XXX3 TECHNOLOGY 240HX3 Gas On Demand Water Heater Owner’s Manual
- June 1, 2024
- XXX3 TECHNOLOGY
Table of Contents
- XXX3 TECHNOLOGY 240HX3 Gas On Demand Water Heater
- Specifications
- Product Information
- Usage Instructions
- FAQs
- SPECIFICATIONS
- INTRODUCTION
- INSTALLATION
- CLEARANCES
- INITIAL OPERATION
- NORMAL OPERATION
- MAINTENANCE AND SERVICE
- TROUBLESHOOTING
- 701).
- 101) when the water heater prepares for combustion.
- 102) when water heater goes into combustion.
- 108). · Check if there is leaking from heat exchanger (Part #401). · Check
- 709) and/or soot on the AFR
- 103) and/or burn marks on the computer board (Part #701).
- 103). · Check for connection/breakage of wires (Part #472, 721).
- PARTS LIST
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
XXX3 TECHNOLOGY 240HX3 Gas On Demand Water Heater
Specifications
- Models: 240HX3, 340HX3, 540HX3
- Low NOx Emissions: 14 ng/J or 20 ppm
- Gas Type: Natural Gas
- Water Heater Type: Gas Tankless Water Heater
- Installation Manual: ANSI Z21.10.3CSA 4.3
Product Information
The On-Demand Water Heater is a gas tankless water heater suitable for potable water heating only. It is designed to provide hot water efficiently and effectively.
Usage Instructions
Safety Guidelines
Follow all safety guidelines provided in the manual to avoid any potential hazards. Installation and service should be performed by qualified professionals only.
Installation
Proper installation is crucial for the safe and efficient operation of the water heater. Ensure all clearances are met according to the guidelines provided in the manual.
Gas Supply and Gas Pipe Sizing
Make sure to correctly size and install the gas supply piping according to the specifications outlined in the manual.
Water Connections
Connect the water heater to the water supply following the instructions provided. Install a pressure relief valve as recommended for safety.
Electrical Connections
For electrical connections, follow the guidelines provided in the manual. Ensure proper installation of any included accessories such as temperature remote controllers.
FAQs
- Q: Can I install the water heater with a recirculation loop?
- A: No, do not install the water heater with a recirculation loop. It is suitable for potable water heating only.
- Q: What should I do if I have questions during installation?
- A: If you have any questions, contact the provided customer support number for assistance.
“`
On-Demand Water Heater Installation Manual and Owner’s Guide
ANSI Z21.10.3CSA 4.3
Models
240HX3 340HX3 540HX3
If the information in these instructions is not followed exactly, a fire or
explosion may result causing property damage,
WARNING personal injury or death.
Gas Tankless Water HeaterTM
Do not install the water heater with a recirculation loop. Suitable for
potable water heating only.
– Do not store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch any electric switch; do not use any phone in your building. ·
Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions. · If you cannot reach your gas supplier, call the
fire department.
– Installation and service must be performed by a qualified installer, service
agency or the gas supplier.
FEATURING · ENDLESS HOT WATER · ON-DEMAND USAGE · COMPACT, SPACE SAVING ·
ENERGY CONSERVATION · COMPUTERIZED SAFETY · NO PILOT LIGHT · X3TM TECHNOLOGY ·
Complies with SCAQMD Rule
1146.2 for natural gas Low NOx Emissions of 14 ng/J or 20 ppm.
If you have any questions, please call or write to:
In the United States 500 Tennessee Waltz Parkway Ashland City, TN 37015 Toll
Free: 1-877-737-2840
Keep this manual near the water heater for future reference whenever maintenance, adjustment, or service is required.
Installation Manual
Installation Manual
CONGRATULATIONS
Congratulations and thank you for choosing our tankless water heater. Before
use, we recommend that you read through this installation manual carefully.
Keep this manual for future reference. If you need an additional manual,
contact the manufacturer or your local distributor. You may also download a
manual from our website. When you call, please tell us the product name and
the serial number of your unit written on the rating plate of the water
heater.
3 Page
SPECIFICATIONS
Installation Manual Specifications
Model
Natural Gas Input (Operating Range) Propane Input (Operating Range)
BTU/h BTU/h
240HX3 Indoor
(AT-H3J-DVSCM)
240HX3 Outdoor
(AT-H3J-OSSCM)
340HX3 Indoor
(AT-H3S-DVSCM)
340HX3 Outdoor
(AT-H3S-OSSCM)
Min.: 15,000 Max.: 160,000
Min.: 15,000 Max.: 180,000
Min.: 13,000 Max.: 160,000
Min.: 13,000 Max.: 180,000
540HX3 Indoor
(AT-H3-DVSCM)
540HX3 Outdoor
(AT-H3-OSSCM)
Min.: 15,000 Max.: 199,000
Min.: 13,000 Max.: 199,000
Gas Connection
3/4″ NPT
Water Connections
Water Pressure*
Natural gas Inlet Pressure
psi (MPa)
” W.C. (kPa)
3/4″ NPT
15 – 150 (0.1 – 1)
Min. 4.0 (1.00) Max. 10.5 (2.61)
Propane Inlet Pressure
Weight
” W.C. (kPa)
lbs. (kg)
60 (27.4)
60 (27.1)
Min. 8.0 (1.99) Max. 13.0 (3.23)
60 (27.4)
60 (27.1)
62 (27.9)
61 (27.6)
Dimensions
inch
(HxWxD) mm
22.4 x 17.7 x 10.7 570 x 450 x 272
Ignition
Electric Ignition
Supply
VAC/Hz
120/60
Electric Consumption
Operation W/A
72.7 / 0.61
78.2 / 0.65
89.0 / 0.74
Standby W/A
3.1 / 0.03
3.1 / 0.03
4.2 / 0.04
FreezeProtection
W/A
197/1.7
Water heater category**
IV
N/A
IV
N/A
IV
N/A
*40 psi or above is recommended for maximum flow. **Water heater Category — water heaters of other than direct vent type, for outdoor installation, are divided into four categories
based on static pressure produced in the vent and flue loss. Category IV – a
water heater that operates with a positive vent static pressure and with a
vent gas temperature that may
cause excessive condensate production in the vent. NOTE: · Check the rating
plate to ensure that this product matches your specifications. · The
manufacturer reserves the right to discontinue, or change at any time,
specifications or designs with-
out notice and without incurring obligation.
NOTICE
The 240HX3/340HX3/540HX3 models do not have Easy-Link or Multi-Unit capability.
4 Page
Installation Manual Introduction
INTRODUCTION
· This manual provides information necessary for the installation, operation,
and maintenance of the water heater.
· The model description is listed on the rating plate attached to the side
panel of the water heater. · Please read all installation instructions
completely before installing this product. · If you have any problems or
questions regarding this equipment, consult the manufacturer or its
local representative. · This equipment is an on-demand, tankless water heater
designed to efficiently supply endless hot
water for your needs when properly sized and installed. · These high
efficiency models have a built-in secondary heat exchanger that absorbs latent
heat
from the exhaust gas. · The Indoor models are only to be installed indoors.
The Outdoor models are only to be installed
outdoors.
· The principle behind tankless water heaters is simple:
Intake port (Indoor only) Exhaust HL (Indoor only) Exhaust thermistor (Indoor
only)
Hi limit switch
HX thermistor (540HX3 only)
Bypass valve (540HX3 only)
Exhaust
Secondary heat exchanger
Primary heat exchanger
Drain plug detector
Burner
Flow sensor/ Water control valve Outlet thermistor
X3TM Cartridge
Hot water outlet
Cold water inlet
Igniter Fan motor Computer board
Gas valves Condensate drain port
Gas
Inlet thermistor
*This diagram illustrates tankless water heater design concepts only and does not accurately represent the water heater’s physical description. 1. A hot water tap is turned on. 2. Water flows through the flow sensor, then through the X3TM Scale Prevention Technology cartridge. 3. The computer initiates the fan motor and gas valve to let gas flow through the heater and sends a signal to
the igniter to create an ignition spark. 4. The gas ignites and flames appear
within the burner chamber. 5. Water is heated as it flows through the heat
exchanger. 6. Using thermistors to measure temperatures throughout the water
heater, the computer modulates the gas
and water valves to ensure proper output water temperature and hot water
outflows. 7. When the tap is turned off, the unit shuts down.
5 Page
SAFETY GUIDELINES
SAFETY DEFINITION
Installation Manual Safety Guidelines
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Indicates an imminently hazardous situation which, if not avoided, could CAUTION result in minor or moderate injury.
Indicates an imminently hazardous situation which, if not avoided, could result WARNING in death or serious injury.
NOTICE Indicates information considered import-
ant but not hazard related.
GENERAL
1. Follow all local codes, or in the absence of local codes, follow the
current edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54 in the USA.
2. Properly ground the unit in accordance with all local codes or in the
absence of local codes, with the National Electrical Codes: ANSI/NFPA 70.
3. Carefully plan where you intend to install the water heater. Please
ensure: · Your water heater will have enough combustion air and proper
ventilation. · Locate your heater where water leakage will not damage
surrounding areas. (Please refer to page 8.)
4. Check the rating plate for the correct GAS TYPE, GAS PRESSURE, WATER
PRESSURE and ELECTRIC RATING. · If this unit does not match your requirements,
do not install and consult with the manufacturer.
5. If any problem should occur, turn off all hot water taps and turn off the
gas. Then call a trained technician, the gas company, or the manufacturer.
· Water temperatures over 125 °F (52 °C) can cause severe burns instantly or
death from scalding. The water temperature is set at 120 °F (50 °C) from the
factory to minimize any scalding risk. Before bathing or showering always
check the water temperature.
· To reduce the risk of scalding, install Thermostatic Mixing Valves
(temperature limiting valves) at each point of use.
· Do not store or use gasoline or other flammables, vapors, or liquids in the
vicinity of this appliance.
· Do not reverse the water and/or gas connections as this will damage the gas
valves and can cause severe injury or death. Follow the diagram on page 32
when installing your water
WARNING heater. · Should overheating occur or the gas supply fails to shut
off, turn off the manual gas control valve to the appliance. · Do not use this
appliance if any part has been in contact with or been immersed in water.
Immediately call a qualified installer or service agency to replace a flooded
water heater. Do not attempt to repair the unit. It must be replaced. · Do not
disconnect the electrical supply if the ambient temperature will drop below
freezing unless the water has been drained from the water heater. The Freeze
Protection System only works if the unit has electrical power. The warranty
will not be covered if the heat exchanger is damaged due to freezing. Refer to
the sections on the Freeze Protection System on page 48 and on Unit Draining &
Power Outage (Freeze protection) on page 50 for more information. · Failure to
observe these warnings could result in severe personal injury or death.
6 Page
Installation Manual Installation
INSTALLATION
GENERAL
1. Follow all local codes, or in the absence of local codes, follow the
current edition of the National Fuel Gas Code: ANSI Z223.1/NFPA 54.
2. All gas water heaters require careful and correct installation to ensure
safe and efficient operation. This manual must be followed exactly. Read the
“Safety Guidelines” Section.
3. The manifold gas pressure is preset at the factory. It is computer
controlled and should not need adjustment.
4. Maintain proper space for servicing. Install the unit so that it can be
connected or removed easily. Refer to the “Clearances” Section on page 9 for
proper clearances.
5. The water heater must be installed in a location where the proper amount
of combustion air will be available to it at all times without obstructions,
or the indoor heater must be direct vented. See pages 13 to 29.
6. Install the water heater so it is level (left-to-right & front-to-back)
and plumb (vertically). 7. Electrical service to the water heater requires a
means of disconnection. This will allow power to the
water heater to be shut off for servicing and safety purposes. 8. Do not
install the unit where the exhaust vent is pointing into any opening in a
building or where the
noise may disturb your neighbors. Make sure the vent termination meets the
required clearance from any doorway or opening to prevent exhaust from
entering a building. (Refer to pages 8, 11, 14 and 15.) Check local code
requirements prior to installation. 9. Carefully plan the installation
location of the heater and vent terminations. Contaminants such as aerosols,
lint, and fine powders (including flour) can clog the air intake and reduce
the operation of the fan. This, in turn, can cause improper combustion and
reduce the life of the water heater. Regularly ensure that the area around the
water heater, vent termination, and air intake are free of dust, debris, and
other contaminants. In environments with a high level of contaminants (laundry
facilities, hair salons, pet salons, chemical plants, commercial kitchens,
etc.), direct venting is required. 10. The Indoor models are to be installed
indoors only. These units are equipped with a thermistor and hi-limit switch
for the exhaust gas, detecting excess temperatures within the flue and
enabling the unit to safely stop operations if needed. These components are
always monitoring exhaust gas conditions in order to prevent heat damage to
ABS, PVC, CPVC, or polypropylene (Plastic) venting if ABS, PVC, CPVC, or
polypropylene is used. If the exhaust gas temperature exceeds 140 °F (60 °C),
these components will enable the unit to safely stop operations. These
components are not installed on the outdoor models since the exhaust vent is
built-in.
· If the water heater is used as a direct-vent appliance, the unit requires 3″
or 4″ combustion air supply pipe. The intake pipe must be sealed airtight.
Refer to pages 13 to 29 for more detail.
· Terminating the venting through a sidewall is recommended for the direct-
vent system. · Running the exhaust vent and the intake pipe parallel is
recommended. · Terminating the exhaust and intake on the same wall/surface is
recommended. Terminating in the
same pressure zone allows for pressure balancing, which prevents nuisance
shutdowns. · Only install the water heater in a heated area where below
freezing temperatures cannot occur.
The warranty does not cover damage caused by freezing. · The water heater must
be securely mounted to a wall or other suitable structure. · The venting
system shall be installed in accordance with the water heater manufacturer’s
and
venting system manufacturer’s instructions. 11. The Outdoor models must only
be installed outdoors and only in an area with mild, temperate climates.
The Outdoor model shall be wall-mounted or mounted on a stand. Locate the
Outdoor model in an open, unroofed area and maintain the following minimum
clearances: There is a 3 in (76 mm) clearance from the left and right sides of
the unit to combustible and non-combustible surfaces.
7 Page
Installation Manual Installation
· Installation and service must be performed by a qualified installer (for
example, a licensed plumber or gas fitter). Otherwise, the warranty will be
void.
· The installer (licensed professional) is responsible for the correct
installation of the water heater and for compliance with all national,
state/provincial, and local codes.
· The manufacturer does not recommend installing the water heater in a pit or
location where WARNING gas and water can accumulate.
· Do not attach the gas line to the water heater until after the gas line
system pressure test for leaks has been completed. See page 30 for additional
information.
· Do not install or locate the vent terminal pointing toward any operating
window, door, opening into a building or other area where people gather, where
combustion gases could create a nuisance or hazard or cause property damage.
· Do not install the air intake next to any source of airborne debris, such as
a clothes dryer, that can cause debris to be trapped inside the combustion
chamber, unless the system is directvented.
· Do not install the unit where water, debris, or flammable vapors may get
into the flue terminal or the air intake line.
· The manufacturer does not recommend installing the water heater in an attic
due to safety issues. If you install the water heater in an attic: – Make sure
the unit will have enough combustion air and proper ventilation. Failure to do
so could lead to carbon monoxide poisoning or death. – Keep the area around
the water heater clean. When dust collects on the flame sensor, the water
heater will shut down on an error code. – Place the unit where it will allow
easy access for service and maintenance. – A drain pan, or other means of
protection against water damage, is recommended to be installed under the
water heater in case of leaks. See the NOTICE below.
