INSTRUCTION MANUAL Ultra Tugger®
Cable Puller and Pulling Packages
6800 and 6805A
(115 V CE for United Kingdom)
Serial Code ALA
**** Read and understand all of the instructions and safety information in this manual before operating or servicing this tool.
Description, Safety, and Purpose of Manual
Description
The Greenlee Ultra Tugger cable puller is intended to be used to pull cable
through conduit and in tray.
The cable puller will develop 35.6 kN (8000 lb) of pulling force. Refer to a
Greenlee catalog for sheaves, pulling rope, and other cable pulling
accessories to create an entire cable pulling system.
No single manual can provide instructions for every possible cable pulling
application; this manual contains general information necessary to accomplish
cable pulls of many different setups.
Safety
Safety is essential in the use and maintenance of Greenlee tools and
equipment. This instruction manual and any markings on the tools provide
information for avoiding hazards and unsafe practices related to use of this
tool. Observe all of the safety information provided.
Do not operate this tool unless fully trained to do so, or under trained
supervision.
Purpose of this Manual
This manual is intended to familiarize all personnel with the safe operation
and maintenance procedures for the Greenlee 6800 and 6805A Ultra Tugger cable
pullers.
Keep this manual available to all personnel.
Replacement manuals are available upon request at no charge at
www.greenlee.com.
Other Publications
Service Manual: 52045365
**** Do not discard this product or throw away!
For recycling information, go to www.greenlee.com.
All specifications are nominal and may change as design improvements occur.
Greenlee Textron Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.
Ultra Tugger is a registered trademark of Greenlee Textron Inc.
Versi-Boom is a trademark of Greenlee Textron Inc.
IMPORTANT SAFETY INFORMATION
SAFETY ALERT SYMBOL
This symbol is used to call your attention to hazards or unsafe practices
which could result in an injury or property damage. The signal word, defined
below, indicates the severity of the hazard. The message after the signal word
provides information for preventing or avoiding the hazard.
DANGER
Immediate hazards which, if not avoided, WILL result in severe injury or
death.
WARNING
Hazards which, if not avoided, COULD result in severe injury or death.
CAUTION
Hazards or unsafe practices which, if not avoided, MAY result in injury or
property damage.
DANGER
Read and understand all of the instructions and safety information in this
manual before operating or servicing this tool.
Failure to observe this warning will result in severe injury or death.
DANGER
Explosion hazard:
Do not operate the cable puller in a hazardous environment. Hazards include
flammable liquids and gases.
Failure to observe this warning will result in severe injury or death.
WARNING
Electric shock hazard:
Disconnect the cable puller from the power supply before servicing.
Failure to observe this warning could result in severe injury or death.
WARNING
Flying components hazard:
- Inspect and verify the maximum load-bearing capacity or maximum strength of all structural supports, pulling system components, and anchoring systems before setting up the puller. Any component that cannot withstand the maximum cable-pulling forces could break and strike nearby personnel with sufficient force to cause severe injury or death.
- Do not allow anything other than the pulling rope to contact the capstan. A grip, swivel, or other component could break and strike operator with great force.
Failure to observe these warnings could result in severe injury or death.
WARNING
Crushing hazard:
Do not stand directly under a vertical pull. Cable could fall suddenly from
the conduit.
Failure to observe this warning could result in severe injury or death.
WARNING
Flying components hazard:
Locate the puller so that it is close to the conduit.
Rope, cable, or connectors could break under tension, causing the rope to whip
violently.
Failure to observe this warning could result in severe injury or death.
WARNING
An under-rated or worn rope may break and whip violently. Use a double-braided
composite rope with the following characteristics:
- Maximum Rated Capacity: at least 35.6 kN (8000 lb)
- Average Breaking Strength: at least 143 kN (32,000 lb)
Failure to observe this warning could result in severe injury or death.
WARNING
-
Check the condition of the entire rope before use.
A worn or damaged rope can break under tension and whip violently. -
Do not maintain a stationary rope on a rotating capstan. The wear generated may cause the rope to break under tension and whip violently.
Failure to observe these warnings could result in severe injury or death.
WARNING
Attach the pulling rope to the cable with appropriate types of connectors as
described in this manual.
Select connectors with a maximum-rated capacity of 35.6 kN (8000 lb). An
under-rated connector could break under tension.
Failure to observe this warning could result in severe injury or death.
WARNING
Shear point:
Do not put fingers through holes in elbow unit. Rotating parts may cut off
fingers.
Failure to observe this warning could result in severe injury or death.
WARNING
Crushing hazard:
Keep hands away from the capstan.
Rope at the capstan could crush a hand.
Failure to observe this warning could result in severe injury or death.
WARNING
Entanglement hazard:
Do not wrap rope around hands, arms, waist, or other body parts.
Do not stand in spent coils or tailed rope. Hold rope so that it may be
released quickly.
Failure to observe this warning could result in severe injury or death.
WARNING
Rope, cable, or a connecting device could break under tension, causing the
rope to whip violently.
- Do not allow any unnecessary personnel to remain in the area during the pull.
- Do not allow any personnel to stand in line with the pulling rope.
Failure to observe these warnings could result in severe injury or death.
