Honeywell TC300 Commercial Thermostat Connected Device
Product Information
Specifications
- Product Name: TC300 Commercial Thermostat
- Usage: Connected device for commercial buildings
- Power Supply: 24VAC from a UL Listed Class2 24VAC transformer
- Mainboard PCBA Substance: Lead, Lead oxide
Product Usage Instructions
Mounting and Installation
Before installing the TC300 Commercial Thermostat, carefully read and
follow the instructions provided to prevent any damage or hazardous
conditions. Ensure that the product ratings match your application
requirements.
- Disconnect the power supply to prevent electrical shock before installation.
- Only trained, experienced service technicians should perform the installation.
- Verify proper wiring compliance with all applicable codes and regulations.
- After installation, check the product’s operation to ensure functionality.
Location Considerations
Avoid installing the thermostat in areas affected by drafts, hot/cold air,
radiant heat, concealed pipes, or unheated spaces. Refer to the manual for
detailed location guidelines.
Using External Temp./Hum. Sensors
When utilizing remote-mounted sensors for ambient conditions, ensure the
thermostat is accessible for temperature and setting adjustments.
WEEE Disposal
Properly dispose of the product following Waste of Electrical and
Electronic Equipment (WEEE) disposal regulations. Do not discard with regular
waste; check local laws for correct disposal methods.
Power Supply Guidelines
The thermostat requires a 24VAC power supply from a specific transformer.
Ensure half-wave rectifier compatibility and maintain wiring polarity to
prevent equipment damage.
MERCURY NOTICE
If replacing a control containing mercury, follow proper disposal
procedures. Contact local waste management for recycling instructions.
Regulation (EC) No 1907/2006
Be aware of substances contained in the product above threshold levels.
Follow Reach Regulation guidelines for compliance.
FAQ
Q: Can I use multiple devices with half-wave power supplies on a single
transformer?
A: Yes, you can power multiple devices with half-wave power supplies from a
single, grounded transformer. Ensure proper wiring polarity to prevent
equipment damage.
TC300 Commercial Thermostat
CONNECTED DEVICE FOR COMMERCIAL BUILDINGS
MOUNTING & INSTALLATION INSTRUCTIONS
INTRODUCTION
TC300 Commercial Touchscreen Thermostat is designed to be wall-mounted
indoors. Mount in a clean, dry location away from windows, air ducts, and
other places where environmental factors may affect temperature and humidity
readings. If you mount the Thermostat on the interior of an outside wall,
thoroughly insulate it so the outside air behind the sensor does not affect
the sensor reading.
To meet the requirements of the Americans with Disabilities Act, mount no
higher than 48″ from the floor and with a minimum clear floor space of 30″ X
48″ (760 X 1220 mm).
Supported Documents
- TC300 Commercial Thermostat Datasheet (31-00645)
- TC300 Commercial Thermostat User Guide (31-00644)
- TC300 Commercial Thermostat Pocket guide (31-00648)
- TC300 Deco Plate Pocket guide (31-00657)
- TC300 BACnet Integration guide (31-00646)
- TC300 Safety Sheet (31-00643)
When installing this product
- Read these instructions carefully. Failure to follow them could damage the product or cause a hazard-ous condition.
- Check the ratings given in the instructions and marked on the product to make sure the product is suitable for your application.
- Installer must be a trained, experienced service tech-nician.
- After installation is complete, check the product operation.
- Be sure wiring complies with all applicable codes, ordinances, and regulations.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect the power supply before beginning installation to prevent
electrical shock and equipment damage. More than one power supply may have to
be disconnected.
MERCURY NOTICE
If this control is replacing a control that contains mercury in a sealed tube,
do not place your old control in the trash. Dispose of it properly. Contact
your local waste management authority for instructions regarding recycling and
the proper disposal of an old control. If you have questions, contact
Honeywell Customer Care Center.
Location
Do not install the Thermostat unit where it can be affected by:
- drafts or dead spots behind doors and in corners.
- hot or cold air from ducts.
- radiant heat from sun or appliances.
- concealed pipes and chimneys.
- unheated (uncooled) areas such as an outside wall behind the thermostat.
