montigo PVW47 Flush Wall Mount Power Vent Instruction Manual

June 1, 2024
Montigo

PVW47 Flush Wall Mount Power Vent

“`html

Specifications

  • Voltage: 120VAC 60HZ
  • Current: 0.8A
  • RPM: 2300
  • CFM: 80

Product Information

The PVW47 4/7 Flush Wall Mount Power Vent is a gas appliance
that requires installation by a qualified and certified gas
appliance installer. It is designed to provide efficient venting
for gas appliances.

Section A: Before You Begin

Important Message: Save these instructions. The
unit must be installed in accordance with these instructions.
Carefully read all the instructions in this manual first. Consult
the Local Gas Branch to determine the need for a permit prior to
starting the installation. It is the responsibility of the
installer to ensure this fireplace is installed in compliance with
the manufacturer’s instructions and all applicable codes.

Notice: Do not use this appliance if any part
has been under water. Immediately call a qualified service
technician to inspect the appliance and to replace any part of the
control system and any gas control that has been under water.

Notice: Children and adults should be alerted
to the hazards of high surface temperature and should stay away to
avoid burns or clothing ignition.

Caution: When cold air enters the warmer
building interior, primarily at the air intake end, condensation
may occur on the exterior of the flex pipe. To limit this
condensation, install insulation over the last twenty feet of flex
pipe. Also, by sloping the last 20 feet of flex pipe.

Frequently Asked Questions (FAQ)

  1. Q: What should I do if I smell gas?

A: If you smell gas, leave the area immediately
and contact your gas supplier or a qualified installer using a
phone outside of the area. Follow the gas supplier’s
instructions.

  1. Q: Can this product expose me to harmful
    substances?

A: Some materials used in the manufacturing
process of this product can expose you to Benzene, which is known
in the State of California to cause cancer and birth defects or
other reproductive harm. For more information, visit
www.P65warnings.ca.gov

  1. Q: What are the power vent
    specifications?

A: The power vent specifications are as
follows: Voltage – 120VAC 60HZ, Current – 0.8A, RPM – 2300, CFM –
80.

“`

Installation & Maintenance Manual

PVW47
4/7 FLUSH WALL MOUNT POWER VENT

· The installation of this fireplace must be done by a

®

qualified and certified gas appliance installer.

· Check local codes and read all instructions prior to

C

US

installation.

WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance.
· Do not touch any electrical switch; do not use any phone in your building.
· Leave the building immediately. · Immediately call your gas supplier from a neighbour’s
phone. Follow the gas supplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a qualified installer, service agency or the gas fitter.

NOTICE
Installer: Leave this manual with the appliance. Consumer: Retain this manual for suture reference.
CAUTION
Installation and service must be performed by a qualified installer, service agency or the gas fitter.
DANGER
Read and understand this manual. Improper installation, adjustment, alteration, service or maintenance can cause serious injury, property
damage or even death. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
WARNING
Some materials used in the manufacturing process of this product can expose you to Benzene which is known in the State of California to
cause cancer and birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov

XG0233 – 101023

General

Safety Alert Key

DANGER
Indicates a hazardous situation which, if not avoided, WILL result in death or serious
injury or property damage.
CAUTION
Indicates a hazardous situation which, if not avoided, WILL result in minor or moderate
injury.

WARNING
Indicates a hazardous situation which, if not avoided, COULD result in death or serious
injury or property damage.
NOTICE
Indicates practices that are important, but not related to personal injury.

Introduction
Congratulations on your purchase of a Montigo Fireplace. This system is designed to allow installation of gas fireplaces that cannot be done with a standard Direct Vent gas fireplace installation. ONLY USE WITH APPROVED FIREPLACES – see fireplace installation manual. Read through the fireplace’s installation & maintenance manual, as it must also be adhered to. Power Cord Harnesses: · EPVH10 – 10 foot power cord and harness · EPVH20 – 20 foot power cord and harness · EPVH40 – 40 foot power cord and harness · EPVH50 – 50 foot power cord and harness · EPVH60 – 60 foot power cord and harness · EPVH80 – 80 foot power cord and harness · EPVH100 -100 foot power cord and harness

Power vent specifications Voltage: ……… 120VAC 60HZ Current: ……… 0.8A RPM:…………. 2300 CFM: …………. 80
·Maintenance-free ball bearings ·Motor insulation class H
Figure 1 PV Specifications

IMPORTANT:
For vent configurations and power vent locations, refer to fireplace manual.
2

XG0233 – 101023

General

Section A: Before You Begin

IMPORTANT MESSAGE: SAVE THESE INSTRUCTIONS The unit must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the Local Gas Branch to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fireplace is installed in compliance with the manufacturers instructions and all applicable codes.
NOTICE
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control that
has been under water
NOTICE
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition
CAUTION
When cold air enters the warmer building interior, primarily at the air intake end, condensation may occur on the exterior of the flex
pipe. To limit this condensation, install insulation over the last twenty feet of flex pipe. Also, by sloping the last 20′-0″ feet of flex
pipe downward toward the exterior of the building, elimination of most of the condensation problems should occur. Ensure the termination is securely fastened, and sealed to the flex pipe. Fasten the termination to exterior of the building with water tight sealant and
the appropriate fasteners.

Contents
Safety Alert Key………………………………………………………………………. 2
Introduction …………………………………………………………………………… 2 Section A: Before You Begin ……………………………………………………………..3 Power Vent Compatibility …………………………………………………………………..4 3/5 CVS Venting ………………………………………………………………………………….6 Alternate venting table……………………………………………………………………….7
Section 1: Dimensions …………………………………………………………….. 8 PVW47 Product Dimensions………………………………………………………………8 PVW47 Mounting Flange Dimensions ……………………………………………….8
Section 2: Preparing the power vent ……………………………………….. 9 Flange setting notes……………………………………………………………………………9 Air diluter adjustment ………………………………………………………………………10
Section 1: Determine the power vent run ……………………………… 11 Venting Installation……………………………………………………………………………11 Example Installation………………………………………………………………………….11 Minimum Venting ……………………………………………………………………………..11 Example with downward venting……………………………………………………..12 Example with downward venting and power vent below fireplace level ……………………………………………………………………………………………………12 Installing the Power Vent (new construction)………………………………….13 Installing the Power Vent (retrofit installation)………………………………..18 Wiring Installation……………………………………………………………………………..21 PVWH-SIT Installation ……………………………………………………………………….22 PVBWH-SIT Installation……………………………………………………………………..26 Removing the cover screen ……………………………………………………………..28 Attaching the EPVH-XX Power vent cord …………………………………………29 PVW47 Motor Replacement……………………………………………………………..31 Replacement parts ……………………………………………………………………………32
Appendix A: Powervent Terminations …………………………………… 33 Appendix B: Warranty …………………………………………………………… 34
Appendix B: Warranty Continued ………………………………………….. 35
Appendix C: Amendment ………………………………………………………. 36
(Gas Fireplace / Equipment sold in the State of Massachusetts) ……………………………………………………………………………………………… 36

