Technical Specifications
- Model: P6SDSeries
- Type: Single Packaged Air Conditioning
- SEER: 13
- Refrigerant: R-410A
- Capacity: 3, 4, 5 Ton Units
- Installation: Roof or Slab
- Design: Convertible unit design
- Certification: ETL and ETLc listed
FAQ
What is the SEER rating of the P6SD Series air conditioners?
- The SEER rating of the P6SD Series air conditioners is 13.
Can the P6SD Series units be installed on a roof?
- Yes, the P6SD Series units can be installed on a roof or on a slab.
Are the P6SD Series units ETL and ETLc listed?
- Yes, the P6SD Series units are ETL and ETLc listed.
What is the warranty for the P6SD Series air conditioners?
- Please refer to the warranty documentation for information on the warranty for the P6SD Series air conditioners.
Features and Benefits
- High efficiency self-contained cooling units
- Simple installation in all applications
- Reliable service and availability
3, 4, 5 Ton Units
The P6 Series single packaged air conditioners are high efficiency self contained cooling units that can be installed on a roof or on a slab. The convertible unit design makes installations simple in all applications. Units are ETL and ETLc listed.
WARRANTY
- 1 Year Limited Parts Warranty
- 1 Year Limited Labor Warranty
- 5 Year Limited Compressor Warranty
FEATURES and BENEFITS
- State-of-the-art Copeland Scroll compressor is standard equipment.
- R-410A Refrigerant Environmentally friendly.
- Proven, Industry Standard Components Easier service and availability.
- TXV Externally equalized. Provides precise refrigerant control under varying load conditions.
- High and Low Pressure Switches Added compressor protection.
- Liquid Line Filter/Drier Insures clean and dry refrigeration system.
- Externally Accessible Service Ports Quick access to refrigerant system without disrupting operation.
- Compact Footprint/Low Profile Easy to handle and transport.
- Convertible Air Delivery Horizontal or downflow to accommodate rooftop or horizontal application.
- Heavy-Gauge, Full Perimeter Base Rails Facilitates forklift handling and curb mounting.
- Galvanized Steel Cabinet Polyurethane finish provides 950 hours salt spray protection.
- Wire Guard Coated with Earth Friendly Epoxy and Mesh Hail Guard Will never rust and protects the coil from being damaged by balls, lawnmowers, hail etc.
- Corrosion-Resistant Drain Pan Quickly drains away evaporator condensate.
- Quiet Operation and Low Vibration 20″ fan blade combined with custom venturi condenser fan.
- Access to Controls and Major Components Easy in and out service.
- Service Access Panels Allows easy access to all major components and the compressor. Designed to make servicing easier for the Contractor.
- Easy to Install Electric heat strip provides up to 20 KW of heat output.
- Accessories Roof curbs, economizers, fresh air dampers and more.
MODEL IDENTIFICATION CODE
DIMENSIONS
Model Number P6SD| Unit Weight| Center of Gravity| Height (in inches)
C
|
---|---|---|---|---
A| B
with base rails|
X36| 405| 29.5| 26.0| 37.7|
X48| 415| 29.5| 26.5| 37.7|
X60| 480| 30.0| 27.5| 41.7|
SPECIFICATIONS
Model Number | P6SD |
---|---|
X36K | X48K |
Performance | |
Capacity -Cooling BTUH | 34,200 |
Efficiency – SEER | 13.3 |
EER (Btuh/watt) | 11.2 |
Electrical Rating – 60 Hz | |
Phase | 1 |
Operating Voltage Range | 187 – 253 |
Compressor Data | |
Volts | 208 / 230 |
Rated Load Amps | 18.6 |
Lock Rotor Amps | 79 |
Indoor Blower | |
Type / No. of Speeds | DD / 3 |
Motor – HP / RPM | 1/4 – 1075 |
