MITSUBISHI ELECTRIC PKA-A12LA1 Split System Heat Pump User Manual

June 17, 2024
Mitsubishi Electric

MITSUBISHI ELECTRIC PKA-A12LA1 Split System Heat Pump

MITSUBISHI-ELECTRIC-PKA-A12LA1-Split-System-Heat-Pump-
product

Product Specifications

  • Model Name: PKA-A12LA1, PKA-A18LA1
  • Service Reference: PKA-A12LA1, PKA-A18LA1
  • Indoor Unit: Split-System Heat Pump
  • Service Manual Date: March 2023

Product Usage Instructions

Indoor Unit Controls

The indoor unit is equipped with the following controls:

  • MENU
  • RETURN
  • SELECT
  • ON
  • HOLD
  • OFF

Remote Controllers

The product supports wireless and wired remote controllers as options for convenient operation.

Parts Catalog and Manuals

  • Parts Catalog: TCB117
  • Service Manual: PUZ-A12/18NKA7, PUY-A12/18NKA7, PUZ-A12/18NKA8, PUZ-A24NHA8, PUY-A12/18NKA8, PUY-A24NHA8, PUZ-HA24NHA1, PUZ-HA36NKA
  • Service Manual No./Parts Catalog No.: OCH636/OCB636, OCH764/OCB764, OCH750/OCB750

Safety Precautions

Always observe safety precautions before accessing terminals. Ensure all supply circuits are disconnected.

Cautions for Refrigerant R410A

When working with R410A refrigerant, follow these precautions:

  • Use specified tools for R410A.
  • Clean refrigerant piping thoroughly to avoid contamination.
  • Avoid using charging cylinders to prevent refrigerant composition changes.
  • Ventilate the room in case of refrigerant leaks to prevent release of poisonous gases.

Frequently Asked Questions

  • Q: Can I use refrigerant other than R410A with this product?
    • A: No, using refrigerant other than R410A can cause deterioration of refrigerant oil and malfunction of the product.
  • Q: What precautions should I take during repair services?
    • A: Always use new refrigerant pipes, clean the refrigerant piping thoroughly, and use specified tools designed for R410A refrigerant to prevent any issues.

“`

SPLIT-SYSTEM HEAT PUMP
SERVICE MANUAL

Indoor unit [Model Name] PKA-A12LA1
PKA-A18LA1

[Service Ref.] PKA-A12LA1 PKA-A18LA1

March 2023
No. TCH117

INDOOR UNIT

MENU RETURN SELECT

ON

HOLD

OFF

WIRELESS REMOTE CONTROLLER (Option)

WIRED REMOTE CONTROLLER (Option)

REFERENCE MANUAL

OUTDOOR UNIT’S SERVICE MANUAL

Model name
PUZ-A12/18NKA7 PUY-A12/18NKA7 PUZ-A12/18NKA8 PUZ-A24NHA8 PUY-A12/18NKA8 PUY- A24NHA8 PUZ-HA24NHA1 PUZ-HA36NKA

Service Ref.
PUZ-A12/18NKA7 PUY-A12/18NKA7 PUZ-A12/18NKA8 PUZ-A24NHA8 PUY-A12/18NKA8 PUY- A24NHA8 PUZ-HA24NHA1 PUZ-HA36NKA

Service manual No./Parts catalog No. OCH636/OCB636 OCH764/OCB764 OCH750/OCB750

SAFETY PRECAUTION

2-1. ALWAYS OBSERVE FOR SAFETY
Before obtaining access to terminal, all supply circuits must be disconnected.
2-2. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilising refrigerant R410A

TCH117

2

Preparation before the repair service.
· Prepare the proper tools. · Prepare the proper protectors. · Provide adequate ventilation. · After stopping the operation of the air conditioner, turn off
the power-supply breaker. · Discharge the condenser before the work involving the
electric parts.
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with the following: · Be sure to clean the pipes and make sure that the insides
of the pipes are clean. · Change flare nut to the one provided with this product.
Use a newly flared pipe. · Avoid using thin pipes. · In case of reconnecting the refrigerant pipes after
detaching, make the flared part of pipe re-fabricated.
Make sure that the inside and outside of refrigerant piping is clean and it has no contamination such as sulfur hazardous for use, oxides, dirt, shaving particles, etc. In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterioration of refrigerant oil, etc.

Precautions during the repair service.
· Do not perform the work involving the electric parts with wet hands.
· Do not pour water into the electric parts. · Do not touch the refrigerant. · Do not touch the hot or cold areas in the refrigerating cycle. · When the repair or the inspection of the circuit needs to be
done without turning off the power, exercise great caution not to touch the live parts. · When opening or closing the valve below freezing temperatures, refrigerant may spurt out from the gap between the valve stem and the valve body, resulting in injuries.

Use a vacuum pump with a reverse flow check valve.
Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil, etc.

Use the following tools specifically designed for use with R410A refrigerant.

The following tools are necessary to use R410A refrigerant.

Tools for R410A

Gauge manifold

Flare tool

Charge hose

Size adjustment gauge

Gas leak detector

Vacuum pump adaptor

Torque wrench

Electronic refrigerant

charging scale

Store the piping indoors, and keep both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor.
The refrigerant oil applied to flare and flange connections must be ester oil, ether oil or alkylbenzene oil in a small amount. If large amount of mineral oil enters, that can cause deterioration of refrigerant oil, etc.
Charge refrigerant from liquid phase of gas cylinder. If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22, etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil, etc.

Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact with a flame, poisonous gases will be released.
Use the specified refrigerant only.
Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.

TCH117

3

[1] Warning for service
(1) Do not alter the unit. (2) For installation and relocation work, follow the instructions in the Installation Manual and use tools and pipe
components specifically made for use with refrigerant specified in the outdoor unit installation manual. (3) Ask a dealer or an authorized technician to install, relocate and repair the unit. (4) This unit should be installed in rooms which exceed the floor space specified in outdoor unit installation manual.
Refer to outdoor unit installation manual. (5) For appliances not accessible to the general public. (6) Refrigerant pipes connection shall be accessible for maintenance purposes. (7) If the air conditioner is installed in a small room or closed room, measures must be taken to prevent the refrig-
erant concentration in the room from exceeding the safety limit in the event of refrigerant leakage. Should the refrigerant leak and cause the concentration limit to be exceeded, hazards due to lack of oxygen in the room may result. (8) Keep gas-burning appliances, electric heaters, and other fire sources (ignition sources) away from the location where installation, repair, and other air conditioner work will be performed. If refrigerant comes into contact with a flame, poisonous gases will be released. (9) When installing or relocating, or servicing the air conditioner, use only the specified refrigerant written on outdoor unit to charge the refrigerant lines. Do not mix it with any other refrigerant and do not allow air to remain in the lines. If air is mixed with the refrigerant, then it can be the cause of abnormal high pressure in the refrigerant line, and may result in an explosion and other hazards. (10) After installation has been completed, check for refrigerant leaks. If refrigerant leaks into the room and comes into contact with the flame of a heater or portable cooking range, poisonous gases will be released. (11) Do not use low temperature solder alloy in case of brazing the refrigerant pipes. (12) When performing brazing work, be sure to ventilate the room sufficiently. Make sure that there are no hazardous or flammable materials nearby. When performing the work in a closed room, small room, or similar location, make sure that there are no refrigerant leaks before performing the work. If refrigerant leaks and accumulates, it may ignite or poisonous gases may be released. (13) Do not install the unit in places where refrigerant may build-up or places with poor ventilation such as a semibasement or a sunken place in outdoor: Refrigerant is heavier than air, and inclined to fall away from the leak source. (14) Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. (15) The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater). (16) Do not pierce or burn. (17) Be aware that refrigerants may not contain an odour. (18) Pipe- work shall be protected from physical damage. (19) The installation of pipe- work shall be kept to a minimum. (20) Compliance with national gas regulations shall be observed. (21) Keep any required ventilation openings clear of obstruction. (22) Servicing shall be performed only as recommended by the manufacturer. (23) The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. (24) Maintenance, service and repair operations shall be performed by authorized technician with required qualification.
[2] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely. (2) Do not release refrigerant in the air. (3) After completing service, charge the cycle with specified amount of refrigerant. (4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[3] Additional refrigerant charge
When charging directly from cylinder (1) Check that cylinder for R410A available on the market is a syphon type. (2) Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)

TCH117

4

Unit

Electronic weighing scale

[4] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.

No. Tool name 1. Gauge manifold
2. Charge hose 3. Electronic weighing scale 4. Gas leak detector 5. Adaptor for reverse flow check 6. Refrigerant charge base 7. Refrigerant cylinder
8. Refrigerant recovery equipment

Specifications · Use the existing fitting specifications. (UNF1/2) · Use high- tension side pressure of 5.3MPa·G [768.7 PSIG] or over. · Use pressure performance of 5.09MPa·G [738.2 PSIG] or over.
· Use the detector for R410A. · Attach on vacuum pump.
· Top of cylinder (R410A refrigerant)
· Cylinder with syphon

PARTS NAMES AND FUNCTIONS

Front Panel

Filter

Air intake

Louver

Vane

Air outlet

Emergency operation switch
Operation indicator lamp Remote control receiving section

TCH117

5

INDOOR UNIT

4 SPECIFICATIONS

Service Ref.

Mode

Power supply (phase, voltage, cycle)

Input

Running current

External finish (Panel)

Heat exchanger

Dimensions

W

D

H

Weight

Fan Fan (drive) × No.

Fan motor output

Fan motor

Airflow (Lo-Mid2-Mid1-Hi)

External static pressure Noise level (Lo-Mid2-Mid1-Hi)

kW A
mm (inch) mm (inch) mm (inch)
kg (lbs)
kW F.L.A m3/min CFM Pa (mmAq)
dB

PKA-A12LA1

Cooling

Heating

Single phase, 208/230 V, 60Hz

0.06

0.03

0.55

0.30

Munsell 0.7PB 9.2/0.4

Plate fin coil

898 (35-23/64)

237 (9-11/32)

299 (11-25/32)

12.7 (28.0)

Line flow fan (direct) × 1

0.030

0.19

6.1 – 7.3 – 9.0 – 10.7

7.5 – 8.2 – 9.2 – 10.9

215 – 255 – 320 – 375

265 – 290 – 325 – 385

0 (direct blow)

34 – 39 – 44 – 48

34 – 37 – 40 – 43

Service Ref.

Mode

Power supply (phase, voltage, cycle)

Input

Running current

External finish (Panel)

Heat exchanger

Dimensions

W

D

H

Weight

Fan Fan (drive) × No.

Fan motor output

Fan motor

Airflow (Lo-Mid2-Mid1-Hi)

External static pressure Noise level (Lo-Mid2-Mid1-Hi)

kW A
mm (inch) mm (inch) mm (inch)
kg (lbs)
kW F.L.A m3/min CFM Pa (mmAq)
dB

PKA-A18LA1

Cooling

Heating

Single phase, 208/230 V, 60Hz

0.06

0.04

0.55

0.45

Munsell 0.7PB 9.2/0.4

Plate fin coil

898 (35-23/64)

237 (9-11/32)

299 (11-25/32)

12.7 (28.0)

Line flow fan (direct) × 1

0.030

0.19

6.1 – 7.3 – 9.0 – 10.7

7.5 – 8.9 – 10.6 – 12.7

215 – 255 – 320 – 375

265 – 310 – 375 – 450

0 (direct blow)

34 – 39 – 44 – 48

34 – 39 – 44 – 48

INDOOR UNIT

TCH117

6

OCTAVE BAND SOUND PRESSURE LEVEL, dB0dB=0.0002bar) 1.0m [3.3 ft]

NOISE CRITERION CURVES

5-1. NOISE CRITERION CURVES

FAN SPL(dB) LINE

High

48

Medium 1 44

Medium 2 39

Low

34

90

80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20
Approximate minimum audible limit on continuous noise

NC-20

10 63

125 250 500 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz

Main unit

TCH117

Measurement location 1.0m [3.3 ft] * Measured in anechoic room.