XG0233 – 101023

3

Installation

Power Vent Compatibility

DRL3613NI DRL3613NI-2 DRL4813NI DRL4813NI-2 DRL6013NI DRL6013NI-2 DRSQ34NI DRSQ34NI-2 DRSQ38NI-2 DRSQ38NI DRSQ42NI-2 DRSQ42NI DRSQ46NI-2 DRSQ46NI
D3615NI-2 D4815NI-2 D6315NI-2 D7215NI-2 D3615STNI-2 D4815STNI-2 D6315STNI-2 D7215STNI-2 H38FSD H38FSDI H42FSD H42FSDI H38PFI-2 HL38PFI-2 H38CLI-2 H38CRI-2 HL38CLI-2 HL38CRI-2

PVBWH-SIT PVWH-SIT PVBWH-SIT PVWH-SIT PVBWH-SIT PVWH-SIT PVBWH-SIT PVWH-SIT PVWH-SIT PVBWH-SIT PVWH-SIT PVBWH-SIT PVWH-SIT PVBWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT
PVBWH-SIT
PVBWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT PVWH-SIT

NO NO NO NO NO NO NO NO PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487
PVA5487
PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487 PVA5487

4

HARNESS/HARNESS+ BOARD REQUIRED REDUCER REQUIRED HARNESS/HARNESS+ BOARD REQUIRED REDUCER REQUIRED

R320 R420 R520 R720 R820 R320ST R420ST R520ST R620ST RP620 RP424PF R324STIO P38DFI-2 P42DFI-2 P52DFI-2 PL38DFI-2 PL42DFI-2 PL52DFI-2 L38FSD L38FSDI L42FSD L42FSDI L52FSD L52FSDI 30FIDIS-01 34FIDIS-01

NO NO NO NO NO NO NO NO NO NO NO
PVWH-SIT PVWH-SIT PVWH-SIT PVBWH-SIT PVBWH-SIT PVBWH-SIT
PVWH-SIT
PVWH-SIT
PVWH-SIT

NO NO NO NO NO NO NO NO NO NO NO
PVA5487 PVA5487 LVA54107 PVA5487 PVA5487 LVA54107
PVA5487
PVA5487
PVA5487

XG0233 – 101023

General

1Power Vent
· Power vent · PVW47

Required Components

2Harness Kit

3Reducer
(IF UNIT IS NOT 4/7)

4Power Cord

PVBWH-SIT
· IFC Control board · SIT PN: 0.584.665 · Montigo PN: GC3104
· Wiring Harness
This kit is designed to power vent fireplaces that were shipped with a Proflame 2 BASIC control board. The PVBWH-SIT kit contains a full load board as well as a power vent wiring harness.
PVWH-SIT
· Wiring Harness
This kit is designed to power vent fireplaces that already have a Proflame 2 control board. The PVWH-SIT kit contains a power vent wiring harness and requires the removal of the power vent jumper from the existing control board.

PVA5487
· For reducing 5/8 venting to 4/7
LVA54107
· For reducing 5/10 venting to 4/7
The PWV47 and the 200 series power vents use 4/7 venting, therefore fireplaces that use 5/8 or 5/10 venting must be reduced.
3/5 CVS Venting
· Permitted on Montigo 4/7 fireplaces
The fireplace manual may reference additional approved alternate venting manufacturers, though these are NOT all approved for power vent runs. The CVS run should follow the clearance and requirements as listed in the CVS specification sheet and manual. 5/10 fireplaces like the Phenom P/ PL52 can use this setup by adding the LVA54107 at the fireplace collar.

· Power Vent system power cord · EPVH-10 · EPVH-20 · EPVH-40 · EPVH-60 · EPVH-80 · EPVH-100

XG0233 – 101023

5

Friday, October 13, 2023 12:28:37 PM

ITEM NO. PART NUMBER

1

MEL90F-F

DESCRIPTION Vent Elbow, 90deg F/F

QTY. 1

2

MEL90F-M

Vent Elbow, 90deg M/F

5

3

MEXT3

Vent Pipe, 36inch F/M

7

4

PVA5487 VERTICAL VENT REDUCER 5″ & 8″ to 4″ & 7″ 1

5 PVW47-Full Assy

PVW47 Assy

1

6 Phenom Aspect

Phenom Aspect

1

General

Wednesday, June 14, 2023 12:42:47 PM

3/5 CVS Venting
5/8 COLLAR TO 3/5 PIPE TO 4/7 COLLAR VENTING DIAGRAM

Friday, October 13, 2023 12:28:37 PM Z:JooyoungCustom DrawingsFOR ALANPVW47 VentingPVW47 VENTING DIAGRAM

PVW47

PVVEX47-200 46DVA-AD-M2

3/5 CVS venting from a native 4/7 fireplace, to power vent

3456CDVVSA–XX4365DCVVAS

· 46DVA-AD-M1 (MONTIGO SUPPLIED)
CONVERTS MONTIGO 4/7 TO DURAVENT 4/7

·

5/8

COLLAR

DIMENSIONS ARE IN INCHES TOLERANCES:

NAME DATE

TO 3/5 PIPE TO 4/7 FRACTIONAL 1/32″

Drawn by

JL

TWO PLACE DECIMAL .015″

THREE PLACE DECIMAL .005″ Revision / Date

9/25/2023

Des3crip5tioPCn VVWS-4_37_6V_e_nting Diagram
COLLAR VENTING DWG. NO.PVW47 VENTING DIAGRAM

DIAGRAM·

ANGULAR .5 ALL BENDS ARE ASSUMED

Revision

MATERIAL

·

TO BE 90 UNLESS NOTED

Finish

OTHERWISE.

SCALE 1:24 WEIGHT:

SHEET 1 OF 2

OLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUTITTEHME WNORI.TTEPNAPRETRNMUISMSBIOENR OF CANADIAN HEADTIENSGCPRRIPOTDIOUNCTS IS PROHIBITEDQ. TY.