Motor – Amps | 1.3 |
Outdoor Fan | |
Motor – HP / RPM | 1/4 – 1100 |
Motor – Amps | 1.2 |
Fan Diameter / CFM | 20/3600 |
Refrigerant Charge – Oz. | 110 |
Shipping Weight | 415 |
BLOWER PERFORMANCE
Model Number | External Static Pressure Drop – inches water column |
---|---|
P6SD- | 0.1 |
0.7 | 0.8 |
X36
| High| 1610| 1562| 1504| 1442| 1365| 1295| 1214| 1109
Medium| 1367| 1320| 1271| 1205| 1138| 1065| 968| 845
Low| 1153| 1102| 1043| 990| 912| 831| 731| 618
X48
| High| 2361| 2278| 2218| 2141| 2066| 1976| 1870| 1758
Medium| 2026| 1982| 1935| 1889| 1822| 1744| 1660| 1554
Low| 1584| 1568| 1532| 1489| 1445| 1387| 1322| 1236
**X60 ***
| Tap T1| 1515| 1450| 1380| 1350| 1280| 1250| 1200| 1160
Tap T2| 1580| 1520| 1460| 1400| 1300| 1280| 1260| 1230
Tap T3| 1740| 1690| 1650| 1600| 1360| 1500| 1460| 1390
Tap T4| 1960| 1910| 1840| 1820| 1540| 1740| 1700| 1600
Tap T5| 2090| 2050| 2010| 1975| 1780| 1900| 1850| 1790
- ***** Denotes factory set cooling speed
- ** Denotes factory set electric heating speed
NOTE: Airflow performance is with a dry coil
MODEL IDENTIFICATION CODE
HEATER APPLICATION MATRIX
TONNAGE & PHASE| UNIT| NOMINAL
KW
| HEATER KIT MODEL| HEATER KIT PART NUMBER| BREAKERS REQUIRED
---|---|---|---|---|---
3 Ton, Single Phase
| ****
P6SD
| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| None
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
4 Ton, Single Phase
| ****
P6SD
| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| None
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
20| H3HK020H-01B| 917170B| 2
20| H3HK020H-21B| 917173B| None
5 Ton, Single Phase
| ****
P6SD
| 5| H3HK005H-01B| 917166B| None
8| H3HK008H-01B| 917167B| None
10| H3HK010H-01B| 917168B| 2
15| H3HK015H-01B| 917169B| 2
15| H3HK015H-21B| 917172B| None
20| H3HK020H-01B| 917170B| 3
20| H3HK020H-21B| 917173B| 1
ELECTRICAL DATA
P6SD SERIES – 208/230V – SINGLE PHASE MODELS
MODEL NUMBER P6SD-
| ****
HEATER INSTALLED NOMINAL KW
| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
MCA
| ****
REC, WIRE GAGE (90° C CU)
| ****
MOP
| CIRCUIT A
(C ompressor & F an )
| CIRCUIT B
(B lower & H eater )
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
| ****
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
X36K
| 0| 25.8| 10| 40| –| –| –| –| –| –
5| 26.5| 10| 40| –| –| –| –| –| –
8| 41.2| 8| 45| –| –| –| –| –| –
10| 51.6| 8| 60| –| –| –| –| –| –
15| 76.6| 4| 80| 50.0| 8| 60| 26.6| 10| 30
X48K
| 0| 32.9| 8| 50| –| –| –| –| –| –
5| 32.9| 8| 50| –| –| –| –| –| –
8| 41.2| 8| 50| –| –| –| –| –| –
10| 51.6| 8| 60| –| –| –| –| –| –
15| 76.6| 4| 80| 51.6| 8| 50| 26.6| 10| 30
20| 101.6| 3| 110| 50| 8| 50| 51.6| 8| 60
MODEL NUMBER P6SD-
| ****
HEATER INSTALLED NOMINAL KW
| SINGLE CIRCUIT| MULTIPLE SUPPLY CIRCUIT OPTION
MCA
| ****
REC, WIRE GAGE (90° C CU)
| ****
MOP
| CIRCUIT A
(C ompressor , B lower , & F an )
| CIRCUIT B
(H eater o nly )
| CIRCUIT C
(H eater o nly )
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
| ****
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
| ****
MCA
| REC, WIRE GAGE (90° C CU)| ****
MOP
X60K
| 0| 43.8| 8| 70| –| –| –| –| –| –| –| –| –
5| 43.8| 8| 70| –| –| –| –| –| –| –| –| –
8| 43.8| 8| 70| –| –| –| –| –| –| –| –| –
10| 51.5| 8| 70| 43.8| 8| 70| 50| 8| 60| –| –| –
15| 76.5| 4| 80| 51.5| 8| 70| 25| 10| 30| –| –| –
20| 101.5| 3| 110| 43.8| 8| 70| 50| 8| 60| 50| 8| 60
NOTE: P6SD 3 & 4 ton models have PSC motors. Since the power wires run through the heater plug, keep the blower and heater on different circuits when adding a heater kit.
