Danfoss MG11AJ22 Variable Speed Drives Instruction Manual
- June 1, 2024
- Danfoss
Table of Contents
- Danfoss MG11AJ22 Variable Speed Drives
- Product Usage Instructions
- FAQs
- Introduction
- Safety
- Mechanical Installation
- Electrical Installation
- Commissioning
- Application Set-up Examples
- Diagnostics and Troubleshooting
- Specifications
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Danfoss MG11AJ22 Variable Speed Drives
Product Usage Instructions
1. Mechanical Installation
Ensure you follow the steps outlined in section 3 of the manual for unpacking, installation environments, and mounting instructions.
2. Electrical Installation
Follow the safety instructions in section 4.1 and proceed with EMC-compliant installation, grounding, wiring schematic as per section 4.4, and motor connection instructions in sections 4.6 and 4.7.
3. Commissioning
For safe commissioning, follow the steps in section 5 after applying power, including local control panel operation, basic programming, motor set-up, energy optimization, and motor adaptation.
4. Diagnostics and Troubleshooting
Refer to section 7 for status messages, warning and alarm types, troubleshooting guidance, and a list of warnings and alarms.
FAQs
- Q: Where can I find detailed electrical specifications for the adjustable frequency drive?
- A: Detailed electrical specifications are available in section 8.1 of the manual.
- Q: How should I proceed with the mechanical installation of the drive?
- A: Follow the unpacking, installation environments, and mounting instructions provided in section 3 of the manual.
MAKING MODERN LIVING POSSIBLE
Instruction Manual VLT® HVAC Drive FC 102
1.190 kW
www.danfoss.com/drives
Introduction
1 Introduction
VLT® HVAC Drive Instruction Manual
1.1 Purpose of the Manual
This instruction manual provides information for safe installation and
commissioning of the adjustable frequency drive.
This instruction manual is intended for use by qualified personnel. Read and
follow the instruction manual in order to use the adjustable frequency drive
safely and professionally, and pay particular attention to the safety
instructions and general warnings. Keep this instruction manual available with
the adjustable frequency drive at all times.
1.2 Additional Resources
Other resources are available to understand advanced adjustable frequency
drive functions and programming.
· The Programming Guide provides greater detail on
working with parameters and many application examples.
· The Design Guide provides detailed information
about capabilities and functionality to design motor control systems.
· Instructions for operation with optional equipment.
Disclosure, duplication and sale of this document, as well as communication of
its content, are prohibited unless explicitly permitted. Infringement of this
prohibition incurs liability for damages. All rights reserved with regard to
patents, utility patents and registered designs. VLT® is a registered
trademark.
1.3 Document and Software Version
This manual is regularly reviewed and updated. All suggestions for improvement
are welcome. Table 1.1 shows the document version and the corresponding
software version.
Edition MG11AJxx
Remarks Replaces MG11AIxx
Software version 3.92
Table 1.1 Document and Software Version
1.4 Intended Use
The adjustable frequency drive is an electronic motor controller that
· regulates motor speed in response to system
feedback or to remote commands from external controllers. A power drive system
consists of the adjustable frequency drive, the motor and equipment driven by
the motor.
· monitors aspects of system and motor status. · can be used for motor
protection.
Depending on configuration, the adjustable frequency drive can be used in
standalone applications or form part of a larger appliance or installation.
The adjustable frequency drive is intended for use in residential, industrial
and commercial environments in accordance with local laws and standards. Do
not use the adjustable frequency drive in applications that do not comply with
specified designated operating conditions and environments.
NOTICE!
In a residential environment this product may cause radio interference, in
which case supplementary mitigation measures may be required.
4
MG11AJ22 – Rev. 2013-09-13
Introduction
VLT® HVAC Drive Instruction Manual
1.5 Block Diagram of the Adjustable Frequency Drive
Figure 1.1 is a block diagram of the adjustable frequency drive’s internal
components. See Table 1.2 for their functions.
Figure 1.1 Adjustable Frequency Drive Block Diagram
Area
Title
1 Line power input
2 Rectifier 3 DC bus
4 DC reactors
5 Capacitor bank 6 Inverter 7 Output to motor
Functions
· 3-phase AC line power supply
to the adjustable frequency drive
· The rectifier bridge converts
the AC input to DC current to supply inverter power
· Intermediate DC bus circuit
handles the DC current
· Filter the intermediate DC
circuit voltage
· Prove line transient protection · Reduce RMS current · Raise the power
factor
reflected back to the line
· Reduce harmonics on the AC
input
· Stores the DC power · Provides ride-through
protection for short power losses
· Converts the DC into a
controlled PWM AC waveform for a controlled variable output to the motor
· Regulated 3-phase output
power to the motor
Area
Title
8 Control circuitry
Functions
· Input power, internal
processing, output, and motor current are monitored to provide efficient
operation and control
· User interface and external
commands are monitored and performed
· Status output and control can
be provided
Table 1.2 Legend to Figure 1.1
1.6 Enclosure Types and Power Ratings
For enclosure types and power ratings of the adjustable frequency drives,
refer to 8.9 Power Ratings, Weight and Dimensions.
1.7 Approvals and Certifications
Table 1.3 Approvals and Certifications
More approvals and certifications are available. Contact local Danfoss
partner. The T7 (525690 V) adjustable frequency drives are not certified for
UL. The adjustable frequency drive complies with UL508C thermal memory
retention requirements. For more information, refer to the section Motor
Thermal Protection in the Design Guide.
1.8 Disposal Instruction
Do not dispose of equipment containing electrical components together with
domestic waste. Collect it separately in accordance with local and currently
valid legislation.
Table 1.4 Disposal Instruction
11
MG11AJ22 – Rev. 2013-09-13
5
Safety
VLT® HVAC Drive Instruction Manual
2 2 2 Safety
2.1 Safety Symbols
The following symbols are used in this document.
WARNING
Indicates a potentially hazardous situation which could result in death or
serious injury.
CAUTION
Indicates a potentially hazardous situation which could result in minor or
moderate injury. It may also be used to alert against unsafe practices.
NOTICE!
Indicates important information, including situations that may result in
damage to equipment or property.
2.2 Qualified Personnel
Correct and reliable transport, storage, installation, operation and
maintenance are required for the trouble-free and safe operation of the
adjustable frequency drive. Only qualified personnel is allowed to install or
operate this equipment.
Qualified personnel is defined as trained staff, who are authorized to
install, commission, and maintain equipment, systems and circuits in
accordance with pertinent laws and regulations. Additionally, the personnel
must be familiar with the instructions and safety measures described in this
document.
2.3 Safety Precautions
WARNING
HIGH VOLTAGE!
Adjustable frequency drives contain high voltage when connected to AC line
power. Installation, start-up, and maintenance must be performed by qualified
personnel only. Failure to perform installation, start-up, and maintenance by
qualified personnel could result in death or serious injury.
WARNING
UNINTENDED START!
When the adjustable frequency drive is connected to AC line power, the motor
may start at any time. The adjustable frequency drive, motor, and any driven
equipment must be in operational readiness. Failure to be in operational
readiness when the adjustable frequency drive is connected to AC line power
could result in death, serious injury, equipment or property damage.
WARNING
DISCHARGE TIME!
Adjustable frequency drives contain DC link capacitors that can remain charged
even when the adjustable frequency drive is not powered. To avoid electrical
hazards, disconnect AC line power, any permanent magnet type motors, and any
remote DC link power supplies, including battery backups, UPS and DC link
connections to other adjustable frequency drives. Wait for the capacitors to
discharge completely before performing any service or repair work. The amount
of waiting time is listed in Table 2.1. Failure to wait the specified time
after power has been removed before doing service or repair could result in
death or serious injury.
Voltage [V]
Minimum waiting time [minutes]
4
7
15
200240
1.13.7 kW
5.545 kW
380480
1.17.5 kW
1190 kW
525600
1.17.5 kW
1190 kW
525690
1.17.5 kW
1190 kW
High voltage may be present even when the warning LED
indicator lights are off.
Table 2.1 Discharge Time
WARNING
LEAKAGE CURRENT HAZARD!
Leakage currents are higher than 3.5 mA. It is the responsibility of the user
or certified electrical installer to ensure correct grounding of the
equipment. Failure to ground the adjustable frequency drive properly could
result in death or serious injury.
6
MG11AJ22 – Rev. 2013-09-13
Safety
VLT® HVAC Drive Instruction Manual
WARNING
EQUIPMENT HAZARD!
Rotating shafts and electrical equipment can be hazardous. All electrical work
must conform to national and local electrical codes. Installation, start-up,
and maintenance are performed only by trained and qualified personnel. Failure
to follow these guidelines could result in death or serious injury.
WARNING
WINDMILLING!
Unintended rotation of permanent magnet motors causes a risk of personal
injury and equipment damage. Ensure permanent magnet motors are blocked to
prevent unintended rotation.
CAUTION
POTENTIAL HAZARD IN THE EVENT OF INTERNAL FAILURE!
Risk of personal injury when the adjustable frequency drive is not properly
closed. Before applying power, ensure all safety covers are in place and
securely fastened.
22
MG11AJ22 – Rev. 2013-09-13
7
Mechanical Installation
VLT® HVAC Drive Instruction Manual
Mechanical Installation
33
3.1 Unpacking 3.1.1 Items Supplied
· Check the packaging and the adjustable frequency
drive visually for damage caused by inappropriate handling during shipment.
File any claim for damage with the carrier. Retain damaged parts for
clarification.
· Make sure the items supplied and the information
on the nameplate correspond to the order confirmation.
VLT R
HVAC Drive www.danfoss.com
1
2
T/C: FC-102P3K0T4Z55H1UGCXXXSXXXXAXBXCXXXXDX 10
P/N: 131U3930 3
S/N: 010102G290
3.0kW(400V) / 4.0HP(460V)
4
8
IN: 3×380-480V 50/60Hz 6.5/5.7A
5
OUT: 3×0-Vin 0-590Hz 7.2/6.3A
6
Type 12 / IP55 Tamb.45 oC/113 oF
7
- 1 3 1 U 3 9 3 0 0 1 0 1 0 2 G 2 9 0 * MADE IN DENMARK Listed 76X1 E134261 Ind. Contr. Eq.
` `
CAUTION:
See manual for special condition/mains fuse
9
voir manual de conditions speclales/fusibles
WARNING: Stored charge, wait 4 min. Charge residuelle, attendez 4 min.
Figure 3.1 Product Nameplate (Example)
130BD511.10
1 Type code 2 Order number 3 Power rating 4 Input voltage, frequency and
current (at low/high voltages)
Output voltage, frequency and current (at low/high 5
voltages) 6 Enclosure type and IP rating 7 Maximum ambient temperature 8
Certifications 9 Discharge time (Warning) 10 Serial number
Table 3.1 Legend to Figure 3.1
NOTICE!
Do not remove the nameplate from the adjustable frequency drive (loss of
warranty).
3.1.2 Storage
Ensure that requirements for storage are fulfilled. Refer to 8.4 Ambient
Conditions for further details.
8
MG11AJ22 – Rev. 2013-09-13
130BB492.10
Mechanical Installation
VLT® HVAC Drive Instruction Manual
3.1.3 Product Overview
1
18
2 3
4 5
17 16 6 15
8
14
13 Figure 3.2 Exploded View Enclosure Type A, IP20
1
Local control panel (LCP)
2
RS-485 serial bus connector (+68, -69)
3
Analog I/O connector
4
LCP input plug
5
Analog switches (A53), (A54)
6
Cable shield connector
7
Decoupling plate
8
Grounding clamp (PE)
9
Shielded cable grounding clamp and strain relief
Table 3.2 Legend to Figure 3.2
7
8
9 10 11 12
10 Motor output terminals 96 (U), 97 (V), 98 (W) 11 Relay 2 (01, 02, 03) 12
Relay 1 (04, 05, 06) 13 Brake (-81, +82) and load sharing (-88, +89) terminals
14 Line power input terminals 91 (L1), 92 (L2), 93 (L3) 15 USB connector 16
Serial bus terminal switch 17 Digital I/O and 24 V power supply 18 Cover
33
MG11AJ22 – Rev. 2013-09-13
9
130BB493.10
Mechanical Installation
2
33 1
VLT® HVAC Drive Instruction Manual
06 05 04 03 02 01
11 10
3 4
9 8
61 68
39 42 50 53 54
Remove jumper to activate Safe Stop
Max. 24 Volt !
12 13
18 19 27
29 32 33 20
7
6 5
12
13
DC-
DC+
19 18
17
16
Figure 3.3 Exploded View Enclosure Types B and C, IP55 and IP66
QDF-30
FAN MOUNTING
14 15
1 Local control panel (LCP) 2 Cover 3 RS-485 serial bus connector 4 Digital
I/O and 24 V power supply 5 Analog I/O connector 6 Cable shield connector 7
USB connector 8 Serial bus terminal switch 9 Analog switches (A53), (A54) 10
Relay 1 (01, 02, 03)
Table 3.3 Legend to Figure 3.3
11 Relay 2 (04, 05, 06) 12 Lifting ring 13 Mounting slot 14 Grounding clamp (PE) 15 Cable shield connector 16 Brake terminal (-81, +82) 17 Load sharing terminal (DC bus) (-88, +89) 18 Motor output terminals 96 (U), 97 (V), 98 (W) 19 Line power input terminals 91 (L1), 92 (L2), 93 (L3)
10
MG11AJ22 – Rev. 2013-09-13
Mechanical Installation
VLT® HVAC Drive Instruction Manual
3.2 Installation Environments
NOTICE!
In environments with airborne liquids, particles, or corrosive gases, ensure
that the IP/Type rating of the equipment matches the installation environment.
Failure to meet requirements for ambient conditions can reduce lifetime of the
adjustable frequency drive. Ensure that requirements for air humidity,
temperature and altitude are met.
Vibration and Shock The adjustable frequency drive complies with requirements
for units mounted on the walls and floors of production premises, as well as
in panels bolted to walls or floors. For detailed ambient conditions
specifications, refer to 8.4 Ambient Conditions.
3.3 Mounting
NOTICE!
Improper mounting can result in overheating and reduced performance.
Cooling
· Ensure that top and bottom clearance for air
cooling is provided. See Figure 3.4 for clearance requirements.
a
a
Figure 3.4 Top and Bottom Cooling Clearance
Enclosure a (mm)
A2-A5 100
B1-B4 200
C1, C3 200
C2, C4 225
Table 3.4 Minimum Airflow Clearance Requirements
Lifting
·
To determine a safe lifting method, check the weight of the unit, see 8.9 Power Ratings, Weight and Dimensions.
· Ensure that the lifting device is suitable for the task.
· If necessary, plan for a hoist, crane, or forklift with
the appropriate rating to move the unit.
· For lifting, use hoist rings on the unit, when
provided.
Mounting
1. Ensure that the strength of the mounting location supports the unit weight. The adjustable frequency drive allows side-by-side installation.
2. Mount the unit vertically on a solid flat surface or on the optional backplate.
3. Use the slotted mounting holes on the unit for wall mounting, when provided.
130BD528.10
33
MG11AJ22 – Rev. 2013-09-13
11
Mechanical Installation
VLT® HVAC Drive Instruction Manual
Mounting with backplate and railings
130BD504.10
33
Figure 3.5 Proper Mounting with Backplate
NOTICE!
Backplate is required when mounted on railings.
12
MG11AJ22 – Rev. 2013-09-13
Electrical Installation
VLT® HVAC Drive Instruction Manual
Electrical Installation
4.1 Safety Instructions
See 2 Safety for general safety instructions.
WARNING
INDUCED VOLTAGE!
Induced voltage from output motor cables that run together can charge
equipment capacitors even with the equipment turned off and locked out.
Failure to run output motor cables separately or use shielded cables or metal
conduits could result in death or serious injury.
CAUTION
DC CURRENT HAZARD!
A DC current in the protective grounding conductor can be caused by the
adjustable frequency drives. When a residual current-operated protective or
monitoring device (RCD/ RCM) is used for protection, only an RCD or RCM of
Type B is allowed.
NOTICE!
The adjustable frequency drive is supplied with Class 20 motor overload
protection.
Overcurrent Protection:
· Additional protective equipment such as short-
circuit protection or motor thermal protection between adjustable frequency
drive and motor is required for applications with multiple motors.