1

MEL90F-F P45V68VDDEVVXAVA4e–n7XtX-E3l3b25o50wCC,0V9V0SdSeg F/F

1

·

2

MEL90F-M

Vent Elbow, 90deg M/F

5

3

MEXT3

Vent Pipe, 36inch F/M

7

4 5

4466DDVA-AD-M21 PVA5487 VERTICAL VENT REDUCER 5″ & 8″ to 4″ & 7″ 1

PVW47-Full Assy

PVW47 Assy

1

·

6 Phenom Aspect 58DVA-PhAeDno-mMA1spect

1

46DVA-X35CVS (LOCALLY SOURCED OR MONTIGO SUPPLIED)
CONVERTS DURAVENT 4/7 TO DURAVENT 3/5 CVS (CVS VENT RUN) (LOCALLY SOURCED)
35CVS-X46DVA (LOCALLY SOURCED OR MONTIGO SUPPLIED)
3/5 INCREASER TO 4/6
46DVA-AD-M2 (MONTIGO SUPPLIED)
CONVERTS DURAVENT 4/7 TO MONTIGO 4/7 (POWER VENT) (MONTIGO SUPPLIED)

Wednesday, June 14, 2023 12:42:47 PM

46DVA-X35CVS
FOR 5/10 UNITS, ADD LVA54107
35CVS-36

The fireplace manual may reference additional approved alternate venting manufacturers, though these are NOT all approved for power vent runs.The CVS run should follow the clearance and requirements as listed in the CVS specification sheet and manual.
5/10 fireplaces like the Phenom P/PL52 can use this setup by adding the LVA54107 at the fireplace collar.

Z:JooyoungCustom Drawings58DVA58DVA35CVS-venting WednesZd:aJyW,oeJoduynnoeeusn1dg4a,y,C2u0Js2ut3noe1m21:4D4,r2a:240wi72n3Pg1sM2:5482 :D4V7AP58MDVA35CVS-venting

PROPRIETARY AND CONFIDENTIAL

NATIVE 4/7 FIREPLACE
5/8 COLLAR TO 3/5 PIPE TO 4/7 CO5L8DLVAA-RX35VCEVSNTING DIAGRAM

5/8 COLLAR TO 3/5 PIPE TO 4/7 COLLAR VENTING DIAGRAM DIMENSIONS ARE IN INCHES TOLERANCES: FRACTIONAL 1/32″

Drawn by

NAME JL

DATE

Description
58DVA35CVS-Venting Diagram

3/5 CVS venting from a native 5/8 TWO PLACE DECIMAL .015″

PV5V8EDXV4A7–A2D0-0M1 THREE PLACE DECIMAL .005″ Revision / Date

ANGULAR .5

Revision

DWG. NO. MATERIAL

58DVA35CVS-venting

ALL BENDS ARE ASSUMED

fireplace, to power vent TO BE 90 UNLESS NOTED

Finish

4P6VDVVEAX-4A7D–2M020 OTHERWISE.

SCALE 1:48 WEIGHT:

SHEET 1 OF 1

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CAPNAVDWIA4N7HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.

Z:JooyoungCustom DrawingsFOR ALANPVW47 VentingPVW47 VENTING DIAGRAM

4466DDVVAA–XA3D5-CMV2S 3456CDVVSA–XX4365DCVVAS

· 58DVA-X35CVS (LOCALLY SOURCED OR MONTIGO SUPPLIED)
CONVERTS 5/8 TO DURAVENT 3/5 CVS
· (CVS VENT RUN) (LOCALLY SOURCED)

35CVS-36

· 35CVS-X46DVA (LOCALLY SOURCED OR MONTIGO SUPPLIED)

PROPRIETARY AND CONFIDENTIAL

3/5 INCREASER TO 4/6

DIMENSIONS ARE IN INCHES TOLERANCES: FRACTIONAL 1/32″ TWO PLACE DECIMAL .015″ THREE PLACE DECIMAL .005″ ANGULAR .5 ALL BENDS ARE ASSUMED

Drawn by

NAME DATE JL 9/25/2023

Revision / Date Revision

Description
3355CCPVVVSSW–3_467__V_enting Diagram

DWG. NO.PVW47 VENTINGDTOIDMLEIEANRSGAINORCNAESSMA: RE IN INCHES

MATERIAL

FRACTIONAL 1/32″

· 46DVA-AD-M2 (MONTIGO SUPPLIED)

Drawn by

CNOAMNEVERDATTSE JL

Description
DU58RDAVAEN35TC4V/7S-TVOenMtiOngNTDIiGagOra4m/7

TO BE 90 UNLESS NOTED OTHERWISE.

Finish

58DVA-X35CVS SCALE 1:24 WEIGHT:

TWO PLACE DECIMAL THREESHPEELTA1COEF 2DECIMAL

OLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTAS NISGPURLOAHRIBITE.5D.

.015″ .005″

ALL BENDS ARE ASSUMED

· (POWER Revision / Date VENTDW)G. N(OM. O5N8TDIVGAO35SCVUSP-vPeLnItEinDg )

Revision

MATERIAL

The fireplace manual may reference additional approved alternate venting 58DVA-X35CVS

TO BE 90 UNLESS NOTED OTHERWISE.

Finish

SCALE 1:48 WEIGHT:

SHEET 1 OF 1

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.

58DVA-AD-M1

manufacturers, though these are NOT all approved for power vent runs. The

58DVA-AD-M1

CVS run should follow the clearance and requirements as listed in the CVS specification sheet and manual.

FOR 5/10 UNITS, ADD RVA51058

5/10 fireplaces like the Phenom P/PL52 can use this setup by adding the RVA51058 at the fireplace collar.

younZ:g\JCouosytoumngDrCauwistnogsm5D8raDVwiAng5s8D58VDA3V5AC5V8SD- vVeAn3ti5nCgVS-venting

IETPARROYPARINEDTCAROYNFIADNEDNCTIOANLFIDENTIAL

NATIVE 5/8 FIREPLACE

DIMENSIONS ARE IN INCHES TOLERANCES: FRACTIONAL 1/32″

Drawn by

NAME JL

DATE

Description
58DVA35CVS-Venting Diagram

6

TWO PLACE DECIMAL .015″ TDHIMREENESPIOLANCSEADRECINIMINALCHE.S005″ ATONLGEURLAANRCE.S5: AFRLLACBETINODNSAAL RE1A/3S2S”UMED

Revision / Date NAME

Revision

Drawn by

JL

DATE

DDWesGcr.ipNtiOon. 58DVA35CVS-venting
M5AT8ERDIALVA35CVS-Venting Diagram

TOWOBEP9L0ACUENDLEECSISMNALOTED.015″ Finish TOHTRHEERWPLISAEC.E DECIMAL .005″ Revision / Date

DSWCAGL. ENO1:.48 WE5IG8HTD: VA35CVS-venStHinEEgT 1 OF 1

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCATNIGOUNLIANRPAR.5T OR AS A WHOLE WIRTeHviOsioUnT THE WRITTEN PERMISSION MOAFTCERAINALADIAN HEATING PRODUCTS IS PROHIBITED.

XG0233 – 101023

Installation
The following venting components are approved for use with Montigo products. Please contact your local Montigo dealer for further information.