Wall

7

1-59/64(49)

(163) 6-27/64

1-31/32(50) MIN.
IN CASE OF LEFT PIPING, LEFT BACK PIPING,2-11/64(55) MIN. OR OPTIONAL DRAIN PUMP INSTALLATION,2-61/64(75) MIN.

E

6 OUTLINES AND DIMENSIONS

TCH117

REQUIRED SPACE(INDOOR UNIT)
AIR INLET

TOP

10-63/64(279)

10-63/64(279)

OPERATING RANGE OF THE HORIZONTAL VANE

8

F

2-23/64(60)

OR LESS

E

MIN. 9/32(7)

F MORE THAN 2-23/64(60)
MIN. 2-23/64(60)

WITH OPTIONAL DRAIN PUMP
MIN. 9-27/32(250)

DETAILS OF CUT OUT FOR PIPING HOLE
D

1-31/32(50) MIN.
IN CASE OF OPTIONAL DRAIN PUMP INSTALLATION, 13-25/32(350) MIN.
10-15/64(260) MIN.
A

AIR OUTLET 5-29/32(150) MIN.
LEFT

(250) 9-27/32 MIN.

FRONT

22-43/64(576)

5-45/64(145)

RIGHT

INSTALLATION PLATE

11-25/32(299)

(47) 1-27/32
(59) 2-21/64

2-3/4

(70)

(50) 1-31/32

25/64(10)

C

3/4(19)

SLEEVE THROUGH HOLE

2-61/64 2-61/64 ­ 3-5/32

( 75)

( 75 ­ 80)

INDOOR UNIT
0 9/32(7.2 )
5/8(16) 59/64(23.5 ) 1-17/64( 32.2 ) 1-49/64( 44.7 ) 2-63/64( 76) 4-7/32(107.2 ) 4-23/32(119.7 ) 5-13/64(132.2 ) 6-3/16(157.2 )
9-41/64(244.7 ) 10-1/8(257.2 )

17-43/64( 449) 15-13/32( 391.5)
11-1/4( 287.2) 9-3/8( 238) 0
5-5/64( 128.8 ) 5-37/64( 141.8 )
8-11/32( 212) 11-1/8( 282.5 )
( 392.5) 15-29/64
( 449) 17-43/64

14-21/64( 364) 13-25/32( 350.2 ) 12-41/64( 321.2 ) 10-51/64( 274.2 ) 9-1/8( 231.7 ) 6-1/2(165) 4-59/64(125) 19/32(15) 0 19/32(15) 4-59/64(125) 6-1/2(165) ( 231.7 ) 10-51/64 11-15/64( 285.2) 12-41/64( 321.2) 13-25/32( 350.2) 14-21/64( 364) 29×
13/64( 5.1HOLE)

2-9/16(65) 2-9/16(65)
B

(67) 2-41/64

1-61/64(49.5)

2-3/4(70)

1-21/32(50)

3-27/64(87)

INSTALLATION PLATE

5× 23/64( 9HOLE)
WALL HOLE 2-61/34( 75) FOR LEFT BACK PIPING

25/64(10)

(67) 2-41/64

D

1-59/64(49)

25-19/32(650)

LEFT PIPING CUT OUT AREA REFRIGERANT PIPE,DRAIN PIPE

35-23/64(898)

FRONT(OPEN THE GRILLE)

TEMPORARILY FIXING HOLE
WALL HOLE 2-61/64( 75) FOR RIGHT BACK PIPING

4.3HOLE)

11/64(

63/64( 25)

0 63/64( 25)

2-1/4( 57.2 ) 2-3/4( 69.7 ) 3-15/64(82.2)
4-55/64(123.5)

DRAIN HOSE
BOTTOM

6-31/32(177.2) 7-15/32(189.7) 9-1/16(230)
10-25/32( 274 )

17-23/32(450)(GAS PIPE) 20-63/64(533)(LIQUID PIPE)
AUTO VANES

C

LOUVERS(MANUAL)

B

UNDER PIPING CUT OUT AREA

REFRIGERANT PIPE,DRAIN PIPE

WALL HOLE 2-61/64( 75) FOR RIGHT BACK CONDIT CABLE

7-53/64(199)

A
9-11/32(237) 13/64(5) RIGHT PIPING CUT OUT AREA REFRIGERANT PIPE,DRAIN PIPE
TERMINAL BLOCK FOR INDOOR/OUTDOOR CONNECTING LINE MA-REMOTE CONTROLLER TERMINAL BLOCK
EMERGENCY OPERATION SWITCH(HEAT)

EMERGENCY OPERATION SWITCH(COOL)

OPERATING LAMP(GREEN)

7-9/16(192)

STANDBY LAMP(ORANGE)

7-1/64(178) 6-19/64(160)

1. FOR CEILING CORNICE: CONSIDER THE DIMENSION

FOR INSTALLATION.

2. MOUNTING BOLT FOR INSTALLATION PLATE: M10 OR W3/8

TAPPING SCREW: NOMINAL DIAMETER · · · 5/32(4)

LENGTH · · · 63/64(25) MIN

SCREW TIGHT AT INSTALLATION PLATE HOLE {11/64( 4.3)}

ON THE UPPER AND LOWER SIDE EVENLY.

DO NOT SCREW TIGHT ONLY IN LINE.

3. REFRIGERANT LIQUID PIPE

1/4( 6.35)

PIPING

GAS PIPE

1/2( 12.7)

DRAIN HOSE CONNECTION 5/8( 16)

INSULATION 1-9/64( 29)

4. LEFT PIPE: CONNECT DRAIN HOSE TO CONNECTION PORT

RECEIVER

ON THE LEFT SIDE OF DRAIN PAN. EXCHANGE DRAIN HOSE AND RUBBER CAP

AND BUTT THEM AGAINST DRAIN PORT.

5. DRAIN PIPE EFFECTIVE LENGTH · · · 19-11/16(500)

UNDER PIPING CUT OUT AREA REFRIGERANT PIPE,DRAIN PIPE

Unit: inch (mm)

7 WIRING DIAGRAM

TCH117

9

REFRIGERANT SYSTEM DIAGRAM

Heat exchanger

Strainer (#50)
Refrigerant GAS pipe connection (Flare)

Thermistor TH2 (Pipe temperature/liquid)

Refrigerant flow in cooling Refrigerant flow in heating

Thermistor TH5 (Cond./ Eva.temperature)

Thermistor TH1 (Room temperature)

Distributor with strainer (#100/#50)

Refrigerant LIQUID pipe connection (Flare)
Strainer (#100)

TCH117

10

TROUBLESHOOTING

9-1. TROUBLESHOOTING
<Check code displayed by self-diagnosis and actions to be taken for service (summary)> Present and past check codes are logged, and they can be displayed on the wired remote controller or controller board of outdoor unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summarized in the table below. Check the contents below before investigating details.

Unit conditions at service The trouble is reoccurring.

Check code

Actions to be taken for service (summary)
Judge the problem and take a corrective action according to “9-3. SELF- DIAGNOSIS ACTION TABLE”.

Displayed

Conduct troubleshooting and ascertain the cause of the trouble according to “9-4. TROUBLESHOOTING OF PROBLEMS”.
Not displayed

The trouble is not reoccurring.

Logged Not logged

Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise, etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring, etc. Reset check code logs and restart the unit after finishing service. There is no abnormality in electrical component, controller board, remote controller, etc.
Re-check the abnormal symptom. Conduct troubleshooting and ascertain the cause of the trouble according to “9-4. TROUBLESHOOTING OF PROBLEMS”. Continue to operate unit for the time being if the cause is not ascertained. There is no abnormality concerning of parts such as electrical component, controller board, remote controller, etc.

TCH117

11

9-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
Refer to “13-7. SELF-DIAGNOSIS” to search for the error history.

[Output pattern A]

Beeper sounds Beep

Beep Beep Beep

Beep

OPERATION

1st

2nd 3rd

nth

INDICATOR

lamp blink pattern

Off Self-check Approx. 2.5 s

On On On 0.5 s 0.5 s 0.5 s

On

Off

0.5 s Approx. 2.5 s

starts

(Start signal received)

Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)

Beep Beep 1st 2nd · · ·Repeated

On

On

0.5 s 0.5 s

Number of blinks/beeps in pattern indicates the check code in the following table

[Output pattern B]

Beeper sounds Beep

OPERATION

INDICATOR

lamp blink pattern

Off Self-check Approx. 2.5 s

starts

(Start signal

received)

On Approx. 3 s

Beep Beep Beep

1st

2nd

3 rd

On On On 0.5 s 0.5 s 0.5 s

Beep nth

On

Off

0.5 s Approx. 2.5 s

Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)

On Approx. 3 s

Beep Beep 1st 2nd · · ·Repeated

On

On

0.5 s 0.5 s

Number of blinks/beeps in pattern indicates the check code in the following table

[Output pattern A] Errors detected by indoor unit

Wireless remote controller Wired remote controller

Beeper sounds/OPERATION INDICATOR lamp blinks (Number of times)

Check code

Symptom

1

P1

Intake sensor error

2

P2

Pipe (TH2) sensor error

P9

Pipe (TH5) sensor error

3

E6,E7

Indoor/outdoor unit communication error

4

P4

Drain sensor error/Float switch connector (CN4F) open

5

P5

Drain pump error

PA

Forced compressor stop(due to water leakage abnormality)

6

P6

Freezing/Overheating protection operation

7

EE

Combination error between indoor and outdoor units

8

P8

Pipe temperature error

9

E4, E5

Remote controller signal receiving error

10

­

­

11

Pb

Indoor unit fan motor error

12

Fb (FB)*

Indoor unit control system error (memory error, etc.)

14 No sound

PL E0, E3

Abnormal refrigerant circuit Remote controller transmission error

No sound

E1, E2

Remote controller control board error

No sound

­ ­ ­ ­

No corresponding

Remarks

[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)

Wireless remote controller Beeper sounds/OPERATION
INDICATOR lamp blinks (Number of times)
1
2 3 4
5
6
7 8 9 10
11
12 13 14

Wired remote controller Check code

Symptom

E9
UP U3,U4
UF
U2
U1,Ud (UD)*
U5 U8 U6 U7
U9,UH
Others

Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) Compressor overcurrent interruption Open/short of outdoor unit thermistors Compressor overcurrent interruption (When compressor locked) Abnormal high discharge temperature/49C operated/ insufficient refrigerant Abnormal high pressure (63H operated)/Overheating protection operation Abnormal temperature of heat sink Outdoor unit fan protection stop Compressor overcurrent interruption/Abnormal of power module Abnormality of super heat due to low discharge temperature Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error Other errors (Refer to the technical manual for the outdoor unit.)

Remarks For details, check the LED display of the outdoor controller board. As for outdoor unit, refer to outdoor unit’s service manual.

Notes: 1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp
does not come on, there are no error records. 2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to confirm the self-check start signal
was received, the specified refrigerant address is incorrect.

TCH117

12

· On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
· On wired remote controller Check code displayed in the LCD.

  • The check code in the parenthesis indicates PAR-41MAA model.

If the unit cannot be operated properly after test run, refer to the following table to find the cause.

Symptom Wired remote controller

LED 1, 2 (PCB in outdoor unit)

Cause

Please Wait
Please Wait Check code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).

For about 3 minutes after power-on

After LED 1, 2 are lit, LED 2 is turned · For about 3 minutes following power- on, operation

off, then only LED 1 is lit.

of the remote controller is not possible

(Correct operation)

due to system startup. (Correct operation)

Only LED 1 is lit.

Subsequent to

LED 1, 2 blink.

about 3 minutes

after power-on Only LED 1 is lit.

LED 1 blinks twice,

LED 2 blinks once.

· Connector for the outdoor unit’s protection device is not connected. · Reverse or open phase wiring for the outdoor unit’s power terminal block (L1, L2, GR).
· Incorrect wiring between indoor and outdoor units (incorrect polarity of S1, S2, S3) · Remote controller wire short

On the wireless remote controller with condition above, following phenomena take place. · No signals from the remote controller can be received. · Operation lamp is blinking. · The buzzer makes a short ping sound.