· Input fusing is required to provide short-circuit and
overcurrent protection. If not factory-supplied, fuses must be provided by the
installer. See maximum fuse ratings in 8.8 Fuse Specifications.
Wire Type and Ratings
· All wiring must comply with local and national
regulations regarding cross-section and ambient temperature requirements.
· Power connection wire recommendation: minimum
75 °C rated copper wire.
See 8.1 Electrical Data and 8.5 Cable Specifications for recommended wire
sizes and types.
4.2 EMC-compliant Installation
To obtain an EMC-compliant installation, follow the instructions provided in
4.3 Grounding, 4.4 Wiring Schematic, 4.6 Motor Connection and 4.8 Control
Wiring.
4.3 Grounding
WARNING
LEAKAGE CURRENT HAZARD!
Leakage currents are higher than 3.5 mA. It is the responsibility of the user
or certified electrical installer to ensure correct grounding of the
equipment. Failure to ground the adjustable frequency drive properly could
result in death or serious injury.
For electrical safety
· Ground the adjustable frequency drive properly in
accordance with applicable standards and directives.
· Use a dedicated ground wire for input power,
motor power and control wiring.
· Do not ground one adjustable frequency drive to
another in a “daisy chain” fashion.
· Keep the ground wire connections as short as
possible.
· Do not use pigtails. · Follow the motor manufacturer wiring
requirements.
· Minimum cable cross-section: 10 mm2 (or 2 rated
ground wires terminated separately).
For EMC-compliant installation
· Establish electrical contact between cable shield
and adjustable frequency drive enclosure by using metal cable connectors or by
using the clamps provided on the equipment.
· Use high-strand wire to reduce electrical
interference.
44
MG11AJ22 – Rev. 2013-09-13
13
Electrical Installation
VLT® HVAC Drive Instruction Manual
44
NOTICE!
POTENTIAL EQUALIZATION!
Electrical interference risks disturbing the entire installation, when the
ground potential between the adjustable frequency drive and the system is
different. To avoid electrical interference, install equalizing cables between
the system components. Recommended cable cross-section: 16 mm2.
4.4 Wiring Schematic
130BD552.11
3-phase power input
DC bus
+10 V DC 0/-10 V DC+10 V DC 0/4-20 mA 0/-10 V DC +10 V DC 0/4-20 mA
91 (L1) 92 (L2) 93 (L3) 95 PE 88 (-) 89 (+) 50 (+10 V OUT)
A53 53 (A IN)
A54 54 (A IN) 55 (COM A IN) 12 (+24 V OUT) 13 (+24 V OUT) 18 (D IN) 19 (D IN)
20 (COM D IN) 27 (D IN/OUT)
29 (D IN/OUT)
32 (D IN) 33 (D IN)
- 37 (D IN)
ON 12
ON ON 12 12
Switch Mode Power Supply 10 V DC 24 V DC 15 mA 130/200 mA
+- + –
(U) 96 (V) 97 (W) 98 (PE) 99
Motor
(R+) 82 (R-) 81
Brake resistor
ON=0/4-20 mA OFF=0/-10 V DC –
+10 V DC
P 5-00 24 V (NPN) 0 V (PNP) 24 V (NPN) 0 V (PNP)
24 V (NPN) 0 V (PNP)
24 V
0 V 24 V (NPN) 0 V (PNP)
24 V
0 V 24 V (NPN) 0 V (PNP) 24 V (NPN) 0 V (PNP)
relay1 03
02
01 relay2
06
05
04
(COM A OUT) 39 (A OUT) 42
S801
ON=Terminated OFF=Open
5V
240 V AC, 2 A
240 V AC, 2 A 400 V AC, 2 A
Analog Output 0/4-20 mA
S801
0 V
RS-485 Interface
(N RS-485) 69
(P RS-485) 68 **
(COM RS-485) 61
RS-485
: Chassis : Ground
Figure 4.1 Basic Wiring Schematic
A=Analog, D=Digital *Terminal 37 (optional) is used for Safe Torque Off. For Safe Torque Off installation instructions, refer to the Safe Torque Off Instruction Manual for Danfoss VLT® Adjustable Frequency Drives. **Do not connect cable shield.
14
MG11AJ22 – Rev. 2013-09-13
Electrical Installation
1
VLT® HVAC Drive Instruction Manual
2 6
3 4
5
9 10
L1 L2 L3 PE
8
Figure 4.2 EMC–compliant Electrical Connection
1
PLC
2
Adjustable frequency drive
3
Output contactor
4
Grounding rail (PE)
5
Cable insulation (stripped)
Table 4.1 Legend to Figure 4.2
U V W PE
7
6
Shielded cable
7
Motor, 3-phase and PE
8
Line power, 3-phase and reinforced PE
9
Control wiring
10
Equalizing min. 16 mm2 (0.025 in)
130BD529.10
44
MG11AJ22 – Rev. 2013-09-13
15
Electrical Installation
VLT® HVAC Drive Instruction Manual
130BT248.10 130BT334.10
44
NOTICE!
EMC INTERFERENCE!
Use separated shielded cables for input power, motor wiring and control
wiring, or run cables in three separate metallic conduits. Failure to isolate
power, motor and control wiring can result in unintended behavior or reduced
performance. Minimum 200 mm (7.9 in) clearance between control cables, motor
and line power.
4.5 Access
· Remove cover with a screwdriver (See Figure 4.3) or
by loosening attaching screws (See Figure 4.4).
Figure 4.3 Access to Wiring for IP20 and IP21 Enclosures
Figure 4.4 Access to Wiring for IP55 and IP66 Enclosures
See Table 4.2 before tightening the covers.
Enclosure
IP55
IP66
A4/A5
2
2
B1/B2
2.2
2.2
C1/C2
2.2
2.2
No screws to tighten for A2/A3/B3/B4/C3/C4.
Table 4.2 Tightening Torques for Covers [Nm]
4.6 Motor Connection
WARNING
INDUCED VOLTAGE!
Induced voltage from output motor cables that run together can charge
equipment capacitors even with the equipment turned off and locked out.
Failure to run output motor cables separately or use shielded cables or metal
conduits could result in death or serious injury.
· Comply with local and national electrical codes for
cable sizes. For maximum wire sizes, see 8.1 Electrical Data.
· Follow the motor manufacturer wiring
requirements.
· Motor wiring knockouts or access panels are
provided at the base of IP21 (NEMA1/12) and higher units.
16
MG11AJ22 – Rev. 2013-09-13
Electrical Installation
VLT® HVAC Drive Instruction Manual
· Do not wire a starting or pole-changing device (e.g.,
Dahlander motor or slip ring induction motor) between the adjustable frequency
drive and the motor.
Procedure
1. Strip a section of the outer cable insulation.
2. Position the stripped wire under the cable clamp to establish mechanical
fixation and electrical contact between cable shield and ground.
3. Connect ground wire to the nearest grounding terminal in accordance with
grounding instructions provided in 4.3 Grounding, see Figure 4.5.
4. Connect the 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W),
see Figure 4.5.
5. Tighten terminals in accordance with the information provided in 8.7
Connection Tightening Torques.
Figure 4.6, Figure 4.7, Figure 4.8 and Figure 4.9 represent line power input, motor, and grounding for basic adjustable frequency drives. Actual configurations vary with unit types and optional equipment.
M
91
L1 92
L2
A I N S
L3
93
+DC BR- B
99
U MVOTWOR
RELAY 1 RELAY 2
130BD577.10
44
130BD531.10
W V 98 U 97 96
Figure 4.6 Motor, Line Power and Ground Wiring for Enclosure Types A2 and A3
130BD513.10
W V 98 U 97 96
Figure 4.5 Motor Connection
Figure 4.7 Motor, Line Power and Ground Wiring for Enclosure Types A4 and A5
MG11AJ22 – Rev. 2013-09-13
17
Electrical Installation
VLT® HVAC Drive Instruction Manual
130BA390.11
44
91 92 L1 L2
95
88 89 81 8 DC- DC+ R- R+
93 L3
96 97
U
V
98 W
99
Figure 4.8 Motor, Line Power and Ground Wiring for Enclosure Types B and C Using Shielded Cable
91 92 L1 L2
95
88 89 91 9 DC+ DC- R- R+
93 L3
96 97
99
UV
W
99
130BB477.10
4.7 AC Line Input Connection
· Size wiring based upon the input current of the
adjustable frequency drive. For maximum wire sizes, see 8.1 Electrical Data.
· Comply with local and national electrical codes for
cable sizes.
Procedure
1. Connect 3-phase AC input power wiring to terminals L1, L2, and L3 (see
Figure 4.10).
2. Depending on the configuration of the equipment, input power will be
connected to the line power input terminals or the input disconnect.
3. Ground the cable in accordance with grounding instructions provided in 4.3
Grounding.
4. When supplied from an isolated line power source (IT line power or
floating delta) or TT/TN-S line power with a grounded leg (grounded delta),
ensure that 14-50 RFI 1 is set to OFF to avoid damage to the intermediate
circuit and to reduce ground capacity currents in accordance with IEC 61800-3.
130BT336.10
L 1 91
L 2 92
L 3 93
Figure 4.9 Motor, Line Power and Ground Wiring for Enclosure Types B and C Using Conduit
Figure 4.10 Connecting to AC Line Power
18
MG11AJ22 – Rev. 2013-09-13
Electrical Installation
VLT® HVAC Drive Instruction Manual
4.8 Control Wiring
· Isolate control wiring from high power components
in the adjustable frequency drive.
· When the adjustable frequency drive is connected
to a thermistor, ensure that the thermistor control wiring is shielded and
reinforced/double insulated. A 24 V DC supply voltage is recommended.
4.8.1 Control Terminal Types
Figure 4.11 shows the removable adjustable frequency drive connectors.
Terminal functions and default settings are summarized in Table 4.3.
130BB921.11
2 3 4
1
130BB931.10
Figure 4.11 Control Terminal Locations
1 12 13 18 19 27 29 32 33 20 37
2
3
61 68 69 39 42 50 53 54 55
Figure 4.12 Terminal Numbers
· Connector 1 provides four programmable digital
inputs terminals, two additional digital terminals programmable as either
input or output, a 24 V DC terminal supply voltage, and a common for optional
customer supplied 24 V DC voltage.
· Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communications connection
· Connector 3 provides two analog inputs, one
analog output, 10 V DC supply voltage, and commons for the inputs and output
· Connector 4 is a USB port available for use with the
MCT 10 Set-up Software
Terminal description
Terminal 12, 13
18 19 32 33 27 29 20 37 39 42
50
53 54
Default
Parameter Setting
Description
Digital Inputs/Outputs
–
+24 V DC
24 V DC supply voltage.
Maximum output
current is 200 mA total
for all 24 V loads. Usable
for digital inputs and
external transducers.
5-10 [8] Start
5-11 [0] No
operation
5-14 [0] No
Digital inputs.
operation
5-15 [0] No
operation
5-12 [2] Coast inverse
Selectable for digital input and output.
5-13 [14] JOG
Default setting is input.
–
Common for digital
inputs and 0 V potential
for 24 V supply.
–
Safe Torque Safe input (optional).
Off (STO)
Used for STO.
Analog Inputs/Outputs
–
Common for analog
output.
6-50 Speed 0 –
Programmable analog
High Limit output. The analog
signal is 020 mA or 4
20 mA at a maximum of
500 .
–
+10 V DC
10 V DC analog supply
voltage. 15 mA
maximum commonly
used for potentiometer
or thermistor.
6-1
Reference
Analog input. Selectable
6-2
Feedback
for voltage or current. Switches A53 and A54
select mA or V.
44
MG11AJ22 – Rev. 2013-09-13
19
Electrical Installation
VLT® HVAC Drive Instruction Manual
44
55 61
68 (+) 69 (-)
01, 02, 03 04, 05, 06
–
Common for analog
input.
Serial Communication
–
Integrated RC filter for
cable shield. ONLY for
connecting the shield
when experiencing EMC
problems.
8-3
RS-485 Interface. A
8-3
control card switch is
provided for termination
resistance.
Relays
5-40 [0] [9] Alarm
Form C relay output.
5-40 [1] [5] Running
Usable for AC or DC voltage and resistive or
inductive loads.
Table 4.3 Terminal Description
Additional terminals:
· 2 form C relay outputs. Location of the outputs
depends on adjustable frequency drive configuration.
· Terminals located on built-in optional equipment.
See the manual provided with the equipment option.
10 mm 130BD546.10
4.8.2 Wiring to Control Terminals
Control terminal connectors can be unplugged from the adjustable frequency
drive for ease of installation, as shown in Figure 4.11.
NOTICE!
Keep control wires as short as possible and separate from high power cables to
minimize interference.
1. Open the contact by inserting a small screwdriver into the slot above the
contact and push the screwdriver slightly upwards.
12 13 18 19 27 29 32 33
1
2
Figure 4.13 Connecting Control Wires
2. Insert the bared control wire into the contact.
3. Remove the screwdriver to fasten the control wire into the contact.
4. Ensure the contact is firmly established and not loose. Loose control
wiring can be the source of equipment faults or less than optimal operation.
See 8.5 Cable Specifications for control terminal wiring sizes and 6
Application Set-up Examples for typical control wiring connections.
20
MG11AJ22 – Rev. 2013-09-13
Electrical Installation
VLT® HVAC Drive Instruction Manual
4.8.3 Enabling Motor Operation (Terminal 27)
A jumper wire may be required between terminal 12 (or 13) and terminal 27 for
the adjustable frequency drive to operate when using factory default
programming values.
· Digital input terminal 27 is designed to receive an
24 V DC external interlock command. In many applications, the user wires an
external interlock device to terminal 27
· When no interlock device is used, wire a jumper
between control terminal 12 (recommended) or 13 to terminal 27. This provides
an internal 24 V signal on terminal 27.
· No signal present prevents the unit from operating. · When the status line
at the bottom of the LCP
reads AUTO REMOTE COAST, this indicates that the unit is ready to operate but
is missing an input signal on terminal 27.
· When factory installed optional equipment is wired
to terminal 27, do not remove that wiring
NOTICE!
The adjustable frequency drive cannot operate without a signal on terminal 27
unless terminal 27 is re-programmed.
4.8.4 Voltage/Current Input Selection (Switches)
NOTICE!
Remove power to the adjustable frequency drive before changing switch
positions.
1. Remove the local control panel (see Figure 4.14). 2. Remove any optional
equipment covering the
switches. 3. Set switches A53 and A54 to select the signal type.
U selects voltage, I selects current.
130BD530.10
NO
12
BUSTER. OFF-ON
A53 A54 U- I U- I
VLT
The analog input terminals 53 and 54 allow setting of input signal to voltage
(010 V) or current (0/420 mA).
Default parameter settings:
· Terminal 53: speed reference signal in open-loop
(see 16-61 Terminal 53 Switch Setting).
· Terminal 54: feedback signal in closed-loop (see
16-63 Terminal 54 Switch Setting).
Figure 4.14 Location of Terminals 53 and 54 Switches
4.8.5 Safe Torque Off (STO)
To run Safe Torque Off, additional wiring for the adjustable frequency drive
is required, refer to Safe Torque Off Instruction Manual for Danfoss VLT®
Adjustable Frequency Drives for further information.
44
MG11AJ22 – Rev. 2013-09-13
21
Electrical Installation
VLT® HVAC Drive Instruction Manual
44
4.8.6 RS-485 Serial Communication
Up to 32 nodes can be connected as a bus, or via drop cables from a common
trunk line to one network segment. Repeaters can divide network segments. Each
repeater functions as a node within the segment in which it is installed. Each
node connected within a given network must have a unique node address across
all segments.
· Connect RS-485 serial communication wiring to
terminals (+)68 and (-)69.
· Terminate each segment at both ends, using either
the termination switch (bus term on/off, see Figure 4.14) on the adjustable
frequency drives, or a biased termination resistor network.
· Connect a large surface of the shield to ground, for
example with a cable clamp or a conductive cable connector.
· Apply potential-equalizing cables to maintain the
same ground potential throughout the network.
· Use the same type of cable throughout the entire
network to prevent impedance mismatch.
