TOWN AND COUNTRY TC42 SERIES D2 Direct Vented Decorative Gas Appliance Instruction Manual
- May 15, 2024
- Town and Country
Table of Contents
- TC42 SERIES D2 Direct Vented Decorative Gas Appliance
- Specifications:
- Product Usage Instructions:
- Installation:
- Linking Wall Switch to Fireplace:
- Maintenance:
- Q: Can this appliance be used for heating purposes?
- Q: What should I do if I smell gas?
- 1 TC42 BODY ASSY….. …………………… 22030009
- 2 GLASS ASSY……………… ………………. 80000210
- 3 FRAMING KIT……………………………… 80002413
- 4 PANEL SETS PARK AVE. HERRINGBONE …………………………… 22200050 MOUNT VERNON RED
- 1
- 2
- 3
- 4
- 1 1a 1b 1c 1d 1e 1f 1g
- 2 GLASS ASSEMBLY 2a REPLACEMENT GLASS (c/w gasket)
- 3 FRAMING KIT 3a STEEL STUDS 3b NON-COMBUSTIBLE BOARD
- 4 PANEL SETS 4a PANEL, LEFT SIDE 4b PANEL, UPPER 4c PANEL, RIGHT SIDE 4d
- 1 CONTROL ASSEMBLY KIT …………….. 100005457
- 4 TEST FITTING ……………………………….. 5019.104-00
- 2 BULKHEAD ASSEMBLY KIT ………. TCRP.8133-30
- 5 WALL SWITCH ASSEMBLY KIT …………….80000498
- 3 COMMUNICATION CABLE KIT ……….. 5062.98-00
- 6 BASIC WALL SWITCH ASSEMLBY ………….100005836
- 7 REMOTE TRANSMITTER ……………………..80000519
- 1
- 2
- 1 CONTROL ASSEMBLY KIT 1a VALVE c/w FITTINGS 1b 1/4″ FLEX TUBE 1c 1/2″ FLEX
- 2 BULKHEAD ASSEMBLY KIT 2a INLET PLATE 2b INLET PLATE GASKET 2c ELEC BULKHEAD
- 3 CABLE COMMUNICATION KIT
- 4 TEST FITTING
- 5 WALL SWITCH ASSEMBLY KIT (not shown)
- 6 REMOTE TRANSMITTER (not shown)
- 7 Lights, Part #80001810 esch.
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
TC42 SERIES D2 Direct Vented Decorative Gas Appliance
Specifications:
-
Model: TC42 Series D2
-
Type: Direct Vented Decorative Gas Appliance
-
Intended Use: Decorative product, not for heating purposes
-
Installation Location: Suitable for installation in a bedroom
or bed sitting room -
Gas Type: Only for use with the type of gas indicated on the
rating plate
Product Usage Instructions:
Installation:
Installation and service must be performed by a qualified
installer, service agency, or the gas supplier. Follow the detailed
instructions provided in the installation manual.
Linking Wall Switch to Fireplace:
- Follow the step-by-step procedure outlined in the manual to
link/pair the wall switch to the fireplace.
Maintenance:
Regular maintenance is essential for the safe and efficient
operation of the appliance.
-
Clean the glass panel periodically to ensure clear
visibility. -
Perform an annual inspection as recommended in the manual.
-
Ensure that children do not touch the hot glass and install the
provided barrier for safety.
FAQ:
Q: Can this appliance be used for heating purposes?
A: No, this appliance is a decorative product and is not
intended for use as a heating appliance.
Q: What should I do if I smell gas?
A: Do not store or use gasoline or other flammable vapors and
liquids near the appliance. Contact a qualified installer, service
agency, or gas supplier immediately if you smell gas.
INSTALLATION MANUAL
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual
for future reference.
WARNING: If the information in these instructions is not followed exactly, a
fire or explosion may result causing property damage, personal injury or
death.
FOR YOUR SAFETY
Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
WHAT TO DO IF YOU SMELL GAS
· Do not try to light any appliance. · Do not touch any electrical switch. ·
Do not use any phone in your building. · Immediately call your gas supplier
from
a neighbour’s phone. Follow the gas supplier’s instructions. · If you cannot
reach your gas supplier call the fire department.
Do not store or use gasoline or other flammable vapours and liquids in the
vicinity of this or any other appliance.
TC42D2 INSTALLATION MANUAL
This appliance may be installed in an aftermarket permanently located,
manufactured home (USA only) or mobile home, where not prohibited by local
codes.
This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
This appliance is suitable for installation in a bedroom or bed sitting room.
MODEL TC42 SERIES D2 DIRECT VENTED DECORATIVE GAS APPLIANCE
This is a decorative product and is not intended to be used as a heating appliance.
Visit www.townandcountryfireplaces.com for the most recent version of this installation manual
190124-48
TC42D2
100000364
Table of Contents
Caution ………………………………………………………………………….. 3 Safety …………………………………………………………………………….
3 Important Note for the Commonwealth of Massachusetts ……. 4 Fireplace
Dimensions ………………………………………………………. 5 Minimum Clearances to Combustible Material
……………………. 5 Installation Requirements …………………………………………………. 6 Manufactured
(Mobile) Home ……………………………………………. 6 Door Frame Removal ………………………………………………………. 6
Top Standoffs …………………………………………………………………. 7 Locating The Fireplace
…………………………………………………….. 7 Framing and Finishing ……………………………………………………… 8 TC42D
Minimum Combustible Framing Dimensions ……………. 9
Recessed Installation ………………………………………………. 9 TC42 Steel Stud Framing Kit
…………………………………………… 11
Steel frame assembly instructions …………………………….. 12 Fixed Lintel
…………………………………………………………………… 13
Framing Kit Adjustment……………………………………………. 13 Fireplace Facing Allowance
……………………………………. 14 Hearth Extension …………………………………………………………… 14 Electrical
………………………………………………………………………. 15 Wall Switch and Remote Control
…………………………………….. 16 Wall Switch to IFC Communication Cable Continuity Check ..
16 Selecting Natural Vent and Power Vent Modes ………………….. 17 Home Automation
…………………………………………………………. 18 Gas Supply …………………………………………………………………… 19 Gas
Pressure Check ………………………………………………………. 19 Correct gas pressure
requirement……………………………… 19 Venting …………………………………………………………………………. 20 Wall
Termination Venting ………………………………………………… 20 Wall Termination Venting Chart
……………………………………….. 23
Roof Termination Venting Chart ……………………………………….. 24 Ceiling
Opening:……………………………………………………… 25 Ceiling Firestop: ……………………………………………………… 25
Vent Pipe Installation:………………………………………………. 25 Roof Support Bracket:
…………………………………………….. 25 Roof Vent Terminal: …………………………………………………. 26
Vent Terminal Clearance …………………………………………………. 27 Vent Terminal Minimum
Clearances …………………………………. 27 Vent Pipe Sealant ………………………………………………………….. 28
Vent Restrictor Adjustment …………………………………………….. 29 Wall Shield Ceiling Firestop
Thimble …………………………………. 30 Roof Termination Kit ………………………………………………………. 30 Wall
Termination Kit ……………………………………………………….. 30 Vent Pipe Dimensions
……………………………………………………. 31 Vent Offset Chart …………………………………………………………… 32 Firebox
Panels Installation ……………………………………………… 33 Finishing Touch Trim Kit
Installation …………………………………. 35 Linking Remote Handset to the Fireplace
…………………………. 37
Step 1: Procedure for linking / pairing wall switch to fireplace
………………………………………… 37
Step 2: Procedure for linking / pairing wall switch to remote handset
…………………………….. 38
Maintenance …………………………………………………………………. 39 Glass Panel: ……………………………………………………………
39 Annual Inspection:…………………………………………………… 40
Periodically:……………………………………………………………. 40
Wiring Diagram ……………………………………………………………… 41 TC42D Replacement Parts
……………………………………………… 42 Replacement Parts Control System ………………………………. 43
Rating Label …………………………………………………………………. 44
Attention!
· Turn off the main gas supply for the appliance during installation or
maintenance of the receiver/ module device.
· Turn off main gas supply for the appliance prior to removing or reinserting
the batteries.
· In case of remote control malfunction, turn off the fireplace using the
“on/off” main switch located on the wall.
· For installation/maintenance, turn off the fireplace at the on/off switch
located on the wall and at the fireplace power supply circuit breaker.
! DANGER
HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
NEVER ALLOW CHILDREN TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass is
provided with the appliance and shall be installed for the protection of
children and other at-risk individuals.
100000364
2
TC42D2_190124-48
Caution
FOR YOUR SAFETY – Do not install or operate your Town & Country fireplace
without first reading and understanding this manual. Any installation or
operational deviation from the following instructions voids the Town & Country
Fireplaces Warranty and may prove hazardous.
This appliance and its individual shut off valve must be disconnected from gas
supply piping system during any pressure testing of that system at test
pressures in excess of 1/2 psig (3.5 kPa).
This appliance must be isolated from the gas supply piping system by closing
its individual manual shut off valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than 1/2 psig (3.5
kPa).
