Kele K-O2-S5 Oxygen Detectors Sensors and Transmitter User Manual
- June 4, 2024
- Kele
Table of Contents
K-O2-S5
Oxygen Sensor/Transmitter and
Two-Stage Alarm Controller
User Manual
PRODUCT ORDERING INFORMATION
This Manual covers the Kele K-O2-xx oxygen concentration and sensor family.
The family comprises 4 models with common features and functionality,
available in two enclosure styles and two sensor lifetime options as shown in
Table 1.
Description | Kele Part Number |
---|---|
Screw down enclosure with 5-year sensor life | K-O2-S5 |
Screw down enclosure with 10-year sensor life | K-O2-S10 |
Lockable, hinged enclosure with 5-year sensor life | K-O2-H5 |
Lockable, hinged enclosure with 10-year sensor life | K-O2-H10 |
Table 1: K-O2 family Part numbers
All K-O2-xx models are shipped with either 5-year life (K-O2-x5) or 10-year life (K-O2-x10) factory calibrated oxygen concentration sensor modules installed. At the end of sensor life this plug-in, calibrated, easily field- replaceable sensor modules are available from Kele.
Description | Kele Part Number |
---|---|
The 5-year calibrated replacement sensor module | KMOD-O2-25 |
The 10-year calibrated replacement sensor module | KMOD-O2-50 |
Table 2: K-O2 Family Replacement Sensor Module Part Numbers
A calibration kit containing the accessories required to calibrate any of the K-O2 family sensors is available from Kele under the part number UCK-1.
SPECIFICATIONS
Mechanical
Chassis Construction| Industrial strength, 18 Ga. Gray powder-coated steel.
Pad-lockable hinged or screw-on cover style available.
Weight| 2.0 lbs
Operating Temperature| 4 to 40°C
Operating Humidity| 15 – 90 %RH, non-condensing
Storage Temperature| -20 to 20°C (to minimize sensor degradation)
Case Dimensions (H x W x D)| K-O2-Hx: 6.4” x 5.9” x 2.4” (163.5 x 150.8 x
60.7 mm)
K-O2-Sx: 6.3” x 5.8” x 2.1” (160.0 x 147.3 x 52.0 mm)
Sensor Vents| Natural ventilation through 18, 0.1” (2.54 mm) diameter vents
External Indicators| Tri-color LED indicates the operational status of the
sensor.
Knockouts| 4 trade ½” knockouts (1 per side)
Table 3: Mechanical Specifications
Electrical
Operating Power Voltage| 14 – 30 VAC (RMS) or DC
Isolated power supply; separate transformer not required.
Power Consumption| < 5W
Control Relays| 2 separate SPDT line-voltage-capable relays for
warning/ventilation and alarm outputs.
UL-rated: 10 Amps max at 120/277 VAC or 30 VDC. (E43203)
Concentration Reporting Output| Isolated, powered 4 – 20 mA current loop
output.
4 mA output => 0 % concentration. 20 mA => 25%
Maximum loop resistance: 510Ω
Termination| Pluggable screw terminals for use with 12 AWG or thinner wire
Table 4: Electrical Specifications
Oxygen Sensor (O2)
Sensor Type| Galvanic cell
Measurement Range| 0 – 25% (by volume)
Analog Output Range| 4-20mA (corresponds to 0 to 25%)
Accuracy| ±0.3% O₂ (typical after calibration)
Calibration Interval| 6 Months (to maintain specified accuracy)
Sensor Life| K-O2-x5: 5 years (typical)
K-O2-x10: 10 years (typical)
Recommended calibrated FieldReplaceable Sensor| KMOD-O2-25 (5 years) or
KMOD-O2-50 (10 years)
Calibration Kit| UCK-1 kit
Calibration gases| Span (20.9% oxygen, balance nitrogen): Kele PN:
GAS-O2-20.9
Zero (100% nitrogen) Kele PN: GAS-N2
Table 5: Oxygen Sensor Specifications
MECHANICAL INSTALLATION
The Model K-O2 is available in two versions of an industrial-strength, 18 Gauge, gray, powder-coated steel enclosure. The pad-lockable, hinged-cover version is shown in Figure 1 and the removable, screw-down cover version is shown in Figure 2. All electronics are attached to the front cover. There are trade ½” conduit knock-outs on all sides for electrical connections. In potentially damp locations the knock-out on the bottom of the case should be used to minimize the possibility of water entry. DO NOT USE THE VENT HOLES FOR WIRE ENTRY.