ACCESSORIES
Description | Part Number |
---|---|
Roof Curb (8”) | 547830 |
Roof Curb (14”) | 547831 |
Roof Curb (18”) | 547850 |
Roof Curb (24”) | 547851 |
Supply/return transition, 16” | 547834 |
Supply/return transition, 18” | 547835 |
Concentric diffuser, flush, 16” | 547836 |
Concentric diffuser, flush, 18” | 547837 |
Concentric diffuser, step down 16” | 547838 |
Concentric diffuser, step down 18” | 547839 |
Manual Fresh Air Damper | 547832 |
Motorized Fresh Air Damper | 547840 |
Economizer, downflow w/filter (does not require filter kit) modulating | 558870 |
Economizer, horizontal modulating | 547841 |
Power Exhaust, downflow economizer (special order) | 547842 |
Power Exhaust horizontal economizer (special order) | 547843 |
HOOD TYPE HAIL GUARD 34” X 76” P6SD-X36, P6SD-X48 | 547846 |
HOOD TYPE HAIL GUARD 38” X 76” P6SD -X60 | 547847 |
DUCT SMOKE DETECTOR PHOTO ELEC | 558863 |
MULTI SIGNAL CONTROL | 547893 |
SAMPLING TUBE DST5, 2-4′ | 558864 |
SAMPLING TUBE DST5, 4-8′ | 558865 |
Filter Rack, All Downflow Applications (not required with economizer) | 547885 |
Filter Kit (not required with economizer) P6SD-X36, P6SD-X48 | 547888 |
Filter Kit (not required with economizer ) P6SD-X60 | 547889 |
Universal Hard Start Kit | 912933 |
Low Ambient Kit | 918837 |
Skirt Trim Kit | 919729 |
Extreme High Wind Kit – Roof Curb Mount | 903696 |
Extreme High Wind Kit – Ground Mount | 903695 |
Heater Kit – 4-Pole single circuit adaptor | 913350 |
Heater Kit – 6-Pole single circuit adaptor | 913556 |
Heater Kit – Circuit breaker single phase (2-pole) | 913554 |
Freezestat Kit | 917108 |
Duct Adopter, 14″ Round (2 each) | 913812A |
Control, CO2 sensor, wall mount | 547848 |
COOLING EXPANDED RATINGS
P6SD-X36
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFM | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. |
900
| 80| 62| 32.7| 26.3| 2.67| 31.2| 26.4| 2.95| 29.6| 27.2| 3.27| 27.9| 26.8|
3.64
80| 67| 35.6| 21.3| 2.70| 33.9| 20.7| 2.98| 32.1| 20.2| 3.30| 30.1| 19.5| 3.67
80| 72| 38.9| 16.3| 2.75| 37.1| 15.8| 3.03| 35.2| 15.2| 3.34| 33.1| 14.7| 3.71
75| 63| 33.1| 21.0| 2.68| 31.5| 21.1| 2.95| 29.8| 21.0| 3.28| 28.0| 20.6| 3.64
1000
| 80| 62| 33.5| 28.0| 2.68| 31.9| 29.0| 2.96| 30.3| 29.0| 3.28| 28.7| 28.7|
3.65
80| 67| 36.2| 22.5| 2.71| 34.4| 22.0| 2.99| 32.6| 21.4| 3.31| 30.7| 20.9| 3.67
80| 72| 39.6| 17.1| 2.76| 37.8| 16.6| 3.04| 35.8| 16.0| 3.35| 33.7| 15.5| 3.72
75| 63| 33.7| 23.1| 2.68| 32.0| 22.9| 2.96| 30.4| 22.8| 3.28| 28.6| 22.2| 3.65
1100
| 80| 62| 34.7| 31.2| 2.69| 33.1| 31.3| 2.97| 31.6| 31.6| 3.30| 29.9| 29.9|
3.66
80| 67| 37.3| 24.5| 2.73| 35.5| 23.9| 3.00| 33.6| 23.2| 3.32| 31.6| 22.6| 3.69
80| 72| 40.7| 18.2| 2.77| 38.8| 17.7| 3.05| 36.7| 17.2| 3.37| 34.5| 16.6| 3.73
75| 63| 34.8| 26.0| 2.70| 33.1| 25.6| 2.97| 31.3| 24.9| 3.29| 29.4| 24.2| 3.66
P6SD-X48