WARNING: This product can expose you to chemicals including ceramic fibers,
which are known to the State of California to cause cancer, and carbon
monoxide, which is known to the State of California to cause birth defects or
other reproductive harm.
For more information go to www.P65Warnings.ca.gov.
This warning is applicable to all Pacific Energy Fireplace Products
Note: When lit for the first time, the appliance will emit a slight odour for
a couple of hours. This is due to the curing of paints, sealants and
lubricants used in the manufacturing process. This condition is temporary.
Open doors and windows to ventilate area. Smoke and fumes caused by the curing
process may cause discomfort to some individuals.
Do not use the fireplace if any part has been under water. Immediately call a
qualified service technician to inspect the fireplace and to replace any part
of the control system and any gas control which has been under water.
We recommend that our gas hearth products be installed and serviced by professionals who are certified in the United States by the National Fireplace Institute® (NFI) as NFI Gas Specialists
Safety
Due to high temperatures, this gas appliance should be located out of traffic
and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface
temperatures and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room
as the appliance. Toddlers, young children, and others may be susceptible to
accidental contact burns. A physical barrier is recommended if there are at-
risk individuals in the house. To restrict access to a fireplace or stove,
install an adjustable safety gate to keep toddlers, young children, and other
at-risk individuals out of the room and away from hot surfaces.
Clothing or other flammable material should not be placed on or near the
appliance.
Any grill, panel or door removed for servicing the unit must be replaced prior
to operating. Failure to do so may create a hazardous condition.
Installation and repair should be done by a qualified service person. The
appliance should be inspected before use and at least annually by a
professional service person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It is imperative that
control compartments, burners and circulating air passageways of the appliance
be kept clean.
It is our policy that no responsibility is assumed by the Company or by any of
its employees or representatives for any damages caused by an inoperable,
inadequate, or unsafe condition which is the result, either directly or
indirectly, of any improper operation or installation procedures.
This appliance must not be connected to a chimney flue serving a separate
solid fuel burning appliance.
TC42D2_190124-48
3
100000364
Important Note for the Commonwealth of Massachusetts
From Massachusetts Rules and Regulations 248 CMR 5.08:
(a) For all side wall horizontally vented gas fuelled equipment installed in
every dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet above finished
grade in the area of the venting, including but not limited to decks and
porches, the following requirements shall be satisfied.
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of
the side wall horizontal vented gas fuelled equipment, the installing plumber
or gas fitter shall observe that a hard wired carbon monoxide detector with an
alarm and battery back-up is installed on the floor level where the gas
equipment is to be installed, in addition, the installing plumber or gas
fitter shall observe that a battery operated or hard-wired carbon monoxide
detector with an alarm is installed on each additional level of the dwelling,
building or structure served by the side wall horizontal vented gas fuelled
equipment. It shall be the responsibility of the property owner to secure the
services of qualified licensed professionals for the installation of hard-
wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas fuelled equipment
is installed in a crawl space or an attic, the hard-wired carbon monoxide
detector with alarm and battery back-up may be installed on the next adjacent
floor level.
b. In the event that the requirements of this subdivision cannot be met at the
time of completion of installation, the owner shall have a period of thirty
(30) days to comply with the above requirements; provided, however, that
during said thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as
required in accordance with the above provisions shall comply with NFPA 720
and be ANSI/UL 2034 listed as IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently
mounted to the exterior of the building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent terminal for the
horizontally vented gas fuelled heating appliance or equipment. The sign shall
read, in print size no less than one-half (1/2) inch in size, “GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally
vented gas fuelled equipment shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide detectors and signage
installed in accordance with the provisions of 248 CMR 5.089(2) (a) 1 through
4.
(b) EXEMPTIONS. The following equipment is exempt from 248 CMR 5.089(2)(a) 1
through 4. 1. The equipment listed in Chapter 10 entitled “Equipment Not
Required To Be Vented” in the most current edition of NFPA 54 as adopted by
the
Board; and 2. Product Approved side wall horizontal vented gas fuelled
equipment installed in a room or structure separate from the dwelling,
building or structure
used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM PROVIDED. When
the manufacturer of Product Approved side wall horizontally vented gas
equipment provides a venting system design or venting system components with
the equipment, the instructions provided by the manufacturer for installation
of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or
the venting system components; and 2. A complete parts list for the venting
system design or venting system.
(d) MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of a Product Approved side wall horizontally vented gas
fuelled equipment does not provide the parts for venting the fuel gases, but
identifies “special venting systems”, the following requirements shall be
satisfied by the manufacturer.
1. The referenced “special venting system” instructions shall be included
with the appliance or equipment installation instructions; and 2. The “special
venting systems” shall be Product Approved by the Board, and the instructions
for that system shall include a parts list and detailed
installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall
horizontally vented gas fuelled equipment, all venting instructions, all parts
lists for venting instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion of the installation.
100000364
4
TC42D2_190124-48
Fireplace Dimensions
29
7 16
”
54″
16
3 4
”
38 1/2″
37 15/16″
42
3 16
”
43
13 16
”
48
1 16
”
51
1 16
”
53
1 16
”
29
3 8
”
Figure 1: TC42D2 Overall dimensions.
Minimum Clearances to Combustible Material
COMBUSTIBLE FRAMING AND FINISH WALL ABOVE STANDOFFS
MAY USE COMBUSTIBLE FACING MATERIAL IN THIS AREA
NON-COMBUSTIBLE
FINISH MATERIAL
SEE FIG #14 & 15
D
E
A
F
B C
TOP OF LINTEL BAR FIREPLACE FRONT
STEEL FRAMING STANDOFFS
NON-COMBUSTIBLE ZONE. DO NOT INSTALL ANY COMBUSTIBLE MATERIAL, ELECTRICAL
WIRING OR GAS PLUMBING IN THIS AREA.
Mantel Clearance Chart
- MANTEL CLEARANCE
A
9″
B
6″
C
3″
** MANTEL DEPTH
D
12″
E
6 3/4″
F
1 1/2″
Figure 2: TC 42 Ver 2 Mantel clearances.
CEILING
24″
** MANTEL
ADJACENT WALL OR MANTEL SUPPORT
4″ 38 1/2″
Minimum Clearances:
Side standoffs ……………………………………………. 0 in. (0 mm) Back standoffs
…………………………………………… 0 in. (0 mm) Top standoffs……………………………………………… 0 in. (0 mm)
Bottom of appliance……………………………………. 0 in. (0 mm) Adjacent side wall
………………………………………. 4 in. (102 mm) Ceiling to appliance…………………………………… 24 in. (610
mm) *Mantel to appliance ………………………. See Figure #2 **Maximum Mantel extension
……………See Figure #2 Mantel support …………………………………………… 4 in. (102 mm) Vertical
vent pipe ………………………………….1 3/4″ in. (45 mm)
Horizontal Vent pipe (Top, sides and bottom)1 3/4″ in. (45 mm)
UNIT MAY BE RECESSED UP TO 4 1/2″ WITH
NON-COMBUSTIBLE MASONRY TYPE MATERIAL
Figure 3: TC 42D Ver 2 Mantel.
TC42D2_190124-48
5
100000364
Installation Requirements
The Town & Country Fireplace installation and venting must conform to the
current CAN/CGA-B149 installation code (in Canada) or the current National
Fuel Gas Code, ANSI Z223.1 (in the USA), and approved per local codes. Only
qualified (licensed or trained) personnel should install this product.
In the state of Massachusetts, only a licensed Plumber and Gas Fitter may
install this product.
Manufactured (Mobile) Home
In some jurisdictions, the Town & Country Fireplace may be installed in
Manufactured Homes after the “first sale”. Consult local codes for approval.
The fireplace must be fastened in place.
Install in accordance with the current standard Mobile Homes, CAN/CSA Z240 MH
(in CANADA), and the Manufacturer’s Home Construction and Safety Standard,
Title 24 CFR, Part 3280 or the current Standard for Fire Safety Criteria for
Manufactured Home Installations, Sites and Communities ANSI/NFPA 501A (in the
USA).
Door Frame Removal
Warning: Turn off the fireplace, and allow ample time for the unit to cool
before proceeding.
Caution: The ceramic glass is very fragile, and should be handled with care.
The door frame is held in place by two spring-loaded latches that are operated
by a one-piece latch handle.
1. Remove safety barrier screen (Figure 4) by prying the top portion of the
screen toward you, then lift the screen from its tabs (inset) located at the
base of the door frame.
2. Remove the TC Finishing Touch Trim Kit from the door frame. (If installed)
3. Using a screwdriver (Figure 5) or other similar object, push against the
notch in the top of the latch and grab the bottom of the latch handle as it
protrudes (Figure 6). Lift handle until latch hook disengages. Repeat for
other side while holding glass so it does not tip out.
4. Tilt the top of the door frame out to clear the top edge of the unit.
Grasp the sides of the frame and lift up and out to disengage from its bottom
track.
5. Place the door frame in a safe place to avoid damage.
6. Re-assemble in reverse order. Latch handle should snap into place and be
flush with door frame when engaged correctly.
7. Reinstall Trim Kit if required.
8. Reinstall safety barrier screen.
TIP:
To ensure glass door is properly latched, grasp the top left and right sides
of the glass frame. Under moderate pressure it should pull forward and return
to original position evenly on both sides.