WARNING
Rope overlap hazard:
Do not allow the rope to become overlapped on the capstan. If an overlap
begins to develop, relax the tailing force immediately and shut off the cable
puller.
Failure to observe this warning could result in severe injury or death.
WARNING
Lifting hazard:
Use this tool for manufacturer’s intended purpose only. Do not use the cable
puller as a hoist or winch.
- The cable puller cannot lower a load.
- The load could fall.
Failure to observe this warning could result in severe injury or death.
WARNING
Inspect puller and accessories before use. Replace any worn or damaged
components with Greenlee replacement parts. A damaged or improperly assembled
item could break and strike nearby personnel with sufficient force to cause
severe injury or death.
WARNING
Entanglement hazard:
- Do not operate the cable puller while wearing loose-fitting clothing.
- Retain long hair.
Failure to observe this warning could result in severe injury or death.
WARNING
Wear eye protection when using this tool. Failure to wear eye protection
could result in severe eye injury from flying debris.
WARNING
When using the wheeled carriage to transport the cable puller:
- Keep personnel out of the path of transport.
- Evaluate the terrain over which the carriage is to move. If in doubt, obtain additional help and move the carriage slowly.
- Do not transport over inclines of more than 10°.
- Do not transport the carriage with boom tubes longer than the supplied 3′ and 4′ tubes.
Failure to observe this warning could result in severe injury or death.
Note: Keep all decals clean and legible, and replace when necessary.
Grounding Instructions
WARNING
Electric shock hazard:
Connect this tool to a grounded receptacle on a 20-amp GFCI- protected
circuit.
Failure to observe this warning could result in severe injury or death.
This tool must be grounded. In the event of a malfunction or breakdown, an
electrical ground provides a path of least resistance for the electric
current.
This path of least resistance is intended to reduce the risk of electric shock
to the operator.
This tool’s electric cord has a grounding conductor and a grounding plug as
shown. Connect the plug to receptacle that is properly installed and grounded
in accordance with all national and local codes and ordinances.
Do not use an adapter.
20-Amp / 115-Volt Plug and Grounded Receptacle This tool is equipped with
a European-style electrical plug. The electrical plug can be replaced with a
compatible plug for the country in which the tool will be used.
The electrical plug should be replaced by a qualified electrician.
Do not use an adapter.
Identification
Ultra Tugger Cable Puller
- Motor (under shroud)
- Circuit Breaker / I/O Switch
- Mounting Plates
- Rope Tie-Off
- Adjustable Sheave Bracket
- Tapered Steel Capstan
- Right Angle Sheave
- Rope Ramp
- Hitch Clip
- Gearbox
- Mounting Pin (2)
- Force Gauge with Remote I/O Switch
Identification (cont’d) Versi-Boom™ Components
1. Elbow Unit
2. Sight Hole
3. 4′ Boom Tube
4. Sight Hole
5. Boom Mount
6. T-Stand
7. Puller
8. Force Gauge| 9. Wheeled Carriage
10. Slip-in Coupler
11. Nose Unit
12. Mounting Pins
13. Hitch Pin Clips
14. 3′ Boom Tube
15. Long Pin
---|---
Specifications
Weight ………………………………………………………………………………………….. 43 kg (95 lb)
Dimensions
Length ……………………………………………………………………………………. 29 cm (11.5″)
Width …………………………………………………………………………………………. 68 cm (27″)
Height ……………………………………………………………………………………….. 25 cm (9.8″)
Motor
Voltage …………………………………………………………115 VAC, 50/60 Hz, single phase
Current Draw at Full Load ………………………………………………………………………. 19 A
Sound Level ……………………………………………………………………………. Lw a 70 at 1 m
Power Source ………………………………………….. 115 VAC, 50/60 Hz, 20 A, single phase
Speed
No Load………………………………………………………………………… 2.74 m/min (9 ft/min)
8900 N (2000 lb) …………………………………………………………….. 2.44 m/min (8 ft/min)
17.8 kN (4000 lb) …………………………………………………………. 2.29 m/min (7.5 ft/min)
26.7 kN (6000 lb) ……………………………………………………………. 2.13 m/min (7 ft/min)
35.6 kN (8000 lb) ……………………………………………………………. 1.83 m/min (6 ft/min)
Pulling Force
0 kN to 17.8 kN (0 lb to 4000 lb) ………………………………………Continuous operation
17.8 kN to 35.6 kN (4000 lb to 8000 lb) ……………………………….. 5 minutes per hour
Pulling Rope
Required Rope …………………………………………………………. 22.2 mm (7/8″) diameter,
double-braided, polyester composite
Average Breaking Strength …………………………………… 143 kN (32,000 lb) minimum
IP Rating
Motor …………………………………………………………………………………………………… IP23
Ultra Tugger Cable Puller and Force Gauge Enclosure……………………………….. IP54
Temperature Rating
Transportation and Storage ………………………….. 55 °C to -25 °C (131 °F to -13 °F)
Elevation Rating ……………………………………………. 1000 m (3280 ft) above sea level
Cable Pulling Glossary
anchoring system
any item or group of items that keeps a cable pulling component in place
during the cable pull
capstan
the hollow cylinder of the cable puller that acts on the pulling rope to
generate pulling force
coefficient of friction
the ratio that compares two amounts of force:
(1) the force needed to move an object over a surface and (2) the force
holding the object against the surface This ratio is used to describe how the
capstan and the rope work together.
