Installation Instructions
Original Instructions
Micro800 4-channel Thermocouple/RTD Input Module
Catalog Numbers 2085-IRT4
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not intended to reflect all changes. Translated versions are not always available for each revision.
Environment and Enclosure
ATTENTION: This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in
EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is not intended for use in residential environments and may not
provide adequate protection to radio communication services in such
environments.
This equipment is supplied as open-type equipment for indoor use. It must be
mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed to
prevent personal injury resulting from accessibility to live parts. The
enclosure must have suitable flame-retardant properties to prevent or minimize
the spread of flame, complying with a flame spread rating of 5VA or be
approved for the application if nonmetallic. The interior of the enclosure
must be accessible only by the use of a tool. Subsequent sections of this
publication may contain more information regarding specific enclosure type
ratings that are required to comply with certain product safety
certifications.
In addition to this publication, see the following:
- Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements.
- NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
Prevent Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
- Touch a grounded object to discharge potential static.
- Wear an approved grounding wriststrap.
- Do not touch connectors or pins on component boards.
- Do not touch circuit components inside the equipment.
- Use a static-safe workstation, if available.
- Store the equipment in appropriate static-safe packaging when not in use.
North American Hazardous Location Approval
The following information applies when operating this equipment in
hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I
Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations
only. Each product is supplied with markings on the rating nameplate
indicating the hazardous location temperature code. When combining products
within a system, the most adverse temperature code (lowest “T” number) may be
used to help determine the overall temperature code of the system.
Combinations of equipment in your system are subject to investigation by the
local Authority Having Jurisdiction at the time of installation.
WARNING: EXPLOSION HAZARD
- Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
- Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
- Substitution of components may impair suitability for Class I, Division 2.
ATTENTION:
- This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more information.
- To comply with UL restrictions, this equipment must be powered from a source compliant with the following: Class 2 or Limited Voltage/Current.
- To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV). • Failure to connect a bus terminator module to the last expansion I/O module will result in a controller hard fault.
- Do not wire more than 2 conductors on any terminal.
WARNING:
-
When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
-
If you connect or disconnect wiring while the field-side power is on, an electric arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
-
If you insert or remove the module while backplane power is on, an electric arc can occur.
This could cause an explosion in hazardous location installations. The module does not support “Removal and Insertion Under Power” (RIUP) capability. Do not connect or disconnect the module while power is applied. Be sure power is removed before proceeding. -
Do not unscrew the RTB hold down screws and remove the RTB while power is on. This could cause an explosion in hazardous location installations. Be sure that power is removed before proceeding.
-
Do not connect directly to line voltage. Line voltage must be supplied by a suitable, approved isolating transformer or power supply having short circuit capacity not exceeding 100 VA maximum or equivalent.
-
When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.
Additional Resources
Resource | Description |
---|
Micro830, Micro850, and Micro870 Programmable Controllers
User Manual, publication 2080-UM002| A more detailed description of how to
install and use your
Micro830, Micro850, and Micro870 programmable controllers.
Micro800 Bus Terminator Installation Instructions,
publication 2085-IN002| Information on installing the bus terminator module.
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1| More information on proper wiring and grounding
techniques.
You can view or download publications at rok.auto/literature.
Overview
The Micro800™ expansion I/O is a modular I/O that complements and extends the
capabilities of Micro850® and Micro870® controllers. These expansion I/O
modules interface with the controllers using an I/O expansion port.
I/O Module Overview
Module Description
| Description| | Description
---|---|---|---
1| Mounting screw hole / mounting foot| 5| Module interconnect latch
2| Removable Terminal Block (RTB)| 6| DIN rail mounting latch
3| Thermistor| 7| I/O status indicator
4| RTB hold down screws|
This equipment is sensitive to electrostatic discharge (ESD).
Follow ESD prevention guidelines when handling this equipment.
Mount the Module
For more information on proper grounding guidelines, see the Industrial
Automation Wiring and Grounding
Guidelines, publication 1770-4.1.
Module Spacing
Maintain spacing from objects such as enclosure walls, wireways, and adjacent
equipment. Allow 50.8 mm (2 in.) of space on all sides for adequate
ventilation, as shown.
