della norma IEC)

o nei rifiuti indifferenziati. Quando si smaltisce questo apparecchio, sono possibili le

· I connettori meccanici utilizzati al chiuso devono essere conformi alla norma ISO 14903.

seguenti opzioni: · Smaltire l’apparecchio presso
gli impianti di raccolta dei rifiuti elettronici municipali designati.

Normative europee per lo smaltimento

· Quando si acquista un nuovo apparecchio, il rivenditore

Questo simbolo riportato sul prodotto o sulla sua documentazione indica che le apparecchiature elettriche ed elettroniche non devono essere smaltite insieme ai normali rifiuti

ritira il vecchio apparecchio gratuitamente. · Il produttore ritira il vecchio apparecchio gratuitamente. (per alcuni Paesi) · Vendere l’apparecchio a rivenditori autorizzati di rottami

domestici.

metallici. (per alcuni Paesi)

Smaltimento corretto

del prodotto (rifiuti

Avviso speciale: Lo smaltimento

di apparecchiature

di questo apparecchio nei

elettriche

ed

boschi o in altri ambienti naturali

C elettroniche)
Questo apparecchio contiene

danneggia la propria salute ed è nocivo per l’ambiente.

refrigerante e altri materiali

Le sostanze nocive possono

potenzialmente pericolosi. Quando

penetrare nelle falde acquifere

si smaltisce questo apparecchio, la

e quindi nella catena alimentare.

66 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

2 Presentazione

Il sistema di climatizzazione include i seguenti accessori. Utilizzare tutti componenti e gli accessori di installazione per montare il condizionatore. Un’installazione non corretta potrebbe comportare perdite d’acqua, scosse elettriche e incendi o malfunzionamenti dell’apparecchiatura. I componenti non inclusi nell’imballaggio del condizionatore d’aria devono essere acquistati separatamente.

Nome dell’accessorio

Qt. (pz.)

Forma

Nome dell’accessorio

Qt. (pz.)

Manuale

2-3

Telecomando

1

Giunto di scarico

(nei modelli con raffreddamento e

1

riscaldamento)

Guarnizione (per

modelli solo freddo o con pompa di

1

calore)

Piastra di montaggio

1

Tassello a espansione

5-8 (a seconda del modello)

Vite di fissaggio della piastra di
montaggio

5-8 (a seconda del modello)

Kit USB wireless

1 (solo per modelli Wi-Fi)

Batteria

2

Portatelecomando (opzionale)

1

Vite di fissaggio per il supporto del telecomando
(opzionale)
Filtro piccolo (deve essere montato sul retro del filtro dell’aria principale dal tecnico autorizzato che installa l’apparecchio)

2
1-2 (a seconda del modello)

Forma

Condizionatore d’aria di tipo split / Manuale utente

67 / 172 IT

2 Presentazione

Nome Gruppo tubazione di collegamento

Condotto del liquido
Condotto del gas

Forma

Quantità (pz.)

6,35 (1/4 di pollice)

9,52 mm (3/8 di pollice) 9,52 mm (3/8 di pollice) 12,7 mm (1/2 pollice) 16 mm (5/8 di pollice)

Componenti da acquistare separatamente. Rivolgersi al rivenditore per informazioni sulle dimensioni corrette del tubo dell’unità acquistata.

19 mm (3/4 di pollice)

Anello magnetico e fascetta (se inclusi, fare riferimento al diagramma di cablaggio per l’installazione sul cavo di connessione)

1 2 3
PFasrsptahsesbaerelt tlahrcoiungghhia tahtetrahvoelersoof tihl efoMroagdneellt’iacnello rminaggntoetfiicxoitpoenrtfhisescaarblaleal cavo

Varia a seconda del modello

2.1 Componenti dell’unità

C

L’installazione deve essere eseguita in conformità con i requisiti degli standard locali e nazionali. L’installazione potrebbe differire leggermente in zone diverse.