IMPORTANT
To avoid electrical interference, which can cause erratic performances, keep
wiring runs as short as possible and do not run thermostat wires adja-cent to
the line voltage electrical distribution sys-tems. Use shielded cable. The
cable shield must be grounded only at the controlled equipment case.
USING ONBOARD TEMPERATURE SENSOR
Install the Thermostat about 4 ft. (1.2m) above the floor in an area with good
air circulation at average temperature. (See Fig. 1). Confirm mounting height
meets Americans with Disabilities Act requirements.
USING EXTERNAL TEMP./HUM. SENSORS
When using the remote-mounted temperature (and humidity) sensor(s) to sense
ambient conditions, install the Thermostat in an area that is accessible for
setting and adjusting the temperature and settings.
WEEE
WEEE (Waste of Electrical and Electronic Equipment)
- At the end of the product life, dispose of the packaging and product in an appropriate recycling center.
- Do not dispose of the device with the usual domestic refuse.
- Do not burn the device.
This symbol on our product shows a crossed-out “wheelie-bin” as required by law regarding the Waste of Electrical and Electronic Equipment (WEEE) disposal. This indicates your responsibility to contribute to saving the environment by proper disposal of this Waste i.e. Do not dispose of this product with your other wastes. To know the right disposal mechanism please check the applicable law.
Regulation (EC) No 1907/2006
According to Article 33 of Reach Regulation be informed that the substances
listed below may be contained in these products above the threshold level of
0.1% by weight of the listed article.
Product/Part Code| Substance
Name
| CAS
Number
---|---|---
Only TC300 thermostat mainboard PCBA| Lead| 7439-92-1
Lead oxide| 1317-36-8
Power supply guidelines and requirements
The thermostat uses 24VAC power from a UL Listed Class-2 24VAC transformer
(not provided in the kit). It also uses a half-wave rectifier to convert the
AC power supply to onboard power. This enables multiple devices with half-wave
power supplies to be powered from a single, grounded transformer.
WARNING
Half wave devices and full wave devices must not use the same AC transformer.
You must maintain wiring polarity. Failure to do so can result in equipment
damage. If the HVAC equipment has an internal circuit board that is powered by
the same transformer that will power the Thermostat, verify that it is NOT
full wave.
Power supply wire sizing
Long power supply wiring runs require selecting the wire gauge appropriately.
If the wire gauge is inadequate the increased resistance and associated
voltage drop may result in insufficient voltage supply to the Thermostat. The
recommended wire gauge guidelines are as follows.
-
- Min. Load = 4VA (all DOs OFF, No Sylk sensor).
- If the 14-18AWG wire is used for R, C terminal,
- Max. Load = 4A, 96VA (all DOs ON).
- If the 20-22AWG wire is used for R, C terminal
- Max. Load = 3A, 72VA (all DOs ON).
- If the 24-26AWG wire is used for R, C terminal,
- Max. Load = 2A, 48VA (all DOs ON).
DO1, DO2, DO3, DIO1, and DIO2 all relay outputs are powered from the external
transformer. The minimum load includes Thermostat and analog outputs at full
load (Max. 10V voltage output with 2Kohms load).
Every relay output is N.O. (Normally Open) contacts with a maximum switch
rating of 24VAC @1A (24VA). The allowed maximum load is 96VA, which assumes
all 5 relay output loads are powered from the transformer. Actual power
requirements depend on connected loads.
IMPORTANT
Use an UL Class 2 rated Transformer or a lesser capable transformer.
WARNING
Ensure that Thermostat power connections only use R and C terminals. COM
should only be used for analog inputs/outputs. Failure to follow these
instructions may result in Thermostat operational and communication failures
or equipment damage.
Mounting wallplate on the drywall
Mount the wallplate vertically on the wall. It supports 14-26AWG (0.2-1.5mm2 for solid or stranded, max 2.5mm2 for solid) wires.
NOTE: If you are using a TC300 Deco plate for thermostat mounting, refer to the Deco plate pocket guide (31-00657) also.
- At the bottom of the thermostat, loosen the Security screw using a screwdriver by turning it counterclock-wise direction.
- Before mounting the wallplate, make sure that the thermostat wires are stripped to the length marked on the wallplate.
