NOVUS N1040 Controller Instruction Manual
- June 3, 2024
- Novus
Table of Contents
- SAFETY ALERTS
- INSTALLATION / CONNECTIONS
- RECOMMENDATIONS FOR THE INSTALLATION
- FEATURES
- OPERATION
- DESCRIPTION OF THE PARAMETERS
- CONFIGURATION PROTECTION
- DETERMINATION OF PID PARAMETERS
- MAINTENANCE
- IDENTIFICATION
- SPECIFICATIONS
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
N1040 Controller
TEMPERATURE CONTROLLER – INSTRUCTIONS MANUAL – V2.1x I
SAFETY ALERTS
The symbols below are used on the equipment and throughout this document to draw the user’s attention to important operational and safety information.
|
---|---
CAUTION: Read the manual thoroughly before installing and operating the
equipment.| CAUTION OR DANGER: Electrical shock hazard
All safety related instructions that appear in the manual must be observed to ensure personal safety and to prevent damage to either the instrument or the system. If the instrument is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
INSTALLATION / CONNECTIONS
The controller must be fastened on a panel, following the sequence of steps described below:
- Prepare a panel cut-out according Specifications;
- Remove the mounting clamps from the controller;
- Insert the controller into the panel cut-out;
- Slide the mounting clamp from the rear to a firm grip at the panel.
ELECTRICAL CONNECTIONS
Fig. 01 below shows the electrical terminals of the controller:
RECOMMENDATIONS FOR THE INSTALLATION
- All electrical connections are made to the screw terminals at the rear of the controller.
- To minimize the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power conductors. If this is impractical, use shielded cables. In general, keep cable lengths to a minimum.
- All electronic instruments must be powered by a clean mains supply, proper for instrumentation.
- It is strongly recommended to apply RC’S FILTERS (noise suppressor) to contactor coils, solenoids, etc. In any application it is essential to consider what can happen when any part of the system fails. The controller features by themselves cannot assure total protection.
FEATURES
INPUT TYPE SELECTION
Table 01 shows the sensor types accepted and their respective codes and
ranges. Access the parameter in the INPUT cycle to select the appropriate
sensor.
TYPE | CODE | RANGE OF MEASUREMENT |
---|---|---|
Thermocouple J | Range: -110 to 950 ºC (-166 to 1742 ºF) | |
Thermocouple K | Range: -150 to 1370 ºC (-238 to 2498 ºF) | |
Thermocouple T | Range: -160 to 400 ºC (-256 to 752 ºF) | |
Pt100 | Range: -200 to 850 ºC (-328 to 1562 ºF) |
Table 01 – Input types
OUTPUTS
The controller offers two, three or four output channels, depending on the
loaded optional features. The output channels are user configurable as Control
Output, Alarm 1 Output, Alarm 2 Output, Alarm 1 OR Alarm 2 Output and LBD
(Loop Break Detect) Output.
OUT1 – Pulse type output of electrical voltage. 5 Vdc / 50 mA max. Available
on terminals 4 and 5
OUT2 – Relay SPST-NA. Available at terminals 6 and 7.
OUT3 – Relay SPST-NA. Available at terminals 13 and 14.
OUT4 – Relay SPDT, available at terminals 10, 11 and 12.
CONTROL OUTPUT
The control strategy can be ON/OFF (when PB = 0.0) or PID. The PID parameters
can be automatically determined enabling the autotuning function ( ).