Alternate venting table

Component
Adaptors
Termination Inline PV
Rigid Pipe
Telescoping Pipe Elbows Wall Thimble Support ring Firestop Roof Flashing Storm collar

Duravent P/N
46DVA-AD-M1 46DVA-AD-M2 58DVA-AD-M1 46DVA-X35CVS 35CVS-X46DVA 58DVA-X35CVS
46DVA-HC 46DVA-VCH 35CVS-HCR 35CVS-VC
35CVS-06 35CVS-12 35CVS-24 35CVS-36
35CVS-12TA 35CVS-18TA
35CVS-E45 35CVS-E90
35CVS-WT 35CVS-WTP
35CVS-RS 35CVS-WS
35CVS-FS
35CVS-F 35CVS-DSA
35CVS-SC

Description
Montigo 4/7 to Duravent 4/6 at fireplace Duravent 4/6 to Montigo 4/7 at termination Montigo 5/8 to Duravent 5/8 at fireplace Duravent 4/6 reducer to 3/5 at fireplace 3/5 increaser to 4/6 at termination 5/8 reducer to 3/5 at fireplace
Duravent wall termination Duravent roof high wind termination 3/5 round wall termination 3/5 Roof termination
3/5 Diameter 6″ Pipe Length 3/5 Diameter 12″ Pipe Length 3/5 Diameter 24″ Pipe Length 3/5 Diameter 36″ Pipe Length
3/5 Diameter Adjustable Pipe 9″-12″ 3/5 Diameter Adjustable Pipe 12″-18″
3/5 Diameter 45° Elbow 3/5 Diameter 90° Elbow
3/5 Wall Thimble 3/5 Wall Thimble with insulation ring
3/5 Roof Support 3/5 Wall Strap
3/5 Firestop with support clamp
3/5 adjustable roof flashing 0/12 to 12/12 pitch 3/5 DSA Roof Flashing, up to 7/12 pitch
3/5 Roof storm collar

Notes Also used on Inline PV downstream Also used on Inline PV upstream
Also used on Inline PV downstream Also used on Inline PV upstream
Requires 35CVS-X46DVA 3/5 to 4/6 increaser Requires 35CVS-X46DVA 3/5 to 4/6 increaser

XG0233 – 101023

7

General

Section 1: Dimensions
PVW47 Product Dimensions

14″

13

1 8

13

1 8

PVW47 Mounting Flange Dimensions

14″

13

1 8

18″

Tuesday, September 26, 2023 7:53:45 AM

Y:ProductsResidential ProductsVentilation SystemsPVW47 Flush Wall Mount PVCad drawingsPVW47-Full Assy

sResidential ProductsVentilation SystemsPVW47 Flush Wall Mount PVCad drawingsPVW47-Full Assy

13

1 2

13

1 2

18″

13

1 2

14″

13 1

Friday, November 3, 2023 12:52:55 PM

13

3 16

8

1 16

FROM

THE BOTTOM OF THE PV

PROPRIETARY AND CONFIDENTIAL

13

1 8

DIMENS

13

1 8

REV.

REVISIONS
DESC1R4IP”TION

DATE

CHANGED BY

TOLERA FRACTI TWO PL THREE ANGUL

ALL BE

18″ –

.

14″ –

TO BE 9 OTHER

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION I

REVISIONS

DIMENSIONS ARE IN INCHES TOLERANCES: FRACTIONAL 1/32″

Drawn by

NAME JL

DATE Description

PVW47 Assy

RE1V3.

1 2

DESCRIPTION

DATE

CHANGED BY

TWO PLACE DECIMAL .015″
3 THREE PLACE DECIMAL .005″ 13 16 ” ANGULAR .5

Revision / Date Revision

A

ALL BENDS ARE ASSUMED

DWG. NO. MATERIAL

PVW47-Full Ass

1 –

.

TO BE 90 UNLESS NOTED

Finish

THE B8O1T6TO”M FORFOMTHE PV THE

INFORMATION

CONTAINED

IN

THIS

DRAWING

IS

THE

SOLE

PROPER1T8Y”OF

CA1N3A12D”IAN

HEATING

PRODUCTS.

ANY

OTHERWISE. REPRODUCTION IN PART

OR

AS

A

1W3H1O36LE”WITHOUT

THE

WRITTEN

PERMISSION

SCALE 1:8 WEIGHT:
OF CANADIAN HEATING

PRODUCTS

IS

PR

8

1 16

FROM

THE

BOTTOM OF THE PV

PROPRIETARY AND CONFIDENTIAL

13

1 8

14″

REVISIONS

DIMENSIONS ARE IN INCHES TOLERANCES: FRACTIONAL 1/32″

Drawn by

NAME DATE JL 7/17/2023

Description
PVW47 Full Assembly

REV.

DESCRIPTION

DATE

CHANGED BY

TWO PLACE DECIMAL .015″ THREE PLACE DECIMAL .005″ ANGULAR .5 ALL BENDS ARE ASSUMED

Revision / Date Revision

DWG. NO. MATERIAL

PVW47-Full Assy

.

TO BE 90 UNLESS NOTED

Finish

8

NAME DATE PVW47 Assy DIMENSIONS ARE IN INCHES

Description

OTHERWISE.

SCALE 1:8 WEIGHT:

SHEET 3 OF 3

TOLERANCES:

XG0233 – 101023 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.

FRACTIONAL 1/32″

Drawn by

JL

TWO PLACE DECIMAL

.015″

Revision / Date A

DWG. NO.

PROPRIETARY AND CONFIDENTIAL

Installation

Section 2: Preparing the power vent

Pilot Hole Setting Pilot Hole 1 Pilot Hole 2 Pilot Hole 3 Pilot Hole 4 Pilot Hole 5 Pilot Hole 6 Pilot Hole 6 (Flipped)

PV sticking out from wall 1¼” 2¼” 3¼” 4¼” 5¼” 6¼” 9″

Flange setting notes
The PVW47 is designed to work with an adjustable flange that can adapt to different finishing depths. Use the chart shown to plan out what setting you should have your flange set.
· PV sticking out from wall dimension – This dimension should be related to whatever finishing material will eventually be applied to the OSB board. Silicone behind the power vent flange may increase this measurement up to ¼”. Materials such as house wrap and furring strips underneath the final finishing will also factor into the final “finish depth”.
· 2×6 stud and 3/4 board dimension – The chart assumes using a 2″x 6″ stud and ¾” board. If your jurisdiction has finishing requirements different from this, then adjust your depths in relation to the chart accordingly.
· PV sticking out from stud dimension – The chart assumes using a 2″x 6″ stud and ¾” board. If your jurisdiction has finishing requirements different from this, then adjust your depths in relation to the chart accordingly.

2×6 stud and 3/4 board

PV sticking out from stud 1½” ½” -½” -1½” -2½” -3½” -6½”

NOTE: The flange can be flipped and affixed to Pilot Hole 6 to allow for up to a 9″
deep finish.