connector
any item, such as a wire grip, clevis, swivel, or pulling grip, that connects
the rope to the cable direct line of pull
the areas next to the pulling rope and along its path; this includes the areas
in front of, in back of, and underneath the rope
maximum rated capacity
the amount of pulling tension that any component can safely withstand, rated
in kilonewtons (metric) or pounds; the maximum rated capacity of every
component must meet or exceed the maximum pulling force of the cable puller
Newton
a metric unit of force, equivalent to .225 pounds of force
pipe adapter sheave
attaches to conduit for pulling or feeding cable
pulling grip
connects the rope to the cable; consists of a wire mesh basket that slides
over the cable and grips the insulation
pulling force
the amount of pulling tension developed by the cable puller, rated in newtons
(metric) or pounds; a cable puller is usually described by the maximum pulling
force that it can develop
resultant force
any force that is produced when two or more forces act on an object; applies
to the sheaves of a cable pulling system
rope ramp
a device that works with a tapered capstan; guides the rope onto the capstan
to prevent rope overlap
sheave
a pulley that changes the direction of the rope and cable
stored energy
the energy that accumulates in the pulling rope as it stretches, described in
newton-meters (metric) or foot-pounds
support structure
any stationary object that a cable pulling system component is anchored to,
such as a concrete floor (for the floor mount) or an I-beam (for a sheave)
tactile feedback
the way the rope feels as it feeds off of the capstan; the feel of the rope
provides information about the progress of the pull to the operator
tail
the portion of the rope that the operator applies force to; this is the rope
coming off of the capstan, and is not under the tension of the pull
tailing the rope
the operator’s main function; this is the process of applying force to the
tail of the pulling rope—see the complete explanation under “Cable Pulling
Principles.”
wire grip
connects the rope to the cable; some use a set screw to clamp onto the
conductors of the cable
Cable Pulling Principles
Pulling cable is a complex process. This section of the manual describes and explains four main topics of pulling cable:
- each cable pulling system component
- how these components work together
- forces that are generated
- procedures for the cable puller operator to follow
While reading through this section of the manual, look for components that are
shaded in the illustrations. The shading indicates components that are
associated with the text.
Greenlee strongly recommends that each member of the cable pulling crew review
this section of the manual before each cable pull.
Cable Pulling Systems
Pulling cable requires a system of components. At a minimum, a cable pulling
system will include a cable puller, a cable pulling rope, and connectors to
join the rope to the cable. Most systems will also include, but are not
limited to, a cable puller anchoring system, pulling sheaves, and sheave
anchoring systems.
The cable puller has a maximum amount of pulling force, which is the amount of
pulling tension that it develops. Every other component of the pulling system
has a maximum rated capacity, which is the amount of pulling tension that it
can withstand. The maximum rated capacity of every component must meet or
exceed the cable puller’s maximum pulling force. Pulling Theory
This section introduces the main ideas involved with pulling cable.
Pulling Resistance
The cable puller must overcome two types of resistance: gravity and friction.
Gravity constantly exerts its force on the vertical portions of the run. When
the pulling force is relaxed, gravity attempts to pull the cable downward.
Friction develops where the cable contacts the sheaves, conduit, and tray.
Friction resists any movement, forward or backward, and tends to hold the
cables in place.
To accomplish a cable pull, the cable pulling system must develop more force
than the combination of gravity and friction.
Generating Pulling Force
To generate pulling force, the capstan works as a force multiplier. The
operator exerts a small amount of force on the rope. The cable puller
multiplies this and generates the pulling force.
This pulling force is applied to the rope, connectors, and cable in order to
accomplish the pull. The direction of force is changed, where necessary, with
pulling sheaves.
Cable Pulling
Forces
This section provides detailed explanations and illustrations of the forces
that are generated during the cable pull.
These explanations are based on the concepts presented in the last section,
“Pulling Theory.”
At the Cable Puller Anchoring System
The cable puller will exert its maximum pulling force on cable puller’s
anchoring system. It is extremely important the anchoring system can withstand
this amount of force.
Refer to “Setup: Floor Mount” for proper setup or installation. At the Capstan
The capstan acts as a force multiplier. The operator exerts a small amount of
tension, or tailing force, on the rope; the capstan multiplies this force to
pull the cable.
The resultant force depends upon the number of times the rope is wrapped
around the capstan, as shown in the formula below.
Pulling Force = Tailing Force x e 0.0175µø
Where: e = the natural logarithm, or 2.7183
µ = the coefficient of friction between the rope and the capstan *
ø = the number of degrees of wrap of rope around the capstan
- The average value for the coefficient of friction when double-braided composite rope is pulled over a clean dry capstan is 0.125.
The following table is based on the formula above.
The input, or tailing force, is constant at 44.5 N (10 lb).
Increasing the number of wraps increases the pulling force.