68 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

2 Presentazione

1
2 4
5

3 2

4 6

5 7

8

9

10

1
Interruttore di aArirr-ebsrteoakarsiwaitch
3
6
7 8

11

1
2.2 Dispositivi di controllo e componenti
1. Piastra di montaggio per parete 2. Pannello anteriore 3. Cavo di alimentazione (solo alcune unità) 4. Deflettore 5. Filtro operativo (sul retro del filtro principale,
su alcuni modelli) 6. Tubo di scarico 7. Cavo del segnale 8. Tubature del refrigerante 9. Telecomando 10. Supporto per telecomando (alcune unità) 11. Cavo di alimentazione dell’unità esterna
(solo alcune unità) Le illustrazioni di questo manuale sono solo a scopo informativo. La forma attuale dell’unità interna potrebbe variare leggermente. Prevale la forma effettiva.
Condizionatore d’aria di tipo split / Manuale utente

2

11
69 / 172 IT

3 Specifiche e caratteristiche dell’unità

3.1 Display dell’unità interna

C

Il pannello anteriore e il display variano a seconda del modello. Gli indicatori descritti di seguito non sono presenti su tutti i condizionatori d’aria. Fare riferimento alla finestra del display interno dell’unità acquistata.

PannelloFroannttePraionreel

C

Le illustrazioni di questo manuale sono solo a scopo informativo. La forma attuale dell’unità interna potrebbe variare leggermente. Prevale la forma effettiva.

CPoawvoerdCi aablilme (eSnotmazeioUnneits()solo alcune unità)

DLeofulevettrore
FunFcilttiroonaolpFeirltaetrivo (sOunl Breatcrko odfeMl failitnroFipltreinr c-ipSaomle,esUunaitslc)uni modelli)

TReelemcootemCaonndtorol

PRoermtaotteeleCcoonmtroalndo (Hsoldoear l(cSuonmeeuUnniittàs)

Display winDdioswplay

(A)

(B)

(C)

(D)

” qwuhaenndEoClaOffuunnzciotinoen EisCaOctèivaattteivda(s(osmoleo uanlcitusn) e unità)

” SLi iagchctesnudpeindiduifnfecroelnotrecoclohuervaacrciaoradsinegcotondthaedoepllearamtioodnalità di funzionamento

(msoolodea(lscoumniemuondites)ll:i):

IInnUUnnmmddooeeddrr aaCHllOEiittAààOTLCHmOEaAnOoTddLe(D(R,RRIiSAtYCFdmFAisRLopEDdlaDeAy,DMsiAtaEMdsNiEsTwpNOalTa)r,mOyss)icaeiolsluDlocmRuoYrion.l(aDcdoEilUoaMurraI.DnIcFiIoCnAeZ. IONE), si illumina di blu.

” ” qwuhaenndoWliarefulenszsioCnoenCtroonltrfeolalotuwreireisleascstièvatetidva(s(osmoleo aulnciutsn)i modelli)

SDiigsnpilfaicyaCtoddeei codicMi edaenlindgissplay

” VDiissupalaliyzzsa tleamtepmepraetruarteu,rao,plaerfautnioznionfeeaitnuruesoanedi Ecorrdoicr icdoideersro: re:

” “” “”p”efro3fro3sre3sceoscneodcniodqnsudawsnhwdeohn:e:n:

·· ·

TFTTRIMIIMMEESEERHRRO,OONSNNWi((sTTINIIsMMGeEEt,RR(TifUAAtTTRhTTBeIIVVOuOOn,))iStèvIiieLsimnEOeNpFoCiFmsE,tpaot”oosrt(aSsteOa)”Ll’AurnReitmPàVaèinEssCpeOonntafwe”,ah”teunreTiI”sM”rteEusRfrtonarOes3Ndulsoisedncissoepntlad)ysqwuhaennd:o

la

funzione

· Le funzioni FRESH (FRESCO), SWING (OSCILLAZIONE), TURBO, SILENCE (SILENZIOSO) o SOLAR PV ECO sono

” attive””” for 3″”speefcoror3n3dssesecwoconhdneidnqs:uwanhdeon:: ·· TvIiMenEeRimOFpFositsatsoeTt IMER OFF (TIMER DI SPEGNIMENTO)