· The water heater must be securely mounted to a wall or other suitable
structure so that it is level (left-to-right & front-to-back) and plumb
(vertically).
· Failure to observe these warnings could result in severe personal injury,
death, and/or property damage.
NOTICE
· The warranty will not cover damage caused by water quality. – Only potable
water can be used with this water heater. Do not introduce pool or spa water,
or any chemically treated water into the water heater. – Introduction of water
with iron greater than 0.3 mg/L. – Water pH levels must be between 6.5 and
8.5. – Well water must be treated.
· The manufacturer recommends direct venting when the water heater is
installed in beauty salons, dry cleaners or any other locations in which such
chemicals are present in the air. Some chemicals used in beauty salons or dry
cleaners may affect the flame sensor. In such cases, the water heater may not
work properly.
· Although the water heater is designed to operate with minimal sound, the
manufacturer does not recommend installing the unit on a wall adjacent to a
bedroom, or a room that is intended for quiet study or meditation, etc.
· Locate your water heater close to a drain where water leakage will not do
damage to surrounding areas. As with any water heating appliance, the
potential for leakage at some time in the life of the product does exist. A
drain pan, or other means of protection against water damage, is recommended
to be installed under the water heater in case of leaks. In addition, you may
install an active water leak detector with a shutoff valve which can turn off
the water supply in the event of a leak. The manufacturer is not responsible
for damage due to water leaks. If you install a drain pan under the unit,
ensure that it will not restrict the combustion air flow.
· This water heater is not suitable for combination water (potable) heating,
space heating, and/ or recirculation
8 Page
CLEARANCES
Installation Manual Installation
Maintain all clearances around the water heater. Failure to do so could create a fire hazard, potentially leading to death, serious injury, and/or property damage. WARNING
Model Indoor
Top
Bottom Front
Back
Sides
12 in
18 in
4 in*
0.5 in
3 in
(305 mm) (458 mm) (102 mm) (13 mm) (76 mm)
Side Front
Top Back
Side
Outdoor
36 in
18 in
24 in
0.5 in
3 in
(914 mm) (458 mm) (610 mm) (13 mm) (76 mm)
*24 inches (610 mm) recommended for maintenance.
Boom
INCLUDED ACCESSORIES
Check that these items below are included with the water heater.
Installation manual and
owner’s guide
Remote controller kit Outdoor models only (Refer to pp. 10 and 37.)
Bird screen Indoor models only
X3TM cartridge
Pressure relief valve
100209924 (TM-RE42)
Qty: 2 100282480
100314491
Model
Temperature remote controller
Pipe cover
Neutralizer kit
3″ PVC concentric termination
Recess box
X3 Cartridge Anti-Freeze Kit
7. Non-return valve
4″ PVC Adapter (for Non-return valve)
OPTIONAL ITEMS
240HX3 Indoor
240HX3 Outdoor
340HX3 Indoor
340HX3 Outdoor
9 Page
540HX3 Indoor
540HX3 Outdoor
1. Temperature remote controller:
100209924 (TM-RE42) The temperature remote controllers have three functions.
It allows the output temperature from the water heater to be adjusted and it
also works as a diagnostic tool and it provides a concise error code whenever
there is a problem with the unit. See the Troubleshooting Section (pages 53 to
55) for information on possible error codes.
Installation Manual Installation
2. Pipe cover: 100112718 (TH-PC03)
The pipe cover protects the piping and X3TM Technology from environmental
factors such as rain, UV rays and improves the appearance of the installation.
The pipe cover or recess box is recommended when the water heater is installed
outside.
3. Neutralizer kit: 100112159 The neutralizer assembly neutralizes the condensate (acidic water) that forms in the secondary heat exchanger of the water heater. It connects to the condensate drain port of the water heater by using connectors included with the neutralizer kit. (Refer to pages 34 and 35.)
4. 3″ PVC concentric termination: 100112163
Used when terminating direct-vent (sealed combustion) systems, with Indoor
models that require a 3 intake and a 3 exhaust. This concentric termination
provides the convenience of only having to make one penetration through a
sidewall instead of two separate penetrations for the intake and exhaust
piping. The termination includes a bird screen, restricting small animals,
pests, and foreign objects from entering into the vent system.
5. Recess box:
6. X3TM Cartridge Anti-Freeze Kit: 100325654
It allows for “clean” installations. The water heater
This kit is recommended for outdoor installations to
fits inside the recess box, which hides and protects the protect the X3 Cartridge. The kit includes a 120 volt
whole water heater and plumbing.
heat trace wire and an insulation blanket.
For retrofit applications For new construction
– no flange
applications – with flange
100298009
100306285
7. Non-return valve: 100113130
It is a must-have item for common venting system. It prevents the escape of
combustion gas through non-operating appliances. (Refer to pages 28 and 29.)
8. 4″ PVC Adapter: 100113129 This adapter transitions from the Non-return
valve outlet to 4″ schedule 40 PVC pipe.
10 Page
WARNING FOR INSTALLATIONS
Installation Manual Installation
FOR YOUR SAFETY, READ BEFORE INSTALLATION:
Do not install the heater where water, debris or flammable vapors may get into the flue terminal. This may cause damage to the heater and void the warranty.
Do not have the vent terminal pointing toward any opening into a building. Do not locate your heater vent terminal, and air intake in a pit or location where gas and water can accumulate.
Prohibited
Prohibited
Ensure that you meet the minimum clearances shown below for a direct vent termination:
Ensure that you meet the minimum clearances shown below for outdoor vent termination:
1 ft min.
1 ft min. 1 ft min.
4 ft min.
4 ft min. 4 ft min.
1 ft above grade and above ancipated snow level
Ancipated snow level
Locate the outdoor water heater so it’s vent terminal meets the following
clearances. Locate the vent terminal of an indoor heater to meet the following
clearances:
2 ft from an inside corner 2 ft from an outside corner 3 ft below a
soffit/overhang
Do not install next to a dryer or any source of airborne debris that can be trapped inside the combustion chamber, unless the system is direct-vented.
Outside corner
2 ft
3 ft 2 ft
Inside corner
11 Page
HIGH-ALTITUDE INSTALLATIONS
Installation Manual Installation
· · WARNING ·
Adjust the appropriate DIP switches according to model and elevation as shown below. DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning or death.
Indoor models
Altitude DIP switches
240HX3/340HX3
540HX3 (Lower bank of DIP switches)
0 to 2,000 ft (0 to 610 m)
(DEFAULT)
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 3 : OFF No. 4 : OFF No. 5 : OFF
ON 1 2 3 4 5 6
OFF
No. 2 : OFF No. 3 : OFF No. 4 : OFF
2,001 to
3,001 to
5,001 to
7,501 to
3,000 ft
5,000 ft
7,500 ft
10,100 ft
(611 to 914 m) (915 to 1,524 m) (1,525 to 2,286 m (2,287 to 3,078 m)
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 3 : OFF No. 4 : O N No. 5 : OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 3 : OFF No. 4 : OFF No. 5 : ON
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 3 : OFF No. 4 : O N No. 5 : O N
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 3 : O N No. 4 : O N No. 5 : O N
ON 1 2 3 4 5 6
OFF
No. 2 : OFF No. 3 : O N No. 4 : OFF
ON 1 2 3 4 5 6
OFF
No. 2 : OFF No. 3 : OFF No. 4 : O N
ON 1 2 3 4 5 6
OFF
No. 2 : OFF No. 3 : O N No. 4 : O N
ON 1 2 3 4 5 6
OFF
No. 2 : O N No. 3 : O N No. 4 : O N
Outdoor models
Altitude DIP switches
0 to 2,000 ft (0 to 610 m)
(DEFAULT)
2,001 to
4,001 to
4,000 ft
6,000 ft
(611 to 1,219 m) (1,220 to 1,829 m)
240HX3/340HX3
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 3 : OFF No. 4 : OFF No. 5 : OFF
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 3 : OFF No. 4 : OFF No. 5 : O N
1 2 3 4 5 6 7 8 9 10 ON
OFF
No. 3 : O N No. 4 : OFF No. 5 : O N
540HX3 (Lower bank of DIP switches)
ON 1 2 3 4 5 6
OFF
No. 2 : OFF No. 3 : OFF No. 4 : OFF
ON 1 2 3 4 5 6
OFF
No. 2 : OFF No. 3 : OFF No. 4 : O N
ON 1 2 3 4 5 6
OFF
No. 2 : O N No. 3 : OFF No. 4 : O N
NOTE: The dark squares indicate the correct DIP switch positions.
240HX3/340HX3
540HX3
Installation altitude
The maximum certified or allowable installed altitude is 10,100 ft (3,078 m)
for indoor models and 6,000 ft (1,829 m) for outdoor models.
Bank of DIP switches
12 Page
Lower bank of DIP switches
VENTING INSTRUCTIONS
Installation Manual Installation
WARNING
· Improper venting of this appliance can result in excessive levels of carbon
monoxide which can result in severe personal injury or death.
· Improper installation can cause nausea or asphyxiation, severe injury or
death from carbon monoxide and flue gases poisoning. Improper installation
will void product warranty.
· When installing the vent system, all applicable national and local codes
must be followed. If you install thimbles, fire stops or other protective
devices and they penetrate any combustible or noncombustible construction, be
sure to follow all applicable national and local codes.
The Indoor model must be vented in accordance with “Venting of Equipment” in
the current edition of the
National Fuel Gas Code: ANSI Z223.1/NFPA 54 as well as applicable local
building codes.
The use of venting materials approved for Category III/IV appliances is
required. In addition, PVC (solid core), CPVC, ABS, and polypropylene are
approved for use with the indoor models. For details, please refer to the
Exhaust Vent (ABS, PVC, CPVC, or Polypropylene Vent) Section on pages 21 to
24.
General rules for venting water heaters: · Place the water heater as close as
possible to the vent termination. · The vent collar of the water heater must
be fastened directly to an unobstructed vent pipe. · Do not weld the vent pipe
to the water heater’s vent collar. · Do not cut or alter the vent collar of
the unit. · The vent must be easily removable from the top of the water heater
for normal service and inspection of the unit. · The water heater vent must
not be connected to any other gas appliance or vent stack except an approved
common-venting system. Refer to pages 28 and 29. · Avoid using an oversized
vent pipe or using extremely long runs of the pipe unless it is part of an
approved common vent system. · Air supply pipe can be made of ABS, PVC (solid
core), CPVC (solid core), polypropylene, corrugated stainless steel, or
Category lll/IV stainless steel. Regarding exhaust pipe, refer to pages 21 to
27. · Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel®
(polyphenylsulfone) in nonmetallic venting systems is prohibited. Covering
non-metallic vent pipe and fittings with thermal insulation is prohibited. ·
Sidewall venting is recommended for the Indoor model. Vertical venting (roof
termination) is acceptable. · Slope horizontal venting sections 1/4″ upwards
for every 12″ (300 mm) toward the termination or according to local and state
codes, or in the absence of local or state codes, the current edition of the
National Fuel Gas Code, ANSI Z223.1 (NFPA 54) · The manufacturer recommends
running the exhaust vent and the intake pipe as parallel as possible. · For
rooftop venting, a rain cap or other form of termination that prevents rain
water from entering into the water heater must be installed. · Do not
terminate vent into a chimney. If the vent must go through the chimney, the
vent must run all the way through the chimney with approved vent pipe. · The
water heater shall not be connected to a chimney flue serving a separate
appliance, designed to burn solid fuel. · When an existing Category I
appliance is removed or replaced, the original venting system may no longer be
sized to properly vent the attached water heater. An improperly sized venting
system may cause formation of condensate, leakage, and spillage and so on.
Follow all instructions in this manual.
General rules for vent terminations: · Avoid locating the water heater vent
termination near any air intake devices. These fans can pick up the exhaust
flue products from the water heater and return them to the building. This can
create a health hazard. · Locate the vent termination so that it cannot be
blocked by any debris, at any time. Most codes require that the termination be
at least 12 in (305 mm) above grade and anticipated snow level, but the
installer may determine if it should be higher depending on the job site
condition and applicable codes. · A proper sidewall termination is recommended
when the water heater is vented through a sidewall. · Regarding the clearances
from the exhaust termination to the air inlet or opening, refer to pages 14 to
16.
13 Page
D E
-Vent termination clearances-
Installation Manual Installation
Inside corner detail
G
V
A
Legend: V = Vent terminal X = Air supply inlet = Area where terminal is not
permied
H
LB
C
V
Fixed closed
Operable
FV
B
B
B Fixed
V
V Operable closed
B
X
V
B A
J
I
15
M
X
V
K
Regulator vent outlet In the event no regulator is present, H and I can be disregarded
US Installations1
Direct vent
Other than direct vent
A Clearance above grade, veranda, porch, deck, or balcony
1 ft (30 cm)
1 ft (30 cm)
B Clearance to window or door that may be opened
1 ft (30 cm)
4 ft (1.2 m) below or to side of opening;
1 ft (30 cm) above opening
C Clearance to permanently closed window
0
0
Vertical clearance to ventilated soffit located above D the terminal within a
horizontal distance of 2 ft (61
cm) from the center line of the terminal
3 ft (91 cm)
3 ft (91 cm)
E Clearance to unventilated soffit
F Clearance to outside corner
G Clearance to inside corner
H
Clearance to each side of center line extended above meter/regulator assembly
3 ft (91 cm) 2 ft (61 cm) 2 ft (61 cm)
3 ft (91 cm) 2 ft (61 cm) 2 ft (61 cm)
I Clearance to service regulator vent outlet
Clearance to non-mechanical air supply inlet to J a building or the combustion
air inlet to any other
appliance.
K Clearance to mechanical air supply inlet
L
Clearance above paved sidewalk or paved driveway located on public property
1 ft (30 cm)
3 ft (91 cm) above if within 10 ft (3 m) horizontally.
7 ft (213 cm)
4 ft (1.2 m) below or to side of opening;
1 ft (30 cm) above opening 3 ft (91 cm) above if within
10 ft (3 m) horizontally.
7 ft (213 cm)
M Clearance under veranda, porch deck, or balcony
1 ft (30 cm)**
1 ft (30 cm)**
*Clearance in accordance with local installation codes and the requirements of the gas supplier. **Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
The vent for condensing water heaters shall not terminate:
· over public walkways; or
· near soffit vents or crawl space vents or other areas where condensate or vapor could create a nuisance or hazard or cause property damage; or
· where condensate vapor could cause damage or could be detrimental to the operation of regulators, relief valves, or other
equipment.
Notes:
-
In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code
-
If locally adopted installation codes specify clearances different than those illustrated, then the most stringent clearance shall prevail.
-
Blocking air supply and exhaust vent by snow may cause incomplete combustion and an appliance failure. Install the termination by
providing sufficient clearance from anticipated snow line in accordance with local code or manufacture’s instructions and make sure
there in no blockage.
- Provide an appropriate clearance between a vent termination and a building to prevent degradation to building materials caused by
flue gases.
- Water heaters installed outdoors follow the Other Than Direct Vent clearances.