ALARM OUTPUT
The controller contains 2 alarms that can be directed (assigned) to any output
channel. The alarm functions are described in Table 02.
o | Output is not used as alarm. |
---|
lo
| Alarm of Absolute Minimum Value. Triggers when the value of measured PV is below the value defined for alarm Setpoint. (SPA1 or SPA2).|
ki
| Alarm of Absolute Maximum Value. Triggers when the value of measured PV is above the value defined for alarm Setpoint.|
di
| Alarm of Differential Value. In this function the parameters SP1 and
SP 2 represent the deviation of PV in relation to the SP of CONTROL.
|
Positive SPA1| Negative SPA1
di l| Alarm of Minimum Differential Value. It triggers when the value of
PV is below the defined point by (using the Alarm 1 as example).
|
Positive SPA1| Negative SPA1
di k
| Alarm of Valor Maximum Differential Value. Triggers when the value of PV is
above the defined point by (using Alarm 1 as example):
|
Positive SPA1| Negative SPA1
ierr
| Alarms of the Sensor Break (Sensor Break Alarm ). It is activated when the Input presents problems such as interrupted sensor, bad connection, etc.
Table 02 – Alarm functions
Note: Alarm functions on Table 02 are also valid for Alarm 2 (SPA2).
Important note: Alarms configured with the HI, diF and diFH
functions also trigger their associated output when a sensor fault is
identified and signaled by the controller. A relay output, for example,
configured to act as a High Alarm (HI), will operate when the SPAL value
is exceeded and also when the sensor connected to the controller input is
broken.
INITIAL BLOCKING OF ALARM
The initial blocking option inhibits the alarm from being recognized if an
alarm condition is present when the controller is first energized. The alarm
will be enabled only after the occurrence of a non-alarm condition.
The initial blocking is useful, for example, when one of the alarms is
configured as a minimum value alarm, causing the activation of the alarm soon
upon the process start-up, an occurrence that may be undesirable.
The initial blocking is disabled for the sensor break alarm function (Open
sensor).
SAFE OUTPUT VALUE WITH SENSOR FAILURE
Function that places the control output in a safe condition for the process
when is identified an error in the sensor input.
With a fault identified in the sensor, the controller determines the
percentage value defined in parameter for the control output. The controller
will remain in this condition until the sensor failure disappears. values are
only 0 and 100 % when in ON/OFF control mode. For PID control mode, any value
in the range from 0 to
100 % is accepted.
LBD FUNCTION – LOOP BREAK DETECTION
The parameter defines a time interval, in minutes, within which the PV is
expect to react to a control output signal. If the PV does not react properly
within the time interval configured, the controller signals in its display
the occurrence of the LBD event, which indicates problems in the control loop.
The LBD event can also be sent to one of the output channels of the
controller. To do this, simply configure the desired output channel with the
function which, in the event of this event, is triggered.
This function is disabled with value 0 (zero). This function allows the user
to detect problems in the installation, such as defective actuators, power
supply failure, etc.
OFFSET
Feature that allows the user to make small adjustment in the PV indication.
Allows correcting measurement errors that appear, for example, when replacing
the temperature sensor.
USB INTERFACE
The USB interface is used to CONFIGURE, MONITOR or UPDATE the controller
FIRMWARE. The user should use QuickTune software, which offers features to
create, view, save and open settings from the device or files on the
computer. The tool for saving and opening configurations in files allows the
user to transfer settings between devices and perform backup copies.
For specific models, QuickTune allows to update the firmware (internal
software) of the controller via the USB interface.
For MONITORING purposes, the user can use any supervisory software (SCADA) or
laboratory software that supports the MODBUS RTU communication over a serial
communication port. When connected to a computer’s USB, the controller is
recognized as a conventional serial port (COM x).
The user must use QuickTune software or consult the DEVICE MANAGER on the
Windows Control Panel to identify the COM port assigned to the controller.
The user should consult the mapping of the MODBUS memory in the controller’s
communication manual and the documentation of the supervision software to
start the MONITORING process.
Follow the procedure below to use the USB communication of the device:
-
Download QuickTune software from our website and install it on the computer. The USB drivers necessary for operating the communication will be installed with the software.
-
Connect the USB cable between the device and the computer.
The controller does not have to be connected to a power supply.