·· FLReEfSuHnz,ioSnWi FINRGES, HTU(FRRBEOSC, OS)I,LSEWNCINEG o(Or SSCOILLLAARZPIOVNEEC),OTUfReBaOtu,rSeILisENtuCrEne(SdILoEffNZIOSO) o SOLAR PV ECO sono disattive
” ” when anti-cold air feature is turned on “” “” quwahnedno alantfiu- nczoilodnaeiranfetia-tcuorled iasirtuèrantetidvaon ” ” when defrosting(cooling & heating units) “” ” quwahnedno dlaefruonsztiionnge(cdoioslbinrgina&mheenattoinègauttnivitas)(unità con pompa di calore)

” ” when unit is self-cleaning “” “” quwahnednoul’nuintiitsà seeslef- gculeeal’naiuntgopulitura

“”” “””quwwahnhedenon8la8CfCuhnhezeaioatnitnienggdfiefreaisatcutuarerldeaisimstuetunrnrtnoeedado8onn°C è accesa

70 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

3 Specifiche e caratteristiche dell’unità

PannellForoannttePraionreel

CPoawvoerdCi aablimlee(SnotamzeionUenit(ssolo alcu)ne unità)

DLeofulevettrore FuFnilcttrioonoapleFrialtteivro
(s(Ounl rBeatrcokdoeflMfialtirnoFpilrtienrc-ipSaolem, esuUnailtcsu)ni modelli)

RTemleoctoemCaonndtrool

PReomrtaoteleCcoonmtroalndo (Hsoolldoear l(cSuonmeeuUnnitiàts))

DDiissppllaayy window

LT’hueniutànièt hdaostaatabudiildu-ninsleignhstosreenisnogr rtaodo

Display Dwiisnpdloawy (E)

ddiertielecvtathree laamlubmienintobsriitgàhdtneells’sa.mWbhieennteth.e Qliguhatnidsotuvrineende osfpf,etnhtea dlaislpulacye,wililldbisepolafyf si sapfteegrn7esdeocpoond7s,sseacvoingdie, nceorngsyeanntednodfofedriing

ryisopuaarmcoiamrefoertnaebrlegisaleeedp.i dormire in modo

più confortevole. “”” “””VDiDissiupslapallyaizsyzsatetlmeampteepmrearptauterurera,et,ouporepare,arltaaiotifnounnfefzaeiotauntrueereiannadnudsEorErroerroirccocododedisec:si:di errore:

“”··” ·

TFfTRIMuIE”Mn”ESpzREH”iefoRo,OrnfrSoN3Oe3WrNiT3sssINeIeM(ssGcTceeooEI,ctMnn(RToidfdUEnsOtidRRhqswNBeAuOhwTu(aeT,hTnnnIoeiMId:tVrnoiO:ESs:RI)LOèEAFNTiFmCT,EIpVof”Oesa)tatvutiroee”ns(reseiesmimtl’auupirnnnoseistdtàoanoètanws) hpeenntTaI,M””ER

O”N”reifsosrtsae3tssu)elcdoinsdpslawyhqeuna: ndo

la

· Le funzioni FRESH (FRESCO), SWING (OSCILLAZIONE), TURBO o SILENCE (SILENZIOSO) sono attive

“” ·

TIM””EpfR”oerfrOo33rFF3sseiesscecosconeondtndsdiwsqhwueahnne:nd:o:

·· FvRieESnHe,imSWpoINsGta,tToUTRIBMOE,RorOSFILFE(NTCIMEEfeRaDtuIreSsPiEsGtuNrInMedENoTffO)

·” Le fun”zwiohneinFRdeEfSroHst(iFnRg(EfoSrCcOoo),liSngW&INhGea(OtinSgCuILnLitAs)ZIONE), TURBO o SILENCE (SILENZIOSO) sono disattive