PILOT HOLE 1 PILOT HOLE 2 PILOT HOLE 3 PILOT HOLE 4 PILOT HOLE 5 PILOT HOLE 6

XG0233 – 101023

9

IMPORTANT
This adjustment must be done BEFORE installation. Changes to the air diluter CANNOT be made after the power vent is installed and the
vent run is connected.

Installation

Air diluter adjustment

Diluter closed: This is the factory setting, keep the diluter closed for distances greater than 30 feet.

Diluter open: Adjust to this setting for distances between 3 and 30 feet. Affix by bending the finger bend tab with a screwdriver.

RUN
30′ +

Finger bend adjustment

RUN
3′-30′

10

XG0233 – 101023

Installation

Section 1: Determine the power vent run

Venting Installation
THIS POWER VENT CAN BE ROUTED IN ANY PATH AS LONG AS IT MEETS THE FOLLOWING REQUIREMENTS:
· Maximum vertical distance above Fireplace floor= 60′ · Maximum effective length with 1 elbow = 125 ft. · Maximum effective length with 8 elbows = 104 ft. · Minimum venting is 3′ with one 90° elbow. · Maximum 8-90° elbows or 16-45° elbows · Maximum drop of 12 ft from highest point in run. · If vent pipe runs downward it cannot turn back upward.

NOTICE
For short vent runs, ensure the diluter is open. Adjust to this setting for distances between 3 and 30 feet. Affix by bending the finger bend
tab with a screwdriver.
Minimum Venting
Minimum venting is 3′ with one 90° elbow.

Friday, October 13, 2023 12:28:37 PM

Example Installation

ITEM NO. PART NUMBER

1

MEL90F-F

Multi-elbow

installations

are

possible

up

to

a

maximum

of

eight 90° 2

MEL90F-M

3

MEXT3

DESCRIPTION Vent Elbow, 90deg F/F Vent Elbow, 90deg M/F Vent Pipe, 36inch F/M

QTY.
1 1′
5 7

elbows. Two 45° elbows classify as 1 90° elbow

4

PVA5487 VERTICAL VENT REDUCER 5″ & 8″ to 4″ & 7″ 1

5 PVW47-Full Assy

PVW47 Assy

1

6 Phenom Aspect

Phenom Aspect

1

3
5′

3′
4
6′

6′

5

3′

6

1

2

6′

4′

2′
1

Z:JooyoungCustom DrawingsFOR ALANPVW47 VentingPVW47 VENTING DIAGRAM

PROPRIETARY AND CONFIDENTIAL

DIMENSIONS ARE IN INCHES TOLERANCES: FRACTIONAL 1/32″

Drawn by

NAME DATE JL 9/25/2023

Description
PVW47 Venting Diagram

TWO PLACE DECIMAL .015″ THREE PLACE DECIMAL .005″ Revision / Date

DWG. NO.PVW47 VENTING DIAGRAM

ANGULAR .5 ALL BENDS ARE ASSUMED

Revision

MATERIAL

TO BE 90 UNLESS NOTED

Finish

MAX OTHERWISE.

SCALE 1:24 WEIGHT:

SHEET 2 OF 2

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED.

ELBOW #

VENTING

RUN

1 ELBOW

125

2 ELBOW

122

3 ELBOW

119

4 ELBOW

116

5 ELBOW

113

6 ELBOW

110

7 ELBOW

107

8 ELBOW

104

Adjust the diluter to fully open for distances between 3 and 30 feet. Affix by bending the finger bend tab with a screwdriver. Restrictor may need to be adjusted at fireplace to get the best looking flame

XG0233 – 101023

11

Installation

Example with downward venting
Maximum downward drop is 12ft from highest point of run. No rise is permitted after the downward section. Maximum 4 elbows.

6′
1 2

24′

12′

12′ FROM HIGHEST POINT OF RUN

3

6′

Example with downward venting and power vent below fireplace level
Maximum downward drop is 12ft from highest point of run. No rise is permitted after the downward section. Power vent can be installed 8ft bellow fireplace, but maximum effective run must be reduced to 56ft including 4 elbows.
4′ 2′
1
2

BOTTOM OF FIREPLACE LEVEL

4′
12′ FROM HIGHEST POINT OF RUN
8′

4′

3

4

6′

DOWNWARD VENTING TABLE (POWER VENT BELOW FIREPLACE LEVEL)

1′

2′

3′

4′

5′

6′

7′

8′

9′

10′

11′

12′

ELBOW #

DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN DOWN

3 ELBOW

114

109

104

99

94

89

84

79

74

69

64

59

4 ELBOW

111

106

101

96

91

86

81

76

71

66

61

56

5 ELBOW

54

49

44

39

34

29

NA

NA

NA

NA

NA

NA

6 ELBOW

51

46

41

36

31

26

NA

NA

NA

NA

NA

NA

7 ELBOW

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

8 ELBOW

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

12

XG0233 – 101023

NOTICE
The following steps are good faith instructions written and designed to result in the best possible performance for the power vent, as well as minimize the impact on the building envelope. Diverting from these instructions due to local code, or other reasons should be done with
common sense and standard building knowledge in mind.
Installing the Power Vent (new construction)

Installation

14½” 14½”

Step 1: Using a level and square, ensure the opening is square and the correct dimensions as noted in the previous section. The power vent is zero clearance to combustibles, so wood framing is permitted.

Step 2: Standard construction OSB can be used to finish the exterior wall around the power vent. Ensure the board is flush with the opening with no gaps.

XG0233 – 101023

13

Installation
FINAL STEP BEFORE INSTALLING THE POWER VENT:
Silicone Rubber Sealant should be applied around
the perimeter of the opening right before installing the power vent.

Step 3: Homewrap can then be applied to the exterior side of the OSB. Using a utility knife, cut out the opening for the power vent and fold the wrap into the cavity. Tape or tack this down to prevent movement, then re-enforce the folded edge with flashing tape.

Step 4: Furring strips are attached the exterior wall (ensure these are attached to the studs underneath the OSB, and not just into the board.) Furring strips should be cut well short of the PV opening, as the power vent flange will protrude well around the perimeter of the opening.

NOTICE
These instructions specifically apply to jurisdictions that require a ventilated rain screen or “air gap” Adjust your installation for codes in
your area.

14

XG0233 – 101023

SEALING THE POWER VENT: Silicone Rubber Sealant should be applied to the gap between the power vent and the trim AFTER installing. This is to prevent the seal breaking during install.

Installation

Step 5: At this point the power vent should have its trim kit attached as described in the previous section. Carefully manoeuver the power vent into the opening and ensure that the unit is square to the opening. Using the included screws, attach the trim into the wall (ensure that the screws are penetrating into the studs and not just the OSB.)