The USB will provide enough power to operate the communication (other device functions may not operate). -
Run the QuickTune software, configure the communication and start the device recognition.
| The USB interface IS NOT SEPARATE from the signal input (PV) or the
controller’s digital inputs and outputs. It is intended for temporary use
during CONFIGURATION and MONITORING periods. For the safety of people and
equipment, it must only be used when the piece of equipment is completely
disconnected from the input/output signals. Using the USB in any other type of
connection is possible but requires a careful analysis by the person
responsible for installing it. When MONITORING for long periods of time and
with connected inputs and outputs, we recommend using the RS485 interface.
---|---
OPERATION
The controller’s front panel, with its parts, can be seen in the Fig. 02:
Fig. 02 – Identification of the parts referring to the front panel
Display: Displays the measured variable, symbols of the
configuration parameters and their respective values/conditions.
COM Indicator: Flashes to indicate communication activity in the
RS485 interface.
TUNE Indicator: Stays ON while the controller is in tuning process.
OUT Indicator: For relay or pulse control output; it reflects the actual
state of the output.
A1 and A2 Indicators: Signalize the occurrence of alarm situation.
P Key: Used to walk through the menu parameters.
Increment key and Decrement key: Allow altering the values of the
parameters.
Back key: Used to retrocede parameters.
STARTUP
When the controller is powered up, it displays its firmware version for 3
seconds, after which the controller starts normal operation. The value of PV
and SP is then displayed and the outputs are enabled.
In order for the controller to operate properly in a process, its parameters
need to be configured first, such that it can perform accordingly to the
system requirements. The user must be aware of the importance of each
parameter and for each one determine a valid condition.
The parameters are grouped in levels according to their functionality and
operation easiness. The 5 levels of parameters are:
1 – Operation / 2 – Tuning / 3 – Alarms / 4 – Input / 5 – Calibration
The “P” key is used for accessing the parameters within a level. Keeping
the “P” key pressed, at every 2 seconds the controller jumps to the next
level of parameters, showing the first parameter of each level:
PV >> atvn >> fva1 >> type >> pass >> PV …
To enter a particular level, simply release the “P” key when the first
parameter in that level is displayed. To walk through the parameters in a
level, press the “P” key with short strokes. To go back to the previous
parameter in a cycle, press :
Each parameter is displayed with its prompt in the upper display and
value/condition in the lower display. Depending on the level of parameter
protection adopted, the parameter PASS precedes the first parameter in the
level where the protection becomes active. See section Configuration
Protection.
DESCRIPTION OF THE PARAMETERS
OPERATION CYCLE
PV + SP| PV Indication screen. On the higher display (red) the value
of the measured variable (PV) temperature is shown. On the lower display
(green), the control setpoint (SP) is shown.
---|---
| Alarm SP. Value that defines the alarm activation point. For the alarms set
up with the functions of the type ifferential , these parameters define
deviations. For the alarm function ierr , this parameter is not used.
Parameters shown in this level only when enabled in the parameters s 1. and s
. .
TUNING CYCLE
| AUTO-TUNE. Enables the auto-tuning function for the PID parameters .
Defines the control strategy to be taken:
– Turned off (no PID tuning);
– Automatic tuning;
– More accurate automatic tuning.
---|---
Pb
| Proportional Band. Value of the term P of the control mode PID, in percentage of the maximum span of the input type. Adjust of between 0 and 500.0 %.
When set to zero (0), control action is ON/OFF.
Ir
| Integral Rate. Value of the term I of the PID algorithm, in repetitions per minute (Reset). Adjustable between 0 and 24.00. Displayed only if proportional band ¹ 0.
dE
| Derivative Time. Value of the term D of the control mode PID, in seconds. Adjustable between 0 and 250.0 seconds. Displayed only if proportional band ¹ 0.
0E
| Cycle time. Pulse Width Modulation (PWM) period in seconds. Adjustable
between 0.5 and 100.0 seconds.