Note: Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.

LED1 (power for microprocessor)

Indicates whether control power is supplied. Make sure that this LED is always lit.

LED2 (power for remote controller) LED3 (communication between indoor and outdoor units)

Indicates whether power is supplied to the remote controller. This LED lights only in the case of the indoor unit which is connected to the outdoor unit refrigerant addresses “0”.
Indicates state of communication between the indoor and outdoor units. Make sure that this LED is always blinking.

TCH117

13

9-3. SELF-DIAGNOSIS ACTION TABLE

Note: Errors to be detected in outdoor unit, such as codes starting with F, U or E (excluding E0 to E7), are not covered in this document. Please refer to the outdoor unit’s service manual for the details.

Check code Abnormal point and detection method

Room temperature thermistor (TH1)

The unit is in 3-minute resume

prevention mode if short/open of

thermistor is detected. Abnormal if

the unit does not reset normally after

3 minutes. (The unit returns to normal

operation, if it has been reset nor-

mally.)

Constantly detected during cooling,

drying, and heating operation.

Short: 90°C [194°F] or more

P1

Open: -40°C [-40°F] or less

Cause Defective thermistor characteristics
Contact failure of connector (CN20) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Defective indoor controller board

Pipe temperature thermistor/Liquid

(TH2)

The unit is in 3-minute resume

prevention mode if short/open of

thermistor is detected. Abnormal if

the unit does not reset normally after

3 minutes. (The unit returns to normal

operation, if it has been reset nor-

mally.)

P2

Constantly detected during cooling,

drying, and heating (except defrost-

ing) operation

Short: 90°C [194°F] or more

Open: -40°C [-40°F] or less

Defective thermistor characteristics Contact failure of connector (CN44) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Defective refrigerant circuit is causing thermistor temperature of 90°C [194°F] or more or -40°C [-40°F] or less.
Defective indoor controller board

Contact failure of drain float switch

Contact failure of connector

(CN4F)

(Insert failure)

· Extract when the connector of drain float

P4

switch is disconnected.

Defective indoor controller

( and of connector CN4F is not short- board

circuited.)

· Constantly detected during operation

Countermeasure
­ Check resistance value of thermistor. 32°F [0°C]……15.0 k 50°F [10°C]……9.6 k 68°F [20°C]……6.3 k 86°F [30°C]……4.3 k
104°F [40°C]……3.0 k If you put force on (draw or bend) the lead wire with measuring resistance value of thermistor, breaking of wire or contact failure can be detected.
Check contact failure of connector (CN20) on the indoor controller board. Refer to “9-7. TEST POINT DIAGRAM”. Turn the power on again and check restart after inserting connector again. Check room temperature display on remote controller. Replace indoor controller board if there is abnormal difference with actual room temperature. Turn the power off, and on again to operate after check.
­ Check resistance value of thermistor. For characteristics, refer to (P1) above.
Check contact failure of connector (CN44) on the indoor controller board. Refer to “9-7. TEST POINT DIAGRAM”. Turn the power on and check restart after inserting connector again. Check pipe temperature with remote controller in test run mode. If pipe temperature is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may be defective. Check pipe temperature with remote controller in test run mode. If there is extremely difference with actual pipe temperature, replace indoor controller board. Turn the power off, and on again to operate after check.
Check contact failure of float switch connector. Turn the power on again and check after inserting connector again. Operate with connector (CN4F) short- circuited. Replace indoor controller board if abnormality reappears.

Drain overflow protection operation

Malfunction of drain pump

Check if drain-up machine works.

Suspensive abnormality, if drain float

Defective drainage

Check drain function.

switch is detected to be underwater for 1 Clogged drain pump

minute and 30 seconds continuously with Clogged drain pipe

drain pump on.

Defective drain float switch

Remove drain float switch connector CN4F

Compressor and indoor fan will be turned Catch of drain float switch or

and check if it is short (Switch On) with the

off.

malfunction of moving parts

moving part of float switch UP, or OPEN with

Drain pump is abnormal if the condition

cause drain float switch to be

the moving part of float switch down.

above is detected during suspensive

detected under water (Switch

Replace float switch if it is short with the

P5

abnormality.

On)

moving part of float switch down.

Constantly detected during drain pump

Defective indoor-controller

Replace indoor controller board if it is short-

operation

board

circuited between ­ of the drain float

switch connector CN4F and abnormality

reappears.

It is not abnormal if there is no problem about the above-mentioned . Turn the power off, and on again to operate after check.

TCH117

14

Check code Abnormal point and detection method
Freezing/overheating protection is working
Freezing protection (Cooling mode) The unit is in 6-minute resume prevention mode if pipe <liquid or condenser/ evaporator> temperature stays under -15°C [-5°F] for 3 minutes, 3 minutes after the compressor started. Abnormal if it stays under -15°C [-5°F] for 3 minutes again within 16 minutes after 6-minute resume prevention mode.

Cause
(Cooling or drying mode) Clogged filter (reduced airflow) Short cycle of air path Low-load (low temperature) operation out of the tolerance range Defective indoor fan motor
· Fan motor is defective. · Indoor controller board is
defective.

Countermeasure (Cooling or drying mode)
Check clogs of the filter. Remove shields.
Refer to “9-6. HOW TO CHECK THE PARTS”.

Defective outdoor fan control Overcharge of refrigerant Defective refrigerant circuit (clogs)

Check outdoor fan motor. Check operating condition of refrigerant circuit.

P6

Overheating protection (Heating mode) The unit is in 6-minute resume prevention mode if pipe <liquid or condenser/evaporator> temperature

(Heating mode) Clogged filter (reduced airflow) Short cycle of air path

(Heating mode) Check clogs of the filter.
Remove shields.

is detected as over 70°C [158°F] after

Overload (high temperature)

the compressor started. Abnormal if

operation out of the toler-

the temperature of over 70°C [158°F]

ance range

is detected again within 30 minutes

Defective indoor fan motor

Refer to “9-6. HOW TO CHECK THE PARTS”.

after 6-minute resume prevention

· Fan motor is defective.

mode.

· Indoor controller board is

defective.

Defective outdoor fan control Check outdoor fan motor.

Overcharge of refrigerant

­ Check operating condition of refrigerant cir-

Defective refrigerant circuit

cuit.

(clogs)

Bypass circuit of outdoor unit

is defective.

Pipe temperature

Slight temperature difference ­ Check pipe <liquid or condenser/evaporator>

between indoor room

temperature with room temperature display

Detected as abnormal when the pipe

temperature and pipe <liquid

on remote controller and outdoor controller

temperature is not in the cooling range

or condenser/evaporator>

circuit board.

3 minutes after compressor start and 6

temperature thermistor

Pipe <liquid or condenser/evaporator> tem-

minutes after the liquid or condenser/

· Shortage of refrigerant

perature display is indicated by setting SW2

evaporator pipe is out of cooling range.

· Disconnected holder of

of outdoor controller circuit board as follows.

Note 1: It takes at least 9 minutes to

pipe <liquid or condenser/

detect. Note 2: Abnormality P8 is not detected in
drying mode. Cooling range: -3°C [-5.4°F] ] (TH-TH1)

evaporator> thermistor · Defective refrigerant circuit Reverse connection of extension pipe (on plural

( ) Conduct temperature check with outdoor controller circuit board after connecting `A-Control Service Tool(PAC-SK52ST)’.

TH: Lower temperature between liquid

units connection)

pipe temperature (TH2) and con-

Reverse wiring of indoor/

denser/evaporator temperature (TH5) outdoor unit connecting wire

P8

TH1: Intake temperature

(on plural units connection)

Check reverse connection of extension pipe or reverse wiring of indoor/outdoor unit connecting wire.

Defective detection of indoor

When 10 seconds have passed after the room temperature and pipe

compressor starts operation and the hot

<condenser/evaporator>

adjustment mode has finished, the unit is temperature thermistor

detected as abnormal when condenser/

Stop valve is not opened

evaporator pipe temperature is not in

completely.

heating range within 20 minutes.

Note 3: It takes at least 27 minutes to detect abnormality.
Note 4: It excludes the period of defrosting. (Detection restarts when defrosting mode is over.)
Heating range: 3°C [5.4°F] [ (TH5-TH1)

TCH117

15

Check code Abnormal point and detection method

Pipe temperature thermistor/

Condenser-Evaporator (TH5)

The unit is in 3-minute resume protec-

tion mode if short/open of thermistor is

detected. Abnormal if the unit does not

get back to normal within 3 minutes. (The

unit returns to normal operation, if it has

been reset normally.)

Constantly detected during cooling,

drying, and heating operation (except

defrosting)

P9

Short: 90°C [194°F] or more Open: -40°C [-40°F] or less

Abnormal refrigerant circuit

During Cooling, Drying, or Auto Cooling

operation, the following conditions are

regarded as failures when detected for 1

second.

a)The compressor continues to run for 30

or more seconds.

b)The liquid pipe temperature or the

PL

condenser/evaporator temperature is

75°C [167°F] or more.

These detected errors will not be

cancelled until the power source is

reset.

Cause

Countermeasure

Defective thermistor characteristics Contact failure of connector (CN44) on the indoor controller board (Insert failure) Breaking of wire or contact failure of thermistor wiring Temperature of thermistor is 90°C [194°F] or more or -40°C [-40°F] or less caused by defective refrigerant circuit.
Defective indoor controller board

­ Check resistance value of thermistor. For characteristics, refer to (P1).
Check contact failure of connector (CN44) on the indoor controller board. Refer to “9-7. TEST POINT DIAGRAM”.
Turn the power on and check restart after inserting connector again. Operate in test run mode and check pipe <condenser/evaporator> temperature with outdoor controller circuit board. If pipe <condenser/evaporator> temperature is extremely low (in cooling mode) or high (in heating mode), refrigerant circuit may have defect. Operate in test run mode and check pipe <condenser/evaporator> temperature with outdoor control circuit board. If there is extreme difference with actual pipe <condenser/evaporator> temperature, replace indoor controller board. There is no abnormality if none of above comes within the unit. Turn the power off and on again to operate.
( ) In case of checking pipe temperature with outdoor controller circuit board, be sure to connect A-control service tool (PAC-SK52ST).

Abnormal operation of 4-way valve Disconnection of or leakage in refrigerant pipes Air into refrigerant piping
Abnormal operation (no rotation) of indoor fan · Defective fan motor. · Defective indoor control
board. Defective refrigerant circuit (clogging)

When this error occurs, replace the 4-way valve. Check refrigerant pipes for disconnection or leakage. After the recovery of refrigerant, vacuum dry the whole refrigerant circuit. Refer to “9-6-2. DC fan motor (fan motor/ indoor controller circuit board”.
Check refrigerant circuit for operation. To avoid entry of moisture or air into refrigerant circuit which could cause abnormal high pressure, purge air in refrigerant circuit or replace refrigerant.

Remote controller transmission error(E0)/signal receiving error(E4)
Abnormal if main or sub remote controller cannot receive any transmission normally from indoor unit of refrigerant address “0” for 3 minutes. (Check code: E0) Abnormal if sub remote controller could not receive any signal for 2 minutes. (Check code: E0)

Contact failure at transmission wire of remote controller All remote controllers are set as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board. Miswiring of remote controller

Check disconnection or looseness of indoor unit or transmission wire of remote controller. Set one of the remote controllers “main” if there is no problem with the action above. Check wiring of remote controller. · Total wiring length: maximum 500 m
(Do not use cable with 3 or more cores.) · The number of connecting indoor units:
maximum 16 units · The number of connecting remote control-
ler: maximum 2 units

E0 or E4

Abnormal if indoor controller board cannot receive any data normally from remote controller board or from other indoor controller board for 3 minutes.