Figure 4: Safety barrier screen.
100000364
6
Figure 5: Accessing handle.
HANDLE
Figure 6: Handle. TC42D2_190124-48
Top Standoffs
The top standoffs are shipped loose inside the fireplace and must be installed
on top of the fireplace (Figure 7). Do this once the fireplace is on site and
in position.
TOP STANDOFFS
Figure 7: TC42D Standoffs.
Locating The Fireplace
In planning the installation for the fireplace, it is necessary to determine
where the unit is to be installed, location of vent system and where gas
supply piping may be plumbed. Various installations are possible, such as,
into an existing wall, a corner, a built-in wall or a wall projection (Figure
8). Due to high temperatures, do not locate this fireplace in areas of high
traffic or near furniture or draperies.
The minimum clearances from the fireplace to combustible surfaces must be
adhered to and are shown in Figure 2 & Figure 3.
Figure 8: TC42D Possible locations.
TC42D2_190124-48
7
100000364
Framing and Finishing
Note: The fireplace should be in place and venting installed before framing in
or building an enclosure around the unit.
The Town & Country fireplace must be framed in as described below or totally
enclosed with non-combustible material, such as facing brick.
If preferred, additional masonry type non-combustible material can be
installed above and to the sides up to 4 1/2 inches proud of the appliance.
The finishing material must not interfere with glass frame access.
A Steel Stud Framing Kit is supplied with the fireplace and must be used
unless the fireplace is totally enclosed with non-combustible material.
Assemble the framing kit as per the instructions on page 11 & page 12 of this
manual. Attach the steel frame to the fireplace once the fireplace is in its
final position.
Secure the steel frame to the framing brackets on each side of the unit.
Ensure that the studs are set back far enough to allow for thickness of
finishing surface.
The sides, back and top of the fireplace can be framed in up to the steel
studs and the fireplace standoffs using conventional lumber. Consult local
building codes for specific requirements.
Due to high temperatures, noncombustible backer board, such as cement board or
its equivalent, must be used to sheet in the front of the fireplace, extending
12″ above and 5 1/2″ to the side of the framing edge bars. (Figure 10)
Standard sheet rock (dry wall) may be used beyond this.
If the backer board is not to be finished with other non-combustible material
such as tiles, it is recommended that top sections of
the framing kit be covered with a single sheet of calcium silicate board or
its equivalent. Taped and mudded joints may crack due to the elevated
temperatures.
Chase Insulation: When installing this fireplace against a noninsulated
exterior wall or chase, it is recommended that the outer walls be insulated to
same degree as other exterior walls. Do not place fireplace directly against
the insulation. Cover the insulation and plastic vapour barrier with a solid
surface, such as dry wall (sheet rock). Consult local codes. Do not insulate
or use plastic vapour barrier within the framing kit.
CAUTION: See Figure 12 on page 9 BEFORE PROCEEDING.
NOTE: The chase must be properly sealed at the ceiling level or between floors
in a multilevel installation.
NON-COMBUSTIBLE ZONE. DO NOT INSTALL ANY COMBUSTIBLE MATERIAL, ELECTRICAL WIRING, INSULATION, PLASTIC VAPOR BARRIER OR GAS PLUMBING WITHIN THE STEEL STUD FRAMING
STEEL STUD FRAMING KIT DIMENSIONS (Supplied with fireplace)
56 1/4″
ALL OTHER FRAMING CAN BE DONE WITH CONVENTIONAL LUMBER
IT IS HIGHLY RECOMMENDED THAT A FULL HEADER BE INSTALLED ABOVE THE METAL FRAMING KIT
Figure 9: TC42D with supplied steel frame.
100000364
8
53 7/8″ TC42D2_190124-48
TC42D Minimum Combustible Framing Dimensions
Non-combustible board detail
NON-COMBUSTIBLE
BOARD
12″
NON-COMBUSTIBLE MATERIALS MUST EXTEND 12″ ABOVE AND 5 1/2″ TO THE SIDES OF THE FRAMING EDGES.
5 1/2″
Figure 10: TC 42D Non combustible board dimensions.
Recessed Installation
FIREPLACE FRONT GLASS
STEEL STUD FRAME
NON-COMBUSTIBLE BOARD
NON-COMBUSTIBLE MATERIAL
If finishing the wall above the unit with paint, the framing kit shipped with
the unit should be discarded. Use full sheets of calcium silicate board or
equivalent and full length metal studs to finish and frame around the unit.
Calcium silicate board is a high grade material with cement, quartz and
natural minerals as the main raw materials. (Note: Calcium Silicate is 1/2″
thick)
CAUTION: Calcium Silicate board can be damaged if dropped or struck. Handle
with care. Inspect board prior to installation and do not use if cracked.
NOTE: It is recommended to pre-drill mounting holes in the board prior to
securing to the framing. This will prevent the board from cracking.
NON-COMBUSTIBLE BOARD
NON-COMBUSTIBLE RECESSED INSTALLATION DETAIL
4 1/2″ MAXIMUM
FACING DEPTH
Top – down view
Figure 11: Recessed installation detail.
56 1/2″
30 1/16″
Control Box & frame can touch
65 1/2″ 21 1/4″
Figure 12: Non combustible calcium silicate board.
12 5/8″
RANGE
26 1/2″ to 28 7/8″
29 3/8″
65 1/2″
FRAMING LINTEL
RANGE 1/2″ – 2 3/4″
56 1/2″ 92 5/8″
54 1/8″
1/2″
NOTE: FIREPLACE SHOULD BE IN ITS FINAL LOCATION BEFORE FRAMING.
Figure 13: TC42D2 minimum combustible framing dimensions.
56 1/2″
TC42D2_190124-48
9
100000364
It is important to note that any finishing material used must not interfere with the glass door being able to open in the event of ignition of excess gas buildup.
Figure 14: Recessed installation details.
100000364
10
TC42D2_190124-48
TC42 Steel Stud Framing Kit
5
8 4
6 2 3 7
Figure 15: TC42D2 Steel frame parts.
Each Kit Contains:
ITEM
DESCRIPTION
1 SCREW, TEKS #8 X 1/2 (NOT SHOWN)
2 SIDE STUD, VERTICAL INNER 53 3/4″ L
3 SIDE STUD, VERTICAL OUTER 53 3/4″ L
4 CENTER STUD, VERTICAL SHORT
QTY. PKG 40
2
2
2
ITEM
DESCRIPTION
5 STUD, HEADER HORIZONTAL 58 1/4″ L
6 STUD PLATE, HORIZONTAL
7 BASE PLATE
8 FRAMING PLATE
QTY. 1 1 2 4
TC42D2_190124-48
11
100000364
Steel frame assembly instructions
1. Top Frame Assembly
Lay out the horizontal header stud (5) on a large flat surface. (Position all pieces on their narrow edges as shown in the illustration (Figure 15).
SIDE OF FRAME WITH SCREW HOLES
Position the two 15 1/2″ center studs (4) perpendicular to the horizontal
header stud, and align with the two innermost sets of screw holes. Fasten with
the screws (1) provided.
Position the 41 1/4″ horizontal stud plate (6) at the bottom end and
perpendicular to the vertical center studs (4). Align the bottom ends of the
vertical center studs to the two innermost sets of screw holes and fasten with
the screws provided.
FLAT SIDE OF FRAME
FRAMING BRACKETS
2. Attach Side Studs (Legs)
Lay the inner vertical side studs (2) so that it’s top end aligns with the 2nd
set of screw holes of the header stud (5). The side stud should attach to, and
be perpendicular to the 41 1/4″ stud plate (6). Fasten with the screws
provided.
Fasten the vertical outer side studs (3) to the ends of the horizontal header
stud (5).
NOTE: After frame is assembled, make sure to have the side of the frame
without the screw holes facing toward the inside of the room.
Figure 16: TC42 body with steel frame.
SIDE OF FRAME WITH SCREW HOLES
Position the base plate (7) at the bottom of the inner and outer side stud legs and fasten with the screws provided.
Turn the assembled frame over and install screws to the remaining fastening
points.
3. Attach the Assembled Frame to the Unit
FLAT SIDE OF FRAME
Align the assembled frame to the unit framing brackets (Figure 16). Align the framing plates (8) to the fastening points through the access holes in the outer side studs (3).
4. Secure to Existing Framing
Secure the frame assembly to existing framing through the horizontal top stud
(5) and the base plates (7).
5. Install Non-combustible Board
Use drywall screws to install the concrete board.
NOTE: AFTER FRAME IS ASSEMBLED, MAKE SURE TO HAVE THE SIDE OF THE FRAME
WITHOUT THE SCREW HOLES FACING TOWARD THE INSIDE OF THE ROOM.
Figure 17: New TC42 updated body with cement board.
100000364
12
TC42D2_190124-48
Framing Brackets
Figure 18: TC42D2 Fixed lintel.
Fixed Lintel
Framing Kit Adjustment
The lintel on the TC42D2 is in a fixed position on the fireplace and there is
no adjustment to move the lintel toward you or away from you once the
fireplace has been located in its final position. Instead, the fireplace
itself must be manoeuvered so that the front face of the lintel determines the
final position of the fireplace.