Displayed only if proportional band ¹ 0.
| Hysteresis. Is the hysteresis for ON/OFF control (set in temperature units).
This parameter is only used when the controller is in ON/OFF mode ( Pb =
0 ).
| Action Control:
Control with Reverse Action. Appropriate for heating. Turns control output on when PV is below SP.
** Control with Direct Action. Appropriate for cooling**. Turns control output on when PV is above SP.
| SoftStart Function. Time interval, in seconds, while the controller limits
the control output (MV) rising rate.
(Zero value disables the Soft Start function).
| Assign functions to the Output channels OUT1, OUT2, OUT3 and OUT4:
– Not used;
– Control output;
– Alarm 1 output;
– Alarm 2 output;
– Alarm 1 + Alarm2 (OR logic);
**** – Loop Break Detect Alarm.
ALARMS CYCLE
| Functions of Alarms. Defines the functions for the alarms among the options
of the Table 02.
---|---
| Alarm SP. Value that defines the point of activation of the alarm outputs.
For the alarms programmed with the functions of the type Differential ,
these parameters represent the deviations.
For the ierr alarm function, this parameter has no meaning.
**| SP Enable. Configures display of SPA1 and SPA2 also in the Operation
Cycle.
YES SPA1/SPA2 are displayed in the Operation Cycle
NO** SPA1/SPA2 are not displayed in the Operation Cycle
| Blocking Alarms.
YES – Enables initial blocking;
NO – Inhibits initial blocking.
| Alarm Hysteresis. Defines the difference between the value of PV at which
the alarm is triggered and the value at which it is turned off.
| Allows visual signalization of an alarm occurrence by flashing the
indication of PV in the operation level.
YES – Enables alarm signaling flashing PV;
NO – Disables alarm signaling flashing PV.
INPUT CYCLE
| Input Type. Selects the input signal type to be connected to the process
variable input. Refer to Table 01 for the available options.
(J): -110 to 950 °C / -166 to 1742 °F
(K): c -150 to 1370 °C / -238 to 2498 °F
(T): c -160 to 400 °C / -256 to 752 °F
(Pt100): -200 to 850 °C / -328 to 1562 °F
---|---
| Digital Input Filter. Used to improve the stability of the measured signal
(PV). Adjustable between 0 and 20. In 0 (zero) it means filter turned off and
20 means maximum filter. The higher the filter value, the slower is the
response of the measured value.
| Selects the decimal point position to be viewed in both PV and SP.
| Selects display indication for degrees Celsius or Fahrenheit:
C – Indication in Celsius;
F – Indication in Fahrenheit.
| Offset value to be added to the PV reading to compensate sensor error.
Default value: Zero.
| SP Low Limit. Defines the SP lower limit of.
| SP High Limit. Defines the upper limit for adjustment of SP.
| Loop Break Detection Time. Time interval for the LBD function. Defines the
maximum interval of time for the PV to react to a control command. In minutes.
| Percentage value to be applied to the output on any failure of the sensor
that is connected to the controller input.
| Digital communication Baud Rate selection. In kbps with the following speeds
available:
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 and 115.2.
Parameter shown only on models with serial communication.
| Parity of the serial communication.
Without parity;
Even parity;
Odd parity.
Parameter shown only on models with serial communication.
---|---
| Communication Address. Number that identifies the controller in the serial
communication network, between 1 and 247. Parameter shown only on models with
serial communication.
CALIBRATION CYCLE
All types of input are calibrated in the factory. In case a recalibration is
required; it shall be carried out by a specialized professional. In case this
cycle is accidentally accessed, do not perform alteration in its parameters.
PRSS
| Password . This parameter is presented before the protected cycles. See
item Protection of Configuration.
---|---
| Calibration . Enables the possibility for calibration of the indicator.