14 Page
Installation Manual Installation
-Clearances for sidewall terminations-
Improper installation can result in carbon monoxide poisoning or death. Follow all local and national codes in regards to proper termination clearances. In the absence of such codes, the clearances below can be used as guidelines. Local codes supersede these guidelines. WARNING
(30m15ifmnt.m) (61m02imfnt.m)
TerEmxAhinnaauttisictoinpat(e30dm51Simfntn.mo)w
level cInosrindeer
Multiple Sidewall Terminations An exhaust termination must be at least 1 ft (305 mm) away from another exhaust termination. An exhaust termination must also be at least 2 ft (610 mm) away from an inside corner. (If the adjacent wall is less than 2 ft (610 mm) of length, the minimum required distance away from the inside corner will be equal to the length of that adjacent wall.)
2 ft (610 mm) min.
Exhaust termination
Combined intake and exhaust termination
2 ft
1 ft (305 mm)
(610 mm) min.
min.
1 ft
(305 mm)
min. Anticipated Snow
level Inside
corner
Multiple DV Sidewall Terminations
A direct vent (DV) termination must be at least 1 ft (305 mm) away from other
direct vent terminations. A direct vent termination must also be at least 2 ft
(610 mm) away from an inside corner. (If the adjacent wall is less than 2 ft
(610 mm) of length, the minimum required distance away from the inside corner
will be equal to the length of that adjacent wall.)
<Case 1> Exhaust
For direct vent sidewall
Intake
terminations that use two
separate penetrations for the
intake and exhaust, keep the
termination clearances shown in 1 ft (305 mm)
the diagrams on the right.
min.
X3TM CARTRIDGE is not shown.
Exhaust Intake
0.5 ft (159 mm) min.
Exhaust and/or direct vent sidewall terminations should be at least 2 ft (610 mm) away from an opposite surface/wall. Do not place the termination directly in front of an opening into a building.
<Case 2> Exhaust
1 ft (305 mm) min. Intake
Exhaust Intake
0.5 ft (159 mm) min.
15 Page
-Clearances for rooftop terminations-
Installation Manual Installation
WARNING
Follow all local and national codes in regards to proper termination clearances. In the absence of such codes, the clearances below must be met. Local codes supersede these clearances. Failure to observe this warning may result in severe personal injury or death.
Angled roof termination
2 ft (610 mm) min.
Exhaust
1 ft (305 mm)
min.
Intake
1 ft (305 mm)
min.
1 ft (305 mm)
min.
Anticipated snow level
Flat roof termination
Intake
3 ft (914 mm) min.
Exhaust
1 ft (305 mm)
min.
1 ft (305 mm)
min.
Anticipated snow level
Multiple angled roof terminations
Multiple flat roof terminations
1 ft (305 mm)
min.
1 ft (305 mm)
min.
Exhaust
1 ft (305 mm)
Exhaust
min.
3 ft (914 mm)
min.
Intake
1 ft (305 mm)
min.
Intake
1 ft (305 mm)
min.
2 ft (610 mm)
min.
2 ft
(610 mm)
min.
Exhaust
Exhaust
1 ft (305 mm)
min.
1 ft (305 mm)
min.
3 ft (914 mm)
min.
Anticipated snow level
Ancipated snow level
Intake
Intake
WARNING
· Exhaust terminations must be at least 1 ft (305 mm) away from any
obstructions. · Minimum spacing between multiple terminals:
intake terminals: 1 ft (305 mm) spacing between each exhaust terminals: 1 ft
(305 mm) spacing between each · The exhaust termination must be a horizontal
distance of at least 2 ft (610 mm) from a wall or surface unless specified
differently by local code. · Failure to observe this warning may result in
severe personal injury or death.
16 Page
-Combustion air supply-
Installation Manual Installation
WARNING
This gas water heater requires an adequate source of clean air for combustion and ventilation. Without sufficient air, your water heater may not operate properly and may emit excessive and abnormal amounts of carbon monoxide which may result in carbon monoxide poisoning or death.
NOTICE
The guidelines in this section apply to installations within the United States. All U.S. installations must conform to the National Fuel Gas Code, ANSI Z223.1/NFPA 54 (current edition) and local codes.
Before installing the water heater, you must determine the amount of air
needed to supply this water heater and any other gas appliances in the same
area and provide adequate air for combuson and venlaon. Consult a qualified
person if you’re unsure of the proper way to supply air to your water heater.
Check for Chemicals: Air for combuson and venlaon must be clean and free of
corrosive chemicals. If corrosive chemicals, such as sulfur, fluorine, or
chlorine are present, the water heater must be direct vented. Failure due to
these corrosive chemicals is not covered by the warranty.
WARNING! In all cases, ensure that corrosive chemicals are not present at the
air intake. Presence of such chemicals at the air intake could result in
death, personal injury, or property damage. Examples of locaons that require
outside air due to chemicals include:
· Beauty salons
· Photo processing labs
· Indoor pools · Laundry, hobby, or craft rooms · Chemical storage areas
· Restaurants
Products such as aerosol sprays, detergents, bleaches, cleaning solvents,
gasoline, air fresheners, paint and varnish removers, and refrigerants should
not be stored or used near the water heater.
Does your installation space have sufficient combustion air?
Venlaon with outside air is recommended for all installaons. Even if the water
heater is installed in a large, open room inside the house, outdoor air is
usually needed because modern homes are very ghtly sealed and often do not
supply enough air to the water heater. However, when installed in a large
indoor space, it may be possible to provide enough air without outside
venlaon. If you are unsure if your installaon locaon has enough venlaon,
contact your local gas ulity company or code officials for a safety inspecon
or direct vent the water heater The following instrucons will help determine
if it may be possible to install the water heater without outside venlaon.
Calculate total BTU/h rating of all appliances. To calculate the combuson air
and venlaon required, add up the total BTU/h rangs of all gas burning
appliances (e.g., water heaters, furnaces, clothes dryers) in the same area.
Do not include appliances that are direct vented. Refer to the following
example.
17 Page
Installation Manual Installation
Your water heater’s BTU/h rating is on the rating plate. The BTU/h ratings
should be on the other appliances’ rating plates. If you have trouble
determining the BTU/h ratings, contact the manufacturer or have a qualified
person determine the ventilation requirements.
NOTICE: If you are replacing your old water heater with one that has a higher
BTU/h rang, the amount of venlaon required may be greater.
Example:
Gas Burning Appliance
Gas Water Heater Furnace Dryer
BTU/h Rating
199,000 75,000 20,000
Your appliances:
Gas Burning Appliance Gas Water Heater
BTU/h Rating
Total
294,000
Total
Calculate the air volume of the room Air requirements depend on the size of
the room.
Room Volume (ft3) = Floor Area (ft2) X Ceiling Height (ft) If there are large
objects in the room (e.g., refrigerator, furnace, car), subtract their volume
from the volume of the room to get a beer esmate of the air available.
Air Volume = Room Volume – Object Volume
NOTE: Adjoining rooms with permanently opened doorways can be counted as part
of the calculaon.
Calculate required air volume
A water heater installed in an unconfined attic, garage, or space requires
that the space be at least 50 ft3 (1.42 m3) per 1,000 BTU/h of the total input
for all gas burning appliances in the same area.
Required Air Volume (ft3) =Total Appliance Energy Rang (btu/h) X 50 ft3 / 1000
(btu/h) Example:
(294,000 / 1000) x 50 = 14,700 ft3
If the air volume of the room is less than the required air volume, you must
direct vent the water heater or provide permanent outside air openings that
draw in sufficient air. Go to “Install with outside venlaon” if you want to
provide combuson air with outside venlaon.
If the air volume of the room is greater than the required air volume, it may
be possible to install the water heater without outside venlaon. However, be
sure to consider the effects of exhaust fans. Exhaust fans can affect the
amount of combuson air that is available in your home. Appliances such as
furnaces, whole house fans, and clothes dryers draw air out of your home. If
they draw air out faster than it can be replaced, your water heater may not
have enough oxygen to fire properly. Back-drafting may also result, which is
when negave air pressure pulls air backwards through chimneys or appliance
vents. These events can cause unsasfactory water heater performance. The best
soluon is to direct vent the water heater or install an adequate number of
make-up air vents. (See “Install with outside venlaon”.) For more informaon,
consult a qualified technician or your local gas ulity. Install with outside
ventilation
Venlaon with outside air is recommended, and, for most installaons, is needed.
There may be exisng venlaon that is adequate, or you may need to add more
venlaon.
Supplying outside air to the water heater typically requires two openings. One
opening must be within 12 in (305 mm) from the floor and the second opening
must be within 12 in (305 mm) from the ceiling. Although a single opening is
not preferred, you may use a single opening to outside air if the minimum free
area is sized according to Table 1. Two openings must be used when venlang
with air from another room. The outside air can be taken from a crawl space or
attic open to the outdoors and adequately venlated. You may use vercal or
horizontal ducts.
18 Page
Installation Manual Installation
Determine type of ventilation
There are several types of venlaon that can be used. The various opons are
listed below. See also the illustraons on the next page.
1. Direct to outdoors
2. Vercal ducts 3. Horizontal ducts-Single opening (not recommended; must be
at least 100 in2 (645 cm2) . Not appropriate for con-
fined spaces smaller than 50 ft3 (1.42 m3) per 1,000 BTU/h or when getting air
from another room.) 4. From a larger room inside the house (not recommended
refer to “Calculate the air volume of the room” above to
determine if the combined volume of the rooms may be adequate).
Determine minimum free area required for each vent opening
The size of the vent openings depends on the total BTU/h rang of all
appliances in the space (use your calculaon from “Before beginning”) and the
type of vent used. Table 1 provides the minimum free area for each vent
opening depending on the type of venlaon.
Calculate minimum size of vent openings and ducts
The vent cross-seconal area needed to provide the free area depends on the
covering on the vent openings. Typical vents use louvers or grilles to protect
the opening. The louver or grill itself blocks some of the free area, so the
opening may need to be larger to meet the minimum free area requirements. Use
the following formula to calculate the required cross-seconal area:
Cross-seconal area = minimum free area required ÷ percent free area of
covering (in decimals e.g., 60 % = 0.6) For example, an installaon area that
requires openings with 100 in2 (645 cm2) of free area would need 134 in2 (865
cm2) openings if using metal louvers rated at 75% free area (100 in2 ÷ 0.75 =
134 in2). If you do not know the % free area for your louver or grill, use the
following values:
· For wood louvers or grilles: 25% · For metal louvers or grilles: 75% Follow
these rules to ensure that vents and ducts provide adequate air flow: · Each
vent opening must be no smaller than 100 in2 (645 cm2). · Ducts must have the
same cross-seconal area as free area of the opening. · Rectangular ducts must
have a minimum dimension of no less than 3 in (76 mm). · All screens must have
mesh ¼” or larger. · Moveable louvers must be locked open or interconnected
with the equipment so that they open automacally during
operaon. · Keep louvers and grills clean and free of debris or other
obstrucons.
Check that air source is clean and free of chemicals
Air for combuson and venlaon must be clean and free of corrosive or flammable
chemicals. A failure due to corrosive chemicals in the air is not covered by
the warranty. Combuson air must be free of acid-forming chemicals such as
sulfur, fluorine, and chlorine. Be sure that air at the vent inlets is free of
such chemicals.
Table 1
Minimum Free Area of Permanent Openings for Venlaon and Combuson Air Supply Air from outdoor or
indoor spaces.
Based on the total BTU/h input rang for all gas burning appliances within a confined space.
Opening Source
Minimum Free Area
Direct to outdoors*
1 in2 (6.5 cm2) per 4,000 BTU/hr (see Figure 1, 2)
Vercal ducts Horizontal ducts
1 in2 (6.5 cm2) per 4,000 BTU/hr (see Figure 3) 1 in2 (6.5 cm2) per 2,000 BTU/hr (see Figure 4)
Single Opening
1 in2 (6.5 cm2) per 3,000 BTU/hr (see Figure 5)
Two permanent openings to another room**
1 in2 (6.5 cm2) per 1,000 Btu/hr (see Figure 6) Opening: 100 in2 (645 cm2) MIn
Minimum dimension of air openings:
no less than 3 in (76 mm)
*These openings connect directly with the outdoors through a venlated attic, a venlated crawl space, or through
an outside wall.
**For direcon on combining spaces in different stories within the structure, refer to the current edion of the Na-
onal Fuel Gas Code ANSI Z223.1/NFPA 54.
See graphics on next page.
19 Page
Combustion air supply options
X3TM CARTRIDGE NOT SHOWN FOR CLARITY.
Confined Space
Gable vent to outdoors
Install above insulation
Outlet air to attic 1 in2 (6.5 cm2) per 4,000 btu/h
Alternate Air Inlet
Inlet air from the crawl space
1 in2 (6.5 cm2) per 4,000 btu/h
Open foundation vent
Figure 1 – Direct to outdoors openings
Confined Space
Gable vent to outdoors Install above insulation
12″ (305 mm) maximum
Outlet air to attic 1 in2(6.5 cm2) per 4,000 btu/h Inlet air duct 1 in2 (6.5 cm2) per 4,000 btu/h
Figure 3 – Vercal duct openings
Installation Manual Installation
12″ (305 mm) maximum
Two permanent Openings
1 in2 (6.5 cm2) per 4,000 btu/h
Confined Space 12″ (305 mm) maximum
Figure 2 – Direct to outdoors openings Two permanent openings
Confined Space
1 in2 (6.5 cm2) per 2,000 btu/h
Outlet Outdoor Air Ducts
Inlet
1 in2 (6.5 cm2) per 2,000 btu/h
Figure 4 – Horizontal duct openings
CSpoancfiened
Alternative Opening Location
1 in2 (6.5 cm2) per 3,000 btu/h
12″ (305 mm) maximum
Confined Space
Two permanent Openings
1 in2 (6.5 cm2) per 1,000 btu/h
12″ (305 mm) maximum
Figure 5 – Single opening
20 Page
Figure 6 – Two permanent openings
Installation Manual Installation
-Exhaust vent (ABS, PVC, CPVC, or polypropylene vent)-
The indoor models can be vented with schedule 40 PVC (temperature rated up to
149 °F), CPVC, ABS, or polypropylene.
Item
Material
United States
Schedule 40 PVC
ANSI/ASTM D1785
Exhaust pipe and Fittings
PVC-DWV Schedule 40 CPVC Schedule 40 ABS-DWV
ANSI/ASTM D2665 ANSI/ASTM F441 ANSI/ASTM D2661
Polypropylene
UL-1738
PVC
ANSI/ASTM D2564
Pipe Cement/Primer
CPVC
ANSI/ASTM F493
ABS
ANSI/ASTM D2235
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenylsulfone) in non-metallic venting systems is prohibited. Covering non-metallic vent pipe and fittings with thermal insulation is prohibited.
· The maximum length of exhaust vent piping must not exceed 70 ft (21.3 m) for
3 venting, which depends on the elevation where the water heater is installed,
and 100 ft (30.5 m) for 4 venting (deducting 5 ft (1.5 m) for each elbow used
in the venting system). Do not use more than 5 elbows. See the table below.
· When the horizontal vent run exceeds 5 ft (1.5 m), support the vent run at 3
ft (0.9 m) intervals with overhead hangers.
Diameter 3 in 4 in
Max. No. of Elbows Max. Vertical and Horizontal (Total) Vent Length*
5
70 ft (21.3 m)
5
100 ft (30.5 m)
*For each elbow added, deduct 5 ft. (1.5 m) from max. vent length.
