Line Filter MCC 107 Installation Instructions
Line Filters of the type MCC 107 combine a harmonic filter and an EMC
filter. The line filters improve performance of the line current to the VLT®
Micro Drive FC 51. The three different Line Filter frame sizes correspond to
the M1, M2 and M3 Micro Drives.
1 | Mounting holes for frequency converter |
---|---|
2 | Input terminal |
3 | Output line |
4 | Protective earth (PE) |
Table 1.1
CAUTION
Hot surfaces
Risk of high surface temperatures.
- Do NOT touch the Line Filter during operation or wear protective gloves
WARNING
High voltage
Risk of electric shock.
- Never carry out maintenance work on the Line Filter during operation. Wait at least 4 minutes after the equipment has been disconnected from the frequency converter before touching any potentially live parts.
NOTE
- Never repair a defective filter
Mounting
There are two options for mounting the Line Filter correctly:
-
Front mounting
• Mount the filter in a vertical position with the terminals at the bottom.
• Mount the frequency converter on the front of the Line Filter using 3 M4 bolts. • Ensure metal-to-metal contact between filter and frequency converter.
NOTE
Metal-to-metal contact improves EMC performance and enables the baseplate of the frequency converter to function as heatsink for the Line Filter -
Side mounting
• Mount the filter side-by-side with the frequency converter.
There is no requirement for spacing between filter and frequency converter.
• Mount the back of the Line Filter to a cooling surface, such as a metal wall. Alternatively, derate the Line Filter by one size: For example use a 0.75 kW Line Filter with a 0.37 kW Micro Drive.
CAUTION
High temperatures
Risk of fire or device damage
- Do not mount the Line Filter in close proximity to other heating elements or heat-sensitive material (such as wood).
Wiring
WARNING
Risk of electrical shock due to high leakage currents
- Do not power up the Line Filter before it is connected to protective earth (PE)
- Connect Line Filter to protective earth (PE). Use a cabinet mounting panel or similar to achieve optimum earthing conditions.
- Connect input terminal to mains power (cable not supplied)
- Connect output cable to the input terminals of the frequency converter
- Ensure solid electrical contact between Line Filter and frequency converter (high frequency earthing)
NOTE
- Reduce common mode interferences by establishing a low impedance current path to the VLT® Micro Drive.
- To ensure optimum EMC performance, use a DeCoupling plate kit (ordering numbers 132B0106 or 132B0107)
For voltage rating, wire size and fuse selection, see the VLT® Micro Drive
Quick Guide at our technical literature website
http://www.danfoss.com/BusinessAreas/DrivesSolutions/Documentations/Technical+Documentation.htm
Dimensions
Frame / | M1 | M2 | M3 | Unit/ |
---|---|---|---|---|
w | 70 | 75 | 90 | mm |
d | 55 | 65 | 69 | mm |
h | 190 | 210 | 300 | mm |
h3 | 230 | 250 | 340 | mm |
w1 | 40 | 40 | 55,6 | mm |
h1 | 213 | 233 | 323 | mm |
w2 | 55 | 59 | 69 | mm |
h2 | 140 | 166,5 | 226 | mm |
11 | 45 | 38,5 | 68 | mm |
12 | 7,6 | 8 | 9,3 | mm |
PE | M6 | M6 | M6 | metric |
Weight | 2 | 3 | 5 | kg |
Table 1.2