Cable Impedance
Shielded twisted pair (STP) 120
Max. cable length 1200 (including drop lines)
[m]
500 station-to-station
Table 4.4 Cable Information
22
MG11AJ22 – Rev. 2013-09-13
Electrical Installation
VLT® HVAC Drive Instruction Manual
4.9 Installation Check List
Before completing installation of the unit, inspect the entire installation as detailed in Table 4.5. Check and mark the items when completed.
Inspect for
Description
Auxiliary equipment · Look for auxiliary equipment, switches, disconnects, or input fuses/circuit breakers that may reside on the
input power side of the adjustable frequency drive or output side to the motor. Ensure that they are ready for
full-speed operation
· Check function and installation of any sensors used for feedback to the adjustable frequency drive. · Remove any power factor correction caps on motor(s) · Adjust any power factor correction caps on the line power side and ensure that they are dampened
Cable routing
· Ensure that motor wiring and control wiring are separated or shielded or in
three separate metallic conduits
for high-frequency interference isolation
Control wiring
· Check for broken or damaged wires and loose connections.
· Check that control wiring is isolated from power and motor wiring for noise immunity.
· Check the voltage source of the signals, if necessary.
· The use of shielded cable or twisted pair is recommended. Ensure that the shield is terminated correctly.
Cooling clearance · Measure that top and bottom clearance is adequate to ensure proper air flow for cooling, see 3.3 Mounting
Ambient conditions · Check that requirements for ambient conditions are met
Fusing and circuit breakers
· Check for proper fusing or circuit breakers.
· Check that all fuses are inserted firmly and are in operational condition
and that all circuit breakers are in the
open position
Grounding
· Check for good ground connections that are tight and free of oxidation.
· Grounding to conduit or mounting the back panel to a metal surface is not a suitable grounding
Input and output power wiring
· Check for loose connections. · Check that motor and line power are in separate conduits or separated shielded cables.
Panel interior
· Make sure that the unit interior is free of dirt, metal chips, moisture, and corrosion. · Check that the unit is mounted on an unpainted, metal surface.
Switches
· Ensure that all switch and disconnect settings are in the proper positions.
Vibration
· Check that the unit is mounted solidly or that shock mounts are used, as necessary.
· Check for an unusual amount of vibration.
Table 4.5 Installation Check List
CAUTION
POTENTIAL HAZARD IN THE EVENT OF INTERNAL FAILURE!
Risk of personal injury when the adjustable frequency drive is not properly
closed. Before applying power, ensure all safety covers are in place and
securely fastened.
44
MG11AJ22 – Rev. 2013-09-13
23
Commissioning
5 Commissioning
VLT® HVAC Drive Instruction Manual
55
5.1 Safety Instructions
See 2 Safety for general safety instructions.
WARNING
HIGH VOLTAGE!
Adjustable frequency drives contain high voltage when connected to AC line
power. Installation, start-up, and maintenance must be performed by qualified
personnel only. Failure to perform installation, start-up, and maintenance by
qualified personnel could result in death or serious injury.
Before applying power: 1. Close cover properly.
2. Check that all cable connectors are firmly tightened.
3. Ensure that input power to the unit is OFF and locked out. Do not rely on
the adjustable frequency drive disconnect switches for input power isolation.
4. Verify that there is no voltage on input terminals L1 (91), L2 (92), and
L3 (93), phase-to-phase and phase-to-ground.
5. Verify that there is no voltage on output terminals 96 (U), 97 (V), and 98
(W), phase-to-phase and phase-to-ground.
6. Confirm continuity of the motor by measuring ohm values on U-V (96-97),
V-W (97-98), and W-U (98-96).
7. Check for proper grounding of the adjustable frequency drive as well as
the motor.
8. Inspect the adjustable frequency drive for loose connections on terminals.
9. Confirm that the supply voltage matches voltage of adjustable frequency
drive and motor.
5.2 Applying Power
WARNING
UNINTENDED START!
When the adjustable frequency drive is connected to AC line power, the motor
may start at any time. The adjustable frequency drive, motor, and any driven
equipment must be in operational readiness. Failure to be in operational
readiness when the adjustable frequency drive is connected to AC line power
could result in death, serious injury, equipment, or property damage.
1. Confirm that the input voltage is balanced within 3%. If not, correct
input voltage imbalance before proceeding. Repeat this procedure after the
voltage correction.
2. Ensure that optional equipment wiring (if present) matches the
installation application.
3. Ensure that all operator devices are in the OFF position. Panel doors must
be closed or cover mounted.
4. Apply power to the unit. DO NOT start the adjustable frequency drive at
this time. For units with a disconnect switch, turn to the ON position to
apply power to the adjustable frequency drive.
NOTICE!
If the status line at the bottom of the LCP reads AUTO REMOTE COASTING or
Alarm 60 External Interlock is displayed, this indicates that the unit is
ready to operate but is missing an input signal on terminal 27. See 4.8.3
Enabling Motor Operation (Terminal 27) for details.
24
MG11AJ22 – Rev. 2013-09-13
Commissioning
VLT® HVAC Drive Instruction Manual
5.3 Local Control Panel Operation
5.3.1 Local Control Panel
The local control panel (LCP) is the combined display and keypad on the front
of the unit.
The LCP has several user functions:
· Start, stop, and control speed when in local control · Display operational
data, status, warnings and
cautions
· Programming adjustable frequency drive functions · Manually reset the
adjustable frequency drive after
a fault when auto-reset is inactive
An optional numeric LCP (NLCP) is also available. The NLCP operates in a
manner similar to the LCP. See the Programming Guide for details on use of the
NLCP.
NOTICE!
For commissioning via PC, install MCT 10 Set-up Software. The software is
available for downloading at
www.danfoss.com/BusinessAreas/DrivesSolutions/softwaredownload (basic version)
or for ordering (advanced version, order number 130B1000).
5.3.2 LCP Layout
The LCP is divided into four functional groups (see Figure 5.1).
A. Display area B. Display menu keys C. Navigation keys and indicator lights
(LEDs) D. Operation keys and reset
Back 130BD512.10
1 Status
3 1(1)
0.0 %
0.00 A
0.00 kW
2
0.0Hz
A
5
2605 kWh
4
Off Remote Stop
6
9
B Status
Quick Menu
Main Menu
Alarm Log
7 8
Info Cancel
11
10
C
12
On
OK
15 Warn.
16
13
Alarm
17
D Hand on
Off
Auto on
Reset
14
18
19
20
21
Figure 5.1 Local Control Panel (LCP)
A. Display Area The display area is activated when the adjustable frequency
drive receives power from AC line voltage, a DC bus terminal, or an external
24 V DC supply.
The information displayed on the LCP can be customized for user application.
Select options in the Quick Menu Q3-13 Display Settings.
Display 1 2 3 4 5
Parameter number 0-20 0-21 0-22 0-23 0-24
Default setting Reference % Motor current Power [kW] Frequency kWh counter
Table 5.1 Legend to Figure 5.1, Display Area
B. Display Menu Keys Menu keys are used for menu access for parameter set-up, toggling through status display modes during normal operation, and viewing fault log data.
55
MG11AJ22 – Rev. 2013-09-13
25
Commissioning
VLT® HVAC Drive Instruction Manual
55
Key
Function
6 Status
Shows operational information.
7 Quick Menu Allows access to programming parameters
for initial set-up instructions and many
detailed application instructions.
8 Main Menu Allows access to all programming
parameters.
9 Alarm Log Displays a list of current warnings, the last
ten alarms, and the maintenance log.
Table 5.2 Legend to Figure 5.1, Display Menu Keys
C. Navigation Keys and Indicator Lights (LEDs) Navigation keys are used for programming functions and moving the display cursor. The navigation keys also provide speed control in local (hand) operation. There are also three adjustable frequency drive status indicator lights in this area.
Key
Function
10 Back
Reverts to the previous step or list in the
menu structure.
11 Cancel
Cancels the last change or command as long
as the display mode has not changed.
12 Info
Press for a definition of the function being
displayed.
13 Navigation Use the four navigation keys to move between
Keys
items in the menu.
14 OK
Use to access parameter groups or to enable a
choice.
Table 5.3 Legend to Figure 5.1, Navigation Keys
Indicator Light
15 ON
Green
16 WARN
Yellow
17 ALARM Red
Function The ON light activates when the adjustable frequency drive receives power from AC line voltage, a DC bus terminal, or an external 24 V supply. When warning conditions are met, the yellow WARN light comes on and text appears in the display area identifying the problem. A fault condition causes the red alarm light to flash and an alarm text is displayed.
Table 5.4 Legend to Figure 5.1, Indicator Lights (LEDs)
D. Operation Keys and Reset Operation keys are located at the bottom of the LCP.
Key 18 Hand On
19 Off 20 Auto On 21 Reset
Function Starts the adjustable frequency drive in local control.
· An external stop signal by control input or
serial communication overrides the local hand on
Stops the motor but does not remove power to the adjustable frequency drive.
Puts the system in remote operational mode.
· Responds to an external start command by
control terminals or serial communication
Resets the adjustable frequency drive manually after a fault has been cleared.
Table 5.5 Legend to Figure 5.1, Operation Keys and Reset
NOTICE!
The display contrast can be adjusted by pressing [Status] and []/[] keys.
5.3.3 Parameter Settings
Establishing the correct programming for applications often requires setting functions in several related parameters. Details for parameters are provided in 9.2 Parameter Menu Structure.
Programming data are stored internally in the adjustable frequency drive.
· For backup, upload data into the LCP memory · To download data to another
adjustable frequency
drive, connect the LCP to that unit and download the stored settings
· Restoring factory default settings does not change
data stored in the LCP memory
5.3.4 Uploading/Downloading Data to/from the LCP
1. Press [Off] to stop the motor before uploading or downloading data.
2. Go to [Main Menu] 0-50 LCP Copy and Press [OK].
3. Select All to LCP to upload data to LCP or select All from LCP to download
data from the LCP.
26
MG11AJ22 – Rev. 2013-09-13
Commissioning
VLT® HVAC Drive Instruction Manual
4. Press [OK]. A progress bar shows the uploading or downloading process.
5. Press [Hand On] or [Auto On] to return to normal operation.
5.3.5 Changing Parameter Settings
View Changes Quick Menu Q5 – Changes Made lists all parameters changed from
default settings.
· The list shows only parameters which have been
changed in the current edit set-up.
· Parameters which have been reset to default values
are not listed.
· The message ‘Empty’ indicates that no parameters
have been changed.
Changing Settings Parameter settings can be accessed and changed from the
[Quick Menu] or from the [Main Menu]. The [Quick Menu] only gives access to a
limited number of parameters.
1. Press [Quick Menu] or [Main Menu] on the LCP.
2. Press [] [] to browse through the parameter groups, press [OK] to select a
parameter group.
3. Press [] [] to browse through the parameters, press [OK] to select a
parameter.
4. Press [] [] to change the value of a parameter setting.
5. Press [] [] to shift digit when a decimal parameter is in the editing
state.
6. Press [OK] to accept the change.
7. Press either [Back] twice to enter “Status”, or press [Main Menu] once to
enter “Main Menu”.
5.3.6 Restoring Default Settings
NOTICE!
Initialization restores the unit to factory default settings. Any programming,
motor data, localization, and monitoring records will be lost. Uploading data
to the LCP provides a backup before initialization.
Restoring the adjustable frequency drive parameter settings back to default
values is done by initialization of the adjustable frequency drive.
Initialization can be carried out through 14-22 Operation Mode (recommended)
or manually.
· Initialization using 14-22 Operation Mode does not
reset adjustable frequency drive settings such as operating hours, serial
communication selections, personal menu settings, fault log, alarm log, and
other monitoring functions.
· Manual initialization erases all motor, programming,
localization, and monitoring data and restores factory default settings.
Recommended Initialization Procedure, via 14-22 Operation Mode
1. Press [Main Menu] twice to access parameters.
2. Scroll to 14-22 Operation Mode and press [OK].
3. Scroll to Initialization and press [OK].
4. Remove power to the unit and wait for the display to turn off.
5. Apply power to the unit.
Default parameter settings are restored during start-up. This may take
slightly longer than normal.
6. Alarm 80 is displayed.
7. Press [Reset] to return to operation mode.
Manual Initialization Procedure
1. Remove power to the unit and wait for the display to turn off.
2. Press and hold [Status], [Main Menu], and [OK] at the same time while
applying power to the unit (approximately 5 s or until audible click and fan
starts).
Factory default parameter settings are restored during startup. This may take
slightly longer than normal.
Manual initialization does not reset the following adjustable frequency drive
information
· 15-00 Operating hours · 15-03 Power-ups · 15-04 Over Temps · 15-05 Over
Volts
55
MG11AJ22 – Rev. 2013-09-13
27
130BP087.10
Commissioning
VLT® HVAC Drive Instruction Manual
55
5.4 Basic Programming 5.4.1 Commissioning with SmartStart
The SmartStart wizard enables fast configuration of basic motor and
application parameters.
· At first power-up or after initialization of the
adjustable frequency drive, SmartStart starts by itself.
· Follow on-screen instructions to complete commis-
sioning of the adjustable frequency drive. SmartStart can always be
reactivated by selecting Quick Menu Q4 – SmartStart.
· For commissioning without use of the SmartStart
wizard, refer to 5.4.2 Commissioning via [Main Menu] or the Programming Guide.
NOTICE!
Motor data are required for the SmartStart set-up. The required data are
normally available on the motor nameplate.
5.4.2 Commissioning via [Main Menu]
Recommended parameter settings are intended for start-up and checkout purposes. Application settings may vary.
Enter data with power ON, but before operating the adjustable frequency drive.
130BP066.10
1. Press [Main Menu] on the LCP.
2. Use the navigation keys to scroll to parameter group 0-**
Operation/Display and press [OK].
1107 RPM
3.84 A
1 (1)
Main Menu
0 – Operation/Display 1 – Load/Motor 2 – Brakes 3 – Reference / Ramps
Figure 5.2 Main Menu
3. Use navigation keys to scroll to parameter group 0-0* Basic Settings and press [OK].
0.0%
0.00A
Operation / Display
0-0 Basic Settings 0-1 Set-up Operations 0-2 LCP Display 0-3 LCP Custom Readout
1(1)
0-**
Figure 5.3 Operation/Display
4. Use navigation keys to scroll to 0-03 Regional Settings and press [OK].
0.0% Basic Settings
0.00A
0-03 Regional Settings
1(1) 0-0*
130BP088.10
[0] International
Figure 5.4 Basic Settings
5. Use navigation keys to select [0] International or [1] North America as
appropriate and press [OK]. (This changes the default settings for a number of
basic parameters).
6. Press [Main Menu] on the LCP. 7. Use the navigation keys to scroll to 0-01
Language. 8. Select language and press [OK]. 9. If a jumper wire is in place
between control
terminals 12 and 27, leave 5-12 Terminal 27 Digital Input at factory default.
Otherwise, No Operation should be selected in 5-12 Terminal 27 Digital Input.
For adjustable frequency drives with an optional bypass, no jumper wire is
required between control terminals 12 and 27. 10. 3-02 Minimum Reference 11.
3-03 Maximum Reference
28
MG11AJ22 – Rev. 2013-09-13
Commissioning
VLT® HVAC Drive Instruction Manual
12. 3-41 Ramp 1 Ramp-up Time 13. 3-42 Ramp 1 Ramp-down Time 14. 3-13
Reference Site. Linked to Hand/Auto Local
Remote.
5.4.3 Asynchronous Motor Set-up
Enter the motor data in parameters 1-20 or 1-21 to 1-25. The information can
be found on the motor nameplate.
1. 1-20 Motor Power [kW] or 1-21 Motor Power [HP] 2. 1-22 Motor Voltage 3.
1-23 Motor Frequency 4. 1-24 Motor Current 5. 1-25 Motor Nominal Speed
5.4.4 Permanent Magnet Motor Set-up
NOTICE!
Only use permanent magnet (PM) motor with fans and pumps.