No. of Elbows*
0
0 to 3,000 ft (0 to 914 m)
70 ft (21.3 m)
Vertical or Horizontal (Total) Vent Length
3″ venting
3,001 to 6,000 ft (915 to 1,829 m)
6,001 to 10,100 ft (1,830 to 3,078 m)
40 ft (12.2 m)
25 ft (7.6 m)
1
65 ft (19.8 m)
2
60 ft (18.3 m)
35 ft (10.7 m) 30 ft (9.1 m)
20 ft (6.1 m) 15 ft (4.6 m)
3
55 ft (16.8 m)
25 ft (7.6 m)
10 ft (3.0 m)
4
50 ft (15.2 m)
20 ft (6.1 m)
N/A
5
45 ft (13.7 m)
N/A
N/A
Excludes vent terminators, one termination elbow, or rain caps. For details on the vent connection, refer to pages 22 to 24. *For each elbow added, deduct 5 ft (1.5 m) from max. vent length.
21 Page
4″ venting 0 to 10,100 ft (0 to 3,078 m) 100 ft (30.5 m)
95 ft (29.0 m)
90 ft (27.4 m)
85 ft (25.9 m)
80 ft (24.4 m)
75 ft (22.9 m)
Installation Manual Installation
-DIP switch settings for vent length-
Typical installations using PVC, CPVC, ABS, or polypropylene vent
·
· WARNING ·
Adjust the appropriate DIP switches according to model and vent length as shown below. DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning or death.
3 inch & 4 inch vent installation
X3TM CARTRIDGE NOT SHOWN.
Two-pipe, direct-vent installation
Horizontal Installation
Wall
Hanger
Vertical Installation
Roof
Hanger
Roof flashing
Fire stop
Connect between exhaust vent collar and piping. See the instrucons on the next
page.
For details on the vent components, refer to the vent manufacturer’s
instructions.
Single-pipe with room-air intake installation
Horizontal Installation
Vertical Installation
Hanger Wall
Roof
Roof flashing
Elbow
Elbow
Fire stop Connect between exhaust vent collar and piping. See the instrucons
on the next page.
For details on the vent components, refer to the vent manufacturer’s
instructions.
22 Page
Installation Manual Installation
·
· WARNING ·
Adjust the appropriate DIP switches according to model and vent length as shown in the following. DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning or death.
240HX3/340HX3
540HX3
Upper bank of DIP switches
Bank of DIP switches
Lower bank of DIP switches
Set DIP switches shown in the table below depending on the vent diameter, the installation, and the vent length.
Vent diameter & Installation
3 venting* 4 venting
Two-pipe, Direct vent
Single vent Two-pipe, Direct vent &
Single vent
240HX3/340HX3 Indoor
5 to 20 ft (1.5 to 6.1 m) (DEFAULT)
5 to 45 ft (1.5 to 13.7 m) (DEFAULT)
5 to 50 ft (1.5 to 15.2 m) (DEFAULT)
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 6 : O N No. 7 : OFF
Vent length
21 to 40 ft (6.2 to 12.2 m) 46 to 70 ft (13.8 to 21.3 m)
51 to 100 ft (15.3 to 30.5 m)
ON 1 2 3 4 5 6 7 8 9 10 OFF
No. 6 : OFF No. 7 : OFF
41 to 70 ft (12.3 to 21.3 m)
ON 1 2 3 4 5 6 7 8 9 10 OFF
No. 6 : O N No. 7 : O N
540HX3 Indoor (Upper bank of DIP switches)
ON 1 2 3 4 5 6 7 8
OFF
No. 3 : O N No. 4 : OFF
ON 1 2 3 4 5 6 7 8
OFF
No. 3 : OFF No. 4 : OFF
ON 1 2 3 4 5 6 7 8
OFF
No. 3 : O N No. 4 : O N
*PVC concentric termination (100112163) installation is applied to the DIP switch settings of 3″ venting. (Refer to page 10.)
3″ vent connection for PVC/CPVC venting only
3″ straight pipe
Intake vent collar with 3″ adapter (Female)
3″ straight pipe
Exhaust vent collar with 3″ adapter (Female)
· PVC adapter will accept 3″ straight pipe.
3″ street elbow with bird screen
3″ straight pipe
Intake vent collar with 3″ adapter (Female)
Exhaust vent collar with 3″ adapter (Female)
1. Connect spigot end of 3″ street elbow into the intake vent collar with 3″
adapter. Be sure to insert bird screen into the hub side.
2. Connect 3″ straight pipe into the exhaust vent collar with 3″ adapter.
23 Page
4″ vent connection for PVC/CPVC venting only
Installation Manual Installation
4″straight pipe
4″ straight pipe
3″ x 4″ increaser
3″straight pipe no more than 12″ (305 mm)
Intake vent collar with 3″ adapter (Female)
3″ x 4″ increaser
3″ straight pipe no more than 12″ (305 mm)
Exhaust vent collar with 3″ adapter (Female)
1. Insert no more than 12″ (305 mm) of 3″ straight pipe into the
exhaust/intake vent collar with 3″ adapter.
2. Connect 3″ x 4″ increasers to straight pipes. 3. Connect 4″ straight pipes
to the increasers.
4″ straight pipe
3″ x 4″ increaser
3″ street elbow with bird screen
3″ straight pipe no more than 12″ (305 mm)
Intake vent collar with 3″ adapter (Female)
Exhaust vent collar with 3″ adapter (Female)
1. Insert no more than 12″ (305 mm) of 3″ straight
pipe into the exhaust vent collar with 3″ adapter.
2. Connect a 3″ x 4″ increaser into the 3″ straight
pipe.
3. Connect 4″ straight pipe into the increaser.
4. Connect spigot end of 3″ street elbow into the
intake vent collar with 3″ adapter. Be sure to
insert bird screen into the hub side.
<How to remove 3″ PVC adapter from the intake/exhaust collar>
*Remove the 3″ adapter when using vent material other than PVC or CPVC.
3″ adapter*
Intake vent collar (Female)
Screws
3″ adapter*
Exhaust vent collar (Female)
1. Remove each screw from 3″ adapter to detach the adapters from each vent collar.
POLYPROPYLENE VENTING
WARNING! Do not mix parts or fittings of different material types, and do not
mix pipe, fittings, or joining methods from different manufacturers.
Combustion exhaust can contain carbon monoxide and must be properly vented
outside. Breathing abnormal amounts of carbon monoxide can result in serious
injury or death.
Centrotherm Innoflue polypropylene venting is approved for use with these water heaters. Follow the instructions in this manual and in the vent manufacturer’s instructions when installing vent pipe.
Description
4”/6” x 39″ (990 mm) Concentric Wall 101 mm to 3″ Adapter
Centrotherm Part No. (Trade Name
InnoFlue)
ICWS4639
ISA010103
Description
3”/5” x 13” (330 mm) Concentric Wall Termination SS
3″ Twin Pipe to 3″/5″ Concentric Adapter
Centrotherm Part No. (Trade Name
InnoFlue)
ICWS3513
ICTC0335
101 mm to 4″ Adapter
ISA010104
24 Page
Installation Manual Installation
-Exhaust vent (Stainless steel vent)-
This is a Category IV appliance and must be vented accordingly. The vent
system must be sealed airtight. All seams and joints without gaskets must be
sealed with high heat resistant silicone sealant or UL listed aluminum
adhesive tape having a minimum temperature rating of 160 °F (71 °C). For best
results, a vent system should be as short and straight as possible.
· The Indoor models are a Category IV appliance and must be vented accordingly
with any 4 vent approved for use with Category III/IV or Special BH type gas
vent.
· The manufacturer recommends the NovaVent® or Z-Vent® venting manufactured by
Z-Flex® U.S. and are listed to UL 1738.
· Follow the vent pipe manufacturer’s instructions when installing the vent
pipe. · The maximum length of exhaust vent piping must not exceed 100 ft (30.5
m) (deducting 5 ft (1.5 m) for
each elbow used in the venting system). Do not use more than 5 elbows. · When
the horizontal vent run exceeds 5 ft (1.5 m), support the vent run at 3 ft
(0.9 m) intervals with over-
head hangers.
Diameter Max. No. of Elbows Max. Vertical and Horizontal (Total) Vent Length*
4 in
5
100 ft (30.5 m )
*For each elbow added, deduct 5 ft. (1.5 m) from max. vent length.
No. of Elbows Max. Vertical or Horizontal Vent Length No. of Elbows Max. Vertical or Horizontal Vent Length
0
100 ft (30.5 m)
3
85 ft (25.9 m)
1
95 ft (29.0 m)
4
80 ft (24.4 m)
2
90 ft (27.4 m)
5
75 ft (22.9 m)
Excludes vent terminators, termination elbows, or rain caps.
-DIP switch settings for vent length-
Typical installations using stainless steel vents
·
· WARNING ·
Adjust the appropriate DIP switches according to model and vent length as shown below. DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning or death.
Horizontal Installation
Wall Hanger
Vertical Installation
Rain cap Roof
Hanger
Roof flashing
Fire stop
Sidewall vent terminaon
For details of the optional items, refer to the Installation manual for each
optional item. X3TM CARTRIDGE NOT SHOWN.
25 Page
Installation Manual Installation
DIP switch settings : Single pipe and Direct vent installations / Vent diameter : 4″ venting
240HX3/340HX3 Indoor
540HX3 Indoor (Upper bank of DIP switches)
5 to 50 ft (1.5 to 15.2 m) (DEFAULT)
ON 1 2 3 4 5 6 7 8 9 10
OFF
No. 6 : O N No. 7 : OFF
Vent length 51 to 100 ft (15.3 to 30.5 m) 5 to 50 ft (1.5 to 15.2 m)
(DEFAULT)
ON 1 2 3 4 5 6 7 8 9 10
ON 1 2 3 4 5 6 7 8
OFF
OFF
No. 6 : OFF No. 7 : OFF
No. 3 : O N No. 4 : OFF
51 to 100 ft (15.3 to 30.5 m)
ON 1 2 3 4 5 6 7 8 OFF
No. 3 : OFF No. 4 : OFF
<How to remove 3″ PVC adapter from the intake/exhaust collar>
*Remove the 3″ adapter when using metal vent.
3″ adapter*
3″ adapter*
Intake vent collar
(Female)
Screw
4″ vent connection for direct-vent installation
Exhaust vent collar (Female)
4″ stainless steel vent straight pipe or appliance adapter
Intake vent collar (Female)
4″ stainless steel vent straight pipe or appliance adapter
Exhaust vent collar of the Indoor models (Female)
· Connect 4″ stainless steel vent straight pipes or appliance adapters to the exhaust/intake vent collar.
4″ vent connection for single vent installation
4″ elbow with bird screen
Intake vent collar (Female)
4″ stainless steel vent straight pipe or appliance adapter
Exhaust vent collar of the Indoor models (Female)
1. Connect a 4″ stainless steel vent pipe or appliance adapter to the exhaust
vent collar.
2. Connect a 4″ elbow to the intake vent collar.
· Follow the clearances listed on pages 14-16 when installing the vent and air
intake terminations.
· Follow the vent manufacturer’s installation instructions and clearance
requirements. WARNING · Use 4″ Category III/IV approved or Special BH, single
or double wall stainless steel vent pipe.
· Do not mix parts or fittings of different material types, and do not mix
pipe, fittings, or joining methods from different manufacturers. Combustion
exhaust can contain carbon monoxide and must be properly vented outside.
Breathing abnormal amounts of carbon monoxide can result in serious injury or
death.
26 Page
Installation Manual Installation
Approved Category IV, Single Wall, Venting Suppliers and Part Numbers
Description
Heater Vent Kits
Z-FLEX®
Nova VENT®
Z-VENT®
4″ Adjustable straight pipe – 10″-18″ (254 – 457 mm) adjustability
100112405 2NVAL4
2SVSPA04
4″ Sidewall termination (4″ Termination Hood)
100112419 2NVTH4
2SVSHTX04
4″ Vent termination tee
100112547 2NVTT4
2SVSTTF04
4″ Rain Cap
100112415 2NVRC4
2SVSRCF04
4″ Extreme weather rain cap
4″ 3-in-1 adapter (F-F adapter, condensate drain, & back-flow preventer)
4″ F-F adapter
100112548 2NVWC4 2SVSHRC04 100112549 2NVBFA4 2SVBFDPA04 100112399 2NVAFF4 2SVEEWCF0445
4″ Backflow preventer w/ F-F adapter
100112416 2NVBFU4
4″ exhaust/3″ intake DV concentric termination – 5″-10″ (127 – 254 mm)
adjustability
4″ exhaust/3″ intake DV concentric termination – 12″-18″ (305 – 457 mm)
adjustability
100112550 100112551
2NVHTC43S 2NVHTC43
4″ Sidewall termination, adjustable pipe
100187853 2NVBV4
4″ exhaust/3″ intake concentric termination – 5″ to 10″ (127 – 254 mm)
adjustability
4″ exhaust/3″ intake concentric termination – 12″ to 18″ (305 – 457 mm)
adjustability
4″ exhaust / 4″ intake concentric termination – 5″ to 10″ (127 – 254 mm)
adjustability
4″ exhaust/4″ intake concentric termination – 12″ to 18″ (305 – 457 mm)
adjustability
100112550 2NVHTC43S 100112551 2NVHTC43 100112552 2NVHTC44S 100112553 2NVHTC44S
2ZVB04 2SVSHTC43S 2SVSHTC43
n/a 2SVSHTC43S 2SVSHTC43 2SVSHTC04S 2SVSHTC04
NOTICE
Refer to heater manufacturer literature/website and the vent manufacturer for available components.
27 Page
Installation Manual Installation
-Common-venting system-
The Indoor model can be vented together using the same exhaust and intake
venting. · The 240HX3/340HX3/540HX3 models do not have Easy-Link or Multi-Unit
capability. · Up to 8 water heaters can be common-vented together. · A non-
return valve (100113130) must be used for each water heater that is part of
the system. · The water heaters must all be direct-vented. · The common-
venting system shall be in accordance with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 (Current Editions), local codes, and the venting manufacturer’s
instructions. · For common-venting pieces and components, the manufacturer
recommends Centrotherm’s vent line.
Allowable Indoor models for common-venting
240HX3, 340HX3, 540HX3, 240H, 340H, 540H, 540P, CT-199
Only the models listed in the table above can be common-vented together. Other models cannot be common-vented. WARNING Failure to observe these warnings could lead to carbon monoxide poisoning or death.
Typical common-vent installation examples
Roof
Exhaust
Roof
Condensate drain port
Intake wall
Condensate drain port
Exhaust
Intake
Roof
Non-Return Valve
Exhaust
Non-Return Valve
wall
Condensate drain port
Non-Return Valve
Intake
NOTICE
For details on the installation of a common-vent system, please refer to “Common Venting Tankless Gas Water Heaters.” It is a manual which is available on the water heater manufacturer’s website.
X3TM CARTRIDGE NOT SHOWN. wall
28 Page
Installation Manual Installation
To determine the dimension of a common-venting system
Determine the vent diameter (D) and the total vent length based on the number of water heaters installed. The total vent length (L) consists of the horizontal width (W) and the vercal height (H). See the table below.
· Total vent length (L)=”H”+”W”+
(Number of Elbows X 5)
· Vent diameter=”D”
NOTICE
· Regarding the clearances
between the exhaust terminaon and the intake terminaon, refer to pages 14 to
16.
· Insert bird screen in elbow
terminations.
Elbow terminal Exhaust
Elbow terminal
“H”
Intake
“D” “W”
X3TM CARTRIDGE NOT SHOWN.