- This unit is designed to mount to a rigid, vibration-free surface near the middle of the area to be monitored about 5 feet above the floor.
- It should be located where there is free airflow – avoid corners or recesses.
- The air vents on the sides of the enclosure should not be closer than 1 foot from the nearest perpendicular wall and must not be obstructed or painted over.
- May be mounted
- Vertically with the status LED in the lower left or lower right corner.
- Horizontally in any orientation.
- Mounting holes are made for direct wall screws for the surface encountered. (Mounting screws not provided) or switch box spacing.
2.1 ENCLOSURE DIMENSIONS
Case Style
| Mtg hole diameter| Distance from center
---|---|---
Horizontal|
Vertical
K-O2-Hx (Hinged)| 5/16” (7.94 mm)| 1.25” (31.75 mm)| 1.50” (38.10 mm)
K-O2-Sx (Screw-down)| 9/32” (7.14 mm)| 1.50” (38.10 mm)| 1.50” (38.10 mm)
ELECTRICAL INSTALLATION
The controller is not equipped with a power switch; it is operational whenever
sufficient power is applied to the power input terminals.
All electrical connections to the controller are made through screw terminals
that can be unplugged for the easy landing of wires. The controller’s
enclosure contains conduit knockouts on all sides for flexibility during
installation; refer to Figure 1 and Figure 2 for details and dimensions of the
enclosures.
3.1 ANALOG OUTPUT CONNECTIONS
The sensor’s readings are reported at the controller’s powered 420mA analog
utput connections. Current flows out of the ‘+’ terminal and returns to the
‘-‘ terminal.
The oxygen sensor output is provided at the terminal highlighted in Figure 3. Analog output connection has polarity as labeled on the controller silkscreen: care must be taken to ensure proper connection. To wire the analog output connections:
- Power down the controller, this can be done by unplugging the controller power terminal (see Figure 6).
- Unplug the analog output screw terminal labeled O1.
- Attach the signal wires, paying close attention to the polarity.
- Plug the analog output screw terminal back into the controller.
3.2 RELAY CONNECTIONS
The controller has two, 10 Amp, 120/277 VAC UL-rated, SPDT dry contact relay
output connections (shown in Figure 4) that can directly control loads up to
10 Amps through the normally-open terminal.
The relay connections have three-terminal screw connectors that allow devices
to be wired to the controller in either normally-open (NO) or normally-closed
(NC) configuration. These outputs are activated when ambient air oxygen
concentration falls below the controller threshold settings (refer to Section
4.2 for more information).
In the NO Configuration, the voltage attached to the NO terminal will be
present at the COM terminal only when the relay output is activated.
In the NC Configuration, the voltage attached to the NC terminal will be
present at the COM terminal only while the relay output is deactivated: the
voltage attached to the NC terminal is removed when the relay output is
activated.
Example wiring diagrams for relay connection are provided in Figure 5. To wire
the Warning/ventilation and Alarm relay outputs:
- Determine if the device is attached to the relay output should be wired in NO or NC configuration.
- Unplug the relay output screw terminal.
- Connect a supply voltage for the device being attached to the controller’s relay output to either the NO or NC location of the screw terminal (see Figure 4).
- Wire the power input of the device being attached to the controller’s relay output to the COM location of the screw terminal.
- Plug the relay output screw terminal back into the correct location on the controller board.
3.3 POWER CONNECTION
The K-O2 has a fully isolated, unpolarized power input; either AC or DC
operating power can be connected in either polarity. Multiple K-O2 units can
operate on the same transformer (up to its load limit) even when they are not
connected with the same positive/negative or hot/common polarity.
Power connection to the controller is made at the two-terminal screw connector
located at the bottom-right side of the board (highlighted in Figure 6). Power
to the controller can be either AC or DC voltage; DC voltage can be connected
in either polarity (see Section 1.0 for more details). To wire power:
- Open the controller’s enclosure and unplug the screw terminal labeled POWER on the controller board.
- Attach power wires to the screw terminal ensuring the connection is snug.
- Plug the screw terminal back into the POWER receptacle on the controller board: this will cause the controller to power up and begin operation.
It is recommended that all wired connections are made prior to providing power to the controller.
OPERATIONAL DESCRIPTION
The K-O2 is a two-stage ventilation and alarm controller that senses the
oxygen concentration in the ambient space around it and operates a
Warning/Ventilation contact closure that can be used to operate ventilation
fans when reduced levels of oxygen are detected. If the oxygen concentration
approaches unsafe levels, a second contact closure is operated; typically to
trigger an alarm.