When it is not the above-mentioned problem of

­

Defective transmitting receiving Diagnose remote controllers.

circuit of remote controller

a) When “OK” is displayed,

(Check code: E4) Indoor controller board cannot receive any signal from remote controller for 2 minutes. (Check code: E4)

Defective transmitting receiving circuit of indoor controller board of refrigerant addresses “0”. Noise has entered into the transmission wire of remote

Remote controllers have no problem. Turn the power off, and on again to check. If abnormality occurs again, replace indoor controller board. b) When “NG” is displayed, Replace remote controller.

controller.

c)When “E3” or “ERC” is displayed, noise

may be causing abnormality.

Note:

If the unit is not normal after replacing indoor

controller board in group control, indoor control-

ler board of address “0” may be abnormal.

TCH117

16

Check code Abnormal point and detection method

Remote controller transmission

error(E3)/signal receiving error(E5)

Abnormal if remote controller could not find blank of transmission path for 6 seconds and could not transmit. (Check code: E3)

Remote controller receives transmitted

data at the same time and compares the

received and transmitted data. Abnormal

E3

if these data are judged to be different

or

30 continuous times. (Check code: E3)

E5

Abnormal if indoor controller board could not find blank of transmission path. (Check code: E5)

Indoor controller board receives transmitted data at the same time and compares the received and transmitted data. Abnormal if these data are judged to be different 30 continuous times. (Check code: E5)

Indoor/outdoor unit communication

error (Signal receiving error)

Abnormal if indoor controller board

cannot receive any signal normally for 6

minutes after turning the power on.

Abnormal if indoor controller board

cannot receive any signal normally for 3

minutes.

E6

Consider the unit abnormal under the

following condition: When 2 or more

indoor units are connected to an

outdoor unit, indoor controller board

cannot receive a signal for 3 minutes

from outdoor controller circuit board, a

signal which allows outdoor controller

circuit board to transmit signals.

Cause

Countermeasure

2 remote controllers are set as “main.” (In case of 2 remote controllers) Remote controller is connected with 2 indoor units or more. Repetition of refrigerant address Defective transmitting receiving circuit of remote controller Defective transmitting receiving circuit of indoor controller board Noise has entered into transmission wire of remote controller.

Set a remote controller to main, and the other to sub.
Remote controller is connected with only one indoor unit. The address changes to a separate setting.
­ Diagnose remote controller. a) When “OK” is displayed, remote control-
lers have no problem. Turn the power off,and on again to check. When becoming abnormal again, replace indoor controller board. b) When “NG” is displayed, replace remote controller. c) When “E3” or “ERC” is displayed, noise may be causing abnormality.

Check LED display on the outdoor control

circuit board. (Connect A-control service

tool, PAC-SK52ST.)

Refer to outdoor unit service manual.

Contact failure, short circuit or, Check disconnection or looseness of indoor/

miswiring (reverse wiring) of indoor/outdoor unit connecting wire

outdoor unit connecting wire of indoor unit or outdoor unit. Check all the units in case of twin triple indoor unit system.

Defective transmitting receiving ­ Turn the power off, and on again to

circuit of indoor controller board

check. If abnormality occurs again,

Defective transmitting receiving

replace indoor controller board or outdoor

circuit of indoor controller board Noise has entered into indoor/

controller circuit board. Note: Other indoor controller board may have defect

outdoor unit connecting wire. in the case of twin triple indoor unit system.

E7
Fb (FB)*

Indoor/outdoor unit communication error (Transmitting error) Abnormal if “1” receiving is detected 30 times continuously though indoor controller board has transmitted “0”.

Defective transmitting receiving circuit of indoor controller board Noise has entered into power supply. Noise has entered into outdoor control wire.

­ Turn the power off, and on again to check. If abnormality occurs again, replace indoor controller board.

Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board.

Defective indoor controller board

Replace indoor controller board. * The check code in the parenthesis indicates
PAR-41MAA model.

Remote controller control board
Abnormal if data cannot be read normally from the nonvolatile memory of the remote controller control board. (Check code: E1)

Defective remote controller

Abnormal if the clock function of remote controller cannot be operated normally. (Check code: E2) E1
or
E2

Replace remote controller.

TCH117

17

Check code Abnormal point and detection method

Forced compressor stop

(due to water leakage abnormality)

The unit has a water leakage abnormal-

ity when the following conditions, a)

and b), are satisfied while the above-

mentioned detection is performed.

a) The intake temperature subtracted with

liquid pipe temperature detects to be

less than -10°C [14°F] for a total of

30 minutes. (When the drain sensor

is detected to be NOT soaked in the

water, the detection record of a) and b)

will be cleared.)

b) Drain float switch detects to be in the

PA

water for more than 15 minutes.

Note:

Once the water leakage abnormality is

detected, abnormality state will not be

released until the main power is reset.

Cause Drain pump trouble
Defective drainage · Drain pump clogging · Drain pipe clogging
Open circuit of float switch
Contact failure of float switch connector
Dew condensation on float switch · Drain water trickles down
lead wire. · Drain water ripples due to
filter clogging.
Extension piping connection difference at twin, triple or quadruple system

Countermeasure Check the drain pump. Check whether water can be drained.
Check the resistance of the float switch. Check the connector contact failure. Check the float switch leadwire mounted. Check the filter clogging.
Check the piping connection.

Fan motor trouble Pb

Miswiring of indoor/outdoor connecting at twin, triple or quadruple system Room temperature thermistor/ liquid pipe temperature thermistor detection is defective.

Check the indoor/outdoor connecting wires.
Check the room temperature display of remote controller. Check the indoor liquid pipe temperature display of outdoor controller board.

Defective fan motor Defective indoor controller board Contact failure of fan motor connector

– Refer to “9-6-2. DC Fan Motor (fan motor/ indoor controller board)”.

TCH117

18

9-4. TROUBLESHOOTING OF PROBLEMS

Note: Refer to the outdoor unit’s service manual for the detail of remote controller.

Phenomena
(1)LED2 on indoor controller board is off.

Cause
· When LED1 on indoor controller board is also off. Power supply of rated voltage is not supplied to outdoor unit.

Defective outdoor controller circuit board

Power supply of 208/230 V is not supplied to indoor unit.

Defective indoor controller board
· When LED1 on indoor controller board is lit. Mis-setting of refrigerant address for outdoor unit (There is no unit corresponding to refrigerant address “0”.)

(2)LED2 on indoor controller board is blinking.

· When LED1 on indoor controller board is also blinking. Connection failure of indoor/outdoor unit connecting wire

Countermeasure
Check the voltage of outdoor power supply terminal block (L1, L2). · When 208/230 V AC is not detected,
check the power wiring to outdoor unit and the breaker. · When 208/230 V AC is detected, check
(below). Check the voltage between outdoor terminal block S1 and S2. · When 208/230 V AC is not detected,
–check the fuse on outdoor controller circuit board. –check the wiring connection. · When 208/230 V AC is detected, check
(below). Check the voltage between indoor terminal block S1 and S2. · When 208/230 V AC is not detected,
check indoor/outdoor unit connecting wire for miswiring. · When 208/230 V AC is detected, check (below). Check the fuse on indoor controller board. Check the wiring connection. If no problem is found, indoor controller board is defective.
Check again the setting of refrigerant address for outdoor unit. Set the refrigerant address to “0”. (For grouping control system under which 2 or more outdoor units are connected, set one of the units to “0”.) Set refrigerant address using SW1 (3-6) on outdoor controller circuit board.
Check indoor/outdoor unit connecting wire for connection failure.

· When LED1 is lit. Miswiring of remote controller wires Under twin or triple indoor unit system, 2 or more indoor units are wired together.
Refrigerant address for outdoor unit is wrong or not set. Under grouping control system, there are some units whose refrigerant addresses are 0.
Short-circuit of remote controller wires Defective remote controller

Check the connection of remote controller wires in case of twin triple indoor unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one of those units. Check the setting of refrigerant address in case of grouping control system. If there are some units whose refrigerant addresses are 0 in one group, set one of the units to 0 using SW1 (3-6) on outdoor controller circuit board.
Remove remote controller wires and check LED2 on indoor controller board. · When LED2 is blinking, check the shortcircuit of remote controller wires. · When LED2 is lit, connect remote controller wires again and: if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block, etc. has returned to normal.

TCH117

19

Phenomena (3)Upward/downward vane
performance failure
(4)Receiver for wireless remote controller

Note: Refer to the outdoor unit’s service manual for the detail of remote controller.

Cause The vane is not downward during defrosting and heat preparation and when the thermostat is OFF in HEAT mode. (Working of COOL protection function) Vane motor does not rotate. · Defective vane motor · Breaking of wire or connection failure of connector
Upward/downward vane does not work. · The vane is set to fixed position.
Weak batteries of wireless remote controller
Contact failure of connector (CNB) on wireless remote controller board (Insert failure) Contact failure of connector (CN90) on indoor controller board (Insert failure) Contact failure of connector between wireless remote controller board and indoor controller board

Countermeasure Normal operation (The vane is set to horizontal regardless of remote control.)
Check (left). · Check the vane motor. (Refer to 9-6.
HOW TO CHECK THE PARTS.) · Check for breaking of wire or connection
failure of connector. Normal operation (Each connector on vane motor side is disconnected or setting the fixed vanes by wired remote controller.) Replace batteries of wireless remote controller.
Check contact failure of each connector. If no problems are found of connector,
replace indoor controller board. When the same trouble occurs even if indoor controller board is replaced, replace wireless remote controller board.

TCH117

20

9-5. EMERGENCY OPERATION

9-5-1. When wireless remote controller fails or its battery is exhausted

CD

When the remote controller cannot be used When the batteries of the remote controller run out or the remote controller malfunctions, the emergency operation can be done using the emergency buttons on the grille.
STANDBY lamp OPERATING lamp Emergency operation cooling switch Emergency operation heating switch Receiver

Starting operation · To operate the cooling mode, press the button for more than 2 seconds. B · To operate the heating mode, press the button for more than 2 seconds. A · Lighting of the OPERATING lamp means the start of operation.

Note:

E

Details of emergency mode are as shown below.

Details of EMERGENCY MODE are as shown below.

Operation mode

COOL

HEAT

Set temperature

24°C [75°F]

24°C [75°F]

Fan speed Airflow direction

High Horizontal (Step 1)

High Downward (Step 5)

Stopping operation · To stop operation, press the button or the button for more than 2 seconds.

9-5-2. When wired remote controller or indoor unit microprocessor fails
1. When the wired remote control or the indoor unit microprocessor has failed, but all other components work properly, Setting the switch (SWE) on the indoor controller board ON will begin the indoor unit Emergency Operation. When Emergency Operation is activated, the indoor unit operates as follows: (1) Indoor fan is running at high speed. (2) Drain pump is working. (option) Note on the wireless remote control When the remote control does not function, it is possible to activate Emergency Operation by using the indoor unit Emergency Operation switch. However, if the indoor unit microprocessor has failed, it is nesessary to proceed with points 2 and 3 below as in the case of the wired remote control.
2. When you activate Emergency Operation of the cooling or heating, you have to set the switch (SWE) on the indoor controller board and activate Emergency Operation of the outdoor unit. For details on how to activate Emergency Operation of the outdoor unit, refer to the outdoor unit wiring diagram.
3. Before you activate Emergency Operation, check the following points: (1) Emergency Operation cannot be activated when: · the outdoor unit malfunctions. · the indoor fan malfunctions. · it has detected the malfunction of drain-up machine during self-diagnosing. (2) Emergency Operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or temperature control, etc. does not function. (3) Avoid operating for a long time when the outdoor unit begins defrosting while Emergency Operation of the heating is activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After Emergency Operation has been deactivated, set the switches, etc. to their original positions. (6) Movement of the vanes does not work in Emergency Operation, therefore you have to slowly set them manually to the appropriate position.

TCH117

21

9-6. HOW TO CHECK THE PARTS

Parts name

Checkpoints

Room temperature thermistor (TH1)

Disconnect the connector then measure the resistance with a multimeter.

Pipe temperature thermistor/liquid(TH2)

Refer to “9-6-1. Thermistor”.

Condenser/evaporator temperature thermistor (TH5)

Vane motor (Upper MV1) Measure the resistance between the terminals with a multimeter.