The Framing Kit allows for a 1 7/8 inch adjustment along the Framing Brackets.
Use this range to help determine the front of the facing material.
The thickness of the facing material, wether 1/2 inch calcium silicate board
or a rock facing must be taken into consideration before settling on a final
position of the fireplace. See “Fireplace Facing Allowance” on page 14.
Range: 1 7/8″
Figure 19: Framing bracket.
TC42D2_190124-48
13
100000364
Fireplace Facing Allowance
This fireplace is designed to finish either flush with the facing material or
can be installed with a 4 1/2 inch recess, see “Figure 10: TC 42D Non
combustible board dimensions.” on page 9.
The fireplace can accommodate facing material thickness from 1/2 of an inch to
2 1/4 inches if installing flush.
Care should be taken to correctly determine the facing material thickness so
that the fireplace is positioned so that the front of the fireplace is flush
with the facing material.
Facing material must not interfere with the ability for the door or the screen
to open.
NON-COMBUSTIBLE FINISH MATERIAL
Figure 20: Facing edge location.
Hearth Extension
Lintel
NON-COMBUSTIBLE BUILDING MATERIAL MAY NOT EXTEND PAST THIS POINT
SCREEN DOOR
Maximum height of 1″ above bottom of fireplace
Hearth Extention
Bottom of fireplace
Figure 21: TC42D Hearth extension.
Caution: While a hearth extension is not required and combustible flooring
materials may be brought directly up to the fireplace, many materials (such as
wood flooring) may not tolerate the radiant heat from this fireplace,
resulting in discoloration, shrinking and cracking. For this reason, we
suggest a noncombustible hearth that is no more than 1″ above the bottom of
the fireplace. If thicker, fireplace must be raised accordingly.
Caution: Hearth extensions thicker than 1″ will interfere with the safety
screen and door frame when opening.
100000364
14
TC42D2_190124-48
Electrical
The gas control system is located on the right hand side of the firebox behind
an access panel and the decorative firebox panel (if installed). The fireplace
is operated via a wall switch and a hand held remote control unit.
The wall switch is connected to the fireplace by a 40 ft. communication cable
supplied with the fireplace.
Installation
1. Place the fireplace in the desired location.
FIREBOX ACCESS PANEL
2. Remove the glass door frame from the fireplace.
3. Remove access panel from right hand side of the firebox (Figure 22).
4. Connect 110 V. AC electrical supply to the wires installed inside the
junction box (Figure 23). The fireplace is rated at 110 volts, 60Hz, 0.25A.
The optional power vent kit is rated at 115 volts, 60Hz, 1.8A.
The electrical wires can be accessed from both inside and outside the junction
box by removing one of the two small access panels (Figure 24).
Figure 22: Access to firebox.
Vent Blower wire – Blue
2 Nuetral wires – White
5. Attach the wall switch to the framing in the desired location (40 ft is
supplied with fireplace).
6. Route the wall switch control cable (supplied) as required to the wall
switch (Figure 27).
Power In wire – Black
7. Attach one end of the wall switch control cable to the wall control (Figure 27), and the other end to the
Figure 23: Junction box wiring.
interface board (Figure 24).
Vacuum Transformer Regulator
switch
board
8. Insert the 4 supplied “AA” batteries
into the battery pack of the wall
switch (Figure 26).
9. If not already installed, install the burner using the instructions
supplied with the burner kit.
10. Turn on the gas supply and check that all connections are tight and leak
free.
11. Turn on gas and electrical supplies.
Gas connector Inside access panel
Wall switch connector
Module
Power vent switch
Junction box
Figure 24: Valve assembly components.
Interface board
TC42D2_190124-48
15
100000364
Wall Switch and Remote Control
Figure 25: Town and Country wall switch.
Figure 26: Wall switch – battery side. Figure 27: Wall switch – interface side.
Figure 28: Basic Wall switch – interface side. Instructions for linking the
wall switch to the remote control handset can be found page 37(Bluetooth Wall
Switch) and page 38(Basic Wall Switch) of this manual and in the User manual
that came with this Fireplace.
If the wall switch is being connected to a Home Automation system, two cables
will be used; the top cable will go from the wall switch to the fireplace and
the bottom cable will go from, the wall switch to the Home Automation system
(Figure 26) .
If not using a Home Automation system, only the upper cable will be used to go
from the wall switch to the fireplace (Figure 27).
Wall Switch to IFC Communication Cable Continuity Check
It is important that the continuity of the individual wires encased within the
communication cable be checked before the cable is plugged into both the wall
switch and the IFC Module. This will ensure that the cable is in good
condition before the cable is walled in or otherwise covered up. Provided that
no staples, screws or nails accidentally impale the cable during the walling
up process, or any cables have otherwise been cut, the cable itself will be
able to be ruled out as a possible cause should trouble shooting the wall
switch be required.
100000364
16
TC42D2_190124-48
Selecting Natural Vent and Power Vent Modes
The NV / PV (Natural Vent / Power Vent) switch (Figure 29) on the interface
board (Figure 24) is set according to which type of evacuating vent system is
present. If the fireplace is vented without the assistance of a power vent,
the switch must be set to “NV”. If using a power vent, “PV” must be selected.
Follow the instructions provided with the power vent kit for proper
installation.
Important Note: When switching between PV and NV, the electrical power supply
to the fireplace must be turned off and the backup batteries removed to
properly re-set the module
Figure 29: Vent mode selection switch.
TC42D2_190124-48
17
100000364
TO HOME AUTOMATION SYSTEM
Figure 30: Complete communication wiring.
Home Automation
The home automation feature supplied with this fireplace is capable of
controlling the flame and light on/off function with the use of a dry contact
relay common to home automation systems. Furthermore, the flame and light
level may be modulated from high to low using the 0 – 10 volt analog output
available on most home automation systems.
(Figure 31) shows the wire designations required to connect the fireplace to a
home automation system.
Note: Leave the wall switch on the “Remote” setting when using home
automation.
NOTE: When a signal has been supplied by the home automation system, the
fireplace control will repeat the signal every 2 hours or until a new command
has been received.
Figure 31: Home automation wiring diagram.
NOTE: · Digital I/O must be connected to a dry contact relay.
Analog flame and light input through 0 – 10 volt DC signal scaled as follows:
Low = 1 volt High = 10 volts
Basic Wall Switch Home Automation
Basic Wall Switch Home Automation is limited to flame on and off using a dry
contact relay with the solid brown wire and common. Figure 31.
TO HOME AUTOMATION SYSTEM
100000364
18
TC42D2_190124-48
Gas Supply
Caution: The gas line should be installed by a qualified service person in
accordance with all building codes. This section is intended as a guide for
qualified technicians installing this appliance. Consult local and / or
national building codes before proceeding.
· Gas supply line access holes are located at the top and left sides of the
Control Box. Gas valve inlet accepts a 3/8″ N.P.T. fitting. Correct gas line
diameter must be used to assure proper operation and pressure.
· NOTE: A sediment trap, as per national fuel gas code, must be installed in
the gas supply line no more than 6 feet from the gas control valve to minimize
the possibility of any loose scale or dirt within the gas supply line from
entering the control valve.
DO NOT HARD PIPE GAS LINE TO VALVE. A method of disconnecting the valve from
the gas line such as a union or flare fitting must be provided to allow for
repair or replacement of the gas valve.
Check local codes for additional requirements.
1. Connect the gas supply to the valve (Figure 24).
2. Turn on the gas supply and check that all connections are tight and leak
free.
Warning:
The access panel – including gasket, must be reinstalled after conversion /
installation or servicing has been completed. Failure to do so will cause
overheating and premature failure of the control system.
Gas Pressure Check
Note: To test the gas pressure, turn off the gas supply before removing the
plug from the supply pressure test port or manifold pressure test port.
Verify gas pressures with the fireplace lit and on the highest setting.
Please refer to the Burner Installation Manual for gas pressure testing procedure.
Correct gas pressure requirement
Natural Gas Propane
Min. Supply Pressure
(For purpose of input adjustment)
Max. Supply Pressure
5.0″ WC 13.9″ WC
12.5″ WC 13.9″ WC
SUPPLY PRESSURE
MANIFOLD PRESSURE
Manifold Pressure Maximum Minimum
3.5″ WC 1.6″ WC
10″ WC 6.4″ WC
Figure 32: Test ports.
TC42D2_190124-48
19
100000364
Venting
Before installing venting for this unit, the installer should read these
instructions to insure that the proper vent configuration has been selected.
Use only Town and Country Termination kits #:
TCVT.WTA – Wall Termination Kit TCVT.RTA – Roof Termination Kit
Vent system components approved for use with the Town and Country Fireplace
are shown on page 21.
NOTE: Optional Power Vents (TCVT.PVI.25, TCVT.PV7.110 & TCVT.PVCV require
different venting. Please refer to Power Vent manuals.