Step 6: Flashing tape should be applied around the perimeter of the flange. Ensure the edges are flush against both the homewrap and the flange to ensure that water intrusion will not occur.

NOTICE
Paint can be applied to the power vent before installation. Ensure you use a high temperature paint. Touch ups may be required after
installation is completed.

XG0233 – 101023

15

Installation
SEALING THE TRIM BOX: Silicone Rubber Sealant should can be applied to the gap between the power vent and the trim box at this
stage.

Step 7: A trim box around the perimeter of the power vent is recommended to ensure a tight seal against weather. This can be done in a similar fashion to a window or door trim box.

Step 8: Rain flashing must be attached above the power vent (or trim box.) This must be sealed and taped as well.

POWER VENT WATER DRAINAGE LIP: The power vent is designed to be
internally water tight, and therefore includes a lip to allow for drainage. Ensure that this lip not obstructed
by the trim box or siding.
16

XG0233 – 101023

FINAL SEALING: Silicone Rubber Sealant should can be applied to the gap between the siding and the trim box at this stage.

Installation
FINAL INSPECTION: Silicone Rubber Sealant should cover the gaps between the power vent and trim box, as well as between the siding and trim box.

Step 9: Final siding can be attached at this time as per the manufacturers specifications.

PAINTING: Paint can be applied to the power vent before or after installation. Ensure you use a high temperature paint. Touch ups may be required after installation is completed.

XG0233 – 101023

17

NOTICE
The following steps are good faith instructions written and designed to result in the best possible performance for the power vent, as well as minimize the impact on the building envelope. Diverting from these instructions due to local code, or other reasons should be done with
common sense and standard building knowledge in mind.
Installing the Power Vent (retrofit installation)

Installation

INSIDE WALL 18″
18″

14½”

14½”

Step 1: Using a utility knife or similar tool, cut out an 18″ x 18″ perimeter in order to fit the powervent frame onto the studs. Additionally, remove any insulation and vapor barrier that exists within this space.

Step 2: Add a header and sill in order to properly support the power vent. Using a square and tape measure, ensure the inner dimensions are 14½” x 14½”.

18

XG0233 – 101023

Installation
TOP VIEW: Trim kit is flipped and attached to the inside stud
edge.

Step 3: Using a sawsall or similar tool, carefully cut out the perimeter created by the header, studs, and sill.

Step 4: At this point the power vent should have its trim kit attached as described above. Carefully manoeuver the power vent into the opening and ensure that the unit is square to the opening. Using the included screws, attach the trim into the wall studs.

XG0233 – 101023

19

Installation

OUTSIDE WALL

RAIN FLASHING: Rain flashing must be attached above the power vent (or trim box.) This must be sealed and taped as well.

Step 5: Seal the perimeter of the power vent with the siding as per local codes.

POWER VENT WATER DRAINAGE LIP: The power vent is designed to be internally water tight, and therefore includes a lip to allow for drainage. Ensure that this lip not obstructed by the trim box or siding.

20

XG0233 – 101023

Installation

Wiring Installation

Connect the wiring to the external power vent termination as outlined in the previous section, and connect the wiring to the fireplace as outlined in the schematic below. Ensure that the proper clearances are maintained for the wiring and conduit.
· When installing the wiring it must never run above the vent run and it must be at least 1″ clear of all venting.
UNIVERSAL POWER VENT

1″ Clearance
WIRING DIAGRAM

TEST PORT

MAIN POWER TO THE ORIGINAL FIREPLACE HARNESS
120VAC, 60 HZ, 6 AMPS

SPARK
SENSOR
MAIN ON/OFF SWITCH

YELLOW YELLOW
X2 X3
X4

885 PROFLAME

X5

PILOT

YELLOW/GREEN ORANGE GREEN

X6

X7 BURNER

X8

X9

LD1 LD2 LD3

LED LIGHTS

LED1 – RED LED

X0A

LED2 – AMBER LED

FUSE 3.15A T

GREEN

X1

WHITE

BLACK

NL

BLACK
VARIABLE SPEED COMFORT FANS

HALOGEN LIGHTS

BLACK

X10

WHITE

RED

X11

RED

110V BV

TRANSFORMER

X12

MALE CONNECTOR

ORANGE MARKED

X13

BULB TYPE G4 SOCKET
12V 10W

GREEN WHITE BLACK

FEMALE CONNECTOR CONNECT TO AUXILIARY

BLACK

GREEN WHITE BLACK YELLOW
YELLOW

POWER VENT HARNESS

WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

XG0233 – 101023

21

NOTICE
Below are the instructions for the PVWH-SIT, designed for full load units with an existing Proflame 2 full load control board. For instructions on the PVBWH- SIT, please refer to PVBWH-SIT section of this manual.

PVWH-SIT Installation

1

Shut off the power to the fireplace before starting.

Locate control board inside the fireplace. It might be

attached to the bottom of fireplace or on the tray.

Control board is secured with two Velcro strips.

Pull out control box/tray from fireplace so all connections are clearly visible, if needed cut zipties on wiring harness to get extra slack.

General

3

Locate combination gas valve and unplug connectors from green and red solenoid valve and yellow ground

from valve body.

Unplug the rest of the connections from control board.
4 Its recommended to take a photo of connections before unplugging. Note: do not discard any wiring (except valve control harness).
2 Unplug valve control harness from X5 plug on control board and remove battery backup (held with Velcro)

Discard valve control wiring harness

22

XG0233 – 101023

General

5 Remove control board lid by gently prying tabs on all 4 corners with screwdriver

7 Discard jumper OR place jumper on only one terminal for storage. Once complete, re-attach module cover.

Lid removed
6 Locate jumper pin on control board

Removing jumper

XG0233 – 101023

23

Installation

8 Unpackage universal power vent harness.

10 ATTENTION! ORANGE MARKED plug connects to the control board (X13-X12). Do not plug pigtail female molex to the board.

9

Connect following PV wiring harness connectors to the control board: female power plug to X1, valve harness to X5, ORANGE MARKED male molex to X13-X12:

Bring control board and PV wiring harness combo to the
11 fireplace so its in the reach of fireplace wiring harness. If applicable mount control board back to the tray Connect valve control harness wires to the valve.

24

XG0233 – 101023

Installation

12 Connect pilot wiring to control board (X2 & X3), connect override On/Off switch to X4, connect stepper motor (if applicable) to X6.

14 Plug female molex connector from fireplace to control board X11-X10 slot.

13 Connect transparent female power plug (from fireplace) to white inverted male power plug (PV harness).

15 Connect male molex from fireplace (if applicable) to pigtail PV female molex.

XG0233 – 101023

25

NOTICE
Below are the instructions for the PVBWH-SIT, designed for basic units without an existing Proflame 2 full load control board. For instructions
on the PVWH-SIT, please refer to PVWH-SIT section of this manual.