The gas sensor is a calibrated module that can be replaced with minimal effort
when it reaches end-of-life (EOL) while leaving the main control mounted and
wired (refer to Section 7.1).
The front cover has an LED status indicator that illuminates in different
colors to indicate normal (green), Warning/Ventilation (yellow), and Alarm
(red) conditions. Blinking red indicates that the sensor is NOT operational.
While the LED is blinking red, the analog output is delivering 4 mA to
indicate the error. The concentration of oxygen in the ambient air is reported
at the controller’s analog current-loop output as percent by volume. The
analog output ranges from 4 to 20mA (refer to Table 4 and Table 5).
Status LED Color | Operational Status Description |
---|---|
Concentration is above the warning/ventilation threshold. No relay outputs |
are active.
| Concentration is below the warning/ventilation threshold and above the alarm
threshold.
The warning/ventilation relay is active.
| Concentration is below the alarm threshold. Both warning/ventilation and
alarm relays are active.
| End of Life warning. The sensor has reached the end of its rated service
life and should be replaced. Relays and analog outputs continue to function
normally.
| Sensor Expired.
The warning/ventilation relay is active and the analog output is 4 mA. (refer
to Section 7)
Table 7: Front Panel Status LED Indications During Normal Operation.
4.1 SPECIAL MODES
The K-O2 operates in several modes as shown in Table 9. Table 9: K-O2
Operating Modes
Normal operation is as described above. During standby mode, the sensor is
stabilizing and analog output is held at 20 mA.
During span calibration, the sensor’s sensitivity is compared to its
sensitivity at initial factory calibration. If its sensitivity has fallen
below the manufacturer’s specification the K-O2 goes into Sensor Expired mode
with the analog output held at 4 mA and only the Warning/Ventilation relay
activated.
Mode
| Front Cover LED| Analog Output| Relays Actuated|
Comment
---|---|---|---|---
Normal| Steady Green, Yellow or Red| 4 – 20 mA| Depends on concentration|
During normal operation
Standby| Various| 20 mA| NONE| During start-up interval or any time during
calibration
EOL warning| Slow Blinking Yellow| 4 – 20 mA| Depends on concentration| Sensor
nearing the end of its rated service life.
Relays and analog output function normally.
Sensor Expired| Slow Blinking Red| 4 mA| Warning / Ventilation| After
calibration of the expired sensor.
The sensor is no longer operational.
Table 9: K-O2 Operating Modes
| O₂
---|---
Federal OSHA Personal Exposure Limit (PEL).| 19.50%
4.2 WARNING /VENTILATION AND ALARM CONDITIONS
Two, 10 Amp, 120/277 VAC rated, dry-contact, SPDT relays activate during
warning/ventilation and alarm conditions: refer to Section 3.2 for wiring
information.
When the concentration of oxygen falls below its configured
warning/ventilation threshold, the WARNING/VENTILATION relay output is
activated. When the concentration falls below the alarm threshold, the
controller’s ALARM relay is also activated. When the oxygen concentration
rises above the alarm threshold, the ALARM relay is deactivated; when it rises
above the ventilation threshold the WARNING/VENTILATION relay is also
deactivated.
4.3 SETTING VENTILATION AND ALARM THRESHOLDS
The four, factory-preset pairs of ventilation and alarm levels are shown in
Table 8. Each setting determines both the controller’s warning/ventilation and
alarm thresholds.
The active threshold values are selected by setting the two DIP switches on
the main board (see Figure 8) as shown in the first column of Table 8 for the
desired setting.
4.4 CONCENTRATION REPORTING
In normal mode, oxygen concentration readings from the sensor are reported by
the controller’s powered 4 – 20mA current loop output. The output connector
location is shown in Figure 6. Output scaling is as shown in Table 5.
ENSOR CALIBRATION
The sensitivity of the galvanic oxygen sensor used on the K-O2 series
decreases as the sensor ages. Over the sensor’s lifetime, its accuracy
decreases by about 30%. Without intervening calibrations, the sensor will
typically indicate about 14.7 % oxygen concentration in fresh air after 5 (for
the K-O2-x5) or 10 (for the K-O2-x10) years.