SDigisnpilfaicyaCtooddeei codicMi edaenlindgisplay

” ” ” ” “quw”ahnwedhnoednleaufrnfouistntiizsnigos(nefolefr- dcclioesoablninrinignga&(smohmeenaettiounngèitusan)tittisv)a (unità con pompa di calore)

” ” ” “”qwu”haewnndhoeunnl’i8tu°insCits(àe4le6f-s°ceFleg)auonerinl1g’a(2su°otCmop(e5u4ulin°tuiFtrs)a)h(seoatloingalmcuondei misotudrenlelid)

“” ” q”uwahneodnno(8sloamme oudniatsli)tà di riscaldamento 8 °C (46 °F) o 12 °C (54 °F) è attiva (solo alcuni modelli)

“” ” “”qwu”hawennhdeofrnelasfrhefusfehnazftieuoarnetueirseFrtiuesrsntcueordnèeodna(otstnoiv(msaoe(msuoenlioutsna)itlsc)une unità)

“” ” “” qw”uhwaehnnedEnoCElOaCOffeuafnetzuairtouenriees iaEscCatOicvtaièvteaadtet(stdio(vsmaome(sueonluoitnsai)tlsc)une unità)

“”” “”qwu”hawenhndeownilraweilfreuesnlsezscisooncneotrnoCtlroofenlatfretuoarltleuorieswaisrceatliecvatsitvseadète(sado(tmstiovemaue(nsuiotnslo)itsa)lcune unità)

IInn Fmaondmaolidtàe,Vtehnetuilnaittowreill, dl’iuspnliatyà tvhiesuroaolimzzteermàplaeratetumrep.eratura dell’ambiente.
NIneolltehearltmreodmeso,dtahelituàn, ilt’uwnililtdàisvpislauyayliozuzretreàmlpaetreamturpeesreatttuinrga. impostata. PPrreesmsethree LilEtDasbtuottLoEnDonstuhleterelemcootme caonndtroolpweirllstuprengonfef rtheeilddisipslpalyasyc, rpereenm, perrelossntuheovLaEmD ente pbeutrto1n5asgeaicnodnudriinpge1r5visseucaolnizdzsawreillladistepmlayptehreatruooramdteemll’paemrabtuierne,teif,pprreesms iet ralogauinnaaftteerrza
v1o5ltsaecpoenrd1s,5itsweicllotnurdni opnerthaecdciespnldaeyrsecrneueon.vamente il display.

3.2 Temperatura di funzionamento
L’uso del condizionatore d’aria al di fuori di questi intervalli potrebbe attivare alcune funzioni di sicurezza che causeranno la disattivazione dell’unità.

Condizionatore d’aria di tipo split / Manuale utente

71 / 172 IT

3 Specifiche e caratteristiche dell’unità

3.3 Modelli split inverter

Modalità COOL (RAFFREDDAMENTO)

Temperatura dell’ambiente
Temperatura esterna

da 17 °C a 32 °C
da 0 °C a 50 °C da -15 °C a 50 °C (Per modelli dotati di sistemi di raffreddamento a bassa temperatura.)
da 0 °C a 52 °C (Per modelli speciali in uso nei paesi tropicali)

C

Per le unità esterne con riscaldamento elettrico ausiliario. Quando la temperatura esterna scende sotto 0 °C, si consiglia caldamente di tenere l’unità sempre inserita per garantire prestazioni continue.

Modalità HEAT (RISCALDAMENTO)
da 0 °C a 30 °C
-15 – 30 °C (5-86 °F)

Modalità DRY (DEUMIDIFICAZIONE)
da 10 °C a 32 °C
da 0 °C a 50 °C
da 0 °C a 52 °C (Per modelli speciali in uso nei paesi tropicali)

3.4 Modelli a velocità fissa

Modalità COOL (RAFFREDDAMENTO)

Temperatura dell’ambiente
Temperatura esterna

da 17 °C a 32 °C
da 18 °C a 43 °C
da -7 °C a 43 °C (Per modelli dotati di sistemi di raffreddamento a bassa temperatura)
da 18 °C a 52 °C (Per modelli speciali in uso nei paesi
tropicali)