Operator’s Tailing Force| Number of Wraps of Rope|
Approximate Pulling Force
---|---|---
44.5 N (10 lb)| 1| 93.4 N (21 lb)
2| 213.5 N (48 lb)
3| 474.9 N (106 lb)
4| 1043.8 N (233 lb)
5| 2293.7 N (512 lb)
6| 5048.9 N (1127 lb)
7| 11.1 kN (2478 lb)
This table shows how the capstan acts as a force multiplier. Because the coefficient of friction depends upon the condition of the rope and capstan, this formula cannot determine an exact amount of pulling force.
At the Pulling Rope
The product of a force (f) moving through a distance (d) is energy (f x d),
and may be measured in newtonmeters or foot-pounds. Energy is stored in a rope
when the rope is stretched.
This is similar to the way energy is stored in a rubber band when it is
stretched.
Failure of the rope or any other component of the pulling system can cause a
sudden uncontrolled release of the energy stored in the rope.
For example, a 100-meter nylon rope with a 50,000 newton average breaking
strength could stretch 40 meters and store 1,000,000 joules of energy. This is
enough energy to throw a 900-kilogram object, such as a small automobile, 113
meters into the air.
A similar double-braided composite rope could store approximately 300,000
joules of energy. This could throw the same object only 34 meters into the
air.
The double-braided composite rope stores much less energy and has much less
potential for injury if it were to break.
Double-braided composite rope is the only type of rope recommended for use
with the Ultra Tugger cable puller. Select a double-braided composite rope
with an average rated breaking strength of at least 143 kN (32,000 lb).
At the Connectors
The connectors will be subjected to the cable puller’s maximum pulling force.
Several types of rope connectors—clevises, swivels, and rope-to-swivel
connectors—are available. Follow the instructions provided with each to
provide a good connection.
Two types of wire connectors—wire grips and pulling grips—are available. The
wire grip uses a set screw to clamp onto the conductors of the cable. The
pulling grip consists of a wire mesh basket that slides over the cable and
grips the insulation.
When selecting a pulling grip, it is extremely important to select a grip of the correct (1) type, (2) size, and (3) maximum rated capacity.
- Select the correct type based on the descriptions of each type in the Greenlee catalog.
- Measure the circumference of the wire bundle. (To do this accurately, fasten a tie strap around the bundle. Cut off and discard the tail. Then cut the tie strap and measure its length.) Use the table provided to find the correct size.
- See the maximum rated capacities in the Greenlee catalog.
Pulling Grip Size Table
Circumference Range
|
Required Grip Diameter
---|---
inches| mm| inches| mm
1.57–1.95| 39.9–49.5| 0.50–0.61| 12.7–15.5
1.95–2.36| 49.5–59.9| 0.62–0.74| 15.8–18.8
2.36–3.14| 59.9–79.8| 0.75–0.99| 19.1–25.1
3.14–3.93| 79.8–99.8| 1.00–1.24| 25.4–31.5
3.93–4.71| 99.8–119.6| 1.25–1.49| 31.8–37.8
4.71–5.50| 119.6–139.7| 1.50–1.74| 38.1–44.2
5.50–6.28| 139.7–159.5| 1.75–1.99| 44.5–50.5
6.28–7.85| 159.5–199.4| 2.00–2.49| 50.8–63.2
7.85–9.42| 199.4–239.3| 2.50–2.99| 63.5–75.9
9.42–11.00| 239.3–279.4| 3.00–3.49| 76.2–88.6
11.00–12.57| 279.4–319.3| 3.50–3.99| 88.9–101.3
12.57–14.14| 319.3–359.2| 4.00–4.49| 101.6–114.0
14.14–15.71| 359.2–399.0| 4.50–4.99| 114.3–126.7
At the Sheaves
Sheaves are used to change the direction of the pull.
A change in direction creates a new resultant force that may be greater than
the cable puller’s maximum pulling force. This new resultant force exerts
itself on the sheaves, sheave anchoring system, and support structures
illustrated.
The resultant amount of force depends on the angle of the change in direction.
A brief table is provided here.
Refer to “Calculating the Hook Load” to determine the resultant force at any
angle.
Resultant Force Table for the Ultra Tugger Cable
Puller (35.6 kN or 8000 lb Maximum Pulling Force)
Illustration| Angle of Change in Direction| Resultant
Force in kN (lb)
---|---|---
| 180°| 0 (0)
| 150°| 18.5 (4160)
| 135°| 27.4 (6160)
| 120°| 35.6 (8000)
| 90°| 50.2 (11,300)
| 60°| 61.6 (13,800)
| 45°| 65.8 (14,800)
| 30°| 68.7 (15,400)
| 0°| 71.2 (16,000)
Calculating the
Hook Load
One Attachment Point
To calculate the hook load exerted at one attachment point, use the Reference
Table and Formula 1. Formula 1:
R = 2 x T x SIN ((180 – θ) / 2)
R = the resultant force, or hook load; this force is exerted on the hook,
anchoring, and structural support
θ = the angle of change in rope direction
T = the tension exerted on the rope by the cable puller
Note: The total load on the support structure = R + the weight of the
sheave.