Various combinations of vertical and horizontal runs may be used (Figure 36 &
Figure 37) . For optimum performance and flame appearance, keep the vent
length to a minimum and limit the number of elbows. Connections between each
vent system component must be tightly joined, secured with sheet metal screws
and sealed with provided high temperature self adhesive tape. A horizontal run
of vent should have a ¼” rise for every 1 ft. of run towards the termination.
CAUTION: UNDER NO CONDITION SHOULD COMBUSTIBLE MATERIAL BE CLOSER THAN 1 ¾
INCHES FROM THE TOP AND 1 ¾ INCHES FROM THE SIDES OF A HORIZONTAL SECTION AND
1 ¾ INCHES FROM THE VERTICAL SECTIONS OF THE VENT PIPE.
Wall Termination Venting
Exterior wall opening: Determine the exact position of the fireplace so that
the vent pipe is centered (if possible) between two building framing members.
Consult your local building codes prior to proceeding. The vent kit will
accommodate up to a maximum wall thickness of 12 inches.
1. Having determined the position of the fireplace, cut and frame a 14½ inch
opening centred at a minimum height of 74 1/4 inches above the floor (Figure
35). The opening may be round or square. Height of the opening will vary with
each installation. As the horizontal vent run increases, so does the minimum
vertical rise, see chart (Figure 36).
IMPORTANT: When locating the opening, it should be noted that vent terminal
clearances must be maintained. See Vent Terminal Minimum Clearance on page 27
section for proper clearances.
A minimum 2 foot length of pipe is required off the top of the fireplace for
any wall termination. With this minimum vertical rise in combination with a
90° elbow, a maximum horizontal run of 18 inches is permitted, See Figure 366
& Figure 377. For longer horizontal runs greater than 18 inches, increase
vertical rise appropriately.
The rise and run must be constrained to the boundaries of the chart shown in
(Figure 36). The horizontal run of vent must have a ¼” rise for every 1 ft. of
run towards the termination.
100000364
20
TC42D2_190124-48
Figure 33: Wall vent terminal.
TRIM TO LENGTH
WALL THIMBLE AND VENT MUST NOT PROTRUDE BEYOND SIDING
Wall thimble:
Where a vent pipe passes through a combustible wall, a wall thimble/shield
must be used to retain insulation and maintain proper clearances. The wall
thimble may be cut to length for various wall thicknesses up to 12″ thick.
Measure the wall thickness including the siding. Trim the shield to match the
wall thickness. Position the wall thimble from inside through the 14-1/2″
opening. Properly adjusted, the thimble should be flush with the outer wall
surface.
Wall Termination Venting
Vent System Components Town & Country
12″ Pipe Length………………………………………………… 18″ Pipe Length………………………………………………… 24″ Pipe Length………………………………………………… 48″ Pipe Length………………………………………………… 12″ Adjustable Pipe Length………………………………… 45° Elbow ………………………………………………………… 90° Elbow ………………………………………………………… Wall/Offset Support ……………………………………………
TCVT.811X12 TCVT.811X18 TCVT.811X24 TCVT.811X48 TCVT.811X12ADJ TCVT.811XLB45 TCVT.811XLB90 TCVT.811XOS
Wall Termination Kit …………………………………………… TCVT.WTA Roof Termination Kit ………………………………………….. TCVT.RTA Wall Shield/Ceiling Firestop………………………………… TCVT.THIMA
Roof Flashing, Adjustable ………………………………….. TCVT.811FLADJ Roof Flashing, Flat
……………………………………………. TCVT.811FLFLT Roof Flashing, Steep ………………………………………….
TCVT.811FLSTP
or any flashing that fits 11″ pipe
Figure 34: Thimble.
TC42D2_190124-48
21
100000364
Vent pipe:
Install vent pipe through the wall thimble and attach to flue outlet collar on
top of the fireplace. Secure all joints with screws and seal with approved
“High Temp.” self-adhesive aluminum tape provided.
Adjust the fireplace position so that the vent pipe does not protrude beyond
the outer wall. The vent connector on the termination will accommodate walls
up to 12″ thick.
Wall vent terminal:
1. Engage the terminal with the vent pipe and slide terminal into place.
Ensure that both inner and outer pipes are fully engaged and then attach the
terminal to the outside wall. The vent terminal must not be recessed into the
exterior wall or siding.
2. Caulk in place to prevent any moisture entering the building.
NOTE: MINIMUM CLEARANCES TO THE VENT TERMINAL MUST BE MAINTAINED See “Vent
Terminal Minimum Clearances” on page 27.
WALL SHIELD THIMBLE TCVT.THIMA
12″ VENT PIPE TCVT.811X12
ELBOW TCVT.811XLB90
24″ VENT PIPE TCVT.811X24
14 1/2″ FRAMED OPENING
HORIZONTAL TERMINAL TCVT.9360
-
74 1/4″
-
MINIMUM HEIGHT FROM THE FLOOR TO CENTER OF THE OPENING WITH A MAXIMUM HORIZONTAL RUN OF 18″ FROM THE CENTER OF THE FLUE OUTLET TO THE OUTSIDE FACE OF THE OUTER WALL. THE HEIGHT WILL NEED TO BE INCREASED IF A LONGER HORIZONTAL PIPE IS REQUIRED.
Figure 35: TC42D Wall vent terminal framing.
100000364
22
TC42D2_190124-48
Wall Termination Venting Chart
A
** Minimum rise
74 1/4″ 78 1/2″ 84 1/2″ 90 1/2″ 98 1/4″
B Pipe length
1-24″ 1-12″ 1-18″ 1-24″ 1-12″
1-24″ 1-18″
1-48″
C Maximum run
18″ 75 3/4″ 11′ 2″
15′ 10 1/2″
20′ 10 1/2″
D Pipe length
Max.
1-12″
1-48″ 1-12″
2-48″ 1-24″ 3-48″ 1-24″
1-12″ 5-48″
For other rise/run combinations see chart below
** All dimensions are approximate. Both rise and run may vary with different
combinations of pipe.
24″ PIPE LENGTH MINIMUM
- 74 1/4″
NOTE: The vent must not exceed a total length of 68 feet. Any combination of rise and run may be used but must be constrained to the boundaries of this chart. A total of 3 90° elbows or combination of other elbows equalling 90° can be used without reducing horizontal run. For each additional 90° elbow, or an equal combination of elbows, reduce horizontal vent run by 2 feet. Ensure vent pipe is properly supported.
Figure 36: TC42D Horizontal run – rise chart.
TC42D2_190124-48
23
100000364
Roof Termination Venting Chart
**
A
Minimum rise
74 1/4″
B Pipe length
1-24″
C Maximum run
29″
D Pipe length Maximum
1-12″
78 1/2″
1-12″ 1-18″
77 1/4″
1-48″ 1-12″
84 1/2″ 90 1/2″ 98 1/4″
1-24″ 1-12″ 1-24″ 1-18″
1-48″
11′ 1 1/2″ 15′ 10″ 20′ 10″
2-48″ 1-24″
3-48″ 1-24″ 1-12″
5-48″
For other rise/run combinations see chart below
** All dimensions are approximate. Both rise and run may vary with different combinations of pipe.
24″ PIPE LENGTH MINIMUM
NOTE: The vent must not exceed a total length of 68 feet. Any combination of rise and run may be used but must be constrained to the boundaries of this chart. A total of 4 90° elbows or combination of other elbows equalling 90° can be used without reducing horizontal run. For each additional 90° elbow, or an equal combination of elbows, reduce horizontal vent run by 2 feet. Ensure vent pipe is properly supported.
Figure 37: TC42D Vertical run – rise chart.
100000364
24
TC42D2_190124-48
A 14 1/2″
B
Figure 38: TC42D Roof opening frame.
Size of the opening will have to increase with the pitch of the roof to ensure a 1 3/4″ inch air space clearance between vent pipe and combustibles.
Roof Pitch
A
B
0/12 4/12 6/12 8/12 12/12
14 1/2″ 16 1/2″
18″ 19 3/4″
24″
7 1/4″ 8 3/4″
10″ 11″ 13 3/4″
Figure 39: Roof support bracket.
Ceiling Opening:
1. Determine the exact position of the fireplace so that the vent pipe is
centered (if possible) between two building framing members. Lay out the vent
system path, minimizing the number of elbows and length of vent. Consult your
local building codes prior to proceeding.
2. Cut and frame a 14 ½” opening in the floor, ceiling or roof where the vent
system will pass. Size of the opening in the roof may need to be increased as
the pitch of the roof increases. Avoid cutting rafters.
Ceiling Firestop:
Where a vent pipe passes through a floor or ceiling, a ceiling firestop
(Figure 46) must be used to retain insulation and maintain proper clearances.
From below, push the ceiling firestop through the opening and secure in place.
If the firestop is used to penetrate a floor, the outer shield may be trimmed
in length. If the firestop penetrates into an attic, leave the shield full
length to keep insulation away from the vent pipe. (Attic Insulation Shield
may be required. SKU #22270029, page 31). Additionally, after the vent pipe is
in place, install a storm collar on top of the shield. This will prevent loose
insulation from falling into the area between the vent pipe and the shield.