Mounting Dimensions and DIN Rail Mounting
Mounting dimensions do not include mounting feet or DIN rail latches.
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 x 1 mm (EN
50022 – 35 x 7.5).
For environments with greater vibration and shock concerns, use the panel
mounting method, instead of DIN rail mounting.
Before mounting the module on a DIN rail, use a flat-blade screwdriver in the
DIN rail latch and pry it downwards until it is in the unlatched position.
- Hook the top of the DIN rail mounting area of the controller onto the DIN rail, and then press the bottom until the controller snaps onto the DIN rail.
- Push the DIN rail latch back into the latched position.
Use DIN rail end anchors (Allen-Bradley® part number 1492-EA35 or 1492-EAHJ35) for vibration or shock environments.
To remove your controller from the DIN rail, pry the DIN rail latch downwards until it is in the unlatched position.
Panel Mounting
The preferred mounting method is to use two M4 (#8) per module. Hole spacing
tolerance: ±0.4 mm (0.016 in.).
For mounting dimensions, see the Micro830®, Micro850, and Micro870
Programmable Controllers User Manual, publication 2080-UM002.
Follow these steps to install your module using mounting screws.
- Place the module next to the controller against the panel where you are mounting it. Make sure that the controller and module are spaced properly.
- Mark drilling holes through the mounting screw holes and mounting feet then remove the module.
- Drill the holes at the markings, then replace the module and mount it.
Leave the protective debris strip in place until you are finished wiring the module and any other devices.
System Assembly
The Micro800 expansion I/O module is attached to the controller or another I/O
module by means of interconnecting latches and hooks, as well as the bus
connector. The controller and expansion I/O modules must terminate with a
2085-ECR Bus Terminator module.
Be sure to lock the module interconnect latches and tighten the RTB hold down
screws before applying power to the module.
For installation of the 2085-ECR module, see the Micro800 Bus Terminator
Module Installation Instructions, publication 2085-IN002.
Field Wiring Connections
In solid-state control systems, grounding and wire routing helps limit the
effects of noise due to electromagnetic interference (EMI).
Wire the Module
Included with your module are two 12-pin Removable Terminal Blocks (RTB).
Basic wiring of the module is shown below.
Basic Wiring to the Module
The module currently ships with the CJC assembly fixed to the module.
Specifications
General Specifications
Attribute | Value |
---|---|
Number of I/O | 4 |
Dimensions, HxWxD | 44.5x90x87mm(1.75 x 3.54 x 3.42 in.) |
Shipping weight, approx. | 220 g (7.76 oz) |
Bus current draw, max | 5V DC,160 mA24V DC, 50 mA |
Wire size | |
Min | Max |
Solid | 0.34 mm2 (22 AWG) |
(194’3F), or greater.1.2 mm (3/64 in.) insulation max
Stranded| 0.20 mm2(22 AWG)| 2.5 mm2 (14 AWG)
Wiring categoryn)| 2 – on signal ports
Terminal screw torque| 0.5…0.6 N•m
(4.4…5.3 lb•in) (2)
Input type| Thermocouple type: B, C, E, J, K, TXK/XK (L), N, R. S, T
RTD type:
100 0 Pt a = 0.00385 Euro
200 0 Pt a = 0.00385 Euro
100 0 Pt a = 0.003916 U.S
200 0 Pt a = 0.003916 U.S.