Non-Return Valve
WARNING
· A Non-Return Valve must be installed for each water heater. This prevents
the escape of combustion gas through non-operating appliances.
· For detailed instructions on the common-venting system, refer to the
instructions that are packaged with the vent parts or web site.
Common-venting system
Vent Diameter*
(D)
4 in
Max. No. of water heaters
2
Max. Vertical and Horizontal
(Total) Vent Length** (L)
25 ft (7.6 m)
DIP switch settings
WARNING
2 5 in
3
2
3
6 in
4
5
6
3
4
5 8 in
6
7
8
5
50 ft (15.2 m) 20 ft (6.1 m) 100 ft (30.5 m) 75 ft (22.9 m) 50 ft (15.2 m 25 ft (7.6 m) 20 ft (6.1 m) 100 ft (30.5 m) 100 ft (30.5 m) 85 ft (25.9 m) 65 ft (19.8 m) 50 ft (15.2 m) 41 ft (12.5 m) 100 ft (30.5 m)
240HX3/340HX3 Indoor
ON 1 2 3 4 5 6 7 8 9 10 OFF
No. 6 : ON / No. 7: OFF
540HX3 Indoor (Upper bank of DIP switches)
ON 1 2 3 4 5 6 7 8 OFF
No. 3 : ON / No. 4: OFF
· Adjust the appropriate DIP switches according to model as shown in the left
table. DO NOT adjust the other DIP switches. (Refer to page 23 for the
location of the DIP switches.)
· Turn off the power supply to the water heater before changing the DIP switch
settings.
· Failure to observe these warnings could lead to carbon monoxide poisoning or
death.
6 10 in
7
100 ft (30.5 m) 100 ft (30.5 m)
8
100 ft (30.5 m)
*Diameters of pipes are in accordance with Centrotherm’s specifications. **One elbow is equivalent to 5 ft (1.5 m) linear length, and the maximum number of elbows is 5.
29 Page
GAS SUPPLY AND GAS PIPE SIZING
-General-
Installation Manual Installation
· Do not use this water heater with any gas other than the one listed on the
rating plate. · Ensure that any and all gas regulators used are operating
properly and providing gas
pressures within the specified range shown below. Excess gas inlet pressure
may cause WARNING serious accidents.
· Conversion of this unit from natural gas to propane or vice versa will void
all warranty. Contact your local distributor to get the correct unit for your
gas type. The manufacturer is not liable for any property and/or personal
damage resulting from gas conversions.
· Failure to observe these warnings could result in severe personal injury,
carbon monoxide poisoning, or death.
· The minimum and maximum inlet gas pressures are:
Gas type
Inlet gas pressure
Natural Gas Min. 4.0″ W.C. (1.00 kPa) Max. 10.5″ W.C. (2.61 kPa)
Propane
Min. 8.0″ W.C. (1.99 kPa) Max. 13.0″ W.C. (3.23 kPa)
· Inlet gas pressures that fall outside the range of values listed above may
adversely affect the performance of the water heater. These pressures are
measured when the water heater is in full operation and in standby.
· Inlet gas pressure must not exceed the above maximum values; gas pressure
above the specified range will cause dangerous operating conditions and damage
to the unit.
· Until testing of the main gas line supply pressure is completed, ensure the
gas line to the water heater is disconnected to avoid any damage to the water
heater.
· If the gas supply pressure to the heater is greater than the specified
maximum, a field-supplied regulator is required. The regulator must lower the
gas pressure within the approved range.
· Install the gas regulator according to the manufacturer’s instructions. ·
The regulator must be sized for the water heater input and provide the
specified pressures that are listed on
the rating plate. · In the absence of minimum install distance stated by the
regulator manufacturer, it is recommended that
there is at least 3 ft (1 m) of piping between the regulator outlet and the
water heater’s inlet gas connection.
-Gas connections-
1. Install a manual gas shutoff valve between the water heater and the gas
supply line. 2. When the gas connections are completed, it is necessary to
perform a gas leak test either by applying soapy
water to all gas fittings and observing for bubbles or by using a gas leak
detection device. · The water heater and its individual shutoff valve must be
disconnected from the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2 psi (3.5 kPa). · The water
heater must be isolated from the gas supply piping system by closing its
individual manual shutoff valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
3. Always purge the gas line of any debris and/or water before connecting to
the gas inlet.
NOTICE
Size the gas pipe appropriately to supply the necessary volume of gas required for the water heater using ANSI Z223.1/NFPA 54. Otherwise, flow capabilities and output temperatures will be limited.
30 Page
Installation Manual Installation
-Natural gas supply piping-
Maximum delivery Capacity in Cubic Feet of Gas per Hour (based on IPS Pipe carrying Natural Gas with 0.60
Specific Gravity with a Pressure Drop of 0.5″ W.C.).
Based on Energy Content of 1,000 BTU/Cubic ft: The water heater requires 160 Cubic ft/hr for the 240HX3 model, 180
Cubic ft/hr for the 340HX3 model, and 199 Cubic ft/hr for the 540HX3 model.
The following tables are from NFPA 54.
Unit: Cubic feet per hour
Pipe Size
Length
Diameter
10′ (3 .0 m)
20′ (6.1 m)
30′ (9.1 m)
40′ (12.2 m)
50′ (15.2 m)
60′ (18.3 m)
70′ (21.3 m)
80′ (24.4 m)
90′ (27.4 m)
100′ (30.5 m)
125′ (38.1 m)
150′ (45.7 m)
200′ (61.0 m)
1/2″ 172 118 95
81
72
65
60
56
52
50
44
40
34
3/4″ 360 247 199 170 151 137 126 117 110 104 92
83
71
1″
678 466 374 320 284 257 237 220 207 195 173 157 134
1-1/4″ 1,390 957 768 657 583 528 486 452 424 400 355 322 275
1-1/2″ 2,090 1,430 1,150 985 873 791 728 677 635 600 532 482 412
2″ 4,020 2,760 2,220 1,900 1,680 1,520 1,400 1,300 1,220 1,160 1,020 928 794
-Propane (LP) supply piping-
Maximum Capacity of Propane (LP) Based on 11″ W.C. supply pressure at a 0.5″ W.C. pressure drop
Unit: kBTU per hour
Pipe Size
Length
Diameter
10′
20′
(3 .0 m) (6.1 m)
30′ (9.1 m)
40′
50′
60′
70′
80′
90′ 100′ 125′ 150′ 200′
(12.2 m) (15.2 m) (18.3 m) (21.3 m) (24.4 m) (27.4 m) (30.5 m) (38.1 m) (45.7 m) (61.0 m)
1/2″ 268 184 148 126 112 101 93
87
82
77
68
62
53
3/4″ 567 393 315 267 237 217 196 185 173 162 146 132 112
1″ 1,071 732 590 504 448 409 378 346 322 307 275 252 213
1-1/4″ 2,205 1,496 1,212 1,039 913 834 771 724 677 630 567 511 440
1-1/2″ 3,307 2,299 1,858 1,559 1,417 1,275 1,181 1,086 1,023 976 866 787 675
2″ 6,221 4,331 3,465 2,992 2,646 2,394 2,205 2,047 1,921 1,811 1,606 1,496 1,260
Gas sizing example (Natural Gas)
Water heater 199,000 BTU/h
Dryer 35,000 BTU/h
5′ (1.5 m)Length 1-1/4″ Pipe size
A
5′ (1.5 m) Length 1-1/4″ Pipe size
10′ (3 m)Length
3/4″ Pipe size
15′ (4.6 m)Length 1″ Pipe size
B
10′ (3 m)Length 1/2″ Pipe size
10′ (3 m )Length 10′(3 m)Length 1″ Pipe size 3/4″ Pipe size
15′ (4.6 m)Length 1/2″ Pipe size
C
Gas meter
Furnace 120,000 BTU/h
Range 65,000 BTU/h
Based on Energy Content of 1,000 BTU/Cubic ft: Divide each appliance’s BTU/h requirement by 1,000 BTU/ft3 to get the appliance’s ft3/h requirement. Take into account the distance the appliance is from the gas meter, then look in the above gas chart to properly size the line. For sections of the gas line supplying gas to more than one appliance (Ex: Point A to Point B), add up the cubic ft per hour requirements of the appliances that are being supplied by that section, and size to the farthest appliance. For Example: The section from A to B supplies gas to the furnace, range and dryer. Adding up the BTU/h requirements and dividing by 1,000 yields a cubic ft per hour requirement of 220 cubic ft of gas per hour. The farthest appliance is the range, which is 50 ft away from the meter. Looking at the above chart, and under the column of 50 ft, Section A to B needs to be 1″ in order to supply 220 cubic ft.
31 Page
WATER CONNECTIONS
Installation Manual Installation
Do not use this appliance if any part has been under water. Immediately
contact a qualified installer or service agency to replace a flooded water
heater. Do not attempt to repair the unit! It must be replaced! WARNING
NOTICE Do not reverse the hot outlet and cold inlet connections to the water
heater. If you reverse the connections, the water heater will not activate
properly.
All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for potable water systems.
1. A manual shutoff valve must be installed on the cold water inlet to
the water heater between the main water supply line and the water
heater.
2. In addion, a manual shutoff valve is also recommended on the hot
water outlet of the unit.
Pressure relief valve
3. If the water heater is installed within, or subjected to, a closed loop
water system, a thermal expansion tank or code approved device to
handle thermal expansion must be installed. NOTE: If the plumbing system is subject to water hammer, then it is
Hot outlet
Cold inlet
Gas inlet
recommended that water hammer arrestors be installed.
4. Before installing the water heater, flush the water line to remove all debris, and after installaon is complete,
purge the air from the line. Failure to do so may cause damage to the heater.
5. There is a wire mesh filter within the cold inlet to trap debris from entering your heater. This will need to be
cleaned periodically to maintain opmum flow. (Refer to page 49.)
-Pressure relief valve-
The water heater has a high-temperature shutoff switch built in as a standard
safety feature (called a Hi-Limit switch) therefore a “pressure only” relief
valve is required. · An approved pressure relief valve is supplied with your
water heater and must be installed on the outlet
connection. NOTE: When an isolation valve kit that includes a pressure relief
valve is installed on the water heater, use the provided ¾” male NPT plug to
close the pressure relief port on the outlet connection. · The discharge
piping for the pressure relief valve must be directed so that the hot water
cannot splash outward and cause damage or personal injury. · Attach the
discharge tube to the pressure relief valve and run the end of the tube to
within 6 in (152 mm) from the floor. This discharge tube must allow free and
complete drainage without any restrictions. WARNING! Do Not plug the pressure
relief valve. · If the pressure relief valve discharges periodically, this may
be due to thermal expansion in a closed water supply system. Contact the water
supplier or a local plumbing professional on how to correct this situation. ·
The pressure relief valve must be manually operated periodically to check for
correct operation. Before operating the valve manually, check that it will
discharge in a place for secure disposal. · No valve must be placed between
the relief valve and the water heater.
If another pressure relief valve is used or needs to be replaced, it must meet
the following: · The pressure relief valve must conform to ANSI Z21.22 · CSA
4.4 and installation must follow local codes, · The discharge capacity must be
at least 160,000 BTU/h for the 240HX3 model, 180,000 BTU/h for the
340HX3 model, and 199,000 BTU/h for the 540HX3 model, · The pressure relief
valve needs to be rated for a maximum of 150 psi (1 MPa).
32 Page
Installation Manual Installation
Hot water could be released when the pressure relief valve is opened. This
could result in severe personal injury. Before operating the pressure relief
valve manually, check that it will discharge in a safe place. If water does
not flow freely from the end WARNING of the discharge pipe, turn the gas
supply and power OFF and call a qualified person to determine the cause. Refer
to the pressure relief valve manufacturer’s instructions for inspection and
maintenance requirements.
-X3TM Scale Prevention Technology-
This water heater is equipped with X3TM Scale Prevention Technology to inhibit
scale formation within the heat exchanger tubing of this unit. Part of the
X3TM Technology’s anti-scale protection comes from the special X3TM Cartridge
media. The X3TM Cartridge must be installed into the manifold located on the
underside of the heater cabinet prior to operation of the unit (shown as
follows). The X3TM system is designed to be hassle-free; eliminating the need
to drain the heater for installation, removal, or replacement of the
cartridge. X3TM Scale Prevention Technology reduces the formation of scale in
the heat exchanger, extending the operating life of the unit in typical
potable water installations. Specific water conditions may impact the
efficiency of X3TM, such as excessive iron (>0.3 mg/l). Consult a water
quality expert to determine if your water is within acceptable X3TM and EPA
guidelines. X3TM Technology Installation/Removal Installation 1. Align the
symbol with the symbol and insert the X3TM Cartridge into the X3TM manifold 2.
Turn it right until the symbol aligns with the symbol. Removal 1. Close the
shutoff valve on the cold water supply. 2. Turn off the power supply. 3. Open
a hot water fixture to relieve water pressure in the heater. 4. If a drain pan
is not installed, place a bucket or pan underneath the X3TM Cartridge as some
water may be
present when removing. 5. Turn the X3TM Cartridge left until the symbol aligns
with the symbol. 6. Pull down to remove it from the water heater. It is normal
for a small amount of water to drip. NOTE: the
cartridge will be full of water. Take care to not tilt it till you can drain
the water.
INSTALLATION
REMOVAL
33 Page
CONDENSATE DRAIN
Installation Manual Installation
This high efficiency water heater produces acidic condensate that must be
properly drained per local codes. The water heater does not have a built-in
neutralizer to raise the pH level. A neutralizer is available from the water
heater manufacturer, if needed. Follow the instrucons in this secon in order
to install the condensate drain line.
· All preventave measures and safety pracces must be adhered to when draining
condensate. The manufacturer will not be responsible for any damage caused by
condensate.
· A drain pan, or other means of protecon against water damage, is recommended
to be installed under the water heater in case of leaks.
· Discharge condensate (acidic water) in accordance with all local codes and
common safety pracces. In the absence of applicable local codes and regulaons,
the manufacturer recommends that a condensate neutralizer is installed and
dispose the condensate into a drain. See picture on page 35.
· Use corrosion resistant pipe, such as PVC, for the condensate drain line. Do
not use metallic pipe.
· The condensate drain does not require a trap.
· A field-supplied bypass is required if a neutralizer is installed. · The
condensate drain is at atmospheric pressure (non-pressurized) and therefore
must be allowed to drain
freely with gravity only. Ensure that the condensate drain tube is not
plugged, blocked, or kinked. Ensure that it slopes downward to allow
condensate to flow freely. All porons of the condensate drain (neutralizer and
drain tube) must be at a lower elevaon than the water heater to prevent
condensate water from building up inside the heat exchanger.
· Do not connect the condensate drain line directly to a condensate pump.
The condensate drain system must be inspected regularly to make sure it drains
properly and in accordance with local codes or the part manufacturer’s
instrucons.
· Condensate cannot be effecvely neutralized if the neutralizer elements
inside the Neutralizer accessory have been completely consumed. If this
happens, condensate will remain acidic and can possibly cause damage to items
such as pipes, concrete, etc.
· The actual life of the neutralizer may vary, depending on the applicaon and
usage. Replace the cartridge when the condensate pH goes below 6.0. This can
be tested using litmus pH test strips.
· Please ensure that the cartridge is properly replaced before the neutralizer
elements have been completely consumed.