VENT PIPE
ROOF SUPPORT BRACKET (TCVT.93915)
Vent Pipe Installation:
1. Install the first section of vent pipe into the collar on top of the
fireplace. Secure in place with screws and seal with approved “High
Temperature” self-adhesive aluminium tape provided.
2. Continue adding vent pipe lengths up and through the firestop(s) and
through the roof. The vent pipe must extend at least 12″ above the roof. Vent
pipe may need to extend further depending on the roof pitch. See Roof pitch
table (minimum) on page 25 for precise lengths.
Seal the vent pipe. See “Vent Pipe Sealant” on page 28.
Roof Support Bracket:
Slip the roof support bracket down over the vent pipe. Rotate the 90° brackets
to accommodate roof pitch. Attach the brackets to the roof joists with nails
or building screws. Tighten the band around the vent pipe and secure in place
with screws.
TC42D2_190124-48
25
100000364
Roof Vent Terminal:
1. Place the roof flashing over the vent pipe, secure and seal it to the roof
using the methods and materials appropriate for the type of roof on the
building. Shingle roof example shown (Figure 40).
2. Place the storm collar down over the vent pipe until it is level. Tighten
storm collar for a snug fit. Apply a thick horizontal ring of mastic around
the pipe at top of the storm collar (Figure 40).
3. Lower the roof vent terminal cap over the vent pipe and secure in place
with screws provided (Figure 40). Seal screw heads and joints with caulking to
prevent any moisture entering the venting system.
Note: Adjustable for various roof pitches, from flat roof to 12/12 pitch roof.
MASTIC
VERTICAL TERMINATION CAP (TCVT.9365)
VENT PIPE STORM COLLAR (TC42.90665)
100000364
FLASHING
Figure 40: Roof vent terminal.
NOTE: ADJUSTABLE FOR VARIOUS ROOF PITCHES, FROM FLAT ROOF TO 12/12 PITCH ROOF.
26
TC42D2_190124-48
Vent Terminal Clearance
Minimum clearances to the vent terminal must be maintained as shown in (Figure
41). Measure clearances to the nearest edge of termination hood.
NOTE: Vent terminal must not be recessed NOTE: LOCAL CODES OR REGULATIONS MAY
REQUIRE DIFFERENT CLEARANCES.
VENT TERMINAL MINIMUM CLEARANCES TO ADJACENT STRUCTURES
36″ (91.5 cm)
Roof Pitch Table
Flat to 6/12 Over 6/12 to 7/12 Over 7/12 to 8/12 Over 8/12 to 9/12 Over 9/12
to 10/12 Over 10/12 to 11/12 Over 11/12 to 12/12
(minimum)
ft
m
1.00 0.30
1.25 0.38
1.50 0.46
2.00 0.61
2.50 0.76
3.25 0.99
4.00 1.22
48″ (122 cm)
See Roof Pitch Table
Adjacent Structures or Fence
Figure 41: Vent roof clearance.
Vent Terminal Minimum Clearances
24″ (61 cm)
D E
V
L
B
G V
A
C
V
FIXED
CLOSED
F V
OPENABLE
B
B
V
V
OPEN- FIXED
ABLE CLOSED
B B
VJA
A
H
I G
M VK A
V VENT TERMINAL
A= 12 inches (30 cm) min. B= 12 inches (30 cm) min. C= 12 inches (30 cm)
min. D= 30 inches (76 cm) min.
E= 30 inches (76 cm) min. F= 6 inches (15 cm) min. G= 6 inches (15 cm) min. H=
3 feet (90 cm) min.
I= 6 feet (1.8 m) min. J= 12 inches (30 cm) min. K= 6 feet (1.8 m) min. L=
7 feet (2.1 m) min. M= **30 inches (76 cm) min
A AIR SUPPLY INLET
AREA WHERE TERMINAL IS NOT PERMITTED
G
GAS METER
Figure 42: Vent terminal minimum clearances.
Clearances above grade, veranda, porch, deck, or balcony
Clearance to window or door that may be opened
Clearance to permanently closed window recommended to prevent condensation on window
Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (60 cm) from the edge of the terminal
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
*Not to be installed above a meter/regulator assembly within 3 feet (90 cm) horizontally from the center-line of the regulator
Clearance to service regulator vent outlet
Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance
Clearance to a mechanical air supply inlet
^ Clearance above paved side-walk or a paved driveway located on public property
Clearance under veranda, porch, deck, or balcony
^ a vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* * only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath the floor as specified in CGA B149 Installation Codes, Note: local Codes or Regulation may require different clearances for U.S.A. Installations follow the current National Fuel Gas Code, ANSI Z223.1
TC42D2_190124-48
27
100000364
Vent Pipe Sealant
APPROVED “HIGH TEMP.” SELF-ADHESIVE TAPE
VENT PIPE
Figure 43: TC42D Sealing vent joints.
All outer joints of the vent pipe must be sealed with the approved “High
Temperature” self-adhesive aluminium tape provided. Wrap the tape completely
around the joint and press firmly in place.
100000364
28
TC42D2_190124-48
Vent Restrictor Adjustment
The vent restrictor is located on the underside of the firebox top. The unit
leaves the factory with the vent restrictor open. The restrictor is built into
the appliance for secondary air flow adjustment. Adjustment enables tuning the
airflow for optimum flame appearance and performance for a wide variety of
vent configurations.
Setting:
WALL AND ROOF TERMINATION RESTRICTOR POSITION
48′
·
Determine the vent height.
·
Determine the vent horizontal length.
·
From the chart determine the restrictor position.
40′
Refer to the chart (Figure 44), for the correct position of restrictor for the vent configuration of your installation. Restrictor positions are based upon lab tests. The ideal position may vary slightly with installation.
1″ OPEN NG 3/4″ OPEN LP
Restrictor position is closed too much if the flame has the following characteristics:
·
Flame is excessively tall and lifting.
·
Flame lacks movement.
·
Flame soots.
30′
30′
2″ OPEN
22′
20′
20′
18′
Restrictor position is too open if the flame has the following characteristics:
·
Flame height is low.
·
Flame has excessive movement.
To adjust the restrictor:
·
Loosen the screws holding the restrictor plates.
·
Move the restrictor plates to its intended opening.
·
Retighten the screws.
3″ OPEN
12′
10′
10′
8′ FULLY OPEN
6′
4′
2′ 18″ 4′ 6′ 8′ 10′ 12′ 14′ 16′ 18′ 20′
0′ 0′
Figure 44: Restrictor rise and run chart.
CAUTION: The vent restrictor must be fully open when using the power vent
OPENING
VENT RESTRICTOR
Figure 45: Vent restrictor.
TC42D2_190124-48
29
100000364
Wall Shield Ceiling Firestop Thimble
Wall Termination Kit
WALL TERMINAL TCVT.9360
16 1/2″
16 1/2″
WALL SHIELD / CEILING FIRESTOP TCVT.THIMA – OPTIONAL
Figure 46: Ceiling firestop thimble.
9 5/8″
Figure 47: Wall termination kit.
Roof Termination Kit
WALL SHIELD/ CEILING FIRESTOP THIMBLE TCVT.THIMA
16 1/2″ 9″
VERTICAL TERMINATION CAP TCVT.9365
STORM COLLAR TC42.90665
ROOF SUPPORT BRACKET TCVT.93915
Figure 48: Roof termination kit.
100000364
WALL SHIELD / CEILING FIRESTOP TCVT.THIMA
30
TC42D2_190124-48
Attic Insulation Shield
(Optional)
Figure 50: Attice Insulation Shield
Vent Pipe Dimensions
12″ PIPE ………. 10 1/4″ 18″ PIPE ………. 16 1/4″ 24″ PIPE ………. 22 1/4″ 48″ PIPE ………. 46 1/4″
9 1/2″
10 15/16″
TCVT.811X12ADJ
11″
- 11 1/8″ TCVT.811X
45°
13 13/16″ 8 5/16″
12 9/16″
10 5/16″ 15 7/8″ TCVT.811XLB90
1 5/16″ 7/16″
Figure 49: Vent pipe dimensions.
TC42D2_190124-48
31
13 1/8″ TCVT.811XLB45
100000364
Vent Offset Chart
1 1/4″ 1 1/4″
11 3/8″
10 7/8″
A 12″ PIPE 18″ PIPE 24″ PIPE 48″ PIPE
B 18 5/8″ 22 7/8″ 27 1/8″ 44 1/16″
C 18″ 22 3/8″ 26 1/2″ 43 1/2″
ADDING AN ADJUSTABLE SECTION TO PIPE WILL INCREASE OFFSET BY 2 1/8″ TO 6 3/4″
1 1/4″
A B
A
B
C
12″ PIPE 13 7/16″ 23 1/4″
16 1/16″ 18″ PIPE 17 9/16″ 27 5/8″
A
24″ PIPE 21 7/8″
31 3/4″
48″ PIPE 38 3/4″
44 7/8″
6 1/8″
ADDING AN ADJUSTABLE
SECTION TO PIPE WILL
INCREASE OFFSET BY 2 1/8″ 1 1/4″
B
TO 6 3/4″
A
20″
C C
20″
1 1/4″
18 3/4″
Figure 51: Vent offsets. 100000364
1 1/4″
A
B
12″ PIPE
29″
18″ PIPE
35″
24″ PIPE
41″
48″ PIPE
65″
B
ADDING AN ADJUSTABLE SECTION TO PIPE WILL INCREASE OFFSET BY 3″ TO 9 1/2″
32
TC42D2_190124-48
TC42 PANEL SETS
Figure 52: Panel V brackets.