Initial Programming Steps 1. Activate PM motor operation 1-10 Motor
Construction, select [1] PM, non salient SPM 2. Set 0-02 Motor Speed Unit to
[0] RPM
Programming motor data After selecting PM motor in 1-10 Motor Construction,
the PM motor-related parameters in parameter groups 1-2 Motor Data, 1-3
Addl. Motor Data and 1-4* are active. The necessary data can be found on the
motor nameplate and in the motor data sheet. Program the following parameters
in the listed order
1. 1-24 Motor Current 2. 1-26 Motor Cont. Rated Torque 3. 1-25 Motor Nominal
Speed 4. 1-39 Motor Poles
5. 1-30 Stator Resistance (Rs) Enter line to common stator winding resistance
(Rs). If only line-line data are available, divide the lineline value by 2 to
achieve the line to common (starpoint) value. It is also possible to measure
the value with an ohmmeter, which will also take the resistance of the cable
into account. Divide the measured value by 2 and enter the result.
6. 1-37 d-axis Inductance (Ld) Enter line to common direct axis inductance of
the PM motor. If only line-line data are available, divide the lineline value
by 2 to achieve the line-common (starpoint) value. It is also possible to
measure the value with an inductance meter, which will also take the
inductance of the cable into account. Divide the measured value by 2 and enter
the result.
7. 1-40 Back EMF at 1000 RPM Enter line-to-line back EMF of PM Motor at 1000
RPM mechanical speed (RMS value). Back EMF is the voltage generated by a PM
motor when no drive is connected and the shaft is turned externally. Back EMF
is normally specified for nominal motor speed or for 1000 RPM measured between
two lines. If the value is not available for a motor speed of 1000 RPM,
calculate the correct value as follows: If back EMF is, e.g., 320 V at 1800
RPM, it can be calculated at 1000 RPM as follows: Back EMF = (Voltage /
RPM)1000 = (320/1800)1000 = 178. This is the value that must be programmed
for 1-40 Back EMF at 1000 RPM.
Test Motor Operation
1. Start the motor at low speed (100 to 200 RPM). If the motor does not turn,
check installation, general programming and motor data.
2. Check if start function in 1-70 PM Start Mode fits the application
requirements.
Rotor detection This function is the recommended choice for applications where
the motor starts from standstill, e.g., pumps or conveyors. On some motors, an
acoustic sound is heard when the impulse is sent out. This does not harm the
motor.
55
MG11AJ22 – Rev. 2013-09-13
29
Commissioning
VLT® HVAC Drive Instruction Manual
55
Parking This function is the recommended choice for applications where the
motor is rotating at slow speed, e.g., windmilling in fan applications. 2-06
Parking Current and 2-07 Parking Time can be adjusted. Increase the factory
setting of these parameters for applications with high inertia.
Start the motor at nominal speed. If the application does not run well, check
the VVCplus PM settings. Recommendations in different applications can be seen
in Table 5.6.
Application Low inertia applications ILoad/IMotor <5
Low inertia applications 50>ILoad/IMotor >5 High inertia applications
ILoad/IMotor > 50
High load at low speed <30% (rated speed)
Settings 1-17 Voltage filter time const. to be increased by factor 5 to 10
1-14 Damping Gain should be reduced 1-66 Min. Current at Low Speed should be
reduced (<100%) Keep calculated values
1-14 Damping Gain, 1-15 Low Speed Filter Time Const. and 1-16 High Speed
Filter Time Const. should be increased 1-17 Voltage filter time const. should
be increased 1-66 Min. Current at Low Speed should be increased (>100% for a
prolonged time can overheat the motor)
Table 5.6 Recommendations for Different Applications
If the motor starts oscillating at a certain speed, increase 1-14 Damping Gain. Increase the value in small steps. Depending on the motor, a good value for this parameter can be 10% or 100% higher than the default value.
Starting torque can be adjusted in 1-66 Min. Current at Low Speed. 100% provides nominal torque as starting torque.
5.4.5 Automatic Energy Optimization (AEO)
NOTICE!
AEO is not relevant for permanent magnet motors.
Automatic Energy Optimization (AEO) is recommended for
· Automatic compensation for oversized motors · Automatic compensation for
slow system load
change
· Automatic compensation for seasonal changes · Automatic compensation for low
motor loading · Reduced energy consumption · Reduced motor heating · Reduced
motor noise
To activate AEO, set parameter 1-03 Torque Characteristics to [2] Auto Energy
Optim. CT or [3] Auto Energy Optim. VT.
5.4.6 Automatic Motor Adaptation (AMA)
NOTICE!
AMA is not relevant for permanent magnet motors.
Automatic motor adaptation (AMA) is a procedure that optimizes compatibility
between the adjustable frequency drive and the motor.
· The adjustable frequency drive builds a
mathematical model of the motor for regulating output motor current. The
procedure also tests the input phase balance of electrical power. It compares
the motor characteristics with the data entered in parameters 1-20 to 1-25
· The motor shaft does not turn and no harm is done
to the motor while running the AMA.
· Some motors may be unable to run the complete
version of the test. In that case, select [2] Enable reduced AMA.
· If an output filter is connected to the motor, select
Enable reduced AMA.
· If warnings or alarms occur, see 7.3 List of Warnings
and Alarms.
· Run this procedure on a cold motor for best results.
30
MG11AJ22 – Rev. 2013-09-13
Commissioning
VLT® HVAC Drive Instruction Manual
To run AMA 1. Press [Main Menu] to access parameters. 2. Scroll to parameter
group 1-* Load and Motor and press [OK]. 3. Scroll to parameter group 1-2
Motor Data and press [OK]. 4. Scroll to 1-29 Automatic Motor Adaptation (AMA)
and press [OK]. 5. Select [1] Enable complete AMA and press [OK]. 6. Follow
the on-screen instructions. 7. The test will run automatically and indicate
when it is complete.
5.5 Checking Motor Rotation
WARNING
MOTOR START!
Ensure that the motor, system, and any attached equipment are ready for start.
It is the responsibility of the user to ensure safe operation under any
condition. Failure to ensure that the motor, system, and any attached
equipment are ready for start could result in personal injury or equipment
damage.
NOTICE!
Risk of damage to pumps/compressors caused by motor running in wrong
direction. Before running the adjustable frequency drive, check the motor
rotation.
The motor will run briefly at 5 Hz or the minimum frequency set in 4-12 Motor
Speed Low Limit [Hz].
1. Press [Main Menu]. 2. Scroll to 1-28 Motor Rotation Check and press [OK].
3. Scroll to [1] Enable. The following text will appear: Note! Motor may run
in wrong direction. 4. Press [OK]. 5. Follow the on-screen instructions.
NOTICE!
To change the direction of rotation, remove power to the adjustable frequency
drive and wait for power to discharge. Reverse the connection of any two of
the three motor wires on the motor or adjustable frequency drive side of the
connection.
5.6 Local Control Test
WARNING
MOTOR START!
Ensure that the motor, system and any attached equipment are ready for start.
It is the responsibility of the user to ensure safe operation under any
condition. Failure to ensure that the motor, system, and any attached
equipment are ready for start could result in personal injury or equipment
damage.
1. Press [Hand On] to provide a local start command to the adjustable
frequency drive.
2. Accelerate the adjustable frequency drive by pressing [] to full speed.
Moving the cursor left of the decimal point provides quicker input changes.
3. Note any acceleration problems.
4. Press [Off]. Note any deceleration problems.
In the event of acceleration or deceleration problems, see 7.4
Troubleshooting. See 7.3 List of Warnings and Alarms for resetting the
adjustable frequency drive after a trip.
55
MG11AJ22 – Rev. 2013-09-13
31
Commissioning
VLT® HVAC Drive Instruction Manual
55
5.7 System Start-up
The procedure in this section requires user-wiring and application programming
to be completed. The following procedure is recommended after application set-
up is completed.
WARNING
MOTOR START!
Ensure that the motor, system, and any attached equipment are ready for start.
It is the responsibility of the user to ensure safe operation under any
condition. Failure to ensure that the motor, system, and any attached
equipment are ready for start could result in personal injury or equipment
damage.
1. Press [Auto On].
2. Apply an external run command.
3. Adjust the speed reference throughout the speed range.
4. Remove the external run command.
5. Check sound and vibration level of the motor to ensure that the system is
working as intended.
If warnings or alarms occur, see 7.3 List of Warnings and Alarms.
5.8 Maintenance
Under normal operating conditions and load profiles, the adjustable frequency
drive is maintenance-free throughout its designed lifetime. To prevent
breakdown, danger, and damage, examine the adjustable frequency drive at
regular intervals depending on the operating conditions. Replace worn or
damaged parts with original spare parts or standard parts. For service and
support, refer to www.danfoss.com/ contact/sales_and_services/.
CAUTION
Risk of personal injury or equipment damage exists. Repair and service must be
carried out by Danfoss authorized personnel only.
32
MG11AJ22 – Rev. 2013-09-13
Application Set-up Examples
VLT® HVAC Drive Instruction Manual
Application Set-up Examples
The examples in this section are intended as a quick reference for common
applications.
· Parameter settings are the regional default values
unless otherwise indicated (selected in 0-03 Regional Settings).
· Parameters associated with the terminals and their
settings are shown next to the drawings.
· Where switch settings for analog terminals A53 or
A54 are required, these are also shown.
NOTICE!
When the optional Safe Torque Off feature is used, a jumper wire may be
required between terminal 12 (or 13) and terminal 37 for the adjustable
frequency drive to operate when using factory default programming values.
6.1 Application Examples 6.1.1 Speed
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U – I
Parameters
Function
Setting
130BB926.10
- -10 – +10V
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53 10 V*
High Voltage
6-14 Terminal 53 0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53 1500 RPM
High Ref./Feedb.
Value
- = Default Value
Notes/comments:
D IN 37 is an option.
A53
Table 6.1 Analog Speed Reference (Voltage)
66
MG11AJ22 – Rev. 2013-09-13
33
Application Set-up Examples
VLT® HVAC Drive Instruction Manual
66
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
U – I
Parameters
Function
Setting
6-12 Terminal 53 4 mA*
Low Current
6-13 Terminal 53 20 mA*
High Current
6-14 Terminal 53 0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53 1500 RPM
High Ref./Feedb.
Value
- = Default Value
Notes/comments:
–
D IN 37 is an option.
4 – 20mA
A53
Table 6.2 Analog Speed Reference (Current)
130BB927.10 130BB683.10
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT 42
COM
39
Parameters
Function
Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53 10 V*
High Voltage
6-14 Terminal 53 0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53 1500 RPM
High Ref./Feedb.
Value
5k * = Default Value
Notes/comments:
D IN 37 is an option.
U – I
A53 Table 6.3 Speed Reference (using a Manual Potentiometer)
34
MG11AJ22 – Rev. 2013-09-13
130BB804.10 130BB802.10
Application Set-up Examples
VLT® HVAC Drive Instruction Manual
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Parameters
Function
Setting
5-10 Terminal 18 [8] Start*
Digital Input
5-12 Terminal 27 [19] Freeze
Digital Input
Reference
5-13 Terminal 29 [21] Speed Up
Digital Input
5-14 Terminal 32 [22] Slow
Digital Input
- = Default Value
Notes/comments:
D IN 37 is an option.
6.1.2 Start/Stop
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Parameters
Function
Setting
5-10 Terminal 18 [8] Start*
Digital Input
5-12 Terminal 27 [0] No
Digital Input
operation
5-19 Terminal 37 [1] Safe Stop
Safe Stop
Alarm
- = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input is
set to [0] No operation, a jumper
wire to terminal 27 is not
needed.
D IN 37 is an option.
66
Table 6.4 Speed Up/Slow
Table 6.5 Start/Stop Command with Safe Stop Option
Speed
130BB840.10 130BB805.11
Speed R efe rence
Start ( 18) Freeze ref (27) Speed up ( 29 ) Speed down ( 32 )
Figure 6.1 Speed Up/Slow
Start (18)
Figure 6.2 Start/Stop Command with Safe Stop
MG11AJ22 – Rev. 2013-09-13
35
Application Set-up Examples
VLT® HVAC Drive Instruction Manual
130BB803.10 130BB934.10
66
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Parameters
Function
Setting
5-10 Terminal 18 [9] Latched
Digital Input
Start
5-12 Terminal 27 [6] Stop
Digital Input
Inverse
- = Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input is
set to [0] No operation, a jumper
wire to terminal 27 is not
needed.
D IN 37 is an option.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.6 Pulse Start/Stop
Speed
Parameters
Function
Setting
5-10 Terminal 18 Digital Input
5-11 Terminal 19 Digital Input
[8] Start
[10] Reverse*
5-12 Terminal 27 [0] No
Digital Input
operation
5-14 Terminal 32 [16] Preset
Digital Input
ref bit 0
5-15 Terminal 33 [17] Preset
Digital Input
ref bit 1
3-10 Preset
Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
- = Default Value
Notes/comments:
D IN 37 is an option.
130BB806.10
Table 6.7 Start/Stop with Reversing and Four Preset Speeds
Latched Start (18) Stop Inverse (27)
Figure 6.3 Latched Start/Stop Inverse
36
MG11AJ22 – Rev. 2013-09-13
Application Set-up Examples
VLT® HVAC Drive Instruction Manual
130BB928.10 130BB685.10
6.1.3 External Alarm Reset
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
Parameters
Function
Setting
5-11 Terminal 19 [1] Reset Digital Input * = Default Value Notes/comments: D IN 37 is an option.
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 6.8 External Alarm Reset
6.1.4 RS-485
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT 42
COM
39
Parameters
Function
Setting
8-30 Protocol
FC*
8-31 Address
1*
8-32 Baud Rate 9600*
- = Default Value
Notes/comments: Select protocol, address and baud rate in the abovementioned parameters. D IN 37 is an option.
R1
01 02 03
R2
04
05
06
RS-485
61 +
68
69 –
Table 6.9 RS-485 Network Connection
66
MG11AJ22 – Rev. 2013-09-13
37
Application Set-up Examples
VLT® HVAC Drive Instruction Manual
66
6.1.5 Motor Thermistor
CAUTION
Use only thermistors with reinforced or double insulation to meet PELV
insulation requirements.
VLT
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
130BB686.12
Parameters
Function
Setting
1-90 Motor
[2] Thermistor
Thermal
trip
Protection
1-93 Thermistor [1] Analog
Source
input 53
- = Default Value
Notes/comments: If only a warning is desired, 1-90 Motor Thermal Protection should be set to [1] Thermistor warning. D IN 37 is an option.
U – I
A53
Table 6.10 Motor Thermistor
38
MG11AJ22 – Rev. 2013-09-13
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
Diagnostics and Troubleshooting
This chapter describes the status messages, warnings and alarms and basic
troubleshooting.
7.1 Status Messages
When the adjustable frequency drive is in status mode, status messages are
generated automatically and appear in the bottom line of the display (see
Figure 7.1).
Status 799RPM
7.83A 0.000 53.2%
1(1) 36.4kW
130BB037.11
Auto Remote Hand Local Off
1
2
Figure 7.1 Status Display
Ramping Stop Running Jogging . . . Stand by
3
1 Operation Mode (see Table 7.2) 2 Reference Site (see Table 7.3) 3 Operation
Status (see Table 7.4)
Table 7.1 Legend to Figure 7.1
Table 7.2 to Table 7.4 describe the displayed status messages.
Off Auto On
The adjustable frequency drive does not react to any control signal until [Auto On] or [Hand On] is pressed. The adjustable frequency drive is controlled from the control terminals and/or the serial communication. The adjustable frequency drive can be controlled by the navigation keys on the LCP. Stop commands, reset, reversing, DC brake, and other signals applied to the control terminals can override local control.
Table 7.2 Operation Mode
Remote Local
The speed reference is given from external signals, serial communication, or internal preset references. The adjustable frequency drive uses [Hand On] control or reference values from the LCP.
Table 7.3 Reference Site
AC Brake
AMA finish OK AMA ready AMA running Braking Braking max.
Coast
AC Brake was selected in 2-10 Brake Function. The AC brake overmagnetizes the
motor to achieve a controlled slow-down. Automatic motor adaptation (AMA) was
carried out successfully. AMA is ready to start. Press [Hand On] to start. AMA
process is in progress. The brake chopper is in operation. Generative energy
is absorbed by the brake resistor. The brake chopper is in operation. The
power limit for the brake resistor defined in 2-12 Brake Power Limit (kW) has
been reached.
· Coast inverse was selected as a function for
a digital input (parameter group 5-1* Digital Inputs). The corresponding
terminal is not connected.