7 Sky Blue 9 Sky Blue

(At the ambient temperature 25°C [77°F])
M
Normal

10 Red
Connector(CNV) pin No.

Sky Sky Blue Blue
68

Red-Sky Blue Red-Sky Blue Red-Sky Blue Red-Sky Blue
300 ± 7%

Vane motor (Lower MV2) Measure the resistance between the terminals with a multimeter.

2 Sky Blue 4 Sky Blue

(At the ambient temperature 25°C [77°F])
M
Normal

5 Red

Connector(CNV) pin No.

Sky Sky Blue Blue
13

Red-Sky Blue Red-Sky Blue Red-Sky Blue Red-Sky Blue 300 ± 26.3

Fan motor (MF)

Refer to “9-6-2. DC Fan motor (fan motor/indoor controller circuit board)”.

9-6-1. Thermistor

Thermistors for lower temperature

Room temperature thermistor (TH1) Pipe temperature thermistor/liquid (TH2) Condenser/evaporator temperature thermistor (TH5)

Thermistor R0=15k ± 3% Fixed number of B=3480 ± 2%

t( )Rt=15exp { 3480( 1 273+t

1 )} 273

1

1

273+

T-32 1.8

273

32°F [0°C] 50°F [10°C] 68°F [20°C] 77°F [25°C] 86°F [30°C] 104°F [40°C]

15 9.6 6.3 5.4 4.3 3.0

Resistance (k”)

< Thermistor for lower temperature > 50 40 30 20 10 0 -20 -10 0 10 20 30 40 50 (°C) -4 -14 32 50 68 86 104 122 (°F) Temperature

TCH117

22

9-6-2. DC Fan motor (fan motor/indoor controller circuit board)
Check method of DC fan motor (fan motor/indoor controller circuit board) Notes · High voltage is applied to the connector (CNMF) for the fan motor. Pay attention to the service. · Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller circuit board and fan motor.) Self check Symptom : The indoor fan cannot rotate.
Wiring contact check Contact of fan motor connector (CNMF)

Yes Is there contact failure?
No

Correct the wiring.

Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit board. TEST POINT : VDC (between 1 (+) and 4 (-) of the fan connector): VDC 294-325 V DC TEST POINT : VCC (between 5 (+) and 4 (-) of the fan connector): VCC 15 V DC

No Is the voltage normal?
Yes

Replace the indoor controller board.

OK Check the operation.
Fail Replace the defective fan motor.

Complete.

Sensor signal check
Measure the voltage between CNMF and 0 V DC and 15 V DC in the indoor controller circuit board.

Does the voltage repeat 0 V DC and 15 V DC?
Yes
Replace the indoor controller board.
OK Check the operation.
Fail Replace the defective fan motor.

No Complete.

Replace the defective fan motor.
Yes OK
Check the operation of fan.
Fail
Replace the indoor controller board.

Complete.

Symptom: The fan motor does not stop when pressing the stop button on the remote controller. The fan motor starts to rotate when turning on the breaker.
Process: The connector for emergency operation on the indoor controller board is possibly set to ON. Check the setting of SWE. Set SWE to OFF if it is set to ON.

TCH117

23

9-7. TEST POINT DIAGRAM Indoor controller board

CN2L Connector (LOSSNAY)

CNP Drain pump output 1­3: 13 VDC (option)

LED1: Power supply (I.B)
CN105 IT Terminal
CN4F Float switch (FS) (option)
CN41 Connector (HA terminal-A)
SWE Emergency operation connector
CN51 Centrally control
CN32 Remote switch
LED3: Transmission (Indoor/Outdoor)

SW1 Model selection
SW2 Capacity setting

CNMF Connect to the fan motor (MF) 1­4 : 294-325 VDC 5­4 : 15 V DC 6­4 : 0­6.5 VDC 7­4 : 0 or 15 VDC
CN01 Connect to the Terminal block (TB4) 1­3 : 208/230 V AC
FUSE (3.15 A 250 V)
CN3C Transmission (Indoor/outdoor) (0­28 VDC)
CN44 Pipe temperature thermistor 1­2 : Liquid (TH2) 3­4 : Condenser/
Evaporator(TH5)
CN90 Connect to the remote operation adapter
CN22 Connect to the terminal block (TB5) (Remote controller connecting wire) (option)

Jumper wire J41,J42 Pair No. setting for wireless remote controller

LED2: Power supply (Wired remote controller)

CNV Vane motor (MV1, MV2) 12 VDC pulse outlet

CN20 Room temp. thermistor (TH1)

CNRU Connect to SWITCH BOARD (S.B), LED BOARD (L.B) and PCB for WIRELESS REMOTE CONTROLLER (option)

TCH117

24

9-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIRE
Each function is controlled by the DIP switch and the jumper wire on the indoor controller board.

The black square () indicates a switch position.

Jumper wire Functions

Setting by the DIP switch and jumper wire

Remarks

SW1

Model settings

MODELS PKA-ALA1

SETTING
123456 ON OFF

SW2

Capacity settings

MODELS PKA-A12LA1
PKA-A18LA1

SETTING
123456 ON OFF
123456 ON OFF

Pair number

J41 J42

setting with wireless remote

controller

Wireless remote Control PCB setting

controller setting J41

J42

0

1

2

3­9

Jumper wire ( : Short : Open)

Wireless remote controller: 0 Control PCB: (for both J41 and J42) 4 pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left. (‘ ‘ in the table indicates the jumper wire is disconnected.)

TCH117

25

10 FUNCTION SETTING

UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER

Each function can be set as necessary using the remote controller. The setting of function for each unit can only be done by the remote controller. (1) Functions available when setting the unit number to “Grp.”
Refer to the service manual that comes with each outdoor unit. (2) Functions available when setting the unit numbers to 1-4 or “All” (07 in case of wireless remote controller)

Function

Settings

Filter sign
Fan speed
Fan speed during the cooling thermostat is OFF

100 Hr 2500 Hr No filter sign indicator Silent Standard High ceiling Setting fan speed Stop Extra low

Mode No. 07 08 27

Setting No. 1 2 3 1 2 3 1 2 3

Initial setting

Setting

TCH117

26

11 SPECIAL FUNCTION

11-1. ROTATION FUNCTION(AND BACK-UP FUNCTION, 2ND STAGE CUT-IN FUNCTION)

Connect optional wired remote controller through Terminal Block kit (PAC- SH29TC-E) to PKA type.

11-1-1. Operation

(1) Rotation function (and Back-up function)

· Outline of functions

· Main and sub unit operate alternately according to the interval of rotation setting.

Main and sub unit should be set by refrigerant address. (Outdoor DIP switch setting)

Refrigerant address”00″

Main unit

Refrigerant address”01″

Sub unit

· When an error occurs to one unit, another unit will start operation. (Back- up function)

· System constraint

· This function is available only by the grouping control system(INDOOR UNIT : OUTDOOR UNIT=1:1) of 2 refrigerant

groups. (Refer to Fig. 1)

· Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit

should also be connected. (Refer to Fig. 1)

(This function cannot be set by wireless remote controller.)

· Set refrigerant address of each unit. (DIP switch on the outdoor unit···Refrigerant address 00/01)

Operation pattern

1 [Back-up function only]··· Request code number “312”

Main unit IC-1

Start operation Run

Error occurs on main unit. Main Sub
Abnormal condition

Fig. 1 Refrigerant address Refrigerant address

“00”

“01”

Main unit

OC-1 3(2)

OC-2 Sub
3(2) unit

Sub

unit

Stop

Run

IC-2

2 [Rotation function] & [Back-up function]··· Request code number “313­318”

Main unit IC-1

Start operation Main Run

Sub Main Stop

Error occurs on main unit. Sub Main Sub
Abnormal condition Run

IC-1

IC-2

2

2

RC

OC : Outdoor unit IC : Indoor unit RC : Wired remote controller

Sub

unit

Stop

Run

Stop

Run

IC-2

1­28 days

1­28 days

(Ex:When the request code number is “313”, each unit operates alternately in daily cycle.)

Note: · When the unit is restarted to operate after turning off the power or operation OFF status, the unit which was operating will
start operation. · To operate the main unit, refer to “11-1-2. How to set rotation function(Back-up function, 2nd stage cut-in function)” and set
the request code No. which is not the same as the current one, then set again the former request code No.
(2) 2nd stage cut-in function · Outline of functions
· When the 1st unit CANNOT supply sufficient capacity for exceptionally high- demand conditions and the actual room temperature reaches set point(), the 2nd unit starts operation in conjunction with the 1st unit.
· Once the actual room temperature goes down to 4°C [7.2°F] below set point(
), the 2nd unit stops operation automatically. (* set point = set temperature by R/C (remote controller) + 4, 6, 8°C [7.2, 10.8, 14.4°F] (selectable) )
· Number of operating units is determined according to the room temperature and set point. · When room temperature reaches higher than set point, standby unit starts. (2 units operation) · When room temperature falls below set point -4°C [-7.2°F], standby unit stops. (1 unit operation)

TCH117

27

· System constraint · This function is available only in cooling mode.

Ex.) Set temp. by R/C = 20°C [68°F] Set point = 26°C [79°F] When request code number is “323”.

26°C [79°F] 22°C [71.5°F] 20°C [68°F]

2nd unit Cut-in
4°C [7.2°F] 2nd unit Cut-out

[2nd stage cut-in function]··· Request code number “322­324”

Main unit IC-1

Room temp. ] Set point Start operation Sub unit start operation
Run

Room temp. < Set point -4°C [-7.2°F] Sub unit stop

Sub

unit

Stop

Run

IC-2

Stop

11-1-2. How to set rotation function(Back-up function, 2nd stage cut-in function) You can set these functions by wired remote controller.(Maintenance monitor)

NOTICE
Both main and sub unit should be set in same setting. Every time replacing indoor controller board for servicing, the function should be set again.

(1) Request Code List

Rotation setting
Setting No. (Request code)
No.1 (310) No.2 (311) No.3 (312) No.4 (313) No.5 (314) No.6 (315) No.7 (316) No.8 (317) No.9 (318)

Setting contents Monitoring the request code of current setting Rotation and Back-up OFF (Normal group control operation)
Back-up function only Rotation ON (Alternating interval = 1day) and back-up function Rotation ON (Alternating interval = 3days) and back-up function Rotation ON (Alternating interval = 5days) and back-up function Rotation ON (Alternating interval = 7days) and back-up function Rotation ON (Alternating interval = 14days) and back-up function Rotation ON (Alternating interval = 28days) and back-up function

2nd unit cut-in setting
Setting No. (Request code)
No.1 (320) No.2 (321) No.3 (322) No.4 (323)
No.5 (324)

Setting contents Monitoring the request code of current setting
Cut-in function OFF Cut-in function ON (Set point = Set temp.+ 4:[7.2-F] Cut- in function ON (Set point = Set temp.+ 6:[10.8-F] Cut-in function ON (Set point = Set temp.+ 8:[14.4-F]

Initial setting
Initial setting

TCH117

28

11-2. BACK-UP HEATING FUNCTION
11-2-1. Operation
The back-up heater turns ON when both of the following conditions have been satisfied: A) When the room temperature has not risen after the heater ON delay time has passed.
Note: The heater ON delay time starts when the condition of “set temperature – room temperature > 1°F [0.5:]” has been satisfied. B) Set temperature – room temperature ] 3°F [1.5:]

The back-up heater turns OFF when the following condition has been satisfied:

· Set temperature – room temperature ] 1°F [0.5:]

Heater output ON

Set temp. – room temp. 1°F [0.5:]

The heater output turns ON when both the conditions A and B have been satisfied.

3°F [1.5:]

Heater output OFF

11-2-2. How to change the heater ON delay time
You can set these functions by wired remote controller. Note that the change can be made only by the wired remote controller PAR-41MAA.
Notes: 1. Both main and sub unit should be set in the same setting. 2. Every time replacing indoor controller board for service, the function should be set again. 3. Stop the air-conditioner operation before changing the heater ON delay time.