Firebox Panels Installation
Item
Part Number
PARK AVE. HERRINGBONE ……………………………………………… 22200050 MOUNT VERNON RED BRICK…………………………………………… 22200049 MANHATTAN BEIGE STACKED BRICK……………………………….. 22200047 BLACK PORCELAIN…………………………………………………………. 22200044 COFFEE BEAN BROWN PORCELAIN ………………………………… 22200042 TITANIUM ……………………………………………………………………….. 22200045 COPPER…………………………………………………………………………. 22200043
(See Porcelain panel instruction manual for specific instructions for these panels) Before proceeding see burner instructions.
FIREBOX LIP
HEAT SHIELD
ADJUSTABLE “V” BRACKET REAR LOWER PANEL
SIDE PANEL RETAINER
Figure 53: Side panel retainer.
A Firebox Panel Set must be installed for safe operation. Do not use the
fireplace without panels. Unpack and inspect all panels. The panels need to be
installed before the logs are in place.
The lower rear panel is held tight against the side panels by two “V” brackets (Figure 52) located on the firebox rear wall. Although the brackets are adjusted at the factory for the best fit, some adjustment may be necessary. Adjust the angle of the bracket by hand to ensure a snug fit.
Caution: The Firebox Panels are very fragile, and should be handled with care.
Remove the Side Panel Retainer located on the underside of the firebox heat
shield. The retainer slips between the lip of the firebox and the heat shield
and is retained in place by two screws (Figure 53 & Figure 54) .
TC42D2_190124-48
SCREWS Figure 54: Side panel retainer location.
33
100000364
Install the Lower Rear Panel. Install the Right Side Panel by inserting the bottom of the panel in first and then angling it up into position. It may be necessary to push the firebox shield up to allow panel to move freely into place. Install the Rear Upper Panel. Install the Left Side Panel by inserting the bottom of the panel in first and then angling it up into position. Re- install the Side Panel Retainers. Install the Left and Right Front Panels.
REAR UPPER PANEL
LEFT SIDE PANEL
RIGHT SIDE PANEL
REAR LOWER PANEL
LEFT FRONT PANEL
Figure 55: TC42D Panel placement.
RIGHT FRONT PANEL
100000364
34
TC42D2_190124-48
Transition Trim Kit Installation
The trim kit(SKU #80002254) includes two side pieces, a top piece, and a
bottom meshed piece which will be placed onto the fireplace floor and in front
of the glass once the fireplace door is installed.
Installation
1. With the door in place, begin by setting out the two side trim pieces and
the top piece. Each of these three trim pieces require 2 small button magnets
which are included with the trim pieces.
2. Install the two side trim pieces first using two smaller magnets on each
piece as shown in Figure 56 and Figure 57.
Figure 56: Installing the side trim.
Figure 57: Side trim in place.
Figure 58: Installing top trim.
Figure 59: Top trim in place.
3. Install the top trim piece over top of the two side trim pieces using two larger magnets (Figure 58 and Figure 59).
TC42D2_190124-48
35
100000364
Figure 60: Installing bottom trim.
Figure 61: Bottom trim in place.
4. The meshed trim piece for the bottom rests on the floor and in the gap between the outer-most door frame and the fireplace glass (Figure 60 and Figure 61).
Figure 62: Town & Country magnetic badge.
5. The trim kit comes with a Town & Country badge (Figure 62). Affix this
badge to the right hand side of the lower meshed trim piece as shown in Figure
63.
6. Attach the magnetic safety barrier screen (Figure 64) to the outer-most
door frame.
Figure 63: T&C badge on right side of trim piece.
100000364
Figure 64: Safety barrier screen.
36
TC42D2_190124-48
Linking Remote Handset to the Fireplace
Town & Country Fireplaces can be operated remotely by using the remote handset
that came with the fireplace, and by using a BlueTooth® enabled apple mobile
device and the “TC Fire” app which can be downloaded free from the Apple® app
store. For linking to the fireplace using a BlueTooth® enabled apple mobile
device, refer to the user manual that came with this fireplace. For linking
the remote handset that came with this fireplace, complete the following two
steps:
Bluetooth Wall Switch Pairing Procedure:
Step 1: Procedure for linking / pairing wall switch to fireplace
1. Set the wall switch selector to the “Remote” setting.
2. Press and hold Program button (Figure 65) on the wall switch for up to 10
seconds. Use a straightened paper clip to access the button.
3. The wall switch will beep 5 times. Release the button following the beeps.
4. The fireplace will beep 3 times repeated by another 3 beeps.
5. The fireplace and wall switch are now linked/paired.
If there is cross communication with another nearby fireplace causing the
other fireplace to activate instead of the intended fireplace, repeat above
procedure to automatically switch to another one of three available channels.
PROGRAM BUTTON
TC42D2_190124-48
Figure 65: Town and Country wall switch.
37
100000364
Step 2: Procedure for linking / pairing wall switch to remote handset 1. Press
and release Program button on the wall switch once (Figure 65). 2. You will
hear 3 beeps from the wall switch. 3. Press and release the on/off button
(Figure 66) on the remote handset (within 60 sec.) 4. The wall switch will
beep 3 times. 5. The remote handset is now linked/paired to the wall switch
and is ready to activate the fireplace.
ON /OFF
Figure 66: Remote handset.
Linking Remote Handset to the Module (Basic Wall Switch only)
Basic Wall Switch pairing procedure: (When using the basic wall switch, the
remote is paired directly to the module.) 1. Press and release Program button
on the wall switch once (Figure 65).
2. You will hear 3 beeps from the module.
3. Press and release the on/off button (Figure 66) on the remote handset
(within 60 sec.)
4. The module will beep 3 times.
5. The remote handset is now linked/paired to the module and is ready to
activate the fireplace.
100000364
38
TC42D2_190124-48
Maintenance
CAUTION: Turn off gas and electrical power supply (if applicable) and allow
ample time for unit to cool before servicing appliance. It is recommended that
the fireplace and its venting should be inspected at least once a year by a
qualified service person.
Glass Panel:
Warning: Do not operate fireplace with glass panel removed, cracked or broken.
Replacement of the glass panel should be done by a licensed or qualified
service person.
Do not strike or otherwise impact the glass in anyway that may cause it to
break. If the glass becomes cracked or broken it must be replaced before using
the fireplace. Replacement glass can be obtained from your nearest Town &
Country Fireplaces dealer. The size required is 42″ x 36″ x 5mm. Use ceramic
glass only. Do not substitute with any other type.
To remove broken glass, remove door frame as noted in “Door Frame Removal”
section.
Unclip the Glass Retainer Clips located at the top and sides of the Door
Frame. Pull the top edge of the glass out of the frame first, then lift it up
and out of the bottom edge.
Install the new piece of glass with the gasket into the frame so that the
thicker bead of gasket faces the fireplace.
Re-install glass retaining clips.
PILOT
FLAME SENSOR
PILOT FLAME ELECTRODE
TC42D2_190124-48
Figure 67: Pilot assembly. 39
100000364
Annual Inspection:
1. Remove glass panel and inspect the decorative burner media (such as logs,
pebbles, glass etc) for soot build up. If excessive build up of soot is
present, have a qualified service person inspect and adjust the unit for
proper combustion. Clean the decorative media and use a brush or vacuum
cleaner to clean the burner, paying close attention to the burner ports.
2. Check the pilot system for proper flame size and operation. Clean pilot
free of soot, dust or any other deposits.
3. Check that the vent pipe and vent terminal are open and free from blockage
or debris. If the venting is disassembled for cleaning, it must be properly
assembled and re-sealed. Refer to See “Vent Pipe Sealant” on page 28 for
proper procedure.
4. Check glass panel gasket, replace if necessary. It is important that the
glass seal be maintained in good condition.
5. Check and replace batteries as needed.
Note: The appliance area must be kept clear and free from combustible
materials, gasoline and other flammable vapours and liquids. Periodically:
a) Viewing glass may be cleaned as necessary with fireplace glass cleaner.
b) Exterior finish may be cleaned with mild soap and water.
CAUTION:
Do not use abrasive cleaners on glass or any other part of the fireplace.
Do not clean glass when hot.
100000364
40
TC42D2_190124-48
Wiring Diagram
Figure 68: TC42D Wiring diagram.
TC42D2_190124-48
41
100000364
TC42D Parts Diagram
(WHEN ORDERING, INCLUDE PART NUMBER WITH DESCRIPTION)
ITEM DESCRIPTION
PART NO.
1 TC42 BODY ASSY….. …………………… 22030009
2 GLASS ASSY……………… ………………. 80000210
3 FRAMING KIT……………………………… 80002413
ITEM DESCRIPTION
PART NO.