Required calibration frequency depends on the accuracy requirement of the
application. To maintain the accuracy specified in Table 5 over the full
operating range of the K-O2 series, a full calibration interval of 6 months is
recommended. Annual calibration will typically maintain accuracy within about
0.5% O2 (for K-O2-x5) and about 0.3% O2 (for K-O2-x10).
For best accuracy, the full two-step calibration process provides the sensor
module with oxygen-free ‘zero’ gas, and then a 21% ‘span’ gas is required. Two
calibration buttons (ZERO and SPAN) are provided on the main board to initiate
each calibration operation as shown in Figure 8.
For applications between 18% and 21% oxygen, a span-only calibration is often
adequate and requires no calibration gas. All that’s required is the certainty
of fresh air around the sensor. For accuracy at lower oxygen percentages, a
zero calibration before the span calibration is recommended.
To perform a gas-less span calibration: Follow the procedure in section
5.4, ignoring all instructions regarding the application or removal of
calibration gas or fittings.
The ‘sensor expired’ test will be performed at the end of a span calibration.
If the sensor’s sensitivity has fallen below the manufacturer’s end-of-life
specification, the K-O2 goes into Sensor Expired mode with the front cover LED
slowly blinking RED, the analog output at a constant 4 mA, and the
warning/ventilation relay activated. The oxygen sensor is no longer
operational and must be replaced (See section 6).
The status of the calibration process is indicated by the flash pattern of the
front cover LED as shown below.
Blinking Green
| Successful sampling. Waiting for user to confirm cal gas removal.
---|---
Blinking Red
| Failed calibration attempt. Waiting for the user to acknowledge with either
a re-try or an exit.
Green/Yellow
| During the ambient equilibration period after successful calibration. The
new calibration is applied.
Red/Yellow
| During the ambient equilibration period after failed sampling. The old
calibration is unchanged.
Table 10: Meaning of Status LED Blink Patterns During Calibration.
5.1 CALIBRATION GASES
Pure nitrogen zero gas and a precise mixture of 20.9% oxygen, and balance
nitrogen (see Table 11) are required to fully calibrate the oxygen sensor for
maximum accuracy.
A calibration kit that includes all the required accessories (but not the gas
itself) in a convenient carrying case is available from Kele.com as part
number UCK-1. The calibration gases are ordered separately using the part
numbers shown in Table 11.
Type | Mixture (by volume) | Kele Part No. |
---|---|---|
Zero gas | Pure nitrogen | GAS-N2 |
Span gas | 20.9% oxygen balance nitrogen | GAS-O2-20.9 |
Table 11: Required Calibration Gases
All K-O2 sensors include an orifice oxygen sensor calibration cap stored in the lower left corner of the enclosure as shown in Figure 10. Calibration gas is supplied through the tube-barb flow restrictor fitted to the narrow end of the cal cap at a pressure of 10 psi.
5.2 CALIBRATION GAS CONNECTION
A schematic of the calibration gas tubing connection between the regulator and
the calibration cap is shown in Figure 9. After connecting the
calibration gas supply hose to the calibration cap, slip the open end of the
cap over the hexagonal white gas port on the oxygen sensor. Verify that the
cap completely covers the gas port; there should be no white showing at the
bottom of the cap.
When ready to start the calibration, adjust the calibration gas regulator so
that the pressure gauge reads 10 psi.
5.3 ZERO CALIBRATION PROCEDURE
For maximum accuracy below 18%, the Zero calibration procedure must be done
before the Span calibration.
The progress and status of the calibration process are indicated by the color
and flash-state of the front cover status LED (see Table 10).
Apply the nitrogen (zero) calibration gas to the sensor using the included
calibration cap. Ensure that gas is flowing to the sensor, then press and hold
the ’ZERO’ button (see Figure 8) for 3 seconds until the front cover LED
starts blinking YELLOW, indicating that gas sampling is in progress.
- Ensure that the calibration adapter remains correctly seated and calibration gas continues to flow for the 2-minute sampling period.
- At the end of the sampling period, the sensor’s status LED blinks GREEN if the sampling was successful or RED if not.
- A. If successful (blinking GREEN):
The gas sampling was completed successfully. Turn off the calibration gas flow, remove the calibration cap then press and hold the ‘ZERO’ calibration button until the LED blinks GREEN/YELLOW indicating that the calibration gas has been removed, the calibration has been applied and the unit is on standby for two minutes while the sensor re-equilibrates to the ambient atmosphere before normal operation resumes. The calibration is complete when the status LED returns to steady GREEN.