When the calibration is not enabled, the related parameters are hidden.
| Input Low Calibration . Enter the value corresponding to the low scale
signal applied to the analog input.
| Input High Calibration . Enter the value corresponding to the full scale
signal applied to the analog input.
| Restore . Restores the factory calibration for all inputs and outputs,
disregarding modifications carried out by the user.
| Cold Junction . This screen is for information purpose only.
| Password Change. Allows defining a new access password, always different
from zero
| Protection. Sets up the Level of Protection. See Table 04.
CONFIGURATION PROTECTION
The controller provides means for protecting the parameters configurations, not allowing modifications to the parameters values, avoiding tampering or improper manipulation. The parameter Protection ( ), in the Calibration level, determines the protection strategy, limiting the access to particular levels, as shown by the Table 04.
PROTECTION LEVEL | PROTECTION CYCLES |
---|---|
1 | Only the Calibration cycle is protected. |
2 | Calibration and Input cycles. |
3 | Calibration, Input and Alarms cycles. |
4 | Calibration, Input, Alarms and Tuning cycles. |
5 | All cycles are protected, but the SP screen in the operation cycle. |
6 | All cycles are protected, including SP. |
Table 04 – Levels of Protection for the Configuration
ACCESS PASSWORD
The protected levels, when accessed, request the user to provide the Access
Password for granting permission to change the configuration of the parameters
on these levels.
The prompt PASS precedes the parameters on the protected levels.
If no password is entered, the parameters of the protected levels can only be
visualized.
The Access Password is defined by the user in the parameter Password Change (
PAS.(), present in the Calibration Level. The factory default for the
password code is 1111. PROTECTION ACCESS PASSWORD
The protection system built into the controller blocks for 10 minutes the
access to protected parameters after 5 consecutive frustrated attempts of
guessing the correct password.
MASTER PASSWORD
The Master Password is intended for allowing the user to define a new password
in the event of it being forgotten. The Master Password doesn’t grant access
to all parameters, only to the Password Change parameter (PAS(). After
defining the new password, the protected parameters may be accessed (and
modified) using this new password. The master password is made up by the
last three digits of the serial number of the controller added to the number
9000. As an example, for the equipment with serial number 7154321, the master
password is 9 3 2 1.
Controller serial number is displayed by pressing for 5 seconds.
DETERMINATION OF PID PARAMETERS
During the process of determining automatically the PID parameters, the system is controlled in ON/OFF in the programmed Setpoint. The auto-tuning process may take several minutes to be completed, depending on the system. The steps for executing the PID autotuning are:
• Select the process Setpoint.
• Enable auto-tuning at the parameter “Atvn”, selecting FAST or FULL.
The option FAST performs the tuning in the minimum possible time, while
the option FULL gives priority to accuracy over the speed. The sign TUNE
remains lit during the whole tuning phase. The user must wait for the tuning
to be completed before using the controller. During auto tuning period the
controller will impose oscillations to the process. PV will oscillate around
the programmed set point and controller output will switch on and off many
times. If the tuning does not result in a satisfactory control, refer to
Table 05 for guidelines on how to correct the behavior of the process.
PARAMETER | VERIFIED PROBLEM | SOLUTION |
---|
Band Proportional
| Slow answer| Decrease
Great oscillation| Increase
Rate Integration
| Slow answer| Increase
Great oscillation| Decrease
Derivative Time
| Slow answer or instability| Decrease
Great oscillation| Increase
Table 05 – Guidance for manual adjustment of the PID parameters
MAINTENANCE
PROBLEMS WITH THE CONTROLLER
Connection errors and inadequate programming are the most common errors
found during the controller operation. A final revision may avoid loss of time
and damages.
The controller displays some messages to help the user identify problems.
MESSAGE | DESCRIPTION OF THE PROBLEM |
---|---|
—- | Open input. No sensor or signal. |
Connection and/or configuration problems. Check the wiring and the |
configuration.
Other error messages may indicate hardware problems requiring maintenance
service.