Two Attachment Points
To calculate the hook loads exerted at two attachment points, use the
Reference Table and Formulas 1, 2 and 3. R1 = resultant force on left hook, anchoring, and
support structure
R2 = resultant force on right hook, anchoring, and support structure
A = angle between the left mounting and the centerline of the two legs of the
rope
B = angle between the right mounting and the centerline of the two legs of the
rope
R = the resultant force, or hook load; this force is exerted on the hook,
anchoring, and structural support
θ = the angle of change in rope direction
T = the tension exerted on the rope by the cable puller
Notes: The total load on the left support structure = R1 + the weight of the
sheave.
The total load on the right support structure = R2 + the weight of the sheave.
Hook Load
Two variables interact with the sheave to produce a resultant (total) force,
or hook load. This load, represented by R in the formulas and illustrations,
is exerted on the hook, anchoring, and structural support.
Sheave Forces R = the resultant force, or hook load; this force is
exerted on the hook, anchoring, and structural support
θ = the angle of change in rope direction
T = the tension exerted on the rope by the cable puller
Reference Table
Illustration | θ | R |
---|---|---|
**** | 180° | 0 |
150° | .52 x T | |
135° | .77 x T | |
120° | 1 x T | |
90° | 1.41 x T | |
60° | 1.73 x T | |
45° | 1.85 x T | |
30° | 1.93 x T | |
0° | 2 x T |
Some Hook Loads Illustrated
A straight rope exerts no load on the hook and structure.| A rope that makes a
120° angle exerts the total pulling force on the hook and structure.
---|---
A rope that makes a 150° angle exerts 1/2 of the pulling force on the hook and
structure.| A rope that makes a 90° angle exerts 1-1/2 times the pulling force
on the hook and structure.
Arope that makes a 135° angle exerts 3/4 of the pulling force on the hook and
structure.| A rope that makes a 0° angle exerts 2 times the pulling force on
the hook and structure.
Tailing the Rope
The rope must be pulled off of the capstan as the pull progresses. The rope
that has left the capstan is the “tail.” The process of pulling the rope off
of the capstan is called tailing the rope.
The resistance of the cable varies throughout the duration of the cable pull.
Changes in resistance are due to characteristics of the rope, changes in
conduit direction, and changes in the amount of friction. The “feel” of the
rope provides this information about the pull. This is called tactile
feedback. Adjust the tailing force as necessary to compensate for these
changes.
Control of the Pull
Decreasing the tailing force will decrease the pulling force, until the rope
slips on the capstan and the pull stops. This provides a high level of control
over the progress of the cable pull.
Do not allow the rope to slip on the capstan for more than a few moments. If
it becomes necessary to completely stop a pull, shut off the puller and
maintain enough tailing force to hold cable in place. Tie the rope off to hold
it in place. Use the rope tie-off to hold it in place.
Amount of Tailing Force
While the rope and cable are under tension, it is im-portant to maintain the
proper amount of tailing force.
Too little tailing force will allow the rope to slip on the capstan. This will
build up excessive heat and accelerate rope wear, increasing the possibility
of breaking the rope.
The proper amount of tailing force will stop the rope from slipping on the
capstan and produce a sufficient amount of pulling force to pull in the rope
and cable.
Too much tailing force is any amount more than is necessary to stop the rope
from slipping on the capstan.
Excessive tailing force will not increase the pulling force or pulling speed.
Number of Wraps of Rope around the Capstan
An experienced operator should choose the number times the rope is wrapped
around the capstan.
The proper number of wraps allows the operator to control the progress of the
pull with a comfortable amount of effort.
Using too few wraps requires a large tailing force to accomplish the pull.
Using too few wraps also makes the rope more likely to slip on the capstan.
This builds up heat and accelerates rope wear.
Using too many wraps causes the rope to grab the capstan tighter. This
accelerates rope wear, wastes power, and increases the possibility of a rope
overlap.
Using too many wraps also reduces tactile feedback, so you receive less
information about the pull. You cannot quickly relax the tailing force when
there are too many wraps.
If the rope becomes difficult to tail, add another wrap of rope. Turn off the
puller and release all of the tension in the rope. Add a wrap and resume
pulling. Be aware, however, that some pulls will require tension to hold the
cables in place. In these cases, do not attempt to release all of the tension
and add a wrap of rope. You will need to anticipate the number of wraps before
starting the pull.
Preventing Rope Overlap
Do not allow the rope to become overlapped on the capstan during a pull.
A rope overlap will make it will impossible to continue or back out of the
pull.
If the rope becomes overlapped, you will lose control of the pull —the rope
will advance with no tailing force and will not feed off of the capstan. The
capstan will not allow you to reverse the direction of the rope, so you cannot
back out of an overlap.
Set up the puller properly. The rope ramp and tapered capstan are intended to
prevent rope overlap. Refer to the instructions in the “Operation” section of
this manual.
Every wrap of the rope must remain in direct contact with the capstan. During
the pull, take great care to prevent the incoming rope from riding up and
overlapping the next wrap. If an overlap begins to develop, immediately relax
the tailing force on the rope so that the rope can feed back toward the
conduit or tray. When the rope resumes its normal path, apply tailing force
and continue the pull.