Request code list

Setting No. (Request code)

Setting contents

No.1

Monitoring the request

code of current setting

No.2 391

10 minutes

No.3 392

15 minutes

No.4 393

20 minutes

No.5 394

25 minutes

No.6 395

5 minutes

Initial setting

11-2-3. How to connect
When connecting to the connector CN24 of the indoor unit, use PAC-SE56RA-E (optional parts). Note: For a twin indoor unit system, connect to the CN24 of the indoor unit that the remote controller is connected to.

TCH117

29

12 DISASSEMBLY PROCEDURE

: Indicates the visible parts in the photos/figures.

OPERATION PROCEDURE

1. REMOVING THE PANEL
(1) Insert the driver to the hole at VANE LOWER shaft and slide the VANE LOWER shaft (2 places each). Push VANE UPPER shaft with the driver.
(2) Pull the VANE LOWER and VANE UPPER from unit. (3) Remove 2 screw caps of the front panel. Remove 2
screws. (See Photo 1) (4) Hold the lower part of both ends of the front panel and pull
it slightly toward you, and then remove the front panel by pushing it upward. (5) Remove the screw of the corner box. (See Photo 1) Remove the corner box.
Unlock the stopper and remove the horizontal vanes using following tool like a screw driver.
Unlock

NOTE: Turn OFF the power supply before assembly. Be careful when removing heavy parts.
PHOTOS/FIGURES

Photo 1 VANE UPPER shaft

VANE UPPER

VANE LOWER shaft

Front panel VANE LOWER

Screw of the Screws and screw caps corner box
Photo 2 Screw of electrical Hook
box cover (side)
Screw of electrical box cover (side)

Unlock

Water cover
Photo 3-1

Screw of electrical box cover (Front)
Connector for ground wire Fixture

2. REMOVING THE ELECTRICAL BOX

(1) Remove the panel and the corner box. (Refer procedure to 1) (2) Remove the front and side electrical box covers (each 2
screw). (3) Disconnect the indoor/outdoor connecting wire from
terminal block (TB4). (4) Disconnect the wired remote controller connecting wire
from terminal block. (5) Disconnect the connectors on the indoor controller board. (6) Disconnect the connector for ground wire. (7) Remove the screw on lower side of the electrical box.
(See Photo 3) (8) Push up the upper fixture catch to remove the box, then
remove it from the box fixture.

Photo 3-2

Electrical box

TCH117

Screw of electrical box
30

OPERATION PROCEDURE
3. REMOVING THE INDOOR CONTROLLER BOARD, THE WIRELESS REMOTE CONTROLLER BOARD AND THE LED BOARD
(1) Remove the panel and the corner box. (Refer to procedure 1)
(2) Remove the front and side electrical box covers (each 2 screw).
(3) Disconnect the connectors on the indoor controller board. (See Photo 4)
(4) Remove the switch board holder and open the cover. (5) Pull out the indoor controller board toward you then
remove the indoor controller board and switch board. (See Photo 4) (6) Remove the holder of wireless remote controller board and LED board. (7) Disconnect the connector of wireless remote controller board and LED board. (8) Remove the wireless remote controller board and LED board from the holder.

PHOTOS/FIGURES

Photo 4
Holder of wireless remote controller board and LED board

Switch board holder (Holder of switch board)

Indoor controller board

Photo 5 (see the bottom)
Nozzle assembly

Vane motor unit

4. REMOVING THE NOZZLE ASSEMBLY (with VANE and VANE MOTOR) AND DRAIN HOSE
(1) Remove the panel and corner box. (Refer to procedure 1) (2) Remove the electrical box covers. (Refer to procedure 2) (3) Disconnect the vane motor connector (CNV) on the indoor
controller board. (4) Push fixture and pull out the drain hose from the nozzle
assembly, and remove nozzle assembly. (See Photo 6)

Drain hose

5. REMOVING THE VANE MOTOR
(1) Remove the nozzle assembly. (Refer to procedure 4) (2) Remove 2 screws of the vane motor unit cover, and pull
out the vane motor unit. (3) Remove screw of the vane motor (LOWER). (4) Remove the vane motor (LOWER) from the vane motor
unit cover. (5) Disconnect the connector (white) from the vane motor.
(LOWER) (6) Remove 2 screw of the vane motor (UPPER). (7) Remove the vane motor (UPPER) from the vane motor
unit cover. (8) Disconnect the connector (blue) from the vane motor
(UPPER).

Photo 6 Screws of the vane motor (LOWER)
Fixture Drain hose
Screws of the vane motor unit cover
Photo 7

TCH117

Screws of the vane motor (UPPER)
31

OPERATION PROCEDURE
6. REMOVING THE INDOOR FAN MOTOR AND THE LINE FLOW FAN
(1) Remove the panel and the corner box. (Refer to procedure 1) (2) Remove the electrical box (Refer to procedure 2) and the
nozzle assembly (Refer to procedure 4). (3) Remove the water cover. (See Photo 2) (4) Loosen the screw fixing the line flow fan. (See Photo 9) (5) Remove 3 screws fixing the motor bed. (See Photo 8) (6) Remove the motor bed together with fan motor and motor
band. (7) Release the 2 hooks of the motor band. Remove the motor
band. Pull out the indoor fan motor. (8) Remove 2 screws fixing the left side of the heat exchanger.
(See Photo 10) (9) Lift the heat exchanger, and pull out the line flow fan to the
lower-left. * When attaching the line flow fan, screw the line flow fan so
4mm, 5/32 inch gap is provided between the right end of the line flow fan and the right wall of the air passage of the box. (Photo 9)

PHOTOS/FIGURES
Photo 8
Lead wire of pipe thermistor
Motor band

Screws of the motor bed

Photo 9

Motor bed Screw of the line flow fan

Photo 10

Screws of the left side of the heat exchanger

4 mm, 5/32 inch

7. REMOVING THE PIPE TEMPERATURE THERMISTOR/LIQUID (TH2) AND COND./EVA. TEMP. THERMISTOR (TH5)
(1) Remove the panel and the corner box. (Refer to procedure 1)
(2) Remove the electrical box covers. (Refer to procedure 2) (3) Remove the water cover. (See Photo 2) (4) Remove the liquid pipe thermistor and gas pipe thermistors. (5) Disconnect the connector (CN44) on the indoor controller
board. (TH2 and TH5/CN44)

Photo 11
Condenser/evaporator temp. thermistor (TH5)
Liquid pipe thermistor (TH2)

Connector for ground wire

TCH117

32

OPERATION PROCEDURE
8. REMOVING THE HEAT EXCHANGER
(1) Remove the panel and the corner box (Refer to procedure 1). (2) Remove the electrical box (Refer to procedure 2) and the
nozzle assembly (Refer to procedure 4). (3) Remove the water cover. (4) Remove the pipe thermistors. (Refer to procedure 7). (5) Remove the motor bed together with fan motor and motor
band (Refer to procedure 6). (6) Remove 2 screws fixing the left side of the heat exchanger.
(See Photo 10) (7) Remove the heat exchanger.

PHOTOS/FIGURES
Photo 12
Heat exchanger

Photo 13
Condenser/evaporator temp. thermistor (TH5)

Water cover Connector for ground wire

Liquid pipe thermistor (TH2)

9. REMOVING THE ROOM TEMPERATURE THERMISTOR
(1) Remove the panel and corner box. (Refer to procedure 1) (2) Remove the electrical box covers. (Refer to procedure 2) (3) Remove the room temperature thermistor. (4) Disconnect the connector (CN20) on the indoor controller
board.

Photo 14

Room temp. thermistor (TH1)

Indoor controller board

TCH117

33

13 REMOTE CONTROLLER

13-1. REMOTE CONTROLLER FUNCTIONS

Controller interface

The functions of the function buttons change depending on the screen. Refer to the button function guide that appears at the bottom of the LCD for the functions they serve on a given screen. When the system is centrally controlled, the button function guide that corresponds to the locked button will not appear.

MENU RETURN SELECT

ON

HOLD

OFF

Function buttons

Main display
Fri

Cool
Mode

Room 83 Set temp.
83
Temp.

Auto
Fan

7 890
Menu screen
Operation Vane·Louver·Vent. (Lossnay) High power Comfort
Main menu: RETURN Cursor

7 890

Main menu
Main Main menu Energy saving
7 890
Function guide

[ON/OFF] button Press to turn ON/OFF the indoor unit.
[SELECT/HOLD] button Press to save the setting. When the Main menu is displayed, pressing this button will enable/disable the HOLD function.
[RETURN] button Press to return to the previous screen.
[MENU] button Press to bring up the Main menu.
Backlit LCD Operation settings will appear. When the backlight is off, pressing any button turns the backlight on and it will stay lit for a certain period of time depending on the screen.
When the backlight is off, pressing any button turns the backlight on and does not perform its function. (except for the [ON/OFF] button)

ON/OFF lamp This lamp lights up in green while the unit is in operation. It blinks while the remote controller is starting up or when there is an error.
Function button [F1] Main display: Press to change the operation mode. Menu screen: The button function varies with the screen.
Function button [F2] Main display: Press to decrease temperature. Main menu: Press to move the cursor left. Menu screen: The button function varies with the screen.
Function button [F3] Main display: Press to increase temperature. Main menu: Press to move the cursor right. Menu screen: The button function varies with the screen.
Function button [F4] Main display: Press to change the fan speed. Menu screen: The button function varies with the screen.

TCH117

34

Display

The main display can be displayed in two different modes: “Full” and “Basic”. The initial setting is “Full”. To switch to the “Basic” mode, change the setting on the Main display setting. (Refer to operation manual included with remote controller.)

All icons are displayed for explanation.

$

2345 6 7

8

$

2

6

7

8 90

Room 83

Cool Set temp.

1

83

1

Mode

Temp.

Fri 3 9 @ )
Auto
4
Fan

Fri 3

Cool Set temp. Auto

1 83

4

Mode

Temp.

Fan

!

2

5 Operation mode

Preset temperature

5
Appears when the Weekly timer is enabled.

Clock Fan speed Button function guide Functions of the corresponding buttons appear here.
Appears when the ON/OFF operation is centrally controlled.

Appears while the units are operated in the energy saving mode. (Will not appear on some models of indoor units)
Appears while the outdoor units are operated in the silent mode.
Appears when the built-in thermistor on the remote controller is activated to monitor the room temperature (1).
appears when the thermistor on the indoor unit is activated to monitor the room temperature.

Appears when the operation mode is centrally controlled.

Indicates the vane setting.

Appears when the preset temperature is centrally controlled. Indicates the louver setting.

Appears when the filter reset function is centrally controlled.

Indicates the ventilation setting.

Indicates when filter needs maintenance. Room temperature

Appears when the preset temperature range is restricted.

Appears when the buttons are locked.
Appears when the On/Off timer or Auto-off timer function is enabled. appears when the timer is disabled by the centralized control system. appears when the HOLD function is enable.

Appears when an energy saving operation is performed using a “3D i-See sensor” function.
Centrally controlled
Appears for a certain period of time when a centrally-controlled item is operated.
Preliminary error display
A check code appears during the preliminary error.

Most settings (except ON/OFF, mode, fan speed, temperature) can be made from the Main menu.

TCH117

35

Menu structure Main menu

Press the MENU button. Move the cursor to the desired item with the F1 and F2 buttons, and press the SELECT/HOLD button.
Operation
Vane · Louver · Vent. (Lossnay) High power Comfort Manual vane angle 3D i-See sensor
Timer menu
Timer ON/OFF timer Auto-OFF timer
Weekly timer OU silent mode

Energy saving

Restriction Temp. range Operation locked
Energy saving Auto return Schedule

Initial setting menu

Basic setting

Main/Sub

Clock

Clock

Daylight saving time

Administrator password

Display setting

Main display

Display details

Contrast · Brightness

Language selection
Operation setting Auto mode Setback mode

Continue to the next page.

Not all functions are available on all models of indoor units.