CALIBRATION OF THE INPUT
All inputs are factory calibrated and recalibration should only be done by
qualified personnel. If you are not familiar with these procedures do not
attempt to calibrate this instrument.
The calibration steps are:
a) Configure the input type to be calibrated in the type parameter.
b) Configure the lower and upper limits of indication for the maximum span of
the selected input type.
c) Go to the Calibration Level.
d) Enter the access password.
e) Enable calibration by setting YES in parameter.
f) Using an electrical signals simulator, apply a signal a little higher than
the low indication limit for the selected input.
g) Access the parameter “inLC”. With the keys and adjust the display reading
such as to match the applied signal. Then press the key.
h) Apply a signal that corresponds to a value a little lower than the upper
limit of indication.
i) Access the parameter “inLC”. With the keys and adjust the display
reading such as to match the applied signal. j) Return to the Operation Level.
k) Check the resulting accuracy. If not good enough, repeat the procedure.
Note: When checking the controller calibration with a Pt100 simulator,
pay attention to the simulator minimum excitation current requirement, which
may not be compatible with the 0.170 mA excitation current provided by the
controller.
SERIAL COMMUNICATION
The controller can be supplied with an asynchronous RS-485 digital
communication interface for master-slave connection to a host computer
(master). The controller works as a slave only and all commands are started
by the computer which sends a request to the slave address. The addressed unit
sends back the requested reply. Broadcast commands (addressed to all
indicator units in a multidrop network) are accepted but no reply is sent back
in this case.
CHARACTERISTICS
- Signals compatible with RS-485 standard. MODBUS (RTU) Protocol. Two wire connection between 1 master and up to 31 (addressing up to 247 possible) instruments in bus topology.
- Communication signals are electrically isolated from the INPUT and POWER terminals. Not isolated from the retransmission circuit and the auxiliary voltage source when available.
- Maximum connection distance: 1000 meters.
- Time of disconnection: Maximum 2 ms after last byte.
- Programmable baud rate: 1200 to 115200 bps.
- Data Bits: 8.
- Parity: Even, Odd or None.
- Stop bits: 1
- Time at the beginning of response transmission: maximum 100 ms after receiving the command.
The RS-485 signals are:
D1 | D | D + | B | Bi-directional data line. | Terminal 15 |
---|---|---|---|---|---|
D0 | D – | A | Bi-directional inverted data line. | Terminal 16 | |
C | Optional connection that improves the performance of the | ||||
communication. | Terminal 17 |
GND
CONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION
Two parameters must be configured for using the serial type:
bavd: Communication speed.
PrtCONFIGURATION OF PARAMETERS FOR SERIAL COMMUNICATION
Two parameters must be configured for using the serial type:
bavd: Communication speed.
Prty: Parity of the communication.
addr: Communication address for the controller. y: Parity of the
communication.
addr: Communication address for the controller.
REDUCED REGISTERS TABLE
FOR SERIAL COMMUNICATION
Communication Protocol
The MOSBUS RTU slave is implemented. All configurable parameters can be
accessed for reading or writing through the communication port. Broadcast
commands are supported as well (address 0).
The available Modbus commands are:
03 – Read Holding Register
06 – Preset Single Register
05 – Force Single Coil
Holding Registers Table
Follows a description of the usual communication registers. For full
documentation download the Registers Table for Serial
Communication in the N1040 section of our website –
www.novusautomation.com.
All registers are 16 bit signed integers.
Address | Parameter | Register Description |
---|---|---|
0000 | Active SP | Read: Active control SP (main SP, from ramp and soak or from |
remote SP).
Write: To main SP.
Range: from Pll to spkl.
0001| PV| Read: Process Variable. Write: Not allowed.
Range: Minimum value is the one configured in spll and the maximum value
is the one configured in sp k l. Decimal point position
depends on dppo value.
In case of temperature reading, the value read is always multiplied by 10,
independently of dppo value.