· Coast activated by serial communication
Ctrl. Ramp-down
Control Ramp-down was selected in 14-10 Mains
Failure.
· The AC line voltage is below the value set in
14-11 Mains Voltage at Mains Fault at line
power fault
· The adjustable frequency drive ramps down
the motor using a controlled ramp-down.
Current High Current Low DC Hold
The adjustable frequency drive output current is above the limit set in 4-51 Warning Current High. The adjustable frequency drive output current is below the limit set in 4-52 Warning Speed Low. DC Hold is selected in 1-80 Function at Stop and a stop command is active. The motor is held by a DC current set in 2-00 DC Hold/Preheat Current.
77
MG11AJ22 – Rev. 2013-09-13
39
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
77
DC Stop
Feedback high Feedback low Freeze output
The motor is held with a DC current (2-01 DC Brake Current) for a specified
time (2-02 DC Braking Time).
· DC Brake is activated in 2-03 DC Brake Cut-in
Speed [RPM] and a stop command is active.
· DC Brake (inverse) is selected as a function
for a digital input (parameter group 5-1 Digital Inputs). The corresponding
terminal is not active.
· The DC Brake is activated via serial
communication.
The sum of all active feedbacks is above the feedback limit set in 4-57
Warning Feedback High. The sum of all active feedbacks is below the feedback
limit set in 4-56 Warning Feedback Low. The remote reference is active, which
holds the present speed.
· Freeze output was selected as a function for
a digital input (parameter group 5-1 Digital Inputs). The corresponding
terminal is active. Speed control is only possible via the terminal functions
Speed Up and Slow.
· Hold ramp is activated via serial communi-
cation.
Freeze output request Freeze ref.
Jog request
A freeze output command has been given, but the motor will remain stopped until a run permissive signal is received. Freeze Reference was chosen as a function for a digital input (parameter group 5-1* Digital Inputs). The corresponding terminal is active. The adjustable frequency drive saves the actual reference. Changing the reference is now only possible via terminal functions Speed Up and Slow. A jog command has been given, but the motor remains stopped until a run permissive signal is received via a digital input.
Jogging
Motor check OVC control PowerUnit Off Protection md
The motor is running as programmed in 3-19 Jog Speed [RPM].
· Jog was selected as function for a digital
input (parameter group 5-1* Digital Inputs). The corresponding terminal (e.g.,
Terminal 29) is active.
· The Jog function is activated via the serial
communication.
· The Jog function was selected as a reaction
for a monitoring function (e.g., No signal). The monitoring function is
active.
In 1-80 Function at Stop, Motor Check was selected. A stop command is active.
To ensure that a motor is connected to the adjustable frequency drive, a
permanent test current is applied to the motor. Overvoltage control was
activated in 2-17 Overvoltage Control, [2] Enabled. The connected motor is
supplying the adjustable frequency drive with generative energy. The
overvoltage control adjusts the V/Hz ratio to run the motor in controlled mode
and to prevent the adjustable frequency drive from tripping. (Only adjustable
frequency drives with an external 24 V power supply installed). Line power
supply to the adjustable frequency drive is removed, but the control card is
supplied by the external 24 V. Protection mode is active. The unit has
detected a critical status (an overcurrent or overvoltage).
· To avoid tripping, switching frequency is
reduced to 4 kHz.
· If possible, Protection mode ends after
approximately 10 s.
· Protection mode can be restricted in
14-26 Trip Delay at Inverter Fault.
QStop
The motor is decelerating using 3-81 Quick Stop Ramp Time.
· Quick stop inverse was chosen as a function
for a digital input (parameter group 5-1* Digital Inputs). The corresponding
terminal is not active.
· The quick stop function was activated via
serial communication.
40
MG11AJ22 – Rev. 2013-09-13
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
Ramping Ref. high Ref. low Run on ref. Run request Running Sleep Mode Speed
high Speed low Standby Start delay Start fwd/rev
Stop Trip
The motor is accelerating/decelerating using the active Ramp-Up/Down. The reference, a limit value, or a standstill is not yet reached. The sum of all active references is above the reference limit set in 4-55 Warning Reference High. The sum of all active references is below the reference limit set in 4-54 Warning Reference Low. The adjustable frequency drive is running in the reference range. The feedback value matches the setpoint value. A start command has been given, but the motor is stopped until a run permissive signal is received via digital input. The motor is driven by the adjustable frequency drive. The energy-saving function is enabled. This means that at present the motor has stopped but it will restart automatically when required. Motor speed is above the value set in 4-53 Warning Speed High. Motor speed is below the value set in 4-52 Warning Speed Low. In Auto On mode, the adjustable frequency drive will start the motor with a start signal from a digital input or serial communication. In 1-71 Start Delay, a delay starting time was set. A start command is activated and the motor will start after the start delay time expires. Start forward and start reverse were selected as functions for two different digital inputs (parameter group 5-1* Digital Inputs). The motor will start in forward or reverse depending on which corresponding terminal is activated. The adjustable frequency drive has received a stop command from the LCP, digital input or serial communication. An alarm occurred and the motor is stopped. Once the cause of the alarm is cleared, the adjustable frequency drive can be reset manually by pressing [Reset] or remotely by control terminals or serial communication.
Trip lock
An alarm occurred and the motor is stopped. Once the cause of the alarm is cleared, power must be cycled to the adjustable frequency drive. The adjustable frequency drive can then be reset manually by pressing [Reset] or remotely by control terminals or serial communication.
Table 7.4 Operation Status
NOTICE!
In auto/remote mode, the adjustable frequency drive requires external commands
to execute functions.
7.2 Warning and Alarm Types
Warnings A warning is issued when an alarm condition is impending or when an
abnormal operating condition is present and may result in the adjustable
frequency drive issuing an alarm. A warning clears by itself when the abnormal
condition is removed.
Alarms Trip An alarm is issued when the adjustable frequency drive is tripped,
which means that the adjustable frequency drive suspends operation to prevent
adjustable frequency drive or system damage. The motor will coast to a stop.
The adjustable frequency drive logic will continue to operate and monitor the
adjustable frequency drive status. After the fault condition is remedied, the
adjustable frequency drive can be reset. It will then be ready to start
operation again.
Resetting the adjustable frequency drive after trip/trip lock A trip can be
reset in any of four ways:
· Press [Reset] on the LCP · Digital reset input command · Serial
communication reset input command · Auto reset
Trip lock Input power is cycled. The motor coasts to a stop. The adjustable
frequency drive continues to monitor the adjustable frequency drive status.
Remove input power to the adjustable frequency drive, correct the cause of the
fault, and reset the adjustable frequency drive.
77
MG11AJ22 – Rev. 2013-09-13
41
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
Warning and Alarm Displays
· A warning is displayed in the LCP along with the
warning number.
· An alarm flashes along with the alarm number.
Status 0.0Hz
0.000kW 0.0Hz 0
1(1) 0.00A
Earth Fault [A14] Auto Remote Trip
Figure 7.2 Alarm Display Example
77
In addition to the text and alarm code on the LCP of the adjustable frequency drive, there are three status indicator lights.
Back
Info Cancel
On Warn. Alarm
Hand on
OK
Auto
Off
on
Reset
Figure 7.3 Status Indicator Lights
Warning Alarm Trip Lock
Warning LED On Off On
Alarm LED Off On (Flashing) On (Flashing)
Table 7.5 Status Indicator Lights Explanations
130BB467.10
130BP086.11
7.3 List of Warnings and Alarms
The warning/alarm information below defines each warning/ alarm condition,
provides the probable cause for the condition, and details a remedy or
troubleshooting procedure.
WARNING 1, 10 Volts low The control card voltage is below 10 V from terminal
50. Remove some of the load from terminal 50, as the 10 V supply is
overloaded. Max. 15 mA or minimum 590 .
A short circuit in a connected potentiometer or improper wiring of the
potentiometer can cause this condition.
Troubleshooting Remove the wiring from terminal 50. If the warning clears, the
problem is with the wiring. If the warning does not clear, replace the control
card.
WARNING/ALARM 2, Live zero error This warning or alarm only appears if
programmed in 6-01 Live Zero Timeout Function. The signal on one of the analog
inputs is less than 50% of the minimum value programmed for that input. Broken
wiring or faulty device sending the signal can cause this condition.
Troubleshooting Check connections on all the analog input terminals. Control
card terminals 53 and 54 for signals, terminal 55 common. MCB 101 terminals 11
and 12 for signals, terminal 10 common. MCB 109 terminals 1, 3, 5 for signals,
terminals 2, 4, 6 common).
Check that the frequency converter programming and switch settings match the
analog signal type.
Perform Input Terminal Signal Test.
WARNING/ALARM 4, Mains phase loss A phase is missing on the supply side, or
the line voltage imbalance is too high. This message also appears for a fault
in the input rectifier on the adjustable frequency drive. Options are
programmed at 14-12 Function at Mains Imbalance.
Troubleshooting Check the supply voltage and supply currents to the adjustable
frequency drive.
42
MG11AJ22 – Rev. 2013-09-13
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
WARNING 5, DC link voltage high The intermediate circuit voltage (DC) is
higher than the highvoltage warning limit. The limit is dependent on the
frequency converter voltage rating. The unit is still active.
WARNING 6, DC link voltage low The intermediate circuit voltage (DC) is lower
than the lowvoltage warning limit. The limit is dependent on the frequency
converter voltage rating. The unit is still active.
WARNING/ALARM 7, DC overvoltage If the intermediate circuit voltage exceeds
the limit, the adjustable frequency drive trips after a time.
Troubleshooting Connect a brake resistor
Extend the ramp time
Change the ramp type
Activate the functions in 2-10 Brake Function
Increase 14-26 Trip Delay at Inverter Fault
If the alarm/warning occurs during a power sag, use kinetic backup (14-10 Line
Failure)
WARNING/ALARM 8, DC under voltage If the intermediate circuit voltage (DC
link) drops below the under voltage limit, the frequency converter checks if a
24 V DC back-up supply is connected. If no 24 V DC back-up supply is
connected, the frequency converter trips after a fixed time delay. The time
delay varies with unit size.
Troubleshooting Check that the supply voltage matches the frequency converter
voltage.
Perform input voltage test.
Perform soft charge circuit test.
WARNING/ALARM 9, Inverter overload The frequency converter is about to cut out
because of an overload (too high current for too long). The counter for
electronic, thermal inverter protection issues a warning at 98% and trips at
100%, while giving an alarm. The frequency converter cannot be reset until the
counter is below 90%. The fault is that the frequency converter has run with
more than 100% overload for too long.
Troubleshooting Compare the output current shown on the LCP with the frequency
converter rated current.
Compare the output current shown on the LCP with measured motor current.
Display the Thermal Drive Load on the LCP and monitor the value. When running
above the frequency converter continuous current rating, the counter
increases. When running below the frequency converter continuous current
rating, the counter decreases.
WARNING/ALARM 10, Motor overload temperature According to the electronic
thermal protection (ETR), the motor is too hot. Select whether the adjustable
frequency drive issues a warning or an alarm when the counter reaches 100% in
1-90 Motor Thermal Protection. The fault occurs when the motor runs with more
than 100% overload for too long.
Troubleshooting Check for motor overheating.
Check if the motor is mechanically overloaded
Check that the motor current set in 1-24 Motor Current is correct.
Ensure that Motor data in parameters 1-20 to 1-25 are set correctly.
If an external fan is in use, check in 1-91 Motor External Fan that it is
selected.
Running AMA in 1-29 Automatic Motor Adaptation (AMA) tunes the adjustable
frequency drive to the motor more accurately and reduces thermal loading.
WARNING/ALARM 11, Motor thermistor over temp Check whether the thermistor is
disconnected. Select whether the frequency converter issues a warning or an
alarm in 1-90 Motor Thermal Protection.
Troubleshooting Check for motor overheating.
Check if the motor is mechanically overloaded.
When using terminal 53 or 54, check that the thermistor is connected correctly
between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V
supply). Also check that the terminal switch for 53 or 54 is set for voltage.
Check 1-93 Thermistor Source selects terminal 53 or 54.
When using digital inputs 18 or 19, check that the thermistor is connected
correctly between either terminal 18 or 19 (digital input PNP only) and
terminal 50. Check 1-93 Thermistor Source selects terminal 18 or 19.
77
MG11AJ22 – Rev. 2013-09-13
43
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
77
WARNING/ALARM 12, Torque limit The torque has exceeded the value in 4-16
Torque Limit Motor Mode or the value in 4-17 Torque Limit Generator Mode.
14-25 Trip Delay at Torque Limit can change this warning from a warning-only
condition to a warning followed by an alarm.
Troubleshooting If the motor torque limit is exceeded during rampup, extend
the ramp-up time.
If the generator torque limit is exceeded during ramp-down, extend the ramp-
down time.
If torque limit occurs while running, possibly increase the torque limit. Make
sure that the system can operate safely at a higher torque.
Check the application for excessive current draw on the motor.
WARNING/ALARM 13, Over current The inverter peak current limit (approximately
200% of the rated current) is exceeded. The warning lasts about 1.5 s, then
the adjustable frequency drive trips and issues an alarm. Shock loading or
quick acceleration with high inertia loads can cause this fault. It can also
appear after kinetic backup if the acceleration during ramp-up is quick. If
extended mechanical brake control is selected, trip can be reset externally.
Troubleshooting Remove power and check if the motor shaft can be turned.
Make sure that the motor size matches the adjustable frequency drive.
Check parameters 1-20 to 1-25 for correct motor data.
ALARM 14, Earth (ground) fault There is current from the output phases to
ground, either in the cable between the adjustable frequency drive and the
motor or in the motor itself.
Troubleshooting Remove power to the adjustable frequency drive and repair the
ground fault.
Check for ground faults in the motor by measuring the resistance to ground of
the motor leads and the motor with a megohmmeter.
ALARM 15, Hardware mismatch A fitted option is not operational with the
present control board hardware or software.
Record the value of the following parameters and contact your Danfoss
supplier:
15-40 FC Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-45 Actual Typecode String
15-49 SW ID Control Card
15-50 SW ID Power Card
15-60 Option Mounted
15-61 Option SW Version (for each option slot)
ALARM 16, Short circuit There is short-circuiting in the motor or motor
wiring.
Remove power to the adjustable frequency drive and repair the short circuit.
WARNING/ALARM 17, Control word timeout There is no communication to the
frequency converter. The warning is only active when 8-04 Control Word Timeout
Function is NOT set to [0] Off. If 8-04 Control Word Timeout Function is set
to [5] Stop and Trip, a warning appears and the frequency converter ramps down
until it stops then displays an alarm.
Troubleshooting Check connections on the serial communication cable.
Increase 8-03 Control Word Timeout Time
Check the operation of the communication equipment.
Verify a proper installation based on EMC requirements.
ALARM 18, Start failed The speed has not been able to exceed 1-77 Compressor
Start Max Speed [RPM] during start within the allowed time. (set in 1-79
Compressor Start Max Time to Trip). This may be caused by a blocked motor.
44
MG11AJ22 – Rev. 2013-09-13
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
WARNING 23, Internal fan fault The fan warning function is an extra protective
function that checks if the fan is running/mounted. The fan warning can be
disabled in 14-53 Fan Monitor ([0] Disabled).
For the D, E, and F Frame filters, the regulated voltage to the fans is
monitored.
Troubleshooting Check for proper fan operation.
Cycle power to the adjustable frequency drive and check that the fan operates
briefly at start-up.
Check the sensors on the heatsink and control card.
WARNING 24, External fan fault The fan warning function is an extra protective
function that checks if the fan is running/mounted. The fan warning can be
disabled in 14-53 Fan Monitor ([0] Disabled).
Troubleshooting Check for proper fan operation.
Cycle power to the adjustable frequency drive and check that the fan operates
briefly at start-up.
Check the sensors on the heatsink and control card.
WARNING 25, Brake resistor short circuit The brake resistor is monitored
during operation. If a short circuit occurs, the brake function is disabled
and the warning appears. The adjustable frequency drive is still operational
but without the brake function. Remove power to the adjustable frequency drive
and replace the brake resistor (see 2-15 Brake Check).