There is no suggested remedy for a rope overlap. Do not allow the rope to
overlap!
Summary of Cable Pulling Principles
-
A cable pulling system consists of many components that work together to accomplish a pull.
-
The cable puller is rated by its maximum pulling force; every other component is rated by its maximum rated capacity. The maximum rated capacity of every component must meet or exceed the maximum pulling force of the cable puller.
-
The cable puller must overcome two types of resis-tance: gravity and friction. The puller’s capstan, the pulling rope, and the operator tailing the rope work together to produce pulling force.
-
The cable puller exerts force on every component of the cable pulling system, including the anchoring systems and the support structures.
-
Energy is stored in a rope when the load causes the rope to stretch. Failure of the rope or any other component can cause a sudden release of energy.
Replace any rope that is worn or damaged. -
Carefully select the number or wraps of rope around the capstan before starting the pull.
-
Control the pull by tailing the rope. Be familiar with the interaction of the rope and capstan.
-
Do not allow a rope overlap to develop.
Planning the Pull
- Pull in a direction that will require the lowest amount of pulling force.
- Plan several shorter pulls rather than fewer longer pulls.
- Locate the puller as close to the end of the conduit as possible to minimize the amount of exposed rope under tension.
- Place each component so that the pulling forces are used effectively.
- Select an anchoring system: adapter sheaves, which are preferred, or the floor mount.
- Verify that each component has the proper load rating.
- Inspect the structural supports. Verify that they have enough strength to withstand the maximum forces that may be generated.
- Make sure area is clear of bystanders, etc.
Typical Setups
Setups are shown without force gauge. Place the force gauge so the operator has an unobstructed view of the meter and quick access to its I/O switch. Setups are shown without force gauge. Place the force gauge so the operator has an unobstructed view of the meter and quick access to its I/O switch.Setups are shown without force gauge. Place the force gauge so the operator has an unobstructed view of the meter and quick access to its I/O switch.
Setup
T-Stand
Requires: Adequate clearance. Refer to “Typical Setups.”
- Set the puller on the floor with the mounting holes upward.
- Position the boom mount so that the puller gearbox will fit into the cradle of the boom mount and the puller mounting plates straddle the boom mount plates.
- Mount the boom mount to the puller.
- Install two pins from the motor side. Secure the pins with two hitch pin clips.
- Align the two sets of holes in the T-stand with the two sets of holes in the boom mount.
- Install two pins. Secure the pins with hitch pin clips.
- Continue with “Setup: Mounting Components” later in this manual.
Wheeled Carriage
Requires: Adequate clearance.Refer to “Typical Setups.”
-
Mount the boom mount to the wheeled carriage.
Align the boom mount holes with the top holes in the wheeled carriage, as illustrated. Install a pin through the boom mount and wheeled carriage.
Secure the pin with a hitch pin clip. -
Position the puller’s gearbox above the boom mount cradle. Align the puller so that the puller mounting plates straddle the boom mount plates. Lower the puller onto the boom mount. Install two pins from the motor side. Secure the pins with two hitch pin clips.
-
Check the right angle sheave support tube to be sure it is fastened with the pin.
-
Rotate the puller and boom mount as shown. When the second hole in the boom mount is aligned with the second hole in the wheeled carriage, install a pin. Secure the pin with a hitch pin clip.
Mounting Components
Boom with Nose Unit
WARNING
- Use only straight 3″ diameter rigid steel conduit or Schedule 40 steel pipe for the boom tubes.
- Do not use boom tubes longer than 3 meters (10′). Longer booms may bend or break.
Failure to observe this warning could result in severe injury or death.
WARNING
Set up the elbow unit as shown.
Improper setup will cause the elbow unit to collapse.
Failure to observe this warning could result in severe injury or death.
Use these boom tubes only:
- boom tubes supplied with the cable puller
- 3″ rigid steel conduit (3 meters or 10 feet maximum)
- 3″ Schedule 40 pipe (3 meters or 10 feet maximum)
1. Slide the boom tube into the boom mount until the tube bottoms out. Sight the tube through the sight hole to be sure the tube is fully inserted. Tighten the set screw.
2. Slide the nose unit onto the tube until the tube bottoms out. Sight the tube through the sight hole to be sure the tube is fully inserted. Tighten the set screw.
Mounting
Components (cont’d)
Booms with Elbow Unit and Nose Unit
WARNING
- Use only straight 3″ diameter rigid steel conduit or Schedule 40 steel pipe for the boom tubes.
- Do not use boom tubes longer than 3 meters (10′).
Longer booms may bend or break.
Failure to observe this warning can result in severe injury or death.
WARNING
Set up the elbow unit as shown.
Improper setup will cause the elbow unit to collapse.
Failure to observe this warning could result in severe injury or death.
Use these boom tubes only:
- boom tubes supplied with the cable puller 3″ rigid steel conduit (3 meters or 10 feet • maximum)
- 3″ Schedule 40 pipe (3 meters or 10 feet maximum)
- Slide the boom tube into the boom mount until the tube bottoms out. Sight the tube through the sight hole to be sure the tube is fully inserted. Tighten the set screw.