---|---|---
0002| MV| Read: Output Power in automatic or manual mode.
Write: Not allowed. See address 29. Range: 0 to 1000 (0.0 to 100.0 %).
IDENTIFICATION
N1040 – | A – | B – | C |
---|
A : Outputs Features
PR: OUT1= Pulse / OUT2= Relay
PRR: OUT1= Pulse / OUT2=OUT3= Relay
PRRR : OUT1= Pulse / OUT2=OUT3= OUT4= Relay
B : Digital Communication
485 : Available RS485 digital communication
C: Power Supply electric
(Blank): 100~240 Vac / 48~240 Vdc; 50~60 Hz
24V: 12~24 Vdc / 24 Vac
SPECIFICATIONS
DIMENSIONS: …………………………………… 48 x 48 x 80 mm (1/16 DIN)
Cut-out in the panel: ………………… 45.5 x 45.5 mm (+0.5 -0.0 mm)
Approximate Weight: ………………………………………………………75 g
POWER SUPPLY:
Model standard: ………………….. 100 to 240 Vac (±10 %), 50/60 Hz
…………………………………………………………. 48 to 240 Vdc (±10 %)
Model 24 V: …………………. 12 to 24 Vdc / 24 Vac (-10 % / +20 %)
Maximum consumption: ……………………………………………….. 6 VA
ENVIRONMENTAL CONDITIONS:
Operation Temperature: ……………………………………….. 0 to 50 °C
Relative Humidity:…………………………………………… 80 % @ 30 °C
For temperatures above 30 °C, reduce 3 % for each °C
Internal use; Category of installation II, Degree of pollution 2; altitude <
2000 meters
INPUT …… Thermocouples J; K; T and Pt100 (according of Table 01)
Internal Resolution:……………………………….. 32767 levels (15 bits)
Resolution of Display: ……… 12000 levels (from -1999 up to 9999)
Rate of Input Reading: ……………………………. up 10 per second (*)
Accuracy: . Thermocouples J, K, T: 0,25 % of the span ±1 °C (*)
………………………………………………………. Pt100: 0,2 % of the span
Input Impedance: ……………… Pt100 and thermocouples: > 10 MΩ
Measurement of Pt100: ……………………. 3-wire type, (α=0.00385)
With compensation for cable length, excitation current of 0.170 mA.
() Value adopted when the Digital Filter parameter is set to 0 (zero) value.
For Digital Filter values other than 0, the Input Reading Rate value is 5
samples per second.
(**) the use of thermocouples requires a minimum time interval of 15 minutes
for stabilization.
OUTPUTS:
OUT1: ………………………………….. Voltage pulse, 5 V / 50 mA max.
OUT2: ………………………….. Relay SPST; 1.5 A / 240 Vac / 30 Vdc
OUT3: ………………………….. Relay SPST; 1.5 A / 240 Vac / 30 Vdc
OUT4: ……………………………..Relay SPDT; 3 A / 240 Vac / 30 Vdc
FRONT PANEL: ……………………. IP65, Polycarbonate (PC) UL94 V-2
ENCLOSURE: ………………………………………. IP20, ABS+PC UL94 V-0
ELECTROMAGNETIC COMPATIBILITY: …………… EN 61326-1:1997 and EN 61326-1/A1:1998
EMISSION: …………………………………………………… CISPR11/EN55011
IMMUNITY: …………………. EN61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-5, EN61000-4-6, EN61000-4-8 and EN61000-4-11
SAFETY: …………………….. EN61010-1:1993 and EN61010-1/A2:1995
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS;
PROGRAMMABLE CYCLE OF PWM: From 0.5 up 100 seconds.
STARTS UP OPERATION: After 3 seconds connected to the power supply.
CERTIFICATIONS: CE, UKCA and UL.
WARRANTY
Warranty conditions are available on our website
www.novusautomation.com/warranty.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>