WARNING/ALARM 26, Brake resistor power limit The power transmitted to the
brake resistor is calculated as a mean value over the last 120 seconds of run
time. The calculation is based on the intermediate circuit voltage and the
brake resistance value set in 2-16 AC Brake Max. Current. The warning is
active when the dissipated braking energy is higher than 90% of the brake
resistance power. If [2] Trip is selected in 2-13 Brake Power Monitoring, the
adjustable frequency drive trips when the dissipated braking energy reaches
100%.
WARNING/ALARM 27, Brake chopper fault The brake transistor is monitored during
operation and if a short circuit occurs, the brake function is disabled and a
warning is issued. The adjustable frequency drive is still operational but,
since the brake transistor has short-circuited, substantial power is
transmitted to the brake resistor, even if it is inactive. Remove power to the
adjustable frequency drive and remove the brake resistor.
WARNING/ALARM 28, Brake check failed The brake resistor is not connected or
not working. Check 2-15 Brake Check.
ALARM 29, Heatsink temp The maximum temperature of the heatsink has been
exceeded. The temperature fault will not reset until the temperature falls
below a defined heatsink temperature. The trip and reset points are different
based on the adjustable frequency drive power size.
Troubleshooting Check for the following conditions.
Ambient temperature too high.
Motor cable too long.
Incorrect airflow clearance above and below the adjustable frequency drive.
Blocked airflow around the adjustable frequency drive.
Damaged heatsink fan.
Dirty heatsink.
ALARM 30, Motor phase U missing Motor phase U between the adjustable frequency
drive and the motor is missing.
Remove power from the adjustable frequency drive and check motor phase U.
ALARM 31, Motor phase V missing Motor phase V between the adjustable frequency
drive and the motor is missing.
Remove power from the adjustable frequency drive and check motor phase V.
ALARM 32, Motor phase W missing Motor phase W between the adjustable frequency
drive and the motor is missing.
Remove power from the adjustable frequency drive and check motor phase W.
77
MG11AJ22 – Rev. 2013-09-13
45
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
77
ALARM 33, Inrush fault Too many power-ups have occurred within a short time
period. Let the unit cool to operating temperature.
WARNING/ALARM 34, Fieldbus communication fault The serial communication bus on
the communication option card is not working.
WARNING/ALARM 36, Mains failure This warning/alarm is only active if the
supply voltage to the frequency converter is lost and 14-10 Mains Failure is
NOT set to [0] No Function. Check the fuses to the frequency converter and
mains supply to the unit.
ALARM 38, Internal fault When an internal fault occurs, a code number defined
in Table 7.6 is displayed.
Troubleshooting Cycle power
Check that the option is properly installed
Check for loose or missing wiring
It may be necessary to contact your Danfoss supplier or service department.
Note the code number for further troubleshooting directions.
No. 0
256-258
512-519
783 1024-1284
1299 1300 1315 1316 1379-2819
2561 2820 2821 2822 3072-5122 5123
Text Serial port cannot be initialized. Contact your Danfoss supplier or Danfoss Service Department. Power EEPROM data is defective or too old. Replace power card. Internal fault. Contact your Danfoss supplier or Danfoss Service Department. Parameter value outside of min/max limits Internal fault. Contact your Danfoss supplier or the Danfoss Service Department. Option SW in slot A is too old Option SW in slot B is too old Option SW in slot A is not supported (not allowed) Option SW in slot B is not supported (not allowed) Internal fault. Contact your Danfoss supplier or Danfoss Service Department. Replace control card LCP stack overflow Serial port overflow USB port overflow Parameter value is outside its limits Option in slot A: Hardware incompatible with control board hardware
No. 5124
5376-6231
Text Option in slot B: Hardware incompatible with control board hardware Internal fault. Contact your Danfoss supplier or Danfoss Service Department.
Table 7.6 Internal Fault Codes
ALARM 39, Heatsink sensor No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on the power card.
The problem could be on the power card, on the gate drive card, or the ribbon
cable between the power card and gate drive card.
WARNING 40, Overload of digital output terminal 27 Check the load connected to
terminal 27 or remove shortcircuit connection. Check 5-00 Digital I/O Mode and
5-01 Terminal 27 Mode.
WARNING 41, Overload of digital output terminal 29 Check the load connected to
terminal 29 or remove shortcircuit connection. Check 5-00 Digital I/O Mode and
5-02 Terminal 29 Mode.
WARNING 42, Overload of digital output on X30/6 or overload of digital output
on X30/7 For X30/6, check the load connected to X30/6 or remove the short-
circuit connection. Check 5-32 Term X30/6 Digi Out (MCB 101).
For X30/7, check the load connected to X30/7 or remove the short-circuit
connection. Check 5-33 Term X30/7 Digi Out (MCB 101).
ALARM 45, Earth fault 2 Ground fault on start-up.
Troubleshooting Check for proper grounding and loose connections.
Check for proper wire size.
Check motor cables for short-circuits or leakage currents.
ALARM 46, Power card supply The supply on the power card is out of range.
There are three power supplies generated by the switch mode power supply
(SMPS) on the power card: 24 V, 5 V, ±18 V. When powered with 24 V DC with the
MCB 107 option, only the 24 V and 5 V supplies are monitored. When powered
with three phase AC line voltage, all three supplies are monitored.
46
MG11AJ22 – Rev. 2013-09-13
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
Troubleshooting Check for a defective power card.
Check for a defective control card.
Check for a defective option card.
If a 24 V DC power supply is used, verify proper supply power.
WARNING 47, 24 V supply low The 24 V DC is measured on the control card. The
external 24 V DC backup power supply may be overloaded; otherwise, contact the
Danfoss supplier.
WARNING 48, 1.8 V supply low The 1.8 V DC supply used on the control card is
outside of allowable limits. The power supply is measured on the control card.
Check for a defective control card. If an option card is present, check for an
overvoltage condition.
WARNING 49, Speed limit When the speed is not within the specified range in
4-11 Motor Speed Low Limit [RPM] and 4-13 Motor Speed High Limit [RPM], the
adjustable frequency drive shows a warning. When the speed is below the
specified limit in 1-86 Trip Speed Low [RPM] (except when starting or
stopping), the adjustable frequency drive trips.
ALARM 50, AMA calibration failed Contact your Danfoss supplier or Danfoss
Service Department.
ALARM 51, AMA check Unom and Inom The settings for motor voltage, motor
current and motor power are wrong. Check the settings in parameters 1-20 to
1-25.
ALARM 52, AMA low Inom The motor current is too low. Check the settings.
ALARM 53, AMA motor too big The motor is too big for the AMA to operate.
ALARM 54, AMA motor too small The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range The parameter values of the motor are
outside of the acceptable range. AMA cannot run.
ALARM 56, AMA interrupted by user The user has interrupted the AMA.
ALARM 57, AMA internal fault Try to restart AMA again. Repeated restarts can
overheat the motor.
ALARM 58, AMA Internal fault Contact your Danfoss supplier.
WARNING 59, Current limit The current is higher than the value in 4-18 Current
Limit. Ensure that Motor data in parameters 1-20 to 1-25 are set correctly.
Possibly increase the current limit. Be sure that the system can operate
safely at a higher limit.
WARNING 60, External interlock A digital input signal is indicating a fault
condition external to the frequency converter. An external interlock has
commanded the frequency converter to trip. Clear the external fault condition.
To resume normal operation, apply 24 V DC to the terminal programmed for
external interlock. Reset the frequency converter.
WARNING 62, Output frequency at maximum limit The output frequency has reached
the value set in 4-19 Max Output Frequency. Check the application to determine
the cause. Possibly increase the output frequency limit. Be sure the system
can operate safely at a higher output frequency. The warning will clear when
the output drops below the maximum limit.
WARNING/ALARM 65, Control card over temperature The cut-out temperature of the
control card is 176 °F [80 °C].
Troubleshooting
· Check that the ambient operating temperature is
within limits.
· Check for clogged filters. · Check fan operation. · Check the control card.
WARNING 66, Heatsink temperature low The frequency converter is too cold to
operate. This warning is based on the temperature sensor in the IGBT module.
Increase the ambient temperature of the unit. Also, a trickle amount of
current can be supplied to the frequency converter whenever the motor is
stopped by setting 2-00 DC Hold/Preheat Current at 5% and 1-80 Function at
Stop
ALARM 67, Option module configuration has changed One or more options have
either been added or removed since the last power-down. Check that the
configuration change is intentional and reset the unit.
ALARM 68, Safe Stop activated Safe stop has been activated. To resume normal
operation, apply 24 V DC to terminal 37, then send a reset signal (via Bus,
Digital I/O, or by pressing the reset key).
77
MG11AJ22 – Rev. 2013-09-13
47
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
77
ALARM 69, Power card temperature The temperature sensor on the power card is
either too hot or too cold.
Troubleshooting Check that the ambient operating temperature is within limits.
Check for clogged filters.
Check fan operation.
Check the power card.
ALARM 70, Illegal FC configuration The control card and power card are
incompatible. To check compatibility, contact your supplier with the type code
of the unit from the nameplate and the part numbers of the cards.
ALARM 80, Drive initialized to default value Parameter settings are
initialized to default settings after a manual reset. To clear the alarm,
reset the unit.
ALARM 92, No flow A no-flow condition has been detected in the system. 22-23
No-Flow Function is set for alarm. Troubleshoot the system and reset the
adjustable frequency drive after the fault has been cleared.
ALARM 93, Dry pump A no-flow condition in the system with the adjustable
frequency drive operating at high speed may indicate a dry pump. 22-26 Dry
Pump Function is set for alarm. Troubleshoot the system and reset the
adjustable frequency drive after the fault has been cleared.
ALARM 94, End of curve Feedback is lower than the setpoint. This may indicate
leakage in the system. 22-50 End of Curve Function is set for alarm.
Troubleshoot the system and reset the adjustable frequency drive after the
fault has been cleared.
ALARM 95, Broken belt Torque is below the torque level set for no load,
indicating a broken belt. 22-60 Broken Belt Function is set for alarm.
Troubleshoot the system and reset the adjustable frequency drive after the
fault has been cleared.
ALARM 96, Start delayed Motor start has been delayed due to short-cycle
protection. 22-76 Interval between Starts is enabled. Troubleshoot the system
and reset the adjustable frequency drive after the fault has been cleared.
WARNING 97, Stop delayed Stopping the motor has been delayed due to short
cycle protection. 22-76 Interval between Starts is enabled. Troubleshoot the
system and reset the adjustable frequency drive after the fault has been
cleared.
WARNING 98, Clock fault Time is not set or the RTC clock has failed. Reset the
clock in 0-70 Date and Time.
WARNING 200, Fire mode This warning indicates the adjustable frequency drive
is operating in Fire mode. The warning clears when fire mode is removed. See
the fire mode data in the alarm log.
WARNING 201, Fire Mode was Active This indicates the adjustable frequency
drive had entered fire mode. Cycle power to the unit to remove the warning.
See the fire mode data in the alarm log.
WARNING 202, Fire mode limits exceeded While operating in fire mode one or
more alarm conditions have been ignored which would normally trip the unit.
Operating in this condition voids unit warranty. Cycle power to the unit to
remove the warning. See the fire mode data in the alarm log.
WARNING 203, Missing motor With an adjustable frequency drive operating multi-
motors, an underload condition was detected. This could indicate a missing
motor. Inspect the system for proper operation.
WARNING 204, Locked rotor With an adjustable frequency drive operating multi-
motors, an overload condition was detected. This could indicate a locked
rotor. Inspect the motor for proper operation.
WARNING 250, New spare part A component in the adjustable frequency drive has
been replaced. Reset the adjustable frequency drive for normal operation.
WARNING 251, New typecode The power card or other components have been
replaced and the type code changed. Reset to remove the warning and resume
normal operation.
48
MG11AJ22 – Rev. 2013-09-13
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
7.4 Troubleshooting
Symptom
Possible cause
Test
Solution
Missing input power
See Table 4.5
Check the input power source.
Missing or open fuses or circuit See open fuses and tripped circuit breaker in Follow the recommendations provided.
breaker tripped
this table for possible causes
No power to the LCP
Check the LCP cable for proper connection Replace the faulty LCP or connection cable.
or damage
Shortcut on control voltage
Check the 24 V control voltage supply for Wire the terminals properly.
Display dark/No function
(terminal 12 or 50) or at control terminals 12/13 to 20-39 or 10 V supply for
terminals
terminals 50 to 55
Wrong LCP (LCP from VLT® 2800
or 5000/6000/8000/ FCD or FCM)
Use only LCP 101 (P/N 130B1124) or LCP 102 (P/N 130B1107).
Wrong contrast setting
Press [Status] + []/[] to adjust the
contrast.
Display (LCP) is defective
Test using a different LCP
Replace the faulty LCP or connection cable.
Internal voltage supply fault or
Contact supplier.
SMPS is defective
Overloaded power supply (SMPS) To rule out a problem in the control wiring, If the display stays lit, then the problem is in
Intermittent display
due to improper control wiring or a fault within the adjustable frequency drive
disconnect all control wiring by removing the the control wiring. Check the wiring for
terminal blocks.
short circuits or incorrect connections. If the
display continues to cut out, follow the
procedure for display dark.
Service switch open or missing Check if the motor is connected and the
Connect the motor and check the service
motor connection
connection is not interrupted (by a service switch.
switch or other device).
No line power with 24 V DC
If the display is functioning but no output, Apply line power to run the unit.
option card
check that line power is applied to the
adjustable frequency drive.
LCP Stop
Check if [Off] has been pressed
Press [Auto On] or [Hand On] (depending on
operation mode) to run the motor.
Motor not
Missing start signal (Standby) Check 5-10 Terminal 18 Digital Input for
Apply a valid start signal to start the motor.
running
correct setting for terminal 18 (use default
setting)
Motor coast signal active
Check 5-12 Coast inv. for correct setting for Apply 24 V on terminal 27 or program this
(Coasting)
terminal 27 (use default setting).
terminal to No operation.
Wrong reference signal source Check reference signal: Local, remote or bus Program correct settings. Check
reference? Preset reference active? Terminal 3-13 Reference Site. Set preset reference
connection correct? Scaling of terminals
active in parameter group 3-1* References.
correct? Reference signal available?
Check for correct wiring. Check scaling of
terminals. Check reference signal.
Motor rotation limit
Check that 4-10 Motor Speed Direction is
Program correct settings.
Motor running Active reversing signal
in wrong direction
programmed correctly. Check if a reversing command is programmed for the terminal in parameter group 5-1* Digital inputs.
Deactivate reversing signal.
Wrong motor phase connection
See 5.5 Checking Motor Rotation.
77
MG11AJ22 – Rev. 2013-09-13
49
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
77
Symptom
Possible cause
Test
Solution
Frequency limits set wrong
Check output limits in 4-13 Motor Speed High Program correct limits.
Motor is not reaching maximum speed
Limit [RPM], 4-14 Motor Speed High Limit [Hz]
and 4-19 Max Output Frequency.
Reference input signal not scaled Check reference input signal scaling in 6-0*
correctly
Analog I/O Mode and parameter group 3-1*
References. Reference limits in parameter
Program correct settings.
group 3-0* Reference Limits.
Possible incorrect parameter
Check the settings of all motor parameters, Check settings in parameter group 1-6*
Motor speed settings
including all motor compensation settings. Load-Depend. Settg. For closed-loop
unstable
For closed-loop operation, check PID settings. operation, check settings in parameter
group 20-0* Feedback.
Motor runs rough
Possible overmagnetization
Check for incorrect motor settings in all motor parameters
Check motor settings in parameter groups 1-2 Motor Data, 1-3 Addl. Motor Data, and 1-5* Load Indep. Setting..
Possible incorrect settings in the Check brake parameters. Check ramp time
Motor will not
brake parameters. Possible too settings brake
short ramp-down times
Check parameter group 2-0 DC Brake and 3-0 Reference Limits.
Phase-to-phase short
Motor or panel has a short phase-to-phase. Eliminate any short circuits detected.
Check motor and panel phase for shorts
Motor overload
Motor is overloaded for the application
Perform start-up test and verify motor
Open power fuses or circuit breaker trip
current is within specifications. If motor current is exceeding nameplate full load current, motor may run only with reduced load. Review the specifications for the
application.