OR
B. If NOT successful (blinking RED):
The most likely cause of zero calibration sampling failure is insufficient gas flow or leaks around the calibration adapter failing to completely immerse the sensor in nitrogen. Verify that calibration gas is still flowing at the required rate (pressure gauge reads 10 psi) and the calibration adapter is properly positioned.
The calibration sampling can be re-started while the LED is blinking RED by again pressing and holding the ‘ZERO’ button until the LED blinks YELLOW, then return to step 1 above.
To exit the zero-calibration routine preserving the original calibration: turn off the calibration gas flow and remove the calibration adapter, then press and quickly release the ‘ZERO’ button. The status LED will blink RED/YELLOW indicating that the calibration gas has been removed, the original calibration has been kept and the unit is on standby for two minutes while the sensor re-equilibrates to the ambient atmosphere before normal operation resumes. The original calibration is completely restored when the status LED returns to steady GREEN.
5.4 SPAN CALIBRATION PROCEDURE
For best accuracy, the Zero calibration procedure in section 5.2 should be
done before the Span calibration. Ignore steps in light blue highlight if
doing a no-gas span calibration.
The progress and status of the calibration process are indicated by the color and flash-state of the front cover status LED (see 10).
-
[Start the calibration gas flowing,] press and hold the ’SPAN’ button (see Figure 8) for 3 seconds until the status LED starts blinking YELLOW, indicating that gas sampling is in progress.
-
[Ensure that the calibration adapter covers the sensor completely for the 2-minute sampling period].
At the end of the sampling period, the sensor’s status LED blinks GREEN if the sampling was successful or RED if not. -
A. If successful (blinking GREEN):
The sampling was completed successfully. [Turn off the calibration gas flow, remove the calibration adapter then] press and hold the ‘SPAN’ calibration button until the LED blinks GREEN/YELLOW indicating that [the calibration gas has been removed,] the new calibration has been applied and the unit is in standby for two minutes while the sensor re-equilibrates to the ambient atmosphere before normal operation resumes. The calibration is complete when the status LED returns to steady GREEN.
OR
3B. If NOT successful (blinking RED):
The most likely causes of span gas sampling failure are:
[Insufficient gas flow or leaks around the calibration adapter not completely immersing the sensor in the calibration gas. Verify that the calibration gas cylinder has not run out and the calibration adapter is properly positioned.] The oxygen concentration at the sensor is NOT between 20.8 and 21.0 percent (by volume).
The calibration sampling can be re-started while the LED is blinking RED
by again pressing and holding the ‘SPAN’ button until the LED blinks
YELLOW, then go to step 1 above.
To exit the span calibration preserving the original calibration, press and
quickly release the ‘SPAN’ calibration button. The status LED will blink
RED/YELLOW indicating that the calibration gas has been removed, the
original calibration will be preserved and the unit is on standby for two
minutes while the sensor re-equilibrates to the ambient atmosphere before
normal operation resumes. The calibration is complete when the status LED
returns to steady GREEN.
At the conclusion of a successful Span calibration, the sensitivity of the sensor is compared to its sensitivity during the initial factory calibration. If its sensitivity has fallen below the manufacturer’s end-of-life specification, the K-O2 goes into Sensor Expired mode with the front cover LED slowly blinking RED, the analog output at a constant 4 mA, and the warning/ventilation relay activated. The oxygen sensor is no longer operational and must be replaced (See section 6).
SENSOR MODULE REPLACEMENT
Calibrated sensor modules are available from Kele.
Calibrated Oxygen Sensor | Cal Kit |
---|---|
5 year: KMOD-O2-25 | UCK-1 KIT |
10 year: KMOD-O2-50
6.1 FIELD REPLACEMENT OF SENSOR MODULES
Sensor modules can be replaced when they reach the end of their service life.
Some early serial numbers have sensor modules with the sensor rotated 90
degrees from the orientation shown in
To replace a sensor module with a new factory-calibrated one, follow the steps
below:
- Open the controller’s front cover.
- Unplug the controller’s power connector (refer to Figure 6).
- Unplug the sensor module by pulling the sensor module firmly away from the main board (Figure 11).
- Plug the new sensor module into the vacant ‘Sensor 1’ location, then press the module firmly until the nylon standoff (shown in Figure 11) has ‘snapped’ into the hole in the bottom-left side of the module board
- Plug in the controller’s power connector.
- Observe that the front cover indicator is no longer flashing red, and then close the controller’s enclosure.