Modalità HEAT

Modalità DRY

(RISCALDAMENTO) (DEUMIDIFICAZIONE)

da 0 °C a 30 °C

da 10 °C a 32 °C

da 11 °C a 43 °C

da -7 °C a 24 °C

da 18 °C a 43 °C
da 18 °C a 52 °C (Per modelli speciali in uso nei paesi tropicali)

72 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

3 Specifiche e caratteristiche dell’unità

C

Umidità ambiente relativa inferiore all’80%. Se il condizionatore d’aria funziona in ambienti con valori superiori, la sua superficie potrebbe attirare la condensa. Impostare il deflettore del flusso d’aria verticale al suo angolo massimo (verticalmente al pavimento) e selezionare la modalità di ventilazione HIGH (ALTA).

Per ottimizzare ulteriormente le prestazioni dell’unità, attenersi a quanto indicato di seguito · Mantenere porte e finestre chiuse.
· Limitare l’uso energetico tramite le funzioni TIMER ON (TIMER DI ACCENSIONE) e TIMER OFF (TIMER DI SPEGNIMENTO).
· Non ostruire le prese e le uscite d’aria.
· Controllare e pulire con regolarità i filtri dell’aria.
La guida all’uso del telecomando a infrarossi non è inclusa in questo manuale. Le funzioni disponibili variano a seconda del modello di condizionatore d’aria: fare riferimento al telecomando e al display dell’unità interna del modello acquistato.
3.5 Altre caratteristiche
· Riavvio automatico (solo alcuni modelli)
Se viene a mancare la corrente elettrica, una volta che viene ripristinata, l’unità si riavvierà in automatico con le impostazioni precedenti. · Antimuffa (solo alcune unità)
Quando si spegne l’unità durante le modalità COOL (RAFFREDDAMENTO), AUTO COOL (RAFFREDDAMENTO AUTOMATICO) o DRY (DEUMIDIFICAZIONE), il condizionatore d’aria continuerà a funzionare a bassa energia per asciugare la condensa ed evitare la formazione di muffe.

· Controllo wireless (solo alcune unità)
Il controllo wireless consente di controllare il condizionatore d’aria tramite il telefono cellulare e la connessione wireless.
Per l’accesso del dispositivo USB, la sostituzione e le operazioni di manutenzione devono essere eseguite da personale qualificato.
· Memoria dell’angolazione del deflettore (solo alcune unità)
Quando si accende l’unità, il deflettore riprenderà in automatico l’angolazione precedente.
· Rilevamento di perdite del refrigerante (solo alcune unità)
Quando viene rilevata una perdita di refrigerante, sull’unità interna appaiono in automatico la scritta “EC” o “EL0C”, o iniziano a lampeggiare dei led.
· Funzione Notte
La funzione SLEEP (NOTTE) si utilizza per diminuire l’energia consumata durante le ore di sonno (quando non occorre la stessa temperatura per dormire in modo confortevole). È possibile attivare questa funzione solo tramite telecomando. Inoltre, la funzione Sleep (Notte) non è disponibile in modalità FAN (VENTILAZIONE) o
DRY (DEUMIDIFICAZIONE).
Premere il pulsante SLEEP (NOTTE) prima di andare a letto. Durante la modalità COOL (RAFFREDDAMENTO), l’unità aumenterà la temperatura di 1 °C dopo la prima ora e di un ulteriore 1 °C ad ogni ora successiva. Durante la modalità HEAT (RISCALDAMENTO), l’unità diminuirà la temperatura di 1 °C dopo la prima ora e di un ulteriore 1 °C ad ogni ora successiva. Dopo otto ore, la funzione Sleep (Notte) si arresta e il sistema continua a funzionare in base alla situazione.