Loose connections
Perform pre-start-up check for loose
Tighten loose connections.
connections
Line power current imbalance greater than 3%
Problem with line power (See Alarm 4 Mains phase loss description) Problem with the adjustable frequency drive
Rotate input power leads into the adjustable frequency drive one position: A to B, B to C, C to A. Rotate input power leads into the adjustable frequency drive one position: A to B, B to C, C to A.
If imbalanced leg follows the wire, it is a power problem. Check line power
supply.
If imbalance leg stays on same input terminal, it is a problem with the unit.
Contact the supplier.
Problem with motor or motor Rotate output motor leads one position: U to If imbalanced leg follows the wire, the
Motor current wiring
V, V to W, W to U.
problem is in the motor or motor wiring.
imbalance
Check motor and motor wiring.
greater than Problem with the adjustable
Rotate output motor leads one position: U to If imbalance leg stays on same output
3%
frequency drives
V, V to W, W to U.
terminal, it is a problem with the unit.
Contact the supplier.
Adjustable
Motor data are entered
If warnings or alarms occur, see 7.3 List of Increase the ramp-up time in 3-41 Ramp 1
frequency
incorrectly
Warnings and Alarms.
Ramp-up Time. Increase current limit in
drive
Check that motor data are entered correctly 4-18 Current Limit. Increase torque limit in
acceleration
4-16 Torque Limit Motor Mode.
problems
50
MG11AJ22 – Rev. 2013-09-13
Diagnostics and Troubleshoo…
VLT® HVAC Drive Instruction Manual
Symptom Adjustable frequency drive deceleration problems
Possible cause Motor data are entered incorrectly
Acoustic noise or vibration (e.g., a fan blade is making noise or vibrations at certain frequencies)
Resonances, e.g., in the motor/fan system
Table 7.7 Troubleshooting
Test If warnings or alarms occur, see 7.3 List of Warnings and Alarms. Check that motor data are entered correctly
Solution Increase the ramp-down time in 3-42 Ramp 1 Ramp-down Time. Enable overvoltage control in 2-17 Over-voltage Control.
Bypass critical frequencies by using parameters in parameter group 4-6 Speed Bypass Turn off overmodulation in 14-03 Overmodulation Change switching pattern and frequency in parameter group 14-0 Inverter Switching Increase Resonance Dampening in 1-64 Resonance Dampening
Check if noise and/or vibration have been reduced to an acceptable limit.
77
MG11AJ22 – Rev. 2013-09-13
51
Specifications
VLT® HVAC Drive Instruction Manual
Specifications
88
8.1 Electrical Data
Line Power Supply 1 x 200240 V AC
Type Designation
P1K1
P1K5
P2K2
P3K0
P3K7
P5K5
P7K5
P15K
P22K
Typical Shaft Output [kW] Typical Shaft Output [HP] at 240 V IP20/Chassis IP21/NEMA 1 IP55/NEMA 12 IP66 Output current Continuous (3×200240 V) [A] Intermittent (3×200240 V) [A] Continuous kVA (208 V AC) [kVA] Max. input current Continuous (1×200240 V) [A] Intermittent (1×200240 V) [A] Max. pre- fuses1)[A] Additional specifications Estimated power loss at rated max. load [W] 4) Max. cable size (line power, motor, brake) [mm2]/(AWG) 2) Efficiency 3)
1.1
1.5
2.2
3.0
3.7
5.5
7.5
15
22
1.5
2.0
2.9
4.0
4.9
7.5
10
20
30
A3
–
–
–
–
–
–
–
–
–
B1
B1
B1
B1
B1
B2
C1
C2
A5
B1
B1
B1
B1
B1
B2
C1
C2
A5
B1
B1
B1
B1
B1
B2
C1
C2
6.6
7.5
10.6
12.5
16.7
24.2
30.8
59.4
88
7.3
8.3
11.7
13.8
18.4
26.6
33.4
65.3
96.8
5.00
6.40
12.27
18.30
12.5
15
20.5
24
32
46
59
111
172
13.8
16.5
22.6
26.4
35.2
50.6
64.9
122.1
189.2
20
30
40
40
60
80
100
150
200
44
30
44
60
74
110
150
300
440
0.968
[0.2-4]/(4-10)
0.98
0.98
0.98
[10]/(7) [35]/(2) [50]/(1)/0 [95]/(4/0)
0.98
0.98
0.98
0.98
0.98
Table 8.1 Line Power Supply 1×200240 V AC – Normal Overload 110% for 1 Minute, P1K1-P22K
52
MG11AJ22 – Rev. 2013-09-13
Specifications
VLT® HVAC Drive Instruction Manual
8.1.1 Line Power Supply 3×200240 V AC
Type Designation Typical Shaft Output [kW] Typical Shaft Output [HP] at 208 V IP20/Chassis 6)
P1K1 1.1 1.5 A2
P1K5 1.5 2.0 A2
P2K2 2.2 2.9 A2
P3K0 3.0 4.0 A3
IP55/Type 12
IP66/NEMA 4X Output current Continuous (3×200240 V) [A] Intermittent
(3×200240 V) [A] Continuous kVA (208 V AC) [kVA] Max. input current
Continuous (3×200240 V) [A] Intermittent (3×200240 V) [A] Additional
specifications Estimated power loss at rated max. load [W] 4) IP20, IP21 max.
cable cross-section (line power, motor, brake and load sharing) [mm2/(AWG)]
IP55, IP66 max. cable cross-section (line power, motor, brake and load
sharing) [mm2/(AWG)] Max. cable cross-section with disconnect Efficiency 3)
A4/A5 A4/A5
6.6 7.3 2.38 5.9 6.5 63
0.96
A4/A5
A4/A5
A5
A4/A5
A4/A5
A5
7.5
10.6
12.5
8.3
11.7
13.8
2.70
3.82
4.50
6.8
9.5
11.3
7.5
10.5
12.4
82
116
155
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
4, 4, 4 (12, 12, 12)
6, 4, 4 (10, 12, 12)
0.96
0.96
0.96
Table 8.2 Line Power Supply 3×200240 V AC – Normal overload 110% for 1 minute, P1K1-P3K7
P3K7 3.7 4.9 A3 A5 A5 16.7 18.4 6.00 15.0 16.5 185
0.96
88
MG11AJ22 – Rev. 2013-09-13
53
MG11AJ22 – Rev. 2013-09-13
54
Type Designation Typical Shaft Output [kW] Typical Shaft Output [HP] at 208 V IP20/Chassis 7) IP21/NEMA 1 IP55/Type 12 IP66/NEMA 4X Output current Continuous (3×200240 V) [A] Intermittent (3×200240 V) [A] Continuous kVA (208 V AC) [kVA] Max. input current Continuous (3×200240 V) [A] Intermittent (3×200240 V) [A] Additional Specifications Estimated power loss at rated max. load [W] 4) IP20 max. cable cross-section (line power, brake, motor and load sharing) IP21, IP55, IP66 max. cable cross-section (line power, motor) [mm2/(AWG)] IP21, IP55, IP66 max. cable cross-section (brake, load sharing) [mm2/(AWG)] Efficiency 3)
P5K5 5.5 7.5 B3 B1 B1 B1
24.2 26.6 8.7
22.0 24.2
P7K5 7.5 10 B3 B1 B1 B1
30.8 33.9 11.1
28.0 30.8
269
310
10, 10 (8,8,-)
10, 10 (8,8,-)
16, 10, 16 (6, 8, 6)
0.96
0.96
P11K 11 15 B3 B1 B1 B1
46.2 50.8 16.6
42.0 46.2
447
35,-,-(2,-,-) 35, 25, 25 (2,
4, 4) 35,-,-(2,-,-)
0.96
P15K 15 20 B4 B2 B2 B2
59.4 65.3 21.4
54.0 59.4
602
35 (2)
0.96
Table 8.3 Line Power Supply 3×200240 V AC – Normal overload 110% for 1 minute, P5K5-P45K
P18K 18.5 25 B4 C1 C1 C1
74.8 82.3 26.9
68.0 74.8
P22K 22 30 C3 C1 C1 C1
88.0 96.8 31.7
80.0 88.0
737
845
50 (1)
50 (1)
50 (1)
0.96
0.97
88
P30K 30 40 C3 C1 C1 C1
115 127 41.4
104.0 114.0
P37K 37 50 C4 C2 C2 C2
143 157 51.5
130.0 143.0
P45K 45 60 C4 C2 C2 C2
170 187 61.2
154.0 169.0
1140
1353
1636
150 (300MCM)
150 (300MCM)
95 (3/0)
0.97
0.97
0.97
VLT® HVAC Drive Instruction Manual
Specifications
Specifications
VLT® HVAC Drive Instruction Manual
8.1.2 Line Power Supply 3×380480 V AC
Type Designation Typical Shaft Output [kW] Typical Shaft Output [HP] at 460 V IP20/Chassis 6) IP55/Type 12 IP66/NEMA 4X Output current Continuous (3×380440 V) [A] Intermittent (3×380440 V) [A] Continuous (3×441480 V) [A] Intermittent (3×441480 V) [A] Continuous kVA (400 V AC) [kVA] Continuous kVA (460 V AC) [kVA] Max. input current Continuous (3×380440 V) [A] Intermittent (3×380440 V) [A] Continuous (3×441480 V) [A] Intermittent (3×441480 V) [A] Additional specifications Estimated power loss at rated max. load [W] 4) IP20, IP21 max. cable cross-section (line power, motor, brake and load sharing) [mm2/(AWG)] 2) IP55, IP66 max. cable cross-section (line power, motor, brake and load sharing) [mm2/(AWG)] 2) Max. cable cross-section with disconnect Efficiency 3)
P1K1 1.1 1.5 A2 A4/A5 A4/A5
3 3.3 2.7 3.0 2.1 2.4
2.7 3.0 2.7 3.0
58
0.96
P1K5 1.5 2.0 A2 A4/A5 A4/A5
4.1 4.5 3.4 3.7 2.8 2.7
3.7 4.1 3.1 3.4
62
0.97
P2K2 2.2 2.9 A2 A4/A5 A4/A5
5.6 6.2 4.8 5.3 3.9 3.8
5.0 5.5 4.3 4.7
P3K0 3.0 4.0 A2 A4/A5 A4/A5
7.2 7.9 6.3 6.9 5.0 5.0
6.5 7.2 5.7 6.3
P4K0 4.0 5.0 A2 A4/A5 A4/A5
10 11 8.2 9.0 6.9 6.5
9.0 9.9 7.4 8.1
88
116
124
4, 4, 4 (12, 12, 12) (min. 0.2 (24))
4, 4, 4 (12, 12, 12)
6, 4, 4 (10, 12, 12)
0.97
0.97
0.97
Table 8.4 Line Power Supply 3×380480 V AC – Normal overload 110% for 1 minute, P1K1-P7K5
P5K5 5.5 7.5 A3 A5 A5
13 14.3 11 12.1 9.0 8.8
11.7 12.9 9.9 10.9
187
0.97
P7K5 7.5 10 A3 A5 A5
16 17.6 14.5 15.4 11.0 11.6
14.4 15.8 13.0 14.3
255
0.97
88
MG11AJ22 – Rev. 2013-09-13
55
MG11AJ22 – Rev. 2013-09-13
56
Type Designation Typical Shaft Output [kW] Typical Shaft Output [HP] at 460 V IP20/Chassis 7) IP21/NEMA 1 IP55/Type 12 IP66/NEMA 4X Output current Continuous (3×380439 V) [A] Intermittent (3×380439 V) [A] Continuous (3×440480 V) [A] Intermittent (3×440480 V) [A] Continuous kVA (400 V AC) [kVA] Continuous kVA (460 V AC) [kVA] Max. input current Continuous (3×380439 V) [A] Intermittent (3×380439 V) [A] Continuous (3×440480 V) [A] Intermittent (3×440480 V) [A] Additional specifications Estimated power loss at rated max. load [W] 4) IP20 max. cable cross-section (line power, brake, motor and load sharing) IP21, IP55, IP66 max. cable crosssection (line power, motor) [mm2/ (AWG)] IP21, IP55, IP66 max. cable crosssection (brake, load sharing) [mm2/ (AWG)] With line power disconnect switch included: Efficiency 3)
P11K 11 15 B3 B1 B1 B1
24 26.4 21 23.1 16.6 16.7
22 24.2 19 20.9
P15K 15 20 B3 B1 B1 B1
32 35.2 27 29.7 22.2 21.5
29 31.9 25 27.5
278
392
16, 10, – (8, 8, -)
10, 10, 16 (6, 8, 6)
10, 10, – (8, 8, -)
0.98
0.98
P18K 18.5 25 B3 B1 B1 B1
37.5 41.3 34 37.4 26 27.1
34 37.4 31 34.1
P22K 22 30 B4 B2 B2 B2
44 48.4 40 44 30.5 31.9
40 44 36 39.6
465
525
35, -, – (2, -, -)
P30K 30 40 B4 B2 B2 B2
61 67.1 52 61.6 42.3 41.4
55 60.5 47 51.7
698
35 (2)
35, 25, 25 (2, 4, 4)
50 (1)
35, -, – (2, -, -)
16/6
0.98
0.98
50 (1) 0.98
Table 8.5 Line Power Supply 3×380480 V AC – Normal overload 110% for 1 minute, P11K-P90K
88
P37K 37 50 B4 C1 C1 C1
73 80.3 65 71.5 50.6 51.8
66 72.6 59 64.9
P45K 45 60 C3 C1 C1 C1
90 99 80 88 62.4 63.7
82 90.2 73 80.3
739
843
50 (1)
P55K 55 75 C3 C1 C1 C1
106 117 105 116 73.4 83.7
96 106 95 105
P75K 75 100 C4 C2 C2 C2
147 162 130 143 102 104
133 146 118 130
P90K 90 125 C4 C2 C2 C2
177 195 160 176 123 128
161 177 145 160
1083
1384
1474
150 (300 MCM)
150 (300 MCM)
95 (3/0)
185/
35/2
35/2
70/3/0
kcmil350
0.98
0.98
0.98
0.98
0.99
VLT® HVAC Drive Instruction Manual
Specifications
Specifications
VLT® HVAC Drive Instruction Manual
8.1.3 Line Power Supply 3×525600 V AC
Type Designation Typical Shaft Output [kW] IP20/Chassis IP21/NEMA 1 IP55/Type 12 IP66/NEMA 4X Output current Continuous (3 x 525550 V) [A] Intermittent (3 x 525550 V) [A] Continuous (3×525600 V) [A] Intermittent (3×525600 V) [A] Continuous kVA (525 V AC) [kVA] Continuous kVA (575 V AC) [kVA] Max. input current Continuous (3×525600 V) [A] Intermittent (3×525600 V) [A] Additional specifications Estimated power loss at rated max. load [W] 4) IP20 max. cable cross-section 5)(line power, motor, brake and load sharing) [mm2/(AWG)] IP55, IP 66 max. cable cross-section 5) (line power, motor, brake and load sharing) [mm2/(AWG)] Max. cable cross-section with disconnect Line power disconnect switch included: Efficiency 3)
P1K1 1.1 A3 A3 A5 A5 2.6 2.9 2.4 2.6 2.5 2.4 2.4 2.7
50
0.97
P1K5 1.5 A3 A3 A5 A5 2.9 3.2 2.7 3.0 2.8 2.7 2.7 3.0
65
0.97
P2K2 2.2 A3 A3 A5 A5 4.1 4.5 3.9 4.3 3.9 3.9 4.1 4.5
92
0.97
P3K0 3.0 A3 A3 A5 A5
5.2 5.7 4.9 5.4 5.0 4.9
5.2 5.7
P3K7 3.7 A2 A2 A5 A5
–
–
122
–
4, 4, 4 (12, 12, 12) (min. 0.2 (24))
4, 4, 4 (12, 12, 12) (min. 0.2 (24))
6, 4, 4 (12, 12, 12)
4/12
0.97
–
Table 8.6 Line Power Supply 3×525600 V AC – Normal overload 110% for 1 minute, P1K1-P7K5
P4K0 4.0 A3 A3 A5 A5 6.4 7.0 6.1 6.7 6.1 6.1 5.8 6.4
145
0.97
P5K5 5.5 A3 A3 A5 A5
9.5 10.5 9.0 9.9 9.0 9.0
8.6 9.5
195
P7K5 7.5 A3 A3 A5 A5
11.5 12.7 11.0 12.1 11.0 11.0
10.4 11.5
261
0.97
0.97
88
MG11AJ22 – Rev. 2013-09-13
57
MG11AJ22 – Rev. 2013-09-13
58
Type Designation Typical Shaft Output [kW] IP20/Chassis IP21/NEMA 1 IP55/Type 12 IP66/NEMA 4X Output current Continuous (3 x 525550 V) [A] Intermittent (3 x 525550 V) [A] Continuous (3×525600 V) [A] Intermittent (3×525600 V) [A] Continuous kVA (525 V AC) [kVA] Continuous kVA (575 V AC) [kVA] Max. input current Continuous (3×525600 V) [A] Intermittent (3×525600 V) [A] Additional specifications Estimated power loss at rated max. load [W] 4) IP21, IP55, IP66 max. cable cross-section (line power, brake and load sharing) [mm2/(AWG)] IP21, IP55, IP66 max. cable cross-section (motor) [mm2/ (AWG)] IP20 max. cable cross-section (line power, brake and load sharing) [mm2/(AWG)]
P11K1 11 B3 B1 B1 B1
19 21 18 20
18.1
17.9
P15K 15 B3 B1 B1 B1
23 25 22 24
21.9
21.9
17.2
20.9
19
23
300
400