PVBWH-SIT Installation

1

Shut off the power to the fireplace before starting.

Locate control board inside the fireplace. It might be

attached to the bottom of fireplace or on the tray.

Control board is secured with two Velcro strips.

Pull out control box/tray from fireplace so all connections are clearly visible, if needed cut zipties on wiring harness to get extra slack

Installation
Unplug rest of connections from control board. Discard
3 control board. Note: Do not discard wiring in the fireplace.

2

Locate combination gas valve and unplug connectors from green and red solenoid valve and ground from valve body.

Discard valve control wiring harness
Unpack control board and wiring combo from PVBWH-
4 SIT kit and bring to the fireplace so its in the reach of fireplace wiring harness. If applicable mount control board back to the tray.

26

XG0233 – 101023

Installation

Connect pilot wiring to control board (X2 & X3), connect
5 LVT wiring (wall switch) to X4, Connect transparent female power plug (from fireplace) to white inverted male power plug (PV harness)

7 Connect the board harness to the PV cable (EPVH-XX):

6 Connect valve control harness wires to the valve:

XG0233 – 101023

27

Removing the cover screen

Operation

Removal: Pull up the screen by lifting by the tabs at the base of the screen, you can then tilt at the top of the screen and pull away. Store the screen somewhere safe from damage.

28

XG0233 – 101023

Installation

Attaching the EPVH-XX Power vent cord
1 Remove the front cover as described in the previous section.
2 Remove the 3 screws holding on the inner block plate.

4 Apply silicone to between the insulation sleeve of the power vent cable and the wire harness plate

5 Reattach the wire harness plate now complete with the siliconed EPVH cable
3 Remove wire harness plate from the powervent and connect to the cord

Connect the wire harness plate to the cord
XG0233 – 101023

6 Apply silicone to the outside of the wire harness plate, spread to ensure coverage of all seams and gaps 29

7 INSIDE OF PV: Attach the EPVH-XX of the hook located in the upper left side.

Installation

8 Connect the Power vent motor harness to the EPVH cable.
9 Re-attach the inner block plate and front cover.
30

XG0233 – 101023

Installation

PVW47 Motor Replacement
1 Remove the front cover as described in the previous section.
2 Remove the 3 screws holding on the inner block plate.

4 Remove the motor plate by unscrewing the 4 screws attaching it to the powervent box.

3 Remove the tube and 3 x wires from the fan blower (green, white and black)

Pulling out the motor/ motor plate
5 Replace with new powervent fan blower. Ensure that all wires and tubes that were removed are re-attached.

XG0233 – 101023

31

PVW47 SPARE PARTS LIST Replacement parts

3

5

1

Appendix

No.# 1 2 3
4 5

Part Description REPLACMENET BLOWER MOTOR FOR PVW47
SWITCH, VACUUM, 0.20″ “ENDURA” REPLACEMENT PV Mounting Trim
HARNESS, POWER VENT (PVW47) REPLACEMNT OF PVW47 FRONT COVER

Part RBMREC RMT-
REC RFC-

PROPRIETARY AND CONFIDENTIAL

2

4

Item

1 REPLACEMENT BLOWER MOTOR AND PLATE

DIMENSIONS ARE IN INCHES TOLERANCES: FRACTIONAL 1/32″ TWO PLACE DECIMAL .015″
SKU THREE PLACE DECIMAL .005″
ANGULAR .5 ALL BENDS ARE ASSUMED
RBM-PVW47 TO BE 90 UNLESS NOTED
OTHERWISE.

Drawn by

NAME DATE JL 7/17/2023

Revision / Date Revision

Finish

Description
PVW47 SPARE PA

DWG. NO. MATERIAL

PVW47-Full Assy

SCALE 1:8 WEIGHT:

SH

2 SWITCH, VACUUM, 0.20″ REC1226 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PRO

3 REPLACEMENT PV MOUNTING TRIM

RMT-PVW47

4 HARNESS, POWER VENT (PVW47)

RECA146

5 REPLACEMENT FRONT COVER

RFC-PVW47

32

XG0233 – 101023

NOTICE
All clearance measurements from the side/edge of powervent frame

Appendix

Appendix A: Powervent Terminations

D
E L
B

F B

H

B

B

I
F A

NOTICE
Default to local code if a greater clearance is required.

M K

K

L

G C

A

Vent Terminal

Air Supply

Terminal not permitted

Location

Canada*

USA**

A Clearances above grade, veranda, porch, deck, or balcony

12 inches

12 inches

B Clearance beside or below a window or door that may be opened.

12 inches (30 cm) for appliances 100,000 BTU, 36 inches (91cm)
for appliances > 100,000 BTU.

9 inches for appliances > 10,000 BTU and
50,000 BTU *12 inches for appliances > 50,000
BTU.

C Clearance to permanently closed window recommended to prevent condensation on window.

12 inches

12 inches

D

Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet from the center line of the terminal.

2 inches

2 inches

E Clearance to unventilated soffit from the center line of the terminal.

2 inches

2 inches

F Clearance to outside corner

6 inches

6 inches

G Clearance to inside corner from the center line of the terminal.

6 inches

6 inches

H Clearance to each side of center line extended above meter/regulator assembly.

3 feet (90 cm) min.

within a height of 15ft (4.5m) above the meter

**

or regulator assembly

I Clearance to service regulator vent outlet.

3 ft.

**

J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance.

12 inches (30 cm) 100,000 BTU.
36 inches (91) cm > 100,000 BTU

19 inches for appliances > 10,000 BTU and
50,000 BTU. 12 inches for appliances > 50,000
BTU.

K Clearance to a mechanical air supply inlet.
L Clearance above paved side-walk or a paved driveway located on public property M Clearance under veranda, porch, deck, or balcony

6 ft.
^ 7 feet (2.1 m) min. 2 inches (5 cm) min.

3 feet (90cm) min. above if within 10ft (3m)
horizontally
**
2 inches min.