- Position and level the wallplate along the wall and mark the drilling location using a pencil.
- Remove the wallplate and drill two pilot holes on the wall, on the marks. For drywall, drill 3/16” (5mm) holes. For firmer material such as plaster, drill 7/32” (6mm)holes.
- Gently tap anchors (provided in the kit) into the pilot holes until flush with the wall.
- Pull the wires through the wiring opening of the wall-plate and position the wallplate over the mounting holes. See Fig. 8 Wiring.
- Insert the screws into the holes and tighten (screw torque 0.1Nm).
Mounting the wallplate on the junction box (optional)
TC300 can support vertical mounting of US 2″x4″ junction box, vertical and
horizontal mounting of 7575mm, 8686 and European round(ø71 for German and
ø75 for French) junction boxes.
NOTE: Use TC300 Deco plate for mounting if you are not using US 2”4” or UK 7575mm junction boxes. Refer to the Deco plate pocket guide (31-xxxxxx).
- Install the junction box and perform the wiring as per its manufacturer’s instructions.
- Before mounting the wallplate, make sure that the thermostat wires are stripped to the length marked on the wallplate.
- Pull the wires through the wiring opening of the wall-plate and position the wallplate along the junction box to align the mounting holes. For junction box screw holes, refer to Fig. 5.
- Insert the screws into the holes and tighten them.
Accessories ordering part numbers
Terminal identification
WARNING
Do NOT wire the thermostat to line voltage.
Table 2. Terminal Identification
Terminal Name| Terminal Label| ****
Description
---|---|---
UIO1| UIO1| Universal input/output
COM| COM| Common
UIO2| UIO2| Universal input/output
COM| COM| Common
UIO3| UIO3| Universal input/output
Terminal Name| Terminal Label| ****
Description
---|---|---
RS485 SLAVE| –| BACnet/Modbus Communications
RS485 SLAVE| +| BACnet/Modbus Communications
SYLK MASTER| | Sylk bus
SYLK MASTER| | Sylk bus
DO1| DO1| Configurable relay output
DO2| DO2| Configurable relay output
DO3| DO3| Configurable relay output
DIO1| DIO1| Configurable relay output, configurable analog/relay input
DIO2| DIO2| Configurable relay output, configurable analog/relay input
24VAC POWER| R| 24VAC power from Class2 transformer
24VAC POWER| C| 24VAC common (Neutral) from Class2 transformer
COM| COM| Common
Wiring the wallplate
IMPORTANT
All wiring must comply with local electrical codes and ordinances.
NOTE: Supports 14-26AWG (0.2-1.5mm2 for solid or stranded, max 2.5mm2 for solid) wires.
Follow equipment manufacturer wiring instructions when available. A letter code is located near each terminal for identification.
CAUTION
Power must not be connected while wiring. Wiring a unit that is powered may
result in electrical shock and/or equipment damage.
- Connect wires to the terminals. See Fig. 7 for terminal assignments and Table 2 for terminal descriptions.
- Loosen the terminal screw, and insert the solid wire (twist if it is stranded) into the wiring terminal hole directly.
- Tight the terminal screw using the Phillips screw- driver (screw torque 0.4Nm).
- Push excess wire back into the hole.
- Check for loose or frayed wire that may cause a short.
Mounting the display unit
After all wiring is completed, install the display onto the wallplate.
- Hold the display unit in forward tilted position and align the slots in the display unit with the protrusions on top of the wall plate.
- Carefully pivot the display onto the wall plate to ensure proper engagement of pins with terminal blocks while ensuring engagement of protrusions and slots is maintained as shown in step 1.
- Gently tighten the Security screw using a screwdriver by turning it in the clockwise direction (screw torque 0.1Nm).
Dismounting the display unit
- Unscrew the security screw.
- Detach the bottom side by pulling the display unit out and detach the top side.
DIMENSIONS
Thermostat
Decoplate
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Honeywell Building Technologies
715 Peachtree Street NE Atlanta, GA 30308
https://customer.honeywell.com https://buildings.honeywell.com
® U.S. Registered Trademark
© 2023 Honeywell International Inc. 31-00642-01 | Rev. 10-23