16, 10, 10 (6, 8, 8)
10, 10, – (8, 8, -)
10, 10, – (8, 8, -)
P18K 18.5 B3 B1 B1 B1
28 31 27 30
26.7
26.9
P22K 22 B4 B2 B2 B2
36 40 34 37
34.3
33.9
25.4
32.7
28
36
475
525
35,-,-(2,-,-)
P30K 30 B4 B2 B2 B2
43 47 41 45
41
40.8
P37K 37 B4 C1 C1 C1
54 59 52 57
51.4
51.8
P45K 45 C3 C1 C1 C1
65 72 62 68
61.9
61.7
39
49
59
43
54
65
700
750
850
50,-,- (1,-,-)
35, 25, 25 (2, 4, 4)
50,-,- (1,-,-)
35, -, – (2, -, -)
50,-,- (1,-,-)
Max. cable cross-section with disconnect
16, 10, 10 (6, 8, 8)
50, 35, 35 (1, 2, 2)
Line power disconnect switch 16/6
included:
Efficiency 3)
0.98
0.98
0.98
0.98
35/2
0.98
0.98
0.98
Table 8.7 Line Power Supply 3×525600 V AC – Normal overload 110% for 1 minute, P11K-P90K
88
P55K 55 C3 C1 C1 C1
87 96 83 91 82.9
82.7
78.9 87
1100
P75K 75 C4 C2 C2 C2
105 116 100 110 100
99.6
95.3 105
1400
95 (4/0)
P90K 90 C4 C2 C2 C2
137 151 131 144 130.5
130.5
124.3 137
1500
150 (300 MCM)
150 (300 MCM)
95, 70, 70 (3/0, 2/0,
2/0)
185, 150, 120 (350 MCM, 300 MCM, 4/0)
70/3/0
185/kcmil350
0.98
0.98
0.98
VLT® HVAC Drive Instruction Manual
Specifications
Specifications
VLT® HVAC Drive Instruction Manual
8.1.4 Line Power Supply 3 x 525690 V AC
Type Designation Typical Shaft Output [kW] Enclosure IP20 (only) Output current Continuous (3 x 525550 V) [A] Intermittent (3 x 525550 V) [A] Continuous kVA (3 x 551690 V) [A] Intermittent kVA (3 x 551690 V) [A] Continuous kVA 525 V AC Continuous kVA 690 V AC Max. input current Continuous (3 x 525550 V) [A] Intermittent (3 x 525550 V) [A] Continuous kVA (3 x 551690 V) [A] Intermittent kVA (3 x 551690 V) [A] Additional specifications Estimated power loss at rated max. load [W] 4) Max. cable cross-section5) (line power, motor, brake and load sharing) [mm2]/(AWG) Max. cable cross- section with disconnect Efficiency 3)
P1K1 1.1 A3
2.1 3.4 1.6 2.6 1.9 1.9
1.9 3.0 1.4 2.3
44
0.96
P1K5 1.5 A3
2.7 4.3 2.2 3.5 2.5 2.6
2.4 3.9 2.0 3.2
60
0.96
P2K2 2.2 A3
P3K0 3.0 A3
P4K0 4.0 A3
3.9
4.9
6.1
6.2
7.8
9.8
3.2
4.5
5.5
5.1
7.2
8.8
3.5
4.5
5.5
3.8
5.4
6.6
3.5
4.4
5.5
5.6
7.1
8.8
2.9
4.0
4.9
4.6
6.5
7.9
88
120
160
6, 4, 4 (10, 12, 12) (min. 0.2 (24))
6, 4, 4 (10, 12, 12)
0.96
0.96
0.96
Table 8.8 Line Power Supply 3×525690 V AC – Normal overload 110% for 1 minute, P1K1-P7K5
P5K5 5.5 A3
9.0 14.4 7.5 12 8.2 9.0
8.0 13 6.7 10.8
220
0.96
P7K5 7.5 A3
11 17.6 10 16 10 12
10 16 9.0 14.4
300
0.96
88
MG11AJ22 – Rev. 2013-09-13
59
Specifications
VLT® HVAC Drive Instruction Manual
88
Type Designation High/Normal Load Typical Shaft Output at 550 V [kW] Typical Shaft Output at 690 V [kW] IP20/Chassis IP21/NEMA 1 IP55/NEMA 12 Output current Continuous (3 x 525550 V) [A] Intermittent (60 s overload) (3 x 525550 V) [A] Continuous (3 x 551690 V) [A] Intermittent (60 s overload) (3 x 551690 V) [A] Continuous kVA (550 V AC) [kVA] Continuous kVA (690 V AC) [kVA] Max. input current Continuous (at 550 V) [A] Intermittent (60 s overload) (at 550 V) [A] Continuous (at 690 V) [A] Intermittent (60 s overload) (at 690 V) [A] Max. pre-fuses1) [A] Additional specifications Estimated power loss at rated max. load [W] 4) Max. cable cross-section (line power/motor, load sharing and brake) [mm2]/(AWG) 2) Max. cable size with line power disconnect [mm2]/(AWG) 2) Efficiency 3)
P11K NO 7.5 11 B4 B2 B2
14 22.4 13 20.8 13.3 15.5
15 23.2 14.5 23.2 63
150
0.98
P15K NO 11 15 B4 B2 B2
P18K NO 15 18.5 B4 B2 B2
P22K NO 18.5 22 B4 B2 B2
19
23
28
20.9
25.3
30.8
18
22
27
19.8
24.2
29.7
18.1
21.9
26.7
21.5
26.3
32.3
19.5
24
29
21.5
26.4
31.9
19.5
24
29
21.5
26.4
31.9
63
63
80
220
300
370
35, 25, 25 (2, 4, 4)
16, 10, 10 (6, 8, 8)
0.98
0.98
0.98
Table 8.9 Line Power Supply 3 x 525690 V AC – Normal overload 110% for 1 minute, P11K-P30K
P30K NO 22 30 B4 B2 B2
36 39.6 34 37.4 34.3 40.6
36 39.6 36 39.6 100
440
0.98
60
MG11AJ22 – Rev. 2013-09-13
Specifications
VLT® HVAC Drive Instruction Manual
Type Designation High/Normal Load Typical Shaft Output at 550 V [kW] Typical
Shaft Output at 690 V [kW] IP20/Chassis IP21/NEMA 1 IP55/NEMA 12 Output
current Continuous (3 x 525550 V) [A] Intermittent (60 s overload) (3 x
525550 V) [A] Continuous (3 x 551690 V) [A] Intermittent (60 s overload) (3
x 551690 V) [A] Continuous kVA (550 V AC) [kVA] Continuous kVA (690 V AC)
[kVA] Max. input current Continuous (at 550 V) [A] Intermittent (60 s
overload) (at 550 V) [A] Continuous (at 690 V) [A] Intermittent (60 s
overload) (at 690 V) [A] Max. pre-fuses1) [A] Additional specifications
Estimated power loss at rated max. load [W] 4) Max. cable cross-section (line
power and motor) [mm2]/(AWG) 2) Max. cable cross-section (load sharing and
brake) [mm2]/(AWG) 2) Max. cable size with line power disconnect [mm2]/(AWG)
2)
Efficiency 3)
P37K NO 30 37 B4 C2 C2
P45K NO 37 45 C3 C2 C2
P55K NO 45 55 C3 C2 C2
P75K NO 55 75 D3h C2 C2
P90K NO 75 90 D3h C2 C2
43
54
65
47.3
59.4
71.5
41
52
62
45.1
57.2
68.2
41
51.4
61.9
49
62.1
74.1
87
105
95.7
115.5
83
100
91.3
110
82.9
100
99.2
119.5
49
59
71
53.9
64.9
78.1
48
58
70
52.8
63.8
77
125
160
160
87
99
95.7
108.9
86
94.3
94.6
112.7
160
–
740
900
1100
1500
1800
150 (300 MCM)
95 (3/0)
95, 70, 70 (3/0, 2/0, 2/0)
185, 150, 120 (350 MCM, 300 MCM, 4/0)
0.98
0.98
0.98
0.98
0.98
Table 8.10 Line Power Supply 3 x 525690 V – Normal overload 110% for 1 minute, P37K-P90K
- For type of fuse, see 8.8 Fuse Specifications. 2) American Wire Gauge. 3) Measured using 5 m shielded motor cables at rated load and rated frequency. 4) The typical power loss is at normal load conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions). Values are based on a typical motor efficiency. Lower efficiency motors will also add to the power loss in the adjustable frequency drive and vice versa. If the switching frequency is raised from nominal, the power losses may rise significantly. LCP and typical control card power consumption values are included. Further options and customer load may add up to 30 W to the losses. (Though typically only 4 W extra for a fully loaded control card or options for slot A or slot B, each). Although measurements are made with state-of-the- art equipment, some measurement inaccuracy must be allowed for (±5%). 5) The three values for the max. cable cross-section are for single core, flexible wire and flexible wire with sleeve, respectively. Motor and line cable: 300 MCM/150 mm2. 6) A2+A3 may be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 Enclosure kit in the Design Guide. 7) B3+4 and C3+4 may be converted to IP21 using a conversion kit. See also Mechanical mounting and IP21/Type 1 Enclosure kit in the Design Guide.
88
MG11AJ22 – Rev. 2013-09-13
61
Specifications
VLT® HVAC Drive Instruction Manual
88
8.2 Line Power Supply
Line power supply Supply Terminals Supply voltage Supply voltage Supply voltage
L1, L2, L3 200240 V ±10% 380480 V/525600 V ±10% 525690 V ±10%
AC line voltage low/line drop-out: During low AC line voltage or a line drop- out, the adjustable frequency drive continues until the intermediate circuit voltage drops below the minimum stop level, which typically corresponds to 15% below the adjustable frequency drive’s lowest rated supply voltage. Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency drive’s lowest rated supply voltage.
Supply frequency Max. temporary imbalance between line phases True Power Factor () Displacement Power Factor (cos ) Switching on input supply L1, L2, L3 (power-ups) 7.5 kW Switching on input supply L1, L2, L3 (power-ups) 1190 kW Environment according to EN60664-1
50/60 Hz ±5% 3.0% of rated supply voltage
0.9 nominal at rated load near unity (> 0.98)
maximum 2 times/min. maximum 1 time/min. overvoltage category III/pollution
degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/500/600/690 V maximum.
8.3 Motor Output and Motor Data
Motor output (U, V, W) Output voltage Output frequency (1.190 kW) Switching on output Ramp times
0100% of supply voltage 05901) Hz Unlimited 13600 s
- From software version 3.92, the output frequency of the adjustable frequency drive is limited to 590 Hz. Contact local Danfoss partner for further information.
Torque characteristics Starting torque (Constant torque) Starting torque Overload torque (Constant torque) Starting torque (Variable torque) Overload torque (Variable torque) Torque rise time in VVCplus (independent of fsw)
maximum 110% for 60 s1) maximum 135% up to 0.5 s1)
maximum 110% for 60 s1) maximum 110% for 60 s1)
maximum 110% for 60 s 10 ms
- Percentage relates to the nominal torque. 2) The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 45 x torque rise time.
62
MG11AJ22 – Rev. 2013-09-13
Specifications
VLT® HVAC Drive Instruction Manual
8.4 Ambient Conditions
Environment
IP rating
IP00/Chassis, IP201)/Chassis, IP212)/Type 1, IP54/Type 12, IP55/Type 12, IP66/Type 4X
Vibration test
1.0 g
Max. relative humidity
5%93% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H2S test
class Kd
Ambient temperature3)
Max. 50 °C (24-hour average maximum 45 °C)
Minimum ambient temperature during full-scale operation
0 °C
Minimum ambient temperature at reduced performance
– 10 °C
Temperature during storage/transport
-25 to +65/70 °C
Maximum altitude above sea level without derating
1000 m
Derating for high altitude, see special conditions in the Design Guide.
EMC standards, Emission EMC standards, Immunity
EN 61800-3, EN 61000-6-3/4, EN 55011 EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions in the Design Guide.
- Only for 3.7 kW (200240 V), 7.5 kW (400480 V) 2) As enclosure kit for 3.7 kW (200240 V), 7.5 kW (400480 V) 3) Derating for high ambient temperature, see special conditions in the Design Guide
88
8.5 Cable Specifications
Cable lengths and cross-sections for control cables1) Max. motor cable length,
shielded Max. motor cable length, non-shielded Maximum cross-section to
control terminals, flexible/ rigid wire without cable end sleeves Maximum
cross-section to control terminals, flexible wire with cable end sleeves
Maximum cross-section to control terminals, flexible wire with cable end
sleeves with collar Minimum cross-section to control terminals
1)For power cables, see electrical data tables in 8.1 Electrical Data.
150 m 300 m 1.5 mm2/16 AWG 1 mm2/18 AWG 0.5 mm2/20 AWG 0.25 mm2/24AWG
MG11AJ22 – Rev. 2013-09-13
63
Specifications
VLT® HVAC Drive Instruction Manual
8.6 Control Input/Output and Control Data
88
Digital inputs Programmable digital inputs Terminal number Logic Voltage level Voltage level, logic’0′ PNP Voltage level, logic’1′ PNP Voltage level, logic ‘0’ NPN2) Voltage level, logic ‘1’ NPN2) Maximum voltage on input Pulse frequency ranges (Duty cycle) Min. pulse width Input resistance, Ri
4 (6)1) 18, 19, 271), 291), 32, 33,
PNP or NPN 024 V DC <5 V DC >10 V DC >19 V DC <14 V DC 28 V DC 0110 kHz 4.5
ms
Approx. 4 k
Safe Torque Off Terminal 373, 4) (Terminal 37 is fixed PNP logic) Voltage level Voltage level, logic’0′ PNP Voltage level, logic’1′ PNP Maximum voltage on input Typical input current at 24 V Typical input current at 20 V Input capacitance
024 V DC <4 V DC
20 V DC 28 V DC
50 mA rms 60 mA rms
400 nF
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 1) Terminals 27 and 29 can also be programmed as output. 2) Except Safe Torque Off input Terminal 37. 3) See for further information about terminal 37 and Safe Torque Off. 4) When using a contactor with a DC coil inside in combination with Safe Torque Off, it is important to make a return way for the current from the coil when turning it off. This can be done by using a freewheel diode (or, alternatively, a 30 or 50 V MOV for quicker response time) across the coil. Typical contactors can be bought with this diode.
64
MG11AJ22 – Rev. 2013-09-13
Specifications
VLT® HVAC Drive Instruction Manual
Analog inputs Number of analog inputs Terminal number Modes Mode select Voltage mode Voltage level Input resistance, Ri Max. voltage Current mode Current level Input resistance, Ri Max. current Resolution for analog inputs Accuracy of analog inputs Bandwidth
2 53, 54 Voltage or current Switch S201 and switch S202 Switch S201/switch S202 = OFF (U) -10 to +10 V (scalable) approx. 10 k ±20 V Sw
References
- Engineering Tomorrow | Danfoss
- Engineering Tomorrow | Danfoss
- Global AC drive manufacturer - Danfoss Drives | Danfoss
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>