- Slide the elbow unit onto the tube until the tube bottoms out. Sight the tube through the sight hole to be sure the tube is fully inserted. Tighten the set screw.
- Adjust the elbow to an appropriate angle and lock it in place with a pin. Secure the pin with a hitch pin clip.
- Slide the boom tube into the elbow unit until the tube bottoms out. Sight the tube through the sight hole to be sure the tube is fully inserted. Tighten the set screw.
- Slide the nose unit onto the tube until the tube bottoms out. Sight the tube through the sight hole to be sure the tube is fully inserted. Tighten the set screw.
Mounting Components
(cont’d)
Slip-in Coupler
Requires: One pin to connect to nose unit
-
Select the coupler that best fits the conduit.
-
Slide the coupler into the conduit until the coupler seats on the end of the conduit.
Note: If the coupler doesn’t seat on the conduit, refer to “Straddling the Conduit with a Slip-In Coupler.” -
Slide the nose unit over the coupler. Align any set of holes and insert one pin. Secure the pin with a hitch pin clip.
Note: If possible, add a second pin and hitch pin clip.
Straddling the Conduit with Slip-in Coupler
Requires: Two pins to connect to nose unit
-
Select a coupler at least 25 mm (1″) larger than the conduit.
-
Place the coupler over the conduit.
Note: Do not use this method if the coupler does not seat on a support structure that can support 35.6 kN (8000 lb) of force. -
Slide the nose unit over the coupler. Align any two sets of holes and insert two pins. Secure the pins with hitch pin clips.
Chain Mount
Requires: Exposed metallic conduit with the following characteristics:
- 63.5 mm to 254 mm (2-1/2″ to 10″) in diameter
- capable of withstanding at least 35.6 kN (8000 lb) of force
WARNING
Do not mount the pipe adapter to the following:
- steel conduit less than 63.5 mm (2-1/2″) in diameter
- PVC conduit of any size.
These conduits will not support the loads imposed by the puller.
Failure to observe this warning could result in severe injury or death.
WARNING
When setting up the pipe adapter, do not use the vise chains on a structural
support that is less than 51 mm (2″) or more than 254 mm (10″) wide. An
oversized or undersized structural support can allow the puller to slide or
break loose and strike nearby personnel.
Failure to observe this warning could result in severe injury or death.
WARNING
Install the vise chains properly.
- Follow the vise chain tightening instructions care-fully. Improperly tightened chains can allow the puller to slide or break loose and strike nearby personnel.
- Do not allow the vise chains to bind at the corners when mounting the puller to a square or rectangu-lar support. The vise chain must be uniformly tight at all points.
Failure to observe this warning could result in severe injury or death.
Do not pull between the 10 o’clock and 2 o’clock directions. Pulling between 10 o’clock and 2 o’clock can damage the mounting conduit. Chain Mount (cont’d)
-
On each vise chain unit:
a. Rotate the vise chain handle counterclockwise to expose most of the threads. Leave only three or four threads engaged in the handle.
b. Wrap the chain around the conduit.c. Pull the vise chain tight and insert the chain pins into the chain pockets, or recesses.
d. Turn the handle clockwise to slightly tighten the chain. -
Set the puller into the cradle of the chain mount.
-
Install two pins from the motor side. Secure the pins with two hitch pin clips.
Floor Mount
Requires: A concrete floor with the following characteristics:
- fully cured structural-type concrete
- minimum compressive strength of 211 kg/cm (3000 psi)
- free of cracks, crumbling, or patchwork
WARNING
Follow all floor mounting instructions carefully.
- An improperly attached floor mount can come loose and strike nearby personnel.
- Do not attach the floor mount to masonry, brick, or cinder block. These materials will not hold the anchors securely.
Failure to observe this warning could result in severe injury or death.
-
Determine the best position for locating the floor
• mount. Locate the floor mount: on a flat section
• at least 152 mm (6″) from edge of concrete
• as close to the conduit as possible to reduce the amount of exposed rope under tension
• so that the pull rope will approach the puller’s capstan at a 90° (±5°) angle. -
Set the floor mount in the desired location. Use thefloor mount as a template to drill four ∅15.87 mm (5/8″) holes at least 152 mm (6″) deep.
Note: Use a ∅15.87 mm (5/8″) carbide-tipped masonry bit manufactured in accordance with ANSI standard B94.12-77. -
Vacuum the debris from the holes.
Installation
Greenlee recommends using Greenlee 35607 Wedge Anchors. If another type of
anchor is used, they must have an ICBO (International Conference of Building
Officials) allowable tension and shear rating of 10.7 kN (2400 lb) in 211
kg/cm2 (3000 psi) concrete.
-
Assemble the nut and washer to the anchor so the top of the nut is flush with the top of the anchor, as shown.
-
Insert the four anchors through the floor mount and into the holes in the floor.
-
Hammer the anchors in until the washer is in firm contact with the floor mount.
-
Expand the anchors by torquing the nuts to 122 to 128 Nm (90 to 95 ft-lb).
WARNING
If any of the four anchors spin before the minimum torque is achieved, abandon the location and start elsewhere. An improperly installed anchor can allow the puller to break loose.