34 Page
Installation without neutralizer
Installation Manual InstallationInstallation with neutralizer
X3TM CARTRIDGE NOT SHOWN FOR CLARITY.
1/2″ Condensate drain tube*
1/2″ MPT Condensate connection
1/2″ Condensate drain tube*
Overflow bypass* (1/2″ Condensate
drain tube)
1/2″ MPT Condensate connection
1/2″ Condensate drain tube
1/2″ MPT x 3/8″ FPT (Included with Neutralizer accessory) Neutralizer
cartridge (Included with Neutralizer accessory)
1/2″ FPT x 1/2″ HB (Included with Neutralizer accessory)
1/2″ Condensate drain tube
2″ (50 mm) MIN. distance**
2″ (50 mm) MIN. distance**
Floor drain, standpipe, pump, or other acceptable drain
2″ (50 mm) MIN. distance**
Floor drain, standpipe, pump, or other acceptable drain
*Maintain downward slope, including installations in which the drain is not directly below the heater. **A 2″ (50 mm) minimum distance must be maintained between the condensate line and drain to allow full flow of the condensation.
35 Page
ELECTRICAL CONNECTIONS
Installation Manual Installation
· Ensure that circuit power is turned OFF before you complete the following steps.
· Follow the electrical code requirements of the local authority having jurisdiction. In the
absence of such requirements, follow the current edition of the National Electrical Code
WARNING
ANSI/NFPA 70.
· When servicing or replacing parts within the water heater, label all wires prior to dis-
connection to facilitate an easy and error-free reconnection. Wiring errors can cause
improper and dangerous operation. Verify proper operation after servicing.
· Failure to observe these warnings could result in personal injury or loss of life.
Indoor model comes with a power plug instead of a junction box. The following
procedure is for the outdoor model only.
1. The water heater must be electrically grounded. Do not attach the ground
wire to either the gas or the water piping.
2. The water heater requires a 120 VAC, 60 Hz electrical power supply that is
properly grounded. · A proper disconnect (i.e. on/off switch, power plug,
etc.) controlling the main power to the water heater must be provided for
service reasons. (Must comply with local codes.) · Connect the power supply to
the water heater exactly as shown in the wiring diagram.
3. A green screw is provided in the junction box to ground the connection. 4.
The water heater can be hardwired or wired to a plug-in. 5. The use of a surge
protector is recommended in order to protect the water heater from power
surges.
Outdoor
Ground
Green screw
Connect Power supply 120VAC, 60Hz
Boom view of water heater
View of electrical connecons in the juncon box
36 Page
Installation Manual Installation
TEMPERATURE REMOTE CONTROLLER
-Included accessories-Outdoor models only
· The remote control is an optional accessory that can be installed in a hall,
closet, etc., to allow for temperature adjustment without having to go to the
heater.
· When installed, the remote will take priority over the built-in controller
of indoor models.
Verify that the items listed below are included with the remote controller.
Temperature remote controller
Screws
Fork terminals
Manual
Remote controller cable*
Qty: 1
Qty: 2
Qty: 4
Qty: 1
Qty: 1
100209924 (TM-RE42) It is also an optional accessory as a second remote for the indoor models. Refer to pages 9 and 10. *The optional remote controller (sold separately) has no remote controller cable.
-Installation-
WARNING
· This remote controller is NOT waterproof. · The water heater can only have
one remote controller. · Do not install in high temperature environments, high
humidity conditions outdoors, in direct
sunlight, or within the reach of children. · Make sure the remote controller
does not come into contact with water or oil. · Failure to observe these
warnings could result in personal injury or electrical shock.
NOTICE
· Do not place the remote controller cable close to other wires from other
products.
· Cables used for the remote controller connection must be: · Minimum 20 gauge
wire (No polarity) · Maximum 400 ft (122 m) long
Fig. A
Press and twist flat head screwdriver against the cutout.
Fig. B
Back plate
Twist
Main body
Attach the screws
3-1/4 inches
Main body
Fig. C
1-3/8 Inch (35 mm)
1-5/8 Inch (41 mm) Remote controller cable
Fork Terminals
37 Page
Cut out the partition with pliers. (removed during later steps.)
4. Tighten the two Fork terminals beneath the two Remote controller terminal
screws on the back of the main body. (Fig. D-1)
5. Cut out the inlet for the remote controller cable from the bottom of the
main body. (Fig. D-2)
6. Place the Main body back on the Back plate, with the Remote controller
cable running out of the bottom inlet.
Fig. D-2
Installation Manual Installation
Fig. D-1
Remote controller terminals
Inlet for the remote controller cable
Cut out
Two fork terminals Remote controller cable
Fig. E-1
240HX3 340HX3
100209924 (TM-RE42)
Connect other end to these terminals
Fig. E-2 540HX3
100209924 (TM-RE42)
Connect other end to these terminals
38 Page
Installation Manual Applications
APPLICATIONS
Below are suggested piping diagrams for a standard installation and one with
the use of a crossover valve. These diagrams are just a suggestion. Check with
local codes and ordinances for additional installation requirements. Refer to
the water heater manufacturer’s website for additional layouts. Thermostatic
mixing valves may be used with tankless water heaters. Consult with the mixing
valve manufacturer for the appropriate mixing valve for the application. To
reduce the risk of scalding, install Thermostatic Mixing Valves (temperature
limiting valves) at each point of use. These models are suitable for (potable)
water heating only. Installation with a dedicated return line is not approved
by the manufacturer. These models do not have Easy-Link or Multi-Unit
capability.
-Standard installation-
-Recirculation with cross over valve-
AIR VENT
COLD WATER SUPPLY
Y-STRAINER
HOT WATER TO FIXTURES
GAS
COLD WATER SUPPLY
LEGEND
TEMPERATURE & PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE
DRAIN
BALL VALVE
CIRCULATION PUMP
CHECK VALVE COLD
HOT BUILDING RETURN GAS
GAS
EXPANSION TANK
CROSS OVER VALVE
This installation is approved with the use of a crossover valve that maintain
water temperature at the valve below 110°F, such as the APCOM® Bypass Valve
for Tankless Water Heaters, model TBPV (kit 100327167). The cross over valve
does not come with the water heater.
NOTICE
· The water heater is suitable for water (potable) heating only and is not
available for recirculation system.
· The 240HX3/340HX3/540HX3 models do not have Easy-Link or Multi-Unit
capability.
39 Page
INITIAL OPERATION
Installation Manual Initial operation
FOR YOUR SAFETY, READ BEFORE OPERATING
· Check the GAS and WATER CONNECTIONS for leaks before firing unit for the
first time. · Open the main gas supply valve to the unit using only your hand
to avoid any spark. Never use tools. If
the knob will not turn by hand, do not try to force it; call a qualified
service technician. Forced repair may result in a fire or explosion due to gas
leaks. · Be sure to check for the presence of leaking gas toward the bottom of
the unit because some gases are heavier than air and may settle towards the
floor. · Check the GAS PRESSURE. Refer to pages 30 and 51. · Do not try to
light the burner manually. It is equipped with an electronic ignition device
which automatically lights the burner. · Check for PROPER VENTING and
COMBUSTION AIR to the water heater. · Purge the GAS and WATER LINES to remove
any air pockets. · Do not use this appliance if any part has been under water.
Immediately contact a qualified installer or service agency to replace a
flooded water heater. Do not attempt to repair the unit! It must be replaced!
WARNING
IF YOU SMELL GAS: · Do not try to start the water heater. · Do not touch any
electric switches; do not use any phone in your building. · Immediately call
your gas supplier from a neighbor’s phone. Follow the gas supplier’s
instructions. · If you cannot reach your gas supplier, call the fire
department. · Failure to observe these warnings could lead to fire or an
explosion, resulting in severe
injury or death.
Operation
Once the above checks have been completed, please clean filter of any debris. Refer to page 49 for instructions.
2. Fully open the manual water control valve on the water supply line.
Open a hot water tap to verify that water is flowing to that tap, then close the hot water tap.
4. Fully open the manual gas control valve installed.
5. Turn on the 120 VAC, 60 Hz power supply to the water heater.
NOTE: To reduce the risk of scalding, install Thermostac Mixing Valves
(temperature liming valves) at each point of use.
40 Page
Owner’s Guide
Owner’s Guide
CONGRATULATIONS
Congratulations and thank you for choosing our tankless water heater. Before
use, we recommend that you read through this owner’s guide carefully. Keep
this manual for future reference. If you need an additional manual, contact
the manufacturer or your local distributor. You may also download a manual
from our website. When you call, please tell us the product name and the
serial number of your unit written on the rating plate of the water heater.
41 Page
OPERATING SAFETY
Owner’s Guide Operating Safety
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions exactly, a fire or explosion
may result
causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the burner
by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be
sure to smell next to the floor because some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL GAS · Do not try to light any appliance. · Do not
touch any electric switch; do not use any phone in your building. ·
Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s
instructions. · If you cannot reach your gas supplier, call the fire
department. C. Use only your hand to turn the gas shutoff valve. Never use
tools. If the valve will not turn by hand, don’t try to repair it, call a
qualified service technician. Force or attempted repair may result in a fire
or explosion. D. Do not use this appliance if any part has been under water.
Immediately contact a qualified installer or service agency to replace a
flooded water heater. Do not attempt to repair the unit! It must be replaced!
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label. 2. Turn off all
electric power to the appliance. 3. Do not attempt to light the burner by
hand. 4. Turn the gas shutoff valve located on the outside of the unit to the
closed position. 5. Wait five (5) minutes to clear out any gas. If you then
smell gas, STOP! Follow “B” in the
safety information above on this label. If you don’t smell gas, go to the next
step. 6. Turn the gas shutoff valve located on the outside of the unit to the
open position. 7. Turn on all electrical power to the appliance. 8. If the
appliance will not operate, follow the instructions in “To Turn Off Gas to
Appliance,” and
call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance if service is to be
performed. 2. Turn the gas shutoff valve located on the outside of the unit to
the closed position.
42 Page
Owner’s Guide Operating Safety
DANGER
Vapors from flammable liquids will explode and catch fire causing death or
severe burns. Do not use or store flammable products such as gasoline,
solvents or adhesives in the same room or area near the water heater.
Flammable Vapors
Do not install water heater where flammable products will be stored or used
unless the main burner is at least 18″ above the floor. This will reduce, but
not eliminate the risk of vapors being ignited by the
main burner.
FLAMMABLES
Read and follow water heater warnings and instructions. If the owner’s manual is missing, contact the retailer or manufacturer.
Keep flammable products:
Vapors:
1. Far away from heater.
1. Cannot be seen.
2. In approved containers.
2. Are heavier than air.
3. Tightly closed and out of reach of children.
3. Go a long way on the floor.
4. Water heater has a main burner, which may 4. Can be carried from other rooms to the main
come on at any time and will ignite flammable
burner by air currents.
vapors.
DANGER
1. Water temperature over 125°F (52°C) can cause severe burns instantly or death from
scalds. 2. Children, disabled and elderly are at highest risk of being scalded. 3. Feel water before bathing or showering.
HOT CHAUDE
BURN HOT
BRÛLURE
4. Temperature limiting valves are available. See manual.
5. To reduce the risk of scalding, install Thermostatic Mixing Valves (temperature limiting valves) at each
point of use.
6. The outlet temperature of the water heater is set at 120°F (50°C). If you require water temperatures
below this setting, follow the instruction manual.
7. Use this heater at your own risk. Test the water before bathing or showering. Do not leave children or
an infirm person unsupervised. See your local water supply company [plumbing hardware retailer] for
temperature limiting valves that are available.
A pressure relief valve listed as complying with the standard for Relief Valve
and Automatic Gas Shutoff Devices for Hot Water Supply System, ANSI Z21.22CSA
4.4, shall be installed at the time of installation of the water heater in the
location specified by the manufacturer. Local codes shall govern the
installation of relief devices for safety operation of the water heater. The
relief valve must not be removed or plugged.
No valve shall be placed between the relief valve and the water heater. The
relief from the discharge of
the pressure relief valve shall be disposed of in a suitable place where it
will cause no damage. Also, there
shall be no other reducing coupling or other restrictions installed on the
discharge line to restrict flow. See Installation Manual heading “PRESSURE
RELIEF VALVES” for installation and maintenance of relief valve discharge line
and other safety precautions.
43 Page
Owner’s Guide Normal Operation
NORMAL OPERATION
BUILT-IN CONTROLLER AND REMOTE CONTROLLER
The illustraon below shows an example of the controllers. The exact display may differ from examples.
Built-in controller
Display for Temperature
When the STAND BY LED is ON, the hot water temperature will be displayed.
Remote controller
“INFO” Button
Each time the button is pressed, the operation mode is selected in the
sequence of the following.
Inlet water Outlet water Water temperature temperature flow
IN USE LED (Green)
The indicator lights during combustion.
STAND BY LED (Orange)
The indicator is ON to show that power is ON.
“ON/OFF” Button
“HOT” Button
Press this button to start or stop operation.
“COLD” Button
Press the “HOT” button or the “COLD” button to adjust the hot water temperature.
NOTICE
· When the remote controller is installed it will take priority over the
built-in controller. · The controller has an energy saving mode. Five minutes
after the water heater stops
operating, the backlight of the controller turns off. · The backlight of the
remote will turn back on once the water heater begins firing again.
GENERAL
WARNING
· Temperatures above 125 °F (52 °C) can cause severe burns or death from
scalding. Children, disabled and the elderly are at high risk of being
injured.
· To reduce the risk of scalding, install Thermostatic Mixing Valves
(temperature limiting valves) at each point of use.
°F °C Time to produce serious burn
120
49
more than 5 min.
125 52
1½ to 2 min.
130 54
about 30 sec.
135 57
about 10 sec.
140 145 60 63
less than less than 5 sec. 3 sec.
150 66
about 1½ sec.
155 68
about 1 sec.
1. Open a cold water fixture.
2. Mix hot water with the cold water 3. When finished, close the
to get the correct temperature water.
water fixtures.
NOTICE
· Flow rate to activate the water heater: 0.5 gallons per minute at the
default set temperature (1.9 L/min).
· Flow rate to keep the water heater running: 0.4 gallons per minute (1.5
L/min).
44 Page
Owner’s Guide Normal Operation
OUTLET WATER TEMPERATURE SETTING
-Set temperature-
Operation
Screen on the controller
Built-in controller Remote controller
Turn on the 120 VAC power supply to the unit (the water heater or the multi- unit controller).
Press the “ON/OFF” button on the controller in order to turn the controller on.
3. When ON, the STAND BY LED is lit.
It shows the set temperature on its display as shown in the picture on the right. (EX.: 120 °F)
Press the “HOT” button or the “COLD” button to set the temperature setting of the unit.
WARNING! Higher temperatures increase the risk of scalding, but even at 120 °F
(50 °C), hot water can scald (page 6).
Increasing temperature from 120 °F (50 °C) to 125 °F (52 °C) :
1. Press the “HOT” buon to set 120 °F (50 °C). 2. Press and hold the “INFO”
buon and the “HOT” buon for at least 3
seconds. The remote will change to 125 °F (52 °C).
5. 3. Press the “HOT” buon to set up to 140 °F (60 °C).
-540HX3 model only-: Increasing temperature above 140 °F (60 °C)
To reduce the risk of scalding, install Thermostatic Mixing Valves
(temperature limiting valves) at each point of use. 1. Press the “HOT” buon to
set 140 °F (60 °C). 2. Press and hold the “INFO” buon and the “HOT” buon for
at least 3
seconds. The remote will change to 145 °F (63 °C). 3. Press the “HOT” buon to
set up to 160 °F (70 °C).