TCH117

36

Continue from the previous page.
Maintenance menu Error information Filter information Cleaning Auto descending panel Descending operation Descending adjustment
Service menu Test run menu Test run Drain pump test run
Maintenance information Model name input Serial No. input Dealer information input Initialize maintenance info.
Settings menu Function setting
Check menu Error history Diagnosis Self check Remote controller check Smooth maintenance Request code
Other menu Maintenance password Initialize remote controller Remote controller information

TCH117

Not all functions are available on all models of indoor units.
37

Main menu list

Main menu

Setting and display items

Setting details

Operation Vane · Louver · Vent. (Lossnay)
High power *3

Use to set the vane angle. · Select a desired vane setting.
Use to turn ON/OFF the louver. · Select a desired setting from “ON” and “OFF.”
Use to set the amount of ventilation. · Select a desired setting from “Off,” “Low,” and “High.”
Use to reach the comfortable room temperature quickly. · Units can be operated in the High-power mode for up to 30 minutes.

Comfort Manual vane angle

Use to fix each vane angle.

Timer

Timer

3D i-See sensor ON/OFF timer *1

Use to set the following functions for 3D i-See sensor. · Air distribution · Energy saving option · Seasonal airflow
Use to set the operation ON/OFF times. · Time can be set in 5-minute increments.

Auto-Off timer

Use to set the Auto-Off time. · Time can be set to a value from 30 to 240 in 10-minute increments.

Weekly timer 1, 2

Use to set the weekly operation ON/OFF times. · Up to 8 operation patterns can be set for each day. (Not valid when the ON/OFF timer is enabled.)

Energy saving

OU silent mode 1, 3 Restriction Temp. range *2

Use to set the time periods in which priority is given to quiet operation of outdoor units over temperature control. Set the Start/Stop times for each day of the week. ·Select the desired silent level from “Normal,” “Middle,” and “Quiet.”
Use to restrict the preset temperature range. · Different temperature ranges can be set for different operation modes.

Energy saving

Operation locked
Auto return *2

Use to lock selected functions. · The locked functions cannot be operated.
Use to get the units to operate at the preset temperature after performing energy saving operation for a specified time period. · Time can be set to a value from 30 and 120 in 10-minute increments. (This function will not be valid when the preset temperature ranges are restricted.)

Schedule 1, 3

Set the start/stop times to operate the units in the energy saving mode for each day of the week, and set the energy saving rate. · Up to 4 energy saving operation patterns can be set for each day. · Time can be set in 5-minute increments. · Energy saving rate can be set to a value from 0% or 50 to 90% in 10% increments.

Initial setting

Basic Main/Sub setting

When connecting 2 remote controllers, one of them needs to be designated as a sub controller.

Clock

Use to set the current time.

Daylight saving time

Set the daylight saving time.

Administrator password

The administrator password is required to make the settings for the following items. · Timer setting · Energy saving setting · Weekly timer setting · Restriction setting · Outdoor unit silent mode setting

1 Clock setting is required. 2 2°F (1°C) increments. *3 This function is available only when certain outdoor units are connected.

TCH117

38

Main menu

Setting and display items

Setting details

Initial setting

Display Main display Use to switch between “Full” and “Basic” modes for the Main display, and use

setting

to change the background colors of the display to black.

Display details

Make the settings for the remote controller related items as necessary. Clock: The initial settings are “Yes” and “24h” format. Temperature: Set either Celsius (°C) or Fahrenheit (°F). Room temp.: Set Show or Hide. Auto mode: Set Auto mode display or Only Auto display.

Contrast · Brightness

Use to adjust screen contrast and brightness.

Language selection

Use to select the desired language.

Operation Auto mode setting

Whether or not to use Auto mode can be selected by using the button. This setting is valid only when indoor units with Auto mode function are connected.

Setback mode

Whether or not to use the Setback mode can be selected by using the button. This setting is valid only when indoor units with the Setback mode function are connected.

Maintenance Error information

Use to check error information when an error occurs. · Check code, error source, refrigerant address, model name, manufacturing number,
contact information (dealer’s phone number) can be displayed. (The model name, manufacturing number, and contact information need to be registered in advance to be displayed.)

Filter information

Use to check the filter status. · The filter sign can be reset.

Cleaning Auto descending panel

Use to lift and lower the auto descending panel (Optional parts).

Service

Test run

Select “Test run” from the Service menu to bring up the Test run menu. · Test run · Drain pump test run

Input maintenance

Select “Input maintenance Info.” from the Service menu to bring up the Maintenance information screen. The following settings can be made from the Maintenance Information screen. · Model name input · Serial No. input · Dealer information input · Initialize maintenance info.

Settings Function set- Make the settings for the indoor unit functions via the remote controller as

ting

necessary.

Check Error history Display the error history and execute “delete error history”.

Diagnosis

Self check: Error history of each unit can be checked via the remote controller. Remote controller check: When the remote controller does not work properly, use the remote controller checking function to troubleshoot the problem.

Smooth main- Use to display the maintenance data of indoor/outdoor units. tenance *1

Request code Use to check operation data such as thermistor temperature and error

*1

information.

Others Maintenance Use to change the maintenance password. password

Initialize re- Use to initialize the remote controller to the factory shipment status. mote controller

Remote con- Use to display the remote controller model name, software version, and serial troller infor- number. mation
*1 This function is available only when certain outdoor units are connected.

TCH117

39

Controller interface

Set Temperature buttons
Mode button (Changes operation mode) Airflow button (Changes up/ down airflow direction) Timer ON button Timer OFF button
Weekly timer ON/OFF button*

Set Time button (Sets the time)

Display

Operation mode Cool Fan
Heat

Dry
Auto (single set point)
Auto (dual set point)

Temperature setting The units of temperature can be changed. For details, refer to the Installation Manual.
Vane setting Step 1 Step 2 Step 3 Step 4 Step 5 Swing Auto

Transmission area Remote controller display

OFF/ON button
Fan Speed button (Changes fan speed) i-see button Menu button SET/SEND button CANCEL button Up/Down buttons
Reset button Note:
This button is enabled or disabled depending on the
model of the indoor unit.

Not available Appears when a non-supported function is selected.
Battery replacement indicator Appears when the remaining battery power is low.
Fan speed setting Auto

3D i-See sensor (Air distribution)

Default

Direct

Indirect When Direct or In-

direct is selected,

the vane setting is

set to “Auto”.

TCH117

40

13-2. ERROR INFORMATION
When an error occurs, the following screen will appear. Check the error status, stop the operation, and consult your dealer. 1. Check code, error unit, refrigerant address, model name, and serial number will appear. The model name and serial number will appear only if the information has been registered. Press the F1 or F2 button to go to the next page.
Contact information (dealer’s phone number) will appear if the information has been registered.
2. Press the F4 button or the [ON/OFF] button to reset the error that is occurring. Errors cannot be reset while the ON/OFF operation is prohibited.
Select “OK” with the F4 button.

Navigating through the screens · To go back to the Service menu ………. [MENU] button

TCH117

41

Error information

Error code A3

Error unit IU

Unit#1

Time Occurred 2/ 1 4:48

Model name

Serial No.

Reset error: Reset button

Page

Reset

F1 F2 F3 MENU RETURN SELECT
HOLD

F4 blinks
ON OFF

Error information
Contact information Dealer
Tel

Reset error: Reset button

Page

Reset

Error information

Error code A3

Error unit IU

Unit#1

Time Occurred 2/ 1 4:48

Model name

Serial No.

Reset error: Reset button

Page

Reset

F1 F2 F3 MENU RETURN SELECT
HOLD

F4 blinks
ON OFF

Error reset Reset current error?
Cancel OK
F1 F2 F3 F4
Error reset Error reset Main menu: MENU

· Checking the error information
While no errors are occurring, page 2/2 of the error information can be viewed by selecting “Error information” from the Maintenance menu. Errors cannot be reset from this screen.

Maintenance menu Error information Filter information Cleaning
Main menu: RETURN Cursor

F1 F2 F3 F4

ON OFF

TCH117

42

13-3. SERVICE MENU
Maintenance password is required 1. Select “Service” from the Main menu, and press the [SELECT/HOLD] button.
*At the main display, the menu button and select “Service” to make the maintenance setting.

Main Main menu Service

2. When the Service menu is selected, a window will appear asking for the password. To enter the current maintenance password (4 numerical digits), move the cursor to the digit you want to change with the F1 or F2 button.
Set each number (0 through 9) with the F3 or F4 button.
Then, press the [SELECT/HOLD] button.
Note: The initial maintenance password is “9999”. Change the default password as necessary to prevent unauthorized access. Have the password available for those who need it.
: If you forget your maintenance password, you can initialize the password to the default password “9999” by pressing and holding the F1 button for 10 seconds on the maintenance password setting screen.
3. If the password matches, the Service menu will appear. The type of menu that appears depends on the connected indoor units’ type.
Note: Air conditioning units may need to be stopped to make only at “Settings”. There may be some settings that cannot be made when the system is centrally controlled.

A screen will appear that indicates the setting has been saved.

Navigating through the screens · To go back to the Service menu ………….. [MENU] button
· To return to the previous screen…………… [RETURN] button

TCH117

43

Service menu Enter maintenance password

Select: SELECT Cursor

F1 F2 F3 MENU RETURN SELECT
HOLD

F4
ON OFF

Service menu Test run Input maintenance info. Settings Check Others Main menu: RETURN
Cursor
Service menu
Not available. Please stop the unit.
Service menu: RETURN

13-4. TEST RUN
13-4-1. PAR-41MAA 1. Select “Service” from the Main menu, and press the [SELECT/HOLD] button.
Select “Test run” with the F1 or F2 button, and press the [SELECT/HOLD] button.
2. Select “Test run” with the F1 or F2 button, and press the [SELECT/HOLD] button.
Test run operation Press the F1 button to go through the operation modes in the order of “Cool and Heat”.
Cool mode: Check the cold air blows out. Heat mode: Check the heat blows out. Check the operation of the outdoor unit’s fan. Press the [SELECT/HOLD] button and open the Vane setting screen.
Auto vane check Check the auto vane with the F1 F2 buttons. Press the [RETURN] button to return to “Test run operation”. Press the [ON/OFF] button. When the test run is completed, the “Test run menu” screen will appear. The test run will automatically stop after 2 hours. *The function is available only for the model with vanes.

Service menu
Test run Input maintenance info. Settings Check Others
Main menu: RETURN Cursor

F1 F2 F3 MENU RETURN SELECT
HOLD

F4
ON OFF

Test run menu
Test run Drain pump test run

Service menu: MENU Cursor

F1 F2 F3 MENU RETURN SELECT
HOLD

F4
ON OFF

Test run

Remain

Cool Mode

Pipe 83°F
Switch disp. SELECT

Auto Fan

F1 F2 F3 MENU RETURN SELECT
HOLD

F4
ON OFF

Test run

Remain

Vane

F1 F2 F3 MENU RETURN SELECT
HOLD

F4
ON OFF

TCH117

44

13-4-2. PAR-SL101A-E

1. Press the

button to stop the air conditioner.

· If the weekly timer is enabled ( is on), press the

button to disable it ( is off).

B

2. Press the

button for 5 seconds.

· comes on and the unit enters the service mode.

3. Press the

button .

·

comes on and the unit enters the test run mode.

A

4. Press the following buttons to start the test run.

: Switch the operation mode between cooling and heating

1

and start the test run.

: Switch the fan speed and start the test run.

: Switch the airflow direction and start the test run.

: Switch the louver and start the test run.

2

: Start the test run.

5. Stop the test run.

3

· Press the

button to stop the test run.

· After 2 hours, the stop signal is transmitted.

TCH117

45

13-5. FUNCTION SETTING
13-5-1. PAR-41MAA 1. Select “Service” from the Main menu, and press the [SELECT/HOLD] button.
Select “Setting” from the Service menu, and press the [SELECT/HOLD] button.
Select “Function setting”, and press the [SELECT/HOLD] button.
2. Set the indoor unit refrigerant addresses and unit numbers with the F1 through F4 buttons, and then press the [SELECT/HOLD] button to confirm the current setting. Note: Checking the indoor unit No. When the [SELECT/HOLD] button is pressed, the target indoor unit will start fan operation. If the unit is common or when running all units, all indoor units for the selected refrigerant address will start fan operation.
3. When data collection from the indoor units is completed, the current settings appears highlighted. Non-highlighted items indicate that no function settings are made. Screen appearance varies depending on the “Unit No.” setting.
4. Use the F1 or F2 button to move the cursor to select the mode number, and change the setting number with the F3 or F4 button.