Condizionatore d’aria di tipo split / Manuale utente

73 / 172 IT

3 Specifiche e caratteristiche dell’unità

ImpSoestare la tteemmppeerraattuurrae

SFLuEnEzPioOnpeeNraottitoen
MCoodoal lmitàodCeo(o+l 1(FCre/d2dFo))p(+er1h°oCu)r afoll’rotrahepefirrslet tpwrimo ehoduersore

1hr

1hr

MHeoadtalmitàodHee(at-1(CCa/l2doF)) (p-1er°hCo) ur

afoll’rotrhaepefirrslet tpwrimo ehoduresore

FunKzeioenpamento rcuonnntiinnugo

RisparmSaiovinengeergneetricgoy dduurraintgesleleeopre di sonno

3.6.2 Impostazione dell’angolazione orizzontale del flusso d’aria
L’angolazione orizzontale del flusso d’aria deve essere impostata a mano. Impugnando la barretta del deflettore (vedere Fig. B), regolarlo a mano secondo la direzione desiderata. Per alcune unità, l’angolo orizzontale del flusso d’aria è impostabile tramite telecomando. Fare riferimento al Manuale del telecomando.

3.6 Impostazione dell’angolazione del flusso d’aria

3.6.1 Impostazione dell’angolazione verticale del flusso d’aria

Mentre l’unità è accesa, utilizzare il pulsante SWING/DIRECT (OSCILLAZIONE/DIREZIONE) sul telecomando per impostare la direzione (l’angolazione verticale) del flusso d’aria. Fare riferimento al manuale d’uso del telecomando per maggiori dettagli.

C

Quando si utilizzano le modalità COOL (RAFFREDDAMENTO) o DRY (DEUMIDIFICAZIONE), non impostare il deflettore con un’angolazione troppo verticale per lunghi periodi di tempo. Ciò può provocare la formazione di condensa sulle lame del deflettore che potrebbe sgocciolare sul pavimento o i mobili. Quando si utilizzano le modalità COOL (RAFFREDDAMENTO) o HEAT (Riscaldamento), impostando il deflettore con un’angolazione troppo verticale è possibile che le prestazioni dell’unità si riducano a causa dello scarso passaggio dell’aria.

3.7 Installazione del Kit HomeWhiz (Modulo Wireless)
1. Rimuovere il cappuccio protettivo del Kit HomeWhiz (modulo wireless)
2. Aprire il pannello frontale e inserire il kit HomeWhiz (modulo wireless) all’interno dell’interfacccia riservata.
Inserire
Avvertenza:
A Questa interfaccia è compatibile solo con chiavette (moduli wireless) forniti dal produttore.

74 / 172 IT

Condizionatore d’aria di tipo split / Manuale utente

3 Specifiche e caratteristiche dell’unità

3.8 Funzionamento manuale (senza telecomando)

A

ATTENZIONE! Il pulsante manuale è destinato solo a scopi di collaudo ed emergenza. Non utilizzare questa funzione a meno che il telecomando non sia andato perso e sia assolutamente necessaria. Per ripristinare il normale funzionamento, utilizzare il telecomando per attivare l’unità. L’unità deve essere spenta prima dell’uso manuale.

Per utilizzare l’unità manualmente: 1. Aprire il pannello anteriore dell’unità interna.
2. Individuare il pulsante manual control (controllo manuale) a destra dell’unità.
3. Premere il pulsante manual control (controllo manuale) una volta per attivare la modalità forced auto (automatica forzata).
4. Premere il pulsante manual control (controllo manuale) di nuovo per attivare la modalità forced cooling (raffreddamento forzato).
5. Premere il il pulsante manual control (controllo manuale) una terza volta per spegnere l’unità.
6. Chiudere il pannello anteriore.

C

Non spostare il deflettore a mano. In questo modo il deflettore andrà fuori sincronia. Se si verifica questo problema, spegnere l’unità e scollegarla per alcuni secondi, quindi riavviarla. Così facendo, si ripristinerà la posizione del deflettore.

A

ATTENZIONE! Non inserire le dita all’interno o in prossimità della ventola o sul lato dell’aspirazione dell’unità. Le ventole ad alta velocità all’interno dell’unità possono provocare lesioni.