WARRANTY
7.1 DURATION
Component / Class | Duration of Warranty |
---|---|
Enclosure & main board | 7 years |
Sensor modules | 1 year |
7.2 LIMITED WARRANTY AND REMEDIES.
KELE warrants to the Buyer that for the duration stated in the “Duration of
Warranty” section above from the date of shipment of Products to the Buyer
that Products will substantially conform to the product specifications agreed
to by KELE. This warranty is not transferable.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. KELE
EXPRESSLY DISCLAIMS ALL IMPLIED WARRANTIES, INCLUDING THE WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
KELE IS NOT RESPONSIBLE IN ANY WAY FOR DAMAGE TO A PRODUCT, PROPERTY DAMAGE,
OR PHYSICAL INJURY RESULTING IN WHOLE OR IN PART FROM (1) IMPROPER OR CARELESS
USE, (2) UNAUTHORIZED USE OR MODIFICATIONS, OR (3) OTHER CAUSES BEYOND KELE’S
CONTROL.
IN NO EVENT IS KELE LIABLE TO THE BUYER OR ANY OTHER PERSON FOR THE COST OF
PROCUREMENT OF SUBSTITUTE GOODS, LOSS OF PROFITS, OR FOR ANY OTHER SPECIAL,
INCIDENTAL OR CONSEQUENTIAL DAMAGES.
This warranty does not cover:
- Defects due to misuse, abuse, or improper or inadequate care, service, or repair of Products;
- Defects due to modification of Products, or due to their alteration or repair by anyone other than KELE;
- Problems that arise from lack of compatibility between KELE’s Products and other components used with those Products or the design of the product into which Products are incorporated. Buyer is solely responsible for determining whether Products are appropriate for Buyer’s purpose, and for ensuring that any product into which Products are incorporated, other components used with KELE’s Products, and the purposes for which Kele’s Products are used are appropriate and compatible with those Products.
Unless KELE agrees otherwise, to obtain service under this warranty, the Buyer must pack any nonconforming Product carefully, and ship it, postpaid or freight prepaid, to Kele, Inc. at
3300 Brother Blvd. • Memphis, TN 38133
before the expiration of the warranty period. The buyer must include a brief
description of the nonconformity. Any actions for breach of this warranty must
be brought within one year of the expiration of this warranty.
If Kele determines that a returned Product does not conform to this warranty
it will, at Kele’s sole discretion, either repair or replace that Product, and
will ship the Product back to the Buyer free of charge. At KELE’s option, KELE
may choose to refund to the Buyer the purchase price for a nonconforming
Product instead of repairing or replacing it.
DISCLAIMERS
8.1 INSPECTION AND MAINTENANCE
In order to maintain the specified accuracy of this device over its full
operating range, its sensor should be calibrated at least every 6 months.
During calibration, the sensitivity of the sensor is compared to its
sensitivity during initial factory calibration. If the sensitivity has fallen
below the manufacturer’s specification, the sensor has reached the end of its
operating life and must be replaced. Contact Kele for a calibrated replacement
module.
In harsh environments, a sensor may fail prematurely. During normal operation,
the sensor is regularly tested to detect common failures. If a failure is
detected, the front cover status LED will blink slowly RED, the warning relay
will be activated and the concentration-reporting analog output will stay at 4
mA until the sensor is replaced.
NEITHER Kele NOR ANY OF ITS SUPPLIERS IS RESPONSIBLE IN ANY WAY FOR DAMAGE TO
A PRODUCT, PROPERTY DAMAGE, OR PHYSICAL INJURY RESULTING IN WHOLE OR IN PART
FROM (1) IMPROPER OR CARELESS USE, (2) UNAUTHORIZED USE OR MODIFICATIONS, OR
(3) OTHER CAUSES BEYOND Kele OR ITS SUPPLIERS CONTROL.
IN NO EVENT ARE Kele OR ANY OF ITS SUPPLIERS LIABLE TO THE BUYER OR ANY OTHER
PERSON FOR COST OF PROCUREMENT OF SUBSTITUTE GOODS, LOSS OF PROFITS, OR FOR
ANY OTHER SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
8.2 LIFE SAFETY
This unit is not designed, certified, sold, or authorized for use in
applications where the failure of this device could be reasonably expected to
result in personal injury or death.
Kele, Inc.
• 3300 Brother Blvd.
• Memphis, TN 38133
www.kele.com
5/20/2022
References
- kele.com - Building Automation Products and Solutions
- kele.com - Building Automation Products and Solutions
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>