5. When the settings are completed, press the [SELECT/HOLD] button to send the setting data from the remote controller to the indoor units. When the transmission is successfully completed, the screen will return to the Function setting screen.
Note: · Make the above settings only on Mr. Slim units as necessary. · The above function settings are not available for the CITY MULTI units. · Table 1 summarizes the setting options for each mode number. Refer to the indoor unit Installation Manual for the detailed information about initial settings, mode numbers, and setting numbers for the indoor units. · Be sure to write down the settings for all functions if any of the initial settings has been changed after the completion of installation work.

TCH117

46

Settings menu Function setting

Service menu: MENU

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

Function setting

Ref. address

Unit No.

Grp./1/2/3/4/All

Monitor: SELECT

Cursor

Address

F1 F2 F3 MENU RETURN SELECT
HOLD

F4
ON OFF

Function setting

Ref. address Grp. Mode 1 Mode 2 Mode 3

Mode 4

Request: SELECT

Cursor

Cursor

Function setting

Ref. address Grp. Mode 1

Mode 2 Mode 3 Mode 4

Request: SELECT

Cursor

Cursor

F1 F2 F3 MENU RETURN SELECT
HOLD

F4
ON OFF

Function setting Ref. address
Sending data

F1 F2 F3 MENU RETURN SELECT
HOLD

F4
ON OFF

13-5-2. PAR-SL101A-E Fig. 1

1. Going to the function select mode

Press the

button between of 5 seconds.

(Start this operation from the status of remote controller display turned off.)

[CHECK] is lit and “00” blinks. (Fig. 1)

Press the button to set the “50”.

Direct the wireless remote controller toward the receiver of the indoor unit and

press the

button.

2. Setting the unit number

Press the button to set unit number . (Fig. 2)

Direct the wireless remote controller toward the receiver of the indoor unit and

press the

button.

Fig. 2 Fig. 3 Fig. 4

3. Select a mode

Press the button to set Mode number . (Fig. 3)

Direct the wireless remote controller toward the receiver of the indoor unit and

press the

button.

Current setting number:

1=1 beep (1 second)

2=2 beep (1 second each)

3=3 beep (1 second each)

4. Selecting the setting number

Use the button to change the Setting number . (Fig. 4)

Direct the wireless remote controller toward the receiver of the indoor unit and

press the

button.

5. To select multiple functions continuously

Repeat select and to change multiple function settings continuously.

6. Complete function selection

Direct the wireless remote controller toward the sensor of the indoor unit and

press the

button.

Note: Be sure to write down the settings for all functions if any of the initial settings has been changed after the completion of installation work.

TCH117

47

13-6. ERROR HISTORY
1. Select “Service” from the Main menu, and press the [SELECT/HOLD] button.
Select “Check” with the F1 or F2 button, and press the [SELECT/HOLD] button.

Service menu
Test run Input maintenance info. Settings Check Others
Main menu: RETURN Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

2. Select “Error history” with the F1 or F2 button, and press the [SELECT/HOLD] button.
3. 16 error history records will appear. 4 records are shown per page, and the top record on the first page indicates the latest error record.

Check menu Error history Diagnosis Smooth maintenance Request code
Service menu: MENU Cursor

Error history Error Unt# dd/mm/yy

Check menu: RETURN

Page

Delete

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

4. Deleting the error history To delete the error history, press the F4 button (Delete) on the screen that shows error history. A confirmation screen will appear asking if you want to delete the error history.
Press the F4 button (OK) to delete the history.
“Error history deleted” will appear on the screen. Press the [RETURN] button to go back to the Check menu screen.

Error history Delete error history?
Cancel OK Error history Error history deleted Check menu: RETURN

TCH117

48

13-7. SELF-DIAGNOSIS
13-7-1. PAR-41MAA
1. Select “Service” from the Main menu, and press the [SELECT/HOLD] button.
Select “Check” from the Service menu, and press the [SELECT/HOLD] button.
Select “Diagnosis” from the Check menu, and press the [SELECT/HOLD] button.
Select “Self check” with the F1 or F2 button, and press the [SELECT/HOLD] button.

Diagnosis
Self check Remote controller check

Service menu: MENU Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

2. With the F1 or F2 button, enter the refrigerant address, and press the [SELECT/HOLD] button.

Self check Ref. address

Select: SELECT Address

3. Check code, unit number, attribute will appear. “-” will appear if no error history is available.

4. Resetting the error history
Press the F4 button (Reset) on the screen that shows the error history.
A confirmation screen will appear asking if you want to delete the error history.
Press the F4 button (OK) to delete the error history. If deletion fails, “Request rejected” will appear. “Unit not exist” will appear if no indoor units that are correspond to the entered address are found.
Navigating through the screens · To go back to the Service menu ………….. [MENU] button · To return to the previous screen…………… [RETURN] button

TCH117

49

Self check Ref. address
Error Unt # Grp.IC

Return: RETURN

Reset

When there is no error history

Self check

Ref. address

0

Error — Unt# – Grp. —

Return: RETURN

Reset

Self check Ref. address
Delete error history?
Cancel OK
F1 FS2elf cheFc3k F4
Ref. address Error history deleted
Return: RETURN

13-7-2. PAR-SL101A-E
B
3 5

1. Press the

button 1 to stop the air conditioner.

is on), press the

button 3

A

to disable it ( is off).

2. Press the A

button 2 for 5 seconds.

3. Press the button 5 to select the refrigerant address (M-NET address) B

of the indoor

4. Press the

button 4.

1

If

indoor unit and the number of blinks of the OPERATION

INDICATOR lamp.

5. Press the

button 1.

A and the refrigerant address (M-NET address) B

2

check is completed.

4

TCH117

50

13-8. REMOTE CONTROLLER CHECK
If operations cannot be completed with the remote controller, diagnose the remote controller with this function.

1. Select “Service” from the Main menu, and press the [SELECT/HOLD] button.
Select “Check” from the Service menu, and press the [SELECT/HOLD] button.
Select “Diagnosis” from the Check menu, and press the [SELECT/HOLD] button.
Select “Remote controller check” with the F1 or F2 button, and press the [SELECT/HOLD] button.

Diagnosis
Self check Remote controller check

Service menu: MENU Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

2. Select “Remote controller check” from the Diagnosis menu, and press the [SELECT/HOLD] button to start the remote controller check and see the check results.
To cancel the remote controller check and exit the “Remote controller check” menu screen, press the [MENU] or the [RETURN] button.
The remote controller will not reboot itself.

Remote controller check Start checking?
Begin: SELECT

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

3. OK:

No problems are found with the remote controller. Check other parts

for problems.

E3, 6832: There is noise on the transmission line, or the indoor unit or another

remote controller is faulty. Check the transmission line and the other

remote controllers.

NG (ALL0, ALL1): Send-receive circuit fault. The remote controller needs replac-

ing.

ERC: The number of data errors is the discrepancy between the number of bits

in the data transmitted from the remote controller and that of the data

that was actually transmitted over the transmission line. If data errors are

found, check the transmission line for external noise interference.

Remote controller check results screen Remote controller check OK
Exit : SELECT

If the [SELECT/HOLD] button is pressed after the remote controller check results are displayed, remote controller check will end, and the remote controller will automatically reboot itself.
Check the remote controller display and see if anything is displayed (including lines). Nothing will appear on the remote controller display if the correct voltage (8.5­12 VDC) is not supplied to the remote controller. If this is the case, check the remote controller wiring and indoor units.

TCH117

51

13-9. SMOOTH MAINTENANCE
1. Select “Service” from the Main menu, and press the [SELECT/HOLD] button.
Select “Check” with the F1 or F2 button, and press the [SELECT/HOLD] button.
Select “Smooth maintenance” with the F1 or F2 button, and press the [SELECT/HOLD] button.

Check menu Error history Diagnosis Smooth maintenance Request code
Service menu: MENU Cursor

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

2. Set each item. Select the item to be changed with the F1 or F2 button. Select the required setting with the F3 or F4 button. <Ref.address>setting [ 0 ] ­ [ 15 ] setting [ Cool ] / [ Heat ] / [ Normal ] Press the [SELECT/HOLD] button, Fixed operation will start. Note: Stable mode will take approx. 20 minutes.
3. The operation data will appear. The Compressor-Accumulated operating (COMP. run) time is 10-hour unit, and the Compressor-Number of operation times (COMP. ON/OFF) is a 100-time unit (fractions discarded).
Navigating through the screens · To go back to the Service menu ………. [MENU] button · To return to the previous screen ……. [RETURN] button

Smooth maintenance

Ref.address Stable mode

Cool / Heat/ Normal

Begin: SELECT

Cursor

Address

Smooth maintenance

Ref.address

Stable mode

Cool / Heat/ Normal

StabilizationCollecting

Exit: ON/OFF

Smooth maintenance
Ref. address Cool COMP. current COMP. run time COMP. On / Off COMP. frequency Return: RETURN
Page

A
Hr times Hz

Smooth maintenance

Ref.address

Cool

Sub cool

OU TH4 temp.

OU TH6 temp.

OU TH7 temp.

Return: RETURN

Page

37 ºF 140 ºF 100 ºF 87 ºF

Smooth maintenance

Ref.address

Cool

IU air temp. IU HEX temp. IU filter time

83 ºF 50 ºF 120 Hr

Return: RETURN Page

TCH117

52

Refrigerant address
Single refrigerant system In the case of single refrigerant system, the refrigerant address is “00” and no operation is required. Simultaneous twin, triple units belong to this category (single refrigerant system).

[1:1] Refrigerant address=00
Outdoor unit [Twin] Refrigerant address=00
Outdoor unit

Multi refrigerant system (group control) Up to 16 refrigerant systems (16 outdoor units) can be connected as a group by 1 remote controller. To check or set the refrigerant addresses.

Refrigerant address 00
Outdoor unit

Refrigerant address 01
Outdoor unit

Refrigerant address 02
Outdoor unit

Refrigerant address 15
Outdoor unit

Indoor unit 01
Remote controller

Indoor unit 01
Remote controller

Indoor unit 02

Indoor unit Indoor unit Indoor unit

01

01

01

Remote controller

Indoor unit 01

13-10. REQUEST CODE

Details on the operation data including each thermistor temperature and error history can be confirmed with the remote controller.

1. Select “Service” from the Main menu, and press the [SELECT/HOLD] button. Select “Check” with the F1 or F2 button, and press the [SELECT/HOLD] button.

Check menu Error history Diagnosis Smooth maintenance Request code
Service menu: MENU Cursor

Select “Request code” with the F1 or F2 button, and press the [SELECT/HOLD] button.

F1 F2 F3 F4

MENU RETURN SELECT HOLD

ON OFF

2. Set the Refrigerant address and Request code. Select the item to be changed with the F1 or F2 button. Select the required setting with the F3 or F4 button.

setting [ 0 ] ­ [ 15 ] setting Press the [SELECT/HOLD] button, Data will be collected and displayed.

Request code
Ref.address Request code

Request: SELECT

Cur.

­ +

F1 F2 F3 F4

­ +

MENU RETURN SELECT HOLD

ON OFF

TCH117

Request code: 004 Discharge temperature: 69°C

Request code
Ref.address Request code

Request: SELECT

Cur.

­ +

53

HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

MITSUBISHI ELECTRIC CONSUMER PRODUCTS (THAILAND) CO., LTD. 700/406 MOO 7, TAMBON DON HUA ROH, AMPHUR MUANG, CHONBURI 20000 THAILAND Published: Mar. 2023 No. TCH117 Made in Thailand

Specifications are subject to change without notice.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mitsubishi Electric User Manuals

Related Manuals