1 In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code. 2 USA – In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code,
* Clearance in accordance with local installation codes and the requirements of the gas supplier ^ A vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

XG0233 – 101023

33

Appendix

Appendix B: Warranty

MONTIGO RESIDENTIAL WARRANTY PROGRAM
Empire Comfort Systems, Inc. and/or Empire Comfort Systems Canada, Inc. (collectively referred to herein as “The Companies”), warrants the Montigo gas appliance (referred to herein as ‘the appliance’) to be free from defects in materials and workmanship at the time of manufacture. The gas appliance and related components are further subject to the terms and conditions set forth below.
This warranty covers the following Montigo product series: Distinction, H, I, L, Linear P and PL, R, RP, Mahana and DelRay

Component Firebox, heat exchanger

Coverage Period 15 years

Labor Coverage 1 year

Main burner

15 years

1 year

Gas control valve and related control components (pilot assembly, spark electrode flame sensors, thermopile)

1 year

Electrical components (internal blowers, ignition control module, wiring, switches, remote control systems, blower control module, accent bulbs)

1 year

Firebox media (logset, glass beads, river rocks)

1 year

Glass (thermal breakage)

1 year

Plated, painted finishes (including interior reflective glass)*

1 year

Refractory lining

1 year

Mesh/Glass safety barriers

1 year

Power Vent Control box

1 year

Montigo Venting (excluding terminations)

15 years

1 year
1 year
1 year 1 year 1 year 1 year 1 year 1 year 1 year

  • Exterior painted surfaces exempt
    QUALIFICATIONS TO THE WARRANTY
    This Warranty only covers gas appliances installed in the United States or Canada.
    To receive the benefits of this warranty, the appliance must be purchased, installed and serviced annually by a dealer authorized by The Companies for the warranty to be valid.
    The gas appliance must be installed by a licensed professional in accordance with The Companies’ installation instructions and local building codes. The warranty on the appliance covers only components manufactured by The Companies. The use of components manufactured or supplied by other manufacturers and used in conjunction with the appliance could create serious safety hazards, may result in the denial of certification by recognized national safety agencies and could violate local building codes. Such use may untimely void this warranty. This warranty does not cover any damages occurring from the use of any components not manufactured or supplied by The Companies.
    The appliance must be subjected to normal use. The appliance is designed to burn natural gas (NG) or liquefied petroleum (LP) only. Burning conventional fireplace fuels such as wood, coal or any other solid fuel will cause damage to the appliance, produce excessive temperatures will result in a fire hazard and void all

warranties. This warranty is transferable. The appliance must remain in its original place of installation to be valid.
If the components of the appliance covered by this warranty are found to be defective within the time frame stated (see The Companies investigation of claims), The Companies will, at its option, replace or repair defective components of the appliance manufactured by The Companies at no charge and will also pay for labor costs (in accordance with schedule) incurred in replacing or repairing components. If repair or replacement is not commercially practical, The Companies will, at its sole discretion, fully discharge all obligations under the warranty by refunding the verified dealer purchase price of the appliance, excluding the cost of labor unless the labor is covered by the terms of the warranty.
This warranty covers only parts and labor as provided above. In no case shall the companies be responsible for materials, components or construction, which are not manufactured or supplied by The Companies, or for the labor necessary to install, repair or remove such materials, components or construction. All replacement or repair components will be shipped F.O.B. from the nearest Company factory.
LIMITATION ON LIABILITY
It is agreed and understood that The Companies sole obligation, and purchaser’s exclusive remedy under this warranty, under any other warranty, expressed or implied, or in contract, tort or otherwise, shall be limited to repair, replacement or refund as specified above. The opinion of The Companies with respect to these matters shall be final.
In no event shall The Companies be responsible for any incidental or consequential damages caused by (but not limited to) improper installation, installation by an unqualified or unauthorized installer, accident, lack of regular maintenance, user error, abuse, misuse, Acts of God, power surges, floods, natural disasters, force majeure, defects in its appliance whether such damage occurs or is discovered before or after replacement or repair, and whether or not such damage is caused by The Companies negligence. Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. The duration of any implied warranty with respect to the appliance is limited to the duration of the foregoing warranty. Some jurisdictions do not allow limitations on how long an implied warranty lasts, so the above limitation or exclusion may not apply to you.

34

XG0233 – 101023

Appendix

Appendix B: Warranty Continued

EXCLUSIONS TO WARRANTY
Corrosion or rust of any kind due to a lack of maintenance, inadequate combustion air or improper venting and corrosive chemicals/environments, expansion and contraction of metals or minor movements of components causing noise are not covered by this warranty.
Willful misconduct (i.e. use of the appliance with problems known to the purchaser and causing further damages), including unauthorized or self- performed ‘fixing’ or exploration of the appliance’s internal workings will void the warranty.
Appliances on which the serial number has been altered, defaced, removed or made illegible will void the warranty.
Costs incurred for diagnosis, service work, shipping and handling of defective or replacement parts are not covered under this warranty.
The published warranties are not applicable for any equipment manufactured by The Companies that has been sold direct to the consumer via internet or auction websites. The Companies do not endorse, approve or certify any online sale of its products through auction websites, online retailers or any other method of online sales direct to consumers.
INVESTIGATION OF CLAIMS AGAINST WARRANTY
The Companies reserve the right to investigate any and all claims against this warranty and decide upon method of settlement.
The Companies are not responsible for work done without written consent of The Companies.
The Companies shall in no event be responsible for any warranty work done without first obtaining the Companies written consent.
The Companies employees and dealers have no authority to make any warranties to neither alter this warranty nor authorize any remedies in addition to or inconsistent with those stated within this warranty.
IF WARRANTY SERVICE IS NEEDED
To make a claim under this warranty, contact your installing dealer or contractor. The installing dealer is responsible for providing service and will contact the companies to initiate warranted parts replacements. In the event the installing dealer is unavailable, contact your nearest authorized Montigo dealer (www.Montigo.com) or contact Montigo direct at techsupport@ montigo.com. Ensure you have your sales receipt and the model and serial number of your appliance.
DO NOT ATTEMPT TO DO ANY SERVICE WORK YOURSELF
If you cannot locate the installing dealer, or nearest dealer/ distributor, you must notify The Companies in writing.

USA Offices 6955 Salashan Parkway Ferndale WA, 98248 techsupport@montigo.com
Canadian Offices 27342 Gloucester Way Langley, BC V4W 4A1 techsupport@montigo.com
The terms and conditions of this warranty may be altered or amended from time to time without prior notice. WARRANTY PERIOD: Warranty coverage begins on the date of original purchase. In the case of new construction, warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent, authorized Company dealer/ distributor, whichever occurs earlier.

XG0233 – 101023

35

Appendix

Appendix C: Amendment
(Gas Fireplace / Equipment sold in the State of Massachusetts) 5.08: Modifications to NFPA-54, Chapter 10

(1) Revise NFPA-54 section 10.5.4.2 by adding a second exception as follows:
Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device that will automatically shut off the gas to the burner in the event of a sustained back-draft.
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery backup may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2042 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
(3) After NFPA-54 section 10.10.4.2 add a new section 10.10.4.3 as follows:
When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation shall be submitted to the Inspector and the serving gas supplier for review and approval.
Extraction from: Massachusetts Rules and Regulations
5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

36

XG0233 – 101023

Notes

XG0783 – 021121

37

Installation & Maintenance Manual
PVW47
Flush Wall Mount Power Vent
XG0233 – 101023

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Montigo User Manuals

Related Manuals