4 PANEL SETS PARK AVE. HERRINGBONE …………………………… 22200050 MOUNT VERNON RED
BRICK………………………… 22200049 MANHATTAN BEIGE STACKED BRICK…………….. 22200047 BLACK PORCELAIN………………………………………. 22200044 COFFEE BEAN BROWN PORCELAIN ……………… 22200042 TITANIUM …………………………………………………….. 22200045 COPPER………………………………………………………. 22200043
1
1a
2
2a
3
1g 1c
1b
1d
1e 1f CONTROL SYSTEM ASSEMBLY – See page 43
4
4a 3a
4b 4c
4f
4d
4e
KIT CONTENTS:
1 1a 1b 1c 1d 1e 1f 1g
TC42 BODY ASSEMBLY FIREBOX SHIELD (c/w insulation) FLUE DAMPER FIREBOX REAR SHIELD SPRING LATCH ASSEMBLY(2) CONTROL ASSEMBLY HOLDER BRICK PANEL RETAINER LED LIGHT ASSY
2 GLASS ASSEMBLY 2a REPLACEMENT GLASS (c/w gasket)
3 FRAMING KIT 3a STEEL STUDS 3b NON-COMBUSTIBLE BOARD
4 PANEL SETS 4a PANEL, LEFT SIDE 4b PANEL, UPPER 4c PANEL, RIGHT SIDE 4d
PANEL, LEFT BASE 4e PANEL, RIGHT BASE 4f PANEL, LOWER BACK
100000364
42
TC42D2_190124-48
Parts Diagram Control System
(WHEN ORDERING, INCLUDE PART NUMBER WITH DESCRIPTION)
ITEM DESCRIPTION
PART NO.
ITEM DESCRIPTION
PART NO.
1 CONTROL ASSEMBLY KIT …………….. 100005457
4 TEST FITTING ……………………………….. 5019.104-00
2 BULKHEAD ASSEMBLY KIT ………. TCRP.8133-30
5 WALL SWITCH ASSEMBLY KIT …………….80000498
3 COMMUNICATION CABLE KIT ……….. 5062.98-00
6 BASIC WALL SWITCH ASSEMLBY ………….100005836
7 REMOTE TRANSMITTER ……………………..80000519
1
1j 1h
1a
3 1d
2
2d
2e
2a
2b 2c 2f
1f
1e
1b
1c
KIT CONTENTS:
1 CONTROL ASSEMBLY KIT 1a VALVE c/w FITTINGS 1b 1/4″ FLEX TUBE 1c 1/2″ FLEX
TUBE 1d CONTROL MOUNTING BRACKET 1e IGNITION MODULE 1f WIRING HARNESS 1h PRESSURE TEST ASSEMBLY 1j PRESSURE SWITCH
2 BULKHEAD ASSEMBLY KIT 2a INLET PLATE 2b INLET PLATE GASKET 2c ELEC BULKHEAD
GASKET 2d 1/2″ BULKHEAD FITTING 2e 1/4″ BULKHEAD FITTING 2f ELEC BULKHEAD FITTING
3 CABLE COMMUNICATION KIT
4 TEST FITTING
4
5 WALL SWITCH ASSEMBLY KIT (not shown)
6 REMOTE TRANSMITTER (not shown)
7 Lights, Part #80001810 esch.
TC42D2_190124-48
43
100000364
Rating Label
VENTED GAS FIREPLACE – NOT FOR USE WITH SOLID FUEL FOYER AU GAZ À ÉVACUATION – NE PAS UTILISER AVEC DU COMBUSTIBLE SOLIDE
This is a decorative product and is not intended to be used as a heating
appliance.
ANSI Z21.50-2016 / CSA 2.22-2016 Vented Gas Fireplaces CAN/CGA 2.17-M91 Gas-
Fired Appliance For Use At High Altitudes.
TM
MODEL/ MODELE:
TC42
SERIES/ SERIE:
D
MADE IN CANADA FABRIQUE AU CANADA
FOR USE WITH/ EN CASE D’EMPLOI AVEC:
Minimum supply pressure / Pression minimum d’alimentation:
(For the purpose of input adjustment / dans le but de régler l’alimenation)
Maximum supply pressure / Pression maximum d’alimentation: Manifold pressure /
Pression de la tuyauterie: Maximum
Input BTU/hr (kW) / Entree BTU/h (kW):
This Appliance is Equipped For Use With / Cet Appareil est Équipé Pour Utilise Avec :
NATURAL GAS GAZ NATUREL
LP-GAS LP GAZ
NATURAL GAS/ DU GAZ NATUREL
5.0 in/wc / 5.0 po/c.e. (1.25 kPa)
13.9 in/wc / 13.9 po/c.e. (3.45 kPa)
3.5 in/wc / 3.5 po/c.e. (0.87 kPa)
NE
Max.: 61,000 (17.9) Min.: 44,000 (12.9)
LP GAS/ DU GAZ LP
12.5 in/wc / 12.5 po/c.e. (3.11 kPa)
13.9 in/wc / 13.9 po/c.e. (3.45 kPa)
10.0 in/wc / 10.0 po/c.e. (2.49 kPa)
LE
Max.: 61,000 (17.9) Min.: 48,000 (14.1)
Optional components/ Éléments facultatifs: Powervent Kit/ kit de ventilation
mécanique TCVT.PVI.25, TCVT.PV7.110, TCVT.PVCV, TCVT.PVVT. Blower electrical
rating: 115v, 60hz, 1.1 A / Normes electriques du ventilateur: 115v, 60hz, 1.1
A This appliance equipped for altitudes 0 – 4500 ft. (0 – 1372 m) / Cet unité
est conçu pour des altitudes variant entre 0 – 4500 pieds (0 – 1372 m). In
Canada, also
must be installed in accordance with local codes, if any; if none, follow the
current CAN/CGA-B149 (Canada), or ANSI Z223.1 (USA) Installation Codes.
Installer l’appareil selon les codes ou règlements locaux, ou, en l’absence de
tels règlements, selon les codes d’installation CAN/CGA-B149 (Canada), or ANSI
Z223.1 (USA) en vigeur.
MANUFACTURED (MOBILE) HOME: This appliance is only for use with the type of gas indicated on the rating plate and may be installed in an aftermarket, permanently located, manufactured (mobile) home where not prohibited by local codes. See owners manual for details. FABRIQUEZ (MOBILE) MAISON: Cet appareil doit être utilisé uniquement avec le type de gaz indiqué sur la plaque signalétique et peut être installé dans une maison préfabriquée (mobile) installée à demeure si les règlements locaux le permettent. Voir la notice du propriétaire pour plus de détails. Cet appareil ne peut
Install in accordance with the current standard Mobile Homes,CAN/CSA Z240 MH (in CANADA), and the Manufacturer’s Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard for Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, (in the U.S.A.). Cet appareil diot être installé conformemént aux exigences de la norme CAN/CSA Z240 MH en vigueur de l’ACNOR, Installations de gaz dans les Constructions Mobiles. FOR USE WITH THE GLASS AND SCREEN BARRIER CERTIFIED WITH THE APPLIANCE ONLY / POUR UTILISATION UNIQUEMENT AVEC LES PORTES IN VERRE CERTIFIÉES AVEC L’APPAREIL
MINIMUM CLEARANCES TO COMBUSTIBLES / CLAIRANCES MINIMALES AVEC LES COMBUSTIBLE Left and Right side are determined when facing the front of the appliance. / Les côtés droit et gauche se déterminent en se mettant devant l’appareil et en lui faisant face.
Top, Back and Side Standoffs / Sommet, Arrière et Côté Butée Sidewall to
Appliance / Du mur latéral a l’appareil Ceiling to Appliance / Plafond a
l’appareil Mantel to Appliance / Du manteau al’appareil Maximum Mantel
Extension / Allongement maximum du manteau
*See Installation Manual for more detail / Voyez des Directive de l’Installation pour plus détaux. Mantel Supports / Supports du manteau Vent Pipe / Déchargez le Tuyau
0 in./ 0 po. 4 in./ 4 po. 24 in./ 24 po. 9 in./ 9 po. 12 in./ 12 po.
4 in./ 4 po. 1.75 in./ 1.75 po.
(0 mm) (102 mm) (610 mm) (229 mm) (305 mm)
(102 mm) (45 mm)
Fireplace Products Ltd. Duncan, British Columbia,
Canada
P.4.1-15 Efficiency: 34.2%
DATE OF MANUFACTURE
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer
installer, service agency or the gas supplier.
des dommages matériels ou des blessures. Voir la notice de l’utilisateur qui accompgne l’appareil. Pour de l’aide ou des renseignements supplémentaires, consultez un installateur, un technicien agréé ou le fournisseur de gaz.
160119
100001669-50
1-TC42-D2
100000364
44
TC42D2_190124-48
TC42D2_190124-48
45
100000364
100000364
46
TC42D2_190124-48
TC42D2_190124-48
47
100000364
© 2019 Copyright Pacific Energy Fireplace Products LTD Reproduction,
adaptation, or translation without prior written permission is prohibited,
except as allowed under the copyright laws.
For technical support, please contact your retailer
Web site: www.townandcountryfireplaces.com 2975 Allenby Rd., Duncan, BC V9L
6V8
Printed in Canada