100 0 Nickel 618 200 0 Nickel 618 120 0 Nickel 672 10 0 Copper 427 mV range:
0…100 mV
Ohm input: 0…500 (1
Resolution| 16 bits
Channel update time, typical| 12…500 ms per enabled channel
Input impedance| >10 MO
Power dissipation, total| 2 W
Enclosure type rating| None (open-style)
Status indicators| 1 health status indicators
Isolation voltage| 50V (continuous), Reinforced Insulation Type, channel to
system. Type tested at 720V DC for 60 s
North American temp code| T4
- Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
- RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Environmental Specifications
Attribute | Value |
---|---|
Temperature, operating | IEC 60068-2-1 (Test Ad, Operating Cold), |
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…+65 °C (-4…+149 °F)
Temperature, surrounding air, max| 65 °C (149 °F)
Temperature, nonoperating| IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…+85 °C
(-40…+185 °F)
Relative humidity| IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95%
noncondensing
Vibration| IEC 60068-2-6 (Test Fc, Operating): 2 g @ 10…500 Hz
Shock, operating| IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g
Shock, nonoperating| IEC 60068-2-27 (Test Ea, Unpackaged Shock): 25 g – DIN
rail mount
35 g – Panel mount
Emissions| IEC 61000-6-4
ESD immunity| IEC 61000-4-2:
6 kV contact discharges 8 kV air discharges
Radiated RF immunity| IEC 61000-4-3:10V/m with 1 kHz sine-wave 80% AM from
80…6000 MHz
EFT/B immunity| IEC 61000-4-4:
±2 kV at 5 kHz on signal ports ±2 kV @ 100 kHz on signal ports
Surge transient immunity| IEC 61000-4-5:
-El kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
Conducted RF immunity| IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Certifications
Certification (when product is marked)(1) | Value |
---|---|
c-UL-us | UL listed Industrial Control Equipment, certified for US and Canada. |
See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified
for U.S. and Canada. See UL File E334470
CE| European Union 2014/30/EU EMC Directive, compliant with: EN 61326-1;
Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union
2011/65/EU RoHS, compliant with:
EN IEC 63000; Technical documentation
RCM| Australian Radiocommunications Act, compliant with: EN 61000-6-4;
Industrial Emissions
KC| Korean Registration of Broadcasting and Communications Equipment,
compliant with: Article 58-2 of Radio Waves Act, Clause 3
- See the Product Certification link at rok.auto/certifications for Declaration of Conformity, Certificates, and other certification details.
Rockwell Automation Support
Use these resources to access support information.
Technical Support Center| Find help with how-to videos, FAQs, chat, user
forums, and product notification updates.|
rok.auto/support
---|---|---
Knowledgebase| Access Knowledgebase articles.|
rok.auto/knowledgebase
Local Technical Support Phone Numbers| Locate the telephone number for your
country.| rok.auto/phonesupport
Literature Library| Find installation instructions, manuals, brochures
brochures,
and technical data publications.|
rok.auto/literature
Product Compatibility and Download
Center (PCDC)| Download firmware, associated files (such as AOP EDS, and DIM),
and access product release notes.’| rok.auto/pcdc
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any
suggestions on how to improve our content, complete the form at
rok.auto/docfeedback.
Waste Electrical and Electronic Equipment (WEEE)
At the end of life, this equipment should be collected separately from any
unsorted municipal waste.
Rockwell Automation maintains current product environmental compliance
information on its website at rok.auto/pec.
Connect with us.
rockwellautomation.com
expanding human possibility”
AMERICAS: Rockwell Automation, 1201 South Second Street, Milwaukee, WI
53204-2496 USA, Tel: (1)414.382.2000, Fax: (1) 414.382.4444 EUROPE/MIDDLE
EAST/AFRICA: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831
Diegem, Belgium, Tel: (32)2 663 0600, Fax: (32)2 663 0640 ASIA PACIFIC:
Rockwell Automation, Level 14, Core F, Cyberport 3,100 Cyberport Road, Hong
Kong, Tel: (852)2887 4788, Fax: (852)2508 1846
Allen-Bradley, expanding human possibility, FactoryTalk, Micro800, Micro830,
Micro850, Micro870, Rockwell Automation, and TechConnect are trademarks of
Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are
property of their respective companies.
Publication 2085-IN007C-EN-P – August 2022 | Supersedes Publication 2085
-IN007B-EN-P – December 2012
Copyright © 2022 Rockwell Automation, Inc. All rights reserved. Printed in
Singapore.
References
- Product Certifications | Rockwell Automation
- Publication Feedback Form | Rockwell Automation
- Rockwell Automation Tech Support ... 24 x 7 around the globe!
- Literature Library | Rockwell Automation
- Support | Rockwell Automation
- Rockwell Automation (@rokautomation) • Instagram photos and videos
- Select a Region | Rockwell Automation
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>