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFM | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. |
1250
| 80| 62| 44.1| 35.7| 3.45| 42.2| 36.0| 3.84| 40.0| 37.1| 4.27| 37.8| 36.6|
4.77
80| 67| 47.9| 28.8| 3.50| 45.5| 28.0| 3.87| 43.1| 27.2| 4.31| 40.6| 26.7| 4.80
80| 72| 52.1| 21.9| 3.54| 49.5| 21.2| 3.92| 46.9| 20.5| 4.35| 44.2| 19.8| 4.85
75| 63| 52.1| 16.3| 3.54| 49.5| 16.7| 3.92| 47.0| 16.7| 4.35| 44.2| 16.4| 4.85
1400
| 80| 62| 45.2| 38.2| 3.46| 43.1| 39.5| 3.85| 41.0| 39.5| 4.29| 39.0| 39.0|
4.78
80| 67| 48.7| 30.6| 3.51| 46.3| 29.8| 3.88| 43.9| 29.4| 4.32| 41.4| 28.6| 4.81
80| 72| 52.9| 23.1| 3.54| 50.4| 22.4| 3.93| 47.7| 21.6| 4.36| 44.9| 20.9| 4.86
75| 63| 53.1| 18.2| 3.55| 50.5| 18.2| 3.93| 47.7| 17.9| 4.36| 45.0| 17.4| 4.86
1550
| 80| 62| 46.2| 41.8| 3.47| 44.2| 41.9| 3.86| 42.2| 42.2| 4.30| 40.1| 40.1|
4.80
80| 67| 49.6| 32.7| 3.51| 47.1| 32.0| 3.89| 44.6| 31.2| 4.33| 42.0| 30.4| 4.82
80| 72| 53.8| 24.2| 3.55| 51.1| 23.5| 3.95| 48.4| 22.8| 4.37| 45.5| 22.0| 4.86
75| 63| 53.8| 20.3| 3.55| 51.1| 19.8| 3.95| 48.4| 19.2| 4.37| 45.5| 18.4| 4.87
P6SD-X60
O.D.T | 85°F | 95°F | 105°F | 115°F |
---|---|---|---|---|
CFM | E.D.B. | E.W.B. | T.C. | S.C. |
T.C. | S.C. | K.W. | T.C. | S.C. |
S.C. | K.W. |
1600
| 80| 62| 56.7| 45.9| 4.53| 54.1| 46.1| 5.02| 51.3| 47.5| 5.57| 48.4| 46.7|
6.19
80| 67| 61.2| 37.4| 4.62| 58.1| 36.4| 5.09| 55.0| 35.3| 5.65| 51.7| 34.2| 6.26
80| 72| 66.6| 28.6| 4.72| 63.1| 27.7| 5.20| 59.5| 26.8| 5.75| 55.7| 25.7| 6.36
75| 63| 57.0| 36.9| 4.54| 54.2| 37.0| 5.02| 51.2| 36.7| 5.57| 48.2| 36.0| 6.18
1750
| 80| 62| 57.8| 48.3| 4.59| 55.1| 49.9| 5.07| 52.2| 49.9| 5.62| 49.3| 49.2|
6.24
80| 67| 62.0| 39.2| 4.67| 58.9| 38.1| 5.14| 55.7| 37.0| 5.70| 52.3| 35.8| 6.31
80| 72| 67.1| 29.8| 4.77| 63.5| 28.8| 5.24| 59.9| 27.8| 5.79| 56.2| 26.8| 6.41
75| 63| 57.8| 40.1| 4.59| 54.9| 39.8| 5.07| 51.9| 39.1| 5.62| 48.8| 38.1| 6.23
1900
| 80| 62| 58.7| 52.1| 4.64| 56.0| 52.2| 5.13| 53.1| 53.0| 5.68| 50.4| 50.4|
6.30
80| 67| 62.7| 40.9| 4.72| 59.6| 39.8| 5.20| 56.3| 38.7| 5.75| 52.8| 37.5| 6.36
80| 72| 67.5| 30.9| 4.81| 64.0| 29.9| 5.29| 60.5| 28.8| 5.84| 56.7| 27.7| 6.46
75| 63| 58.5| 43.5| 4.64| 55.6| 42.7| 5.12| 52.5| 41.6| 5.66| 49.3| 40.3| 6.28
LIMITED WARRANTY
GENERAL TERMS OF LIMITED WARRANTY
- NORDYNE will furnish a replacement for any part of this product in accordance with the terms of the warranty.
- For complete details of the Limited Warranty, including applicable terms and conditions, see your local installer or contact the NORDYNE warranty department for a copy.
Contact
- 8000 Phoenix Parkway | O’Fallon, MO
- 63368-3827
- www.nutonehvac.com
Specifications and illustrations subject to change without notice and without
incurring obligations.
Printed in U.S.A (09/2010)
NuTone® trademark used under license. © Nortek Global HVAC, LLC. All Rights Reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>