(EX.: 120 °F)
TEMPERATURE TABLE OF CONTROLLER
a) For 240HX3 and 340HX3 models
°F 100 105 110 115 120 125 130 135 140 °C 38 40 43 45 50 52 55 57 60
b) For 540HX3 model
°F 100 105 110 115 120 125 130 135 140 145 150 155 160 °C 38 40 43 45 50 52
55 57 60 63 65 68 70 *Factory setting (Default): 120 °F
45 Page
Owner’s Guide Normal Operation
ADDITIONAL FEATURES
-Information mode-
You can get some information about the water heater condition by pressing the “INFO” button. For more information, follow the procedures below:
INFO Button
Operation
Screen on the controller
Built-in controller
Remote controller
1st. press 2nd. press 3rd. press
Inlet water temperature will be displayed on the controller by pressing the
“INFO” button.
Outlet water temperature will be displayed on the controller by pressing the
“INFO” button.
And then, water flow will be displayed on the controller by pressing the
“INFO” button.
Inlet water temperature (EX.: 60 °F)
Outlet water temperature (EX.: 120 °F) Water flow (EX.: 3.5 GPM)
4th. press
Press the “INFO” button to finish information mode.
-Unit conversion mode-
Units of measure can be changed from Imperial to Metric and vice versa. For
example, temperature can be changed from °F to °C. Flow rate will also change
from gallons per minute to liters per minute when this setting is changed.
Follow this procedure to change this setting:
Operation
Screen on the controller
Built-in controller
Remote controller
Press the “ON/OFF” button on the controller in order to turn the controller on.
2. When ON, the orange LED is lit.
The previous set temperature will be displayed on the screen.
(EX.: 100 °F)
4. Press the “INFO” buttons for at least 3 seconds.
The set temperature should now be displayed in the alternate unit of measurement.
(EX.: 38 °C)
NOTICE
When the water heater is connected with the remote controller, the builtin controller will not operate temperature settings. It will only work for the information mode (Indoor models only).
46 Page
Owner’s Guide Normal Operation
TEMPERATURE SETTINGS ON THE PCB (WITHOUT REMOTE CONTROLLER)
· · WARNING ·
Adjust the appropriate DIP switches according to model and temperature as shown below. DO NOT adjust the other DIP switches. Turn off the power supply to the water heater before changing the DIP switch settings. Failure to observe these warnings could lead to carbon monoxide poisoning, severe personal injury, or death.
· There are 2 preset temperatures , 120 °F (50 °C) and 140 °F (60 °C), that
you can select by changing the DIP switch settings on the computer board
without the remote controller. See below.
· To reduce the risk of scalding, install Thermostatic Mixing Valves
(temperature limiting valves) at each point of use.
· When the remote controller is in normal operation, the set temperature of
the remote controller is given priority over the set temperature of the DIP
switch settings.
The temperature has been preset at the factory to 120 °F (50 °C).
240HX3/340HX3
120 °F (50 °C) DEFAULT
140 °F (60 °C)
ON 1 2 3 4 5 6 7 8 9 10 OFF
ON 1 2 3 4 5 6 7 8 9 10 OFF
No. 9 : OFF
No. 9 : ON
540HX3 (Lower bank of DIP switches)
Bank of DIP switches
120 °F (50 °C) DEFAULT
ON 1 2 3 4 5 6
140 °F (60 °C)
ON 1 2 3 4 5 6
Upper bank of DIP switches
Computer board Computer board
OFF No. 5 : OFF
OFF No. 5 : ON
Lower bank of DIP switches
NOTE: The dark squares indicate the correct DIP switch positions.
FLOW
· The flow rate through the water heater is limited to a maximum of 6.6 GPM
(25 L/min) for the 240HX3 model, 8.0 GPM (30 L/min) for the 340HX3 model, and
10.0 GPM (38 L/ min) for the 540HX3 model.
· The flow rate capacity of the water heater will vary based on temperature
difference of the set temperature and supply water temperature. Flow Capacity
tables are located on page 63.
· The table to the right provides typical household plumbing fixture flow
rates.
Appliance/Use
Lavatory Faucet Bath Tub Shower
Kitchen Sink Dishwasher Washing machine
Household Flow Rates
Flow rate
GPM (US) L/min
1.0
3.8
4.0 10.0 15.2 – 37.8
2.0
7.5
1.5
5.6
1.5
5.6
4.0
15.2
Taken from UPC 2006
47 Page
Owner’s Guide Normal Operation
FREEZE PROTECTION SYSTEM
· This water heater comes equipped with heating blocks to protect it from
damage associated with freezing. When the freeze protection thermostat senses
air temperature below 36.5 °F (2.5 °C), the blocks will heat up to prevent
freezing of the unit.
· The 540HX3 Indoor model briefly fires on for about 3 seconds to provide
freeze protection around the heat exchanger drum – Automatic firing system.
Once 5 minutes have elapsed since the 540HX3 Indoor previous firing operation,
the computer will continually check the temperature of the exhaust thermistor.
The freeze protection firing system will activate if: Tex < 32 °F (0 °C)
(where Tex is the temperature of exhaust thermistor.)
· To operate these freeze protection systems, there has to be electrical power
to the unit. Damage to the heat exchanger caused by freezing temperatures due
to power loss is not covered under the warranty. In cases where power losses
can occur, consider the use of a backup power supply. In the event of a power
outage during freezing conditions, the manufacturer recommends draining water
(page 50) from the water heater and disconnecting power.
· In any areas subject to freezing temperatures, the manufacturer highly
recommends an indoor installation with an indoor model.
· The manufacturer also highly recommends the use of a backflow preventer
(sold separately) to minimize the amount of cold air entering through the
exhaust venting when the water heater is off.
· It is the installer’s responsibility to be aware of freezing issues and take
all preventative measures. The manufacturer will not be responsible for any
damage to the heat exchanger as a result of freezing.
· If you will not be using your heater for a long period of time: 1.
Completely drain the water out of the unit. Refer to page 50. 2. Disconnect
power to your heater.
This will keep your unit from freezing and being damaged.
NOTICE
· Only pipes within the water heater are protected by the freeze protection
system. Any water pipes (hot or cold) located outside the unit will not be
protected. Properly protect and insulate these pipes from freezing.
· The freeze protection system does not protect the X3TM Cartridge. Install
the X3 Cartridge Anti-Freeze Kit, 100325654. The manufacturer also recommends
installing the pipe cover or installing the water heater in a recess box.
Refer to page 10.
48 Page
MAINTENANCE AND SERVICE
Owner’s Guide Maintenance and service
· Turn off the electrical power supply and close the manual gas shutoff valve
and the manual water control valve before servicing.
WARNING · Failure to do so could result in severe personal injury, or death.
The following maintenance is required for the proper operation of water
heaters. · Regularly ensure that the area around the water heater, vent
termination, and air intake are free from dust,
debris, and other contaminants. · Be sure that all openings for combustion and
ventilation air are not blocked. · The venting system should be checked
annually for any leaks, corrosion, blockages or damage. · The screen of the
termination (if it is installed) must be inspected regularly. Remove any
blockages or debris
including dust, dirt, and snow/ice. · Keep the area around the water heater
clear. Remove any combustible materials, gasoline or any flammable
vapors and liquids. · Clean the cold-water inlet filter. (Refer to Inlet Water
Filter Cleaning in the following.) · If the relief valve discharges
periodically, it may be due to thermal expansion in a closed water supply
system.
Contact a service technician to correct this issue. · The pressure relief
valve must be manually operated periodically to check for correct operation.
Before
operating the valve manually, check that it will discharge in a place for
secure disposal. · Condensate drain system must be inspected regularly to make
sure it drains properly and accordance with
local code or the part manufacturer’s instructions. (Refer to pages 34 and
35.) · The burner should be checked annually for dust, lint, grease or dirt by
a licensed technician. · Visually check the burner flames (see below) through
the burner window in the burner assembly located at
the middle of the water heater.
Blue flame Sasfactory
Flame blowing up
Unsasfactory
Red or Yellow flame
Unsasfactory
The manufacturer recommends having the unit checked once a year or as
necessary by a licensed technician. If repairs are needed, any repairs should
be done by a licensed technician.
INLET WATER FILTER CLEANING
If this filter is clogged, water will not be supplied to the water heater
properly. 1. Close the manual gas shutoff valve. 2. Turn off power to the unit
and wait a couple of seconds. Turn on again. 3. Wait 30 seconds, and then turn
off power to the unit. 4. Close the inlet water valve. If the heater is part
of an common vent System, close the inlet and outlet water
valves to isolate the heater. Then proceed to step 5. 5. Open all hot water
taps in the house. When the residual water flow has ceased, close all hot
water taps. 6. Have a bucket or pan to catch the water from the unit’s large
drain plug with filter. If Isolation valves are
installed, open the drains to drain the water. If isolation valves are not
installed, unscrew the large drain plug to drain all the water out of the
unit. Do not lose the o-ring that will be on the large drain plug. 7. Wait a
few minutes to ensure all water has completely drained from the unit. 8. Clean
the filter: Check the water filter located within the cold inlet. With a tiny
brush, clean the water filter of any debris which may have accumulated and
reinsert the filter back into the cold water inlet. 9. Securely screw the
drain plug back into place. Hand- tighten only.
49 Page
Owner’s Guide Maintenance and service
UNIT DRAINING & POWER OUTAGE (FREEZE PROTECTION)
If you will not be using your heater for a long period of time, drain the
water out of the unit completely and disconnect power to your heater to keep
the water heater from freezing and being damaged.
1. Close the manual gas shutoff valve.
2. Turn off power to the unit and wait five (5) seconds.
Turn on again. 3. Wait 30 seconds, and then turn off power to the unit.
Pressure relief valve Drain plug with Filter (Large)
4. Close the inlet water valve.
5. Open all hot water taps in the house. When the
residual water flow has ceased, close all hot water
taps.
6. Have a bucket or pan to catch the water from the
unit’s drain plug (Large). If isolation valves are
installed, open the drains to drain the water. If iso-
lation valves are not installed, unscrew the filter and
open the pressure relief valve to drain all the water
out of the unit. Do not lose the o-ring that will be on the filter cap. 7. In addition to the large drain plug, the model has another drain plug that drains the small line that covers the water line between the primary and sec-
Outlet water valve
*Drain plug for the water line of heat exchangers
Inlet water valve
Gas valve
ondary heat exchangers*. Unscrew this drain plug to
drain the water line as well.
8. Drain the X3TM Cartridge: Have a bucket or pan to catch water from the X3TM Cartridge. To remove the X3TM
Cartridge, turn it left until the symbol aligns with the symbol. Pull down to remove it from the
water heater.
9. Drain the water in the X3TM Cartridge completely.
10. Wait a few minutes to ensure all water has completely drained from the unit.
11. Keep the cold/hot water valves closed. Keep the gas valve closed. Keep supply power disconnected.
12. Securely screw the drain plugs back into place. Hand- tighten only.
Removal of the X3TM Cartridge:
50 Page
Owner’s Guide Maintenance and service
MEASURING INLET GAS PRESSURE
1. Turn off all electric power to the water heater if service is to be
performed.
2. Turn the manual gas valve located on the outside of the unit to the off
position. 3. Failure to follow these steps could lead to fire or explosion,
resulting in personal injury or WARNING death.
The water heater cannot perform properly without sufficient inlet gas pressure. Below are instructions on how to check the inlet gas pressure. ONLY A LICENSED PROFESSIONAL SHOULD PERFORM THE PROCEDURE BELOW.
1. Shut off the manual gas valve on the gas supply line.
2. Remove the screw from the pressure port which is located on the gas inlet of
the water heater shown in the diagram on the right.
3. Connect the manometer to the pressure port and zero the manometer.
4. Re-open the manual gas valve. Verify that there are no gas leaks.
5. With all gas burning equipment off, take a reading of the static gas pressure
and make a note of it.
6. Measure gas supply pressure at maximum heater operation: Open hot water faucets to create maximum flow. Press the MAX button on the computer
Pressure port
board. (Refer to the diagrams below.) Take a reading of the supply dynamic
gas pressure with all gas burning equipment running at maximum rate.
7. The static and dynamic pressures should be within the ranges specified on the
heater’s rating plate and the table on page 30.
8. The difference of static to dynamic pressure should not exceed 1.5″ W.C. Pressure drops that exceed 1.5″
W.C. can indicate restricted gas flow, undersized gas lines, and/or undersized supply regulators.
9. Measure gas supply pressure at minimum heater operation: Reduce water flow so the heater is running at
minimal operation. Press the MIN button on the computer board. (Refer to the diagrams below.) Take a
supply gas pressure reading and verify that it is within the specified inlet gas pressure range.
240HX3/340HX3
MAX button MIN button
540HX3 MIN button
MAX button
51 Page
Owner’s Guide Troubleshooting
TROUBLESHOOTING
PROBLEM
SOLUTIONS
It takes a long time to · The time it takes to deliver hot water from the water heater to your fixtures
get hot water at the
depends on the length of piping between the two. The longer the distance or
fixtures.
the bigger the pipes, the longer it will take to get hot water.
TEMPERATURE and AMOUNT OF HOT WATER
The water is not hot enough.
The water is too hot.
· Compare the flow and temperature. See the charts on p.62. · Check cross plumbing between the cold water lines and hot water lines. · Is the gas supply valve open fully? (p. 40) · Is the gas line sized properly? (p. 31) · Is the gas supply pressure sufficient? (pp. 30 and 51) · Is the set temperature set too low? (pp. 45 and 47) · Check if the POU mixing valve are set correctly, if they are installed. · Is the set temperature set too high? (pp. 45 and 47)
The hot water is not available when a fixture is opened.
· Make sure the unit has 120 VAC, 60 Hz power supply. · If you are using the
remote controller and/or temperature controller, is the
power button turned on? · Is the gas supply valve open fully? (p. 40) · Is the
water supply valve open fully? (p. 40) · Is the filter on the cold water inlet
clean? (p. 49) · Is the hot water fixture sufficiently open to draw at least
0.5 GPM
(1.9 L/min) through the water heater? (p. 44) · Is the unit frozen? (p. 48) ·
Is there enough gas in the tank / cylinder? (For Propane models)
The hot water turns cold and stays cold.
· Is the flow rate enough to keep the water heater running? (p. 44) · Is the gas supply valve open fully? (p. 40) · Is the filter on the cold water inlet clean? (p. 49) · Are the fixtures clean of debris and obstructions? · Check if the flow rate is too low. (p. 44)
Fluctuation in hot water temperature.
· Is the filter on the cold water inlet clean? (p. 49) · Is the gas line sized properly? (p. 31) · Is the supply gas pressure sufficient? (pp. 30 and 51) · Check for cross connection between the cold water lines and hot water lines.
Unit does not ignite · Is the flow rate over 0.5 GPM (1.9 L/min)? (p. 44)
when water goes
· Check for the filter on the cold water inlet. (p. 49)
through the unit.
· Check for reverse connection and cross connection.
· If you use the remote controller and/or built-in controller, is the power button
turned on?
· Check if the inlet temperature is too high. If it is too close to the set tempera-
ture, the water heater will not activate.
The fan motor is still · This is normal. After operation has stopped, the fan motor keeps running
spinning after operation from 15 to 70 seconds in order to re-ignite quickly, as well as purge all the
has stopped.
exhaust gas out of the flue.