Failure to observe this warning could result in severe injury or death. -
Have the installation checked by a qualified inspector.
Operation
-
Fish the rope through the conduit.
-
Set up the cable puller. Refer to “Typical Setups” illustrations and instructions in this manual.
WARNING
Set up the cable puller so that the rope will approach the capstan at an angle of 90° (±5°).
Angles outside of this range may cause the rope to overlap. -
Set the rope ramp as follows:
a. Wind the rope several times around the capstan. b. Pull the ramp away from the mounting plate and rotate it until the flat surface contacts the rope. c. Push the ramp toward the mounting plate and rotate it counterclockwise until it locks into place. -
Check the I/O switch on the puller to be sure it is OFF (O). Plug the puller into the receptacle of the standard force gauge.
-
Connect the force gauge to an appropriate power supply (refer to “Grounding Instructions” in this manual).
Note: If using an extension cord, it must be rated for 20 amps. Use the shortest cord possible. Longer cords reduce puller speed. -
Position the force gauge so that it can be monitored by the puller operator.
Duty Cycle Table Color Band on Meter| Pounds of Pulling Force| Duty Cycle (in minutes)
---|---|---
Green| 0–17.8 kN (0–4000 lb)| continuous
Yellow| 17.8–35.6 kN (4000–8000 lb)| 5 per hour
Red| over 35.6 kN (8000 lb)| puller will stop -
Turn the circuit breaker in the force gauge ON (I).
-
Grasp the tailing end of the rope. Apply a slight amount of tailing force.
-
Turn the puller ON (I).
-
Tail the rope, allowing the spent rope to accumulate on the floor between the operator and the puller.
-
When the pull is complete, turn the puller OFF (O).
Tie off the rope and anchor the cable.
WARNING
Entanglement hazard:
Do not wrap rope around hands, arms, waist, or other body parts.
Do not stand in spent coils or tailed rope. Hold rope so that it may be
released quickly.
Failure to observe this warning could result in severe injury or death.
Removing Cable
Removing old cable involves the same principles as installing new cable.
However, there are some important differences.
Pulling Force
It is difficult to predict the amount of pulling force necessary to remove an
old cable. The cable may be damaged, and it may break with an unexpectedly low
pulling force.
The required pulling forces may be very high:
- The cable has probably “taken a set.” Unlike the new cable on a reel, cable in conduit has probably been in the conduit for years, or perhaps decades. The cable will resist bending and straightening as it is pulled through the conduit.
- The pulling lubricant has probably hardened, increasing pulling resistance.
- The insulation may be damaged and the cable may be corroded.
- Dirt or other foreign matter may have entered the conduit and may have cemented the cable in place.
Using a Force Gauge
When pulling old cable out of a conduit, the pulling force will be highest
when starting the pull. Select a cable puller and pulling components to meet
or exceed the estimated amount of pulling force necessary to remove the old
cable. Because breaking the cable free will require the largest amount of
pulling force, it is necessary to use a force gauge to prevent overloading the
system components. Use the 07120 Force Gauge Unit.
Carefully monitor the pulling force at the force gauge; if the puller is not
able to begin the pull, shut off the puller and disassemble the setup. Start
over with a puller and components of a higher force rating.
Puller Placement
Pulling out old cable is generally accomplished with the puller located some
distance away from the end of the conduit. This allows the pulling crew to
pull out a long section of cable before turning off the puller, cutting off
the cable, and reattaching the grip(s). Mounting the cable puller a distance
away from the end of the conduit increases the amount of exposed rope, which
greatly increases the amount of violent whipping action which would occur if
the rope were to break.
To isolate the operator from the rope path:
-
Locate the puller so that you will stand behind an obstruction, such as a wall. Set up the puller so that you will be able to maintain control of the pull. You need a clear view of the rope as it feeds onto the capstan, including several feet of the rope in front of the capstan. You must be able to turn off the puller before the pulling grip, connector, or swivel contacts the capstan.
-
Use an additional pulling sheave to change the direc-tion of the tailing rope. Anchor the sheave so that you are close enough to maintain control of the pull.
You need a clear view of the rope as it feeds onto the capstan, including several feet of the rope in front of the capstan. You must be able to turn off the puller before the pulling grip, connector, or swivel contacts the capstan.
Note: Use the additional pulling sheave to change the direction of the tailing rope (after the rope leaves the capstan). Do not change the direction of the pulling rope. -
Use a longer tailing rope than usual and stand away from the puller. Stand as far from the puller as pos-sible, while maintaining control of the pull. You need a clear view of the rope as it feeds onto the capstan, including several feet of the rope in front of the capstan. You must be able to turn off the puller before the pulling grip, connector, or swivel contacts the capstan.
USA 800-435-0786 Fax:
800-451-2632
815-397-7070 Fax:
815-397-1865
Canada 800-435-0786 Fax:
800-524-2853
International +1-815-397-7070 Fax:
+1-815-397-9247
4455 Boeing Drive
Rockford, IL 61109-2988 • USA •
815-397-7070
An ISO 9001 Company
Greenlee Textron Inc. is a subsidiary of Textron Inc.
www.greenlee.com
References