BDaerfrleacdtoerl droedflettore

FFig. B

d’aRRzaaiognngegioe
Condizionatore d’aria di tipo split / Manuale utente

Pulsante per il Mcaonnutarloclloonmtroalnbuuatlteon
75 / 172 IT

4 Installazione

4.1 Riepilogo dell’installazione ­ Unità interna

1

15cm15 (cm5.9in)

2

3

12c1m2 cm (4.75in)
2.3m (90.525,3inm)

1122ccmm (4.75in)

SeleSzioenlearcetlaInpsotsaizliloanteiopnerLl’oincstaatlliaoznione SDtaebtileirremlainpoesiWzioanlel dHeoi floeriPsuollsaitpiaornete

4

5

FissAartetalachpiaMstoraundti imngonPtalgagteio
6

PraticaDrerilulnWfoarlol sHuolllaeparete

CCololengnaerectlePtuipbiantgure

7

8

CCoollengnaerecti Wcaviriienlgettrici (no(nnoatppalpicpalbicileabpleer faolcrusnoemlocealità
locatidoenlsNionrdNAomrtehricAam) erica )

PrePpraerpaarereilDturbaiondHi oscsaerico

WraApvvPoilpgeinregleantudbaCtaurbelee i cavi (n(nootnaapppliiccaabbilleepfeorraslcoumneelolocaclaittàiodnesl NinordNAomrtehriAcam) erica)
9 8 STEP

76 / 172 IT

MMonotuarnet lI’unnditoàoirntUernniat Condizionatore d’aria di tipo split / Manuale utente

4 Installazione

4.2 Istruzioni di installazione ­ Unità interna
4.2.1 Prima dell’installazione
Prima di installare l’unità interna, fare riferimento all’etichetta apposta sulla confezione del prodotto per assicurarsi che il codice del modello dell’unità interna corrisponda al codice del modello dell’unità esterna. Passaggio 1: Selezionare la posizione di installazione. Prima di installare l’unità interna, è necessario scegliere una posizione adeguata. Quanto segue sono i parametri standard che permetteranno di scegliere la posizione adeguata per l’unità.
Le posizioni di installazione corrette soddisfano i seguenti standard: · Circolazione dell’aria adeguata
· Scarico facilmente accessibile
· Il rumore prodotto dall’unità non disturba altre persone
· Stabile e robusta: la posizione non dovrà comportare vibrazioni
· Sufficientemente solida per sostenere il peso dell’unità
· La posizione dovrà trovarsi almeno a 1 metro di distanza da tutti gli altri dispositivi elettrici (ad esempio, TV, radio, computer)

· In prossimità della porta d’ingresso

· In una posizione esposta alla luce solare diretta

C

Se non è presente alcuna tubatura fissa del refrigerante: Durante la scelta di una posizione, tenere presente che è necessario riservare un ampio spazio per il foro sulla parete (vedere il passaggio Praticare un foro sulla parete per le tubature di collegamento) per il cavo del segnale e per le tubature del refrigerante che collegano l’unità interna ed esterna. La posizione predefinita per tutte le tubature è sul lato destro dell’unità interna (guardando l’unità anteriormente). Tuttavia, l’unità consente la sistemazione delle tubature sia sul lato sinistro che destro.

Fare riferimento al diagramma seguente per assicurarsi una corretta distanza dalle pareti e dal soffitto:
15cm15(5c.m9ino) ooltrremore

12cm (4.72in) 12 ocrmmoooreltre

12cm (4.72in) 12orcmooreoltre

2.3m 2(9,30.m55oino)ltorremore

NON installare l’unità nelle seguenti posizioni: · In prossimità di qualsiasi fonte di calore, vapore
o gas combustibile
· In prossimità di oggetti, ad esempio tende o abbigliamento
· In prossimità di qualsiasi ostacolo che potrebbe bloccare la circolazione dell’aria

Passaggio 2: Fissare la piastra di montaggio alla parete
La piastra di montaggio è il dispositivo sul q