VLT® Micro Drive

MCC 107 Line Filter

Line Filter MCC 107 Installation Instructions
Line Filters of the type MCC 107 combine a harmonic filter and an EMC filter. The line filters improve performance of the line current to the VLT® Micro Drive FC 51. The three different Line Filter frame sizes correspond to the M1, M2 and M3 Micro Drives.

1 Mounting holes for frequency converter
2 Input terminal
3 Output line
4 Protective earth (PE)

Table 1.1

Warning-icon.png CAUTION
Hot surfaces
Risk of high surface temperatures.

  • Do NOT touch the Line Filter during operation or wear protective gloves

Warning-icon.png WARNING
High voltage
Risk of electric shock.

  • Never carry out maintenance work on the Line Filter during operation. Wait at least 4 minutes after the equipment has been disconnected from the frequency converter before touching any potentially live parts.

NOTE

  • Never repair a defective filter

Mounting

There are two options for mounting the Line Filter correctly:

  1. Front mounting
    • Mount the filter in a vertical position with the terminals at the bottom.
    • Mount the frequency converter on the front of the Line Filter using 3 M4 bolts. • Ensure metal-to-metal contact between filter and frequency converter.
    NOTE
    Metal-to-metal contact improves EMC performance and enables the baseplate of the frequency converter to function as heatsink for the Line Filter

  2. Side mounting
    • Mount the filter side-by-side with the frequency converter.
    There is no requirement for spacing between filter and frequency converter.
    • Mount the back of the Line Filter to a cooling surface, such as a metal wall. Alternatively, derate the Line Filter by one size: For example use a 0.75 kW Line Filter with a 0.37 kW Micro Drive.

Warning-icon.png CAUTION
High temperatures
Risk of fire or device damage

  • Do not mount the Line Filter in close proximity to other heating elements or heat-sensitive material (such as wood).

Wiring

Warning-icon.png WARNING
Risk of electrical shock due to high leakage currents

  • Do not power up the Line Filter before it is connected to protective earth (PE)
  1. Connect Line Filter to protective earth (PE). Use a cabinet mounting panel or similar to achieve optimum earthing conditions.
  2. Connect input terminal to mains power (cable not supplied)
  3. Connect output cable to the input terminals of the frequency converter
  4. Ensure solid electrical contact between Line Filter and frequency converter (high frequency earthing)

Danfoss MCC 107 Line Filter - Illustration 1Danfoss MCC 107 Line Filter - Illustration
2 NOTE

  • Reduce common mode interferences by establishing a low impedance current path to the VLT® Micro Drive.
  • To ensure optimum EMC performance, use a DeCoupling plate kit (ordering numbers 132B0106 or 132B0107)

For voltage rating, wire size and fuse selection, see the VLT® Micro Drive Quick Guide at our technical literature website http://www.danfoss.com/BusinessAreas/DrivesSolutions/Documentations/Technical+Documentation.htm
Dimensions
Danfoss MCC 107 Line Filter - Dimensions

Frame / M1 M2 M3 Unit/
w 70 75 90 mm
d 55 65 69 mm
h 190 210 300 mm
h3 230 250 340 mm
w1 40 40 55,6 mm
h1 213 233 323 mm
w2 55 59 69 mm
h2 140 166,5 226 mm
11 45 38,5 68 mm
12 7,6 8 9,3 mm
PE M6 M6 M6 metric
Weight 2 3 5 kg