Unit sounds abnormal · Contact the manufacturer at 1-877-737-2840 (USA). while in operation
WATER HEATER
52 Page
Owner’s Guide Troubleshooting
PROBLEM
SOLUTIONS
Controller does not · Make sure the unit is supplied with power.
display anything when · Make sure the connection to the unit is correct. (pp. 37 and 38)
the power button is NOTICE:
turned on.
When the unit has not operated for five minutes or more, the display of the
controllers turns off to conserve energy.
When the
Built-in controller
controller turned ON, STAND BY LED
is lit.
BUILT-IN CONTROLLER AND REMOTE CONTROLLER
An ERROR code is displayed.
· Please see pp. 54 to 55.
ERROR CODES
· The units have self-diagnostic functions for safety and convenience when
troubleshooting. · If there is a problem with the installation or the unit,
the error code will be displayed on the built-in
controller and remote controller. The green LED on the computer board will
flash in a pattern shown on the next page. · Consult the table on the
following pages for the description of each error code.
Error code indicator on the built -in temperature controller
240HX3/340HX3
540HX3
Error code indicator on the remote controller
Green LED
Green LED
Error code on the computer board Indicated by 1/2-second flashes on the Green LED.
Example: If your unit has a “321” error code (which signifies an inlet
thermistor failure) · Indicator on the built-in controller or remote
controller : “321” will be displayed
on the screen.
Error code
· Green LED on the computer board: The green LED on the computer board will
indicate this code with two flashes with a 1/2 second pause in between. The
pattern will repeat with a three second pause between patterns.
Error code
Green LED
321
on on off
on on
off
off
on on
off
off
53 Page
Owner’s Guide Troubleshooting
Error Indication
Error Code on the temperature
controller
The number of flashes
Green LED Flash paern
031 701 711
311 321 331 341 391
One
on
on
off
off
Two
111 121
Three
611 661
Four
101 291 941 991 Five
510 551 721
Six
0.5 sec. on, 0.5 sec. off 3 sec. off
-Fault Analysis of Error Codes-
If the error code is displayed on the computer board of the water heater or
remote controller and/or temperature controller, please check the following.
After checking, consult with the manufacturer.
Controller
Green LED
Malfunction description
Diagnosis
031 One Incorrect DIP switch · Check the DIP switch settings on the PCB (Part
701).
Flash setting
101 111*
Five Warning for the “991” · Ensure the gas type of the water heater matches the gas supplied.
Flashes error code
· Inspect the environment around the water heater. Determine how long the
unit has been installed.
· Ensure the heater altitude DIP switches are properly set to match the
installed altitude.
· Check if there is any blockage in the intake air and/or exhaust.
· If the water heater is installed as a direct-vent system, check whether there
is enough distance between the intake air terminal and the exhaust terminal.
· Check if there is grease and/or dirt in the burner (Part #101) and the fan motor
(Part #103), especially if the water heater has been installed in a contaminated
area.
Three Ignition failure
· Check if the Hi-limit switch (Part #412) is properly functioning.
Flashes
· Check for connection/breakage of wires (Part #413, 708, 709, 711) burn marks on
the computer board (Part #701), and/or soot on the flame rod (Part #108).
· Check if there is a buzzing spark ignition sound coming from the burner (Part
101) when the water heater prepares for combustion.
· Listen for the double “clunk” sound coming from gas valve assembly (Part
102) when water heater goes into combustion.
· Check if there is leaking from heat exchanger (Part #401).
121* Three Loss of flame
Flashes
291 Five Blocked condensate
Flashes drain system
· Check if the Hi-limit switch (Part #412) is functioning properly. · Check
for connection/breakage of wires (Part #413, 708, 709, 711) burn
marks on the computer board (Part #701), and/or soot on the flame rod (Part
108). · Check if there is leaking from heat exchanger (Part #401). · Check
for and remove any blockage in the condensate drain line, neutralizer (if installed), condensate drain assembly inside the water heater (part #416, 421, 423). · Ensure that any horizontal drain line runs are sloped downward. Removal any sags in the drain line.
54 Page
Owner’s Guide Troubleshooting
Controller
Green LED
Malfunction description
Diagnosis
311
321 331 341 391 510 551 611
661 701 711 721
741
Two 240HX3/340HX3:
Flashes Outlet Thermistor
Failure
540HX3: Heat
Exchanger Thermistor
Two
Failure Inlet thermistor
failure
·
Check for connection/breakage #407, 408, 411, 715, 718, 721).
of
wires
and/or
debris
on
thermistor
(Part
Flashes
Two Outlet thermistor failFlashes ure (540HX3 only)
Two Exhaust thermistor failure Flashes (Indoor models only)
Two Air-fuel ratio rod fail- · Check for connection/breakage of wires (Part
709) and/or soot on the AFR
Flashes ure
rod (Part #108).
Six Abnormal main gas · Check for connection/breakage of wires (Part #708) and/or burn marks on the
Flashes solenoid valve
computer board (Part #701).
Six Abnormal gas solenoid · Check for connection/breakage of wires (Part #708) and/or burn marks on the
Flashes valve
computer board (Part #701).
Four Fan motor fault Flashes
· Check for connection/breakage of wires, dust buildup in the fan motor (Part
103) and/or burn marks on the computer board (Part #701).
· Check for frozen/corrosion of connectors (Part #103).
Four Bypass valve fault Flashes (540HX3 only)
· Inspect the bypass valve (Part #403), for connection/breakage of wires, locked motor drive due to scale buildup, and/or water leakage.
One Flash
Computer board fault
· Check for connection/breakage of wires (Part #714).
One Gas solenoid valve · Refer to the 111 and 121 error codes.
Flash drive circuit failure
Six False flame detection · For indoor models, check if condensate drain is installed on the vent collar of
Flashes
the water heater. · Check if there is leaking from heat exchanger (Part #401).
N/A Miscommunication · Check the model type of the remote controller. between water heater · Inspect the connections between the water heater and remote controller. and remote controller · Check the power supply of the water heater.
751
941 991
N/A Miscommunication · Inspect the connections between the water heater and built-in controller. between water heater · Check the power supply of the water heater. and built-in controller (Indoor models only)
Five Abnormal exhaust Flashes temperature (Indoor
models only)
Five Imperfect Flashes combustion
· Check for connection/breakage of wires, dust buildup in the fan motor (Part
103). · Check for connection/breakage of wires (Part #472, 721).
· Check the gas type of the water heater. · Inspect the environment around the
water heater. Determine how long the
unit has been installed. · Check the altitude/elevation of the area where the
water heater is installed. · Check if there is any blockage in the intake air
and/or exhaust. · If the water heater is installed as a direct-vent system,
check whether there is
enough distance between the intake air terminal and the exhaust terminal. ·
Check if there is grease and/or dirt in the burner (Part #101) and the fan
motor
(Part #103), especially if the water heater has been installed in a
contaminated area.
*These error codes will be cleared when water flow stops.
55 Page
COMPONENTS DIAGRAM
Case assembly
Indoor
052
419
052 003 007
067 713
052 004 010
Owner’s Guide Components Diagram
Outdoor
001
002
717
001
050 050
008 052
702 704
702 704
006 005 052 002
Built-in controller
Indoor
723
056 722
Surge box assembly
121 703
713
Temperature remote controller
724
703 706
053 713 704
56 Page
Owner’s Guide Components Diagram
Computer board assembly
240HX3/340HX3 701
711
540HX3 701
708 714 721
716
707
408 407
713 103 709 402
722 402 061
714 715
716
715
709 711 708
713 103 402 402
707 722 721
Wiring diagram
SV3
240HX3/340HX3
R SV2
SV1 G 708 711
IG P
P
Igniter rod Heater
Y Y
PCB
Y BK
MV LB
BL BL BL O.H.C.F BL BL
73 53
9 3
Hi-limit
BL
switch
BL
713 103
Drain plug detector
G G
721 240HX3/340HX3 Outdoor Only GG
Hi-limit switch for exhaust
W
Drain plug detector
G G
Exhaust W
thermistor
721
240HX3/340HX3 Indoor Only
W
W
G W
W
709 402
402
240HX3/340HX3
713 Thermostat
BK W
G
SW
BK W
BK
Ground
FM W
Y
O BL
R
Surge box
W
W
BK
OG
Y AFR Flame
rod rod
704 713 Ground G120 VAC
R BK
W
Flow Sensor
BK R
Ground
Flow Adjustment Valve
Gas
Proporonal Valve
W R
MAX buon
714
Indoor Only
408
407
BK BL
R W
Built-in controller
BK BK
Outlet thermistor Inlet thermistor
722
MIN buon Increase buon
Decrease buon
1 2 3 4 5 6 7 8 910 OFF
W BK
707
Remote controller
Green LED
DIP switches
240HX3/340HX3 Outdoor Only
Heater Heater Heater
240HX3/340HX3 Indoor Only
Heater Heater Heater
713
O Y
Y Y
Y
Y Y
Y Y
O
540HX3
Igniter rod
R
FM
BL YO
W
Flame rod O
Ground
AFR
G rod
Y
PrGoapsoronal Valve
WR
714
R
Bypass Valve
YW BL
ON
715
BR
Y
IG P P
711 PCB
713 103
708
3 9
709
53
73
G
402
402
Heater
Y
Y BK
713 713 Thermostat
G BK W
SW
Ground Hi-
BL limit
BL switch
W BK
BK
MV
Surge box
W
SV1
W BK
BL BL
BL BL O.H.C.F BL LB
SV2
713
R
SV3 120 VAC
R
Flow
BK
Adjust-
W
R BK
Flow Sensor
ment Valve
G 704
Ground
540HX3 Outdoor Only
Heater Heater Heater
540HX3 Indoor Only
Heater Heater Heater
713
1234 56 7 8 1 2345 6
DIP switches
ON
721
540HX3 Indoor Only
540HX3 Indoor Only
W BK
W R
BL BK
Built-in controller
722
Remote controller 707
BK
Green LED
BK
MAX buon MIN buon
Increase buon
BK
715 BK
Decrease buon
BK
Heat exchanger thermistor Inlet thermistor
Outlet thermistor
WW GG WW
Hi-limit switch for exhaust
Drain plug detector
Exhaust thermistor
540HX3 Outdoor
Only 721 GG
Drain plug detector
57 Page
Burner assembly
Owner’s Guide Components Diagram
Burner assembly 101
104 115 053
053
106 107 108 709
401 116
110
062 109 111 711
112 053
Manifold
assembly 114
102
113
063 121
150
709 711
G
055
057
707
719
062 063 540HX3
055 117
066 714
053
117 103
105 065 708
054
119 151 118 051
58 Page
Water Way assembly
453
Owner’s Guide Components Diagram
413
418
452
403 458
F
412
456 058
460 462
B
A
473 064
462
Bypass section 458 540HX3
468 473
419
472 067
418
153 152
468
467
462
E
458
462
E 540HX3
064 458
B
458
F
471
718 470
053
401
415
459 454 411
466
451
421
451
A
415
458
414
455 422
462
466
451
C 463 423
458
476 414
458
462
451
465
G
240HX3/340HX3
422 414
416
424 069
414 475 461
D
464
009
455
052
469 463
458
458
052
477
C
456 460 474
540HX3
450
402
068
462
458
409
725
454 408
059
052
417
Water outlet section
458
420 458
462 052
451
D
406 457
405
461 404 417
059 454
407
Water inlet section
59 Page
PARTS LIST
N/A: Part with no part number assignment
Item #
Description
001 Case assembly Indoor Case assembly Outdoor
002 Front cover Indoor Front cover Outdoor
003 Intake air port assembly 004 Bracket 005 Junction box 006 Power supply
cord assembly 007 Back guard panel 008 Chamber fixing plate 009 Condensate
drain port 010 Bottom bracket 050 Truss screw M4X12 (W/Washer) SUS410 051
Truss screw M4×10 (W/Washer) 052 Truss screw M4×10 (Coated) SUS3 053 Truss
screw M4×10 SUS 054 Hex head screw M4×12 (W/Washer) SUS3 055 Hex head screw
M4x8 FEZN 056 Pan screw M4x20 057 Tap tight screw M4x12 FEZN 058 Pan head
screw M3x6 SUS3 059 Truss head screw M4x6 SUS3 060 Tap tight screw M4x12 061
Screw M3x6 Plus bind FEZN 062 Pan screw M4x8 MFZN 063 Wire clamp 60 064 Screw
M4x10 065 Screw M3x6 SUS3 Binding head 066 Pan screw M4x10 067 Pan screw M4x10
for 3″ adapter 068 Truss screw M4×12 (Coated) SUS3 069 Plus Truss P tight
M3.5×12 101 Burner assembly 102 Manifold with gas valve assembly LP
Manifold with gas valve assembly NA 103 Fan motor for Indoor model
Fan motor for Outdoor model 104 Burner gasket 105 Fan damper for Indoor model
106 Burner window 107 Rod holder gasket 108 Flame rod 109 Igniter rod 110 Rod
holder 111 Rod cap 112 Burner damper LP
Burner damper NA 113 Manifold gasket A
240HX3
60 Page
Owner’s Guide Parts list
Model
340HX3 N/A N/A N/A N/A
100074667 N/A
100074668 100074669
N/A N/A 100074203 N/A 100074210 100074509 100074211 100074245 100074510
100074248 N/A 100074385 100074272 100074512 100076269 N/A 100074244 100074233
N/A 100074514 100074247 N/A N/A N/A 100074670 100074671 100074672 100074606
100074228 100074216 100074466 100074218 100074219 100074673 100074222
100074221 100074223 100074674 100074675 100074229
540HX3
Item #
Description
114 Manifold gasket B 115 Burner holder gasket 116 Pressure port 117
Combustion chamber tube 118 Gas inlet 119 Gas inlet ring 121 Surge box plate
150 O-ring P18 NBR (Black) 151 O-ring P20 NBR (Black) 152 Silicon ring for
Outdoor models 153 Exhaust port for Outdoor models 401 Primary heat exchanger
assembly 402 Flow adjustment valve / Flow sensor 403 Bypass valve (540HX3) 404
Water inlet 405 Inlet drain plug 406 Inlet water filter 407 Inlet thermistor
408 Outlet thermistor 409 Water outlet 411 Heat exchanger thermistor (540HX3)
412 Hi-Limit switch 413 Overheat-cut-off fuse 414 Pipe heater 415 Inlet heater
for Indoor model
Inlet heater for Outdoor model 416 Drain plug detector assembly 417 Inlet
heater 418 Secondary heat exchanger for Indoor model
Secondary heat exchanger for Outdoor model 419 3 PVC adapter 420 Inlet pipe
heater 421 Upper drain tube 422 Band A 423 Lower drain tube 424 Drain detector
fixing plate 450 Pipe heater fixing plate 451 Heater fixing plate 16 452 Fuse
fixing plate 18 453 Fuse fixing plate 14 454 O-ring P4 FKM 455 O-ring P6 FKM
456 O-ring P14 FKM 457 O-ring P15 FKM 458 O-ring P16 FKM 459 Fastener “4-11”
460 Fastener “14-22” 461 Fastener “16A” 462 Fastener “16-25A” 463 Fastener
“6-15” 464 Flat heater 465 Drain pipe 466 Cold pipe 467 Stainless heat
exchanger out pipe 468 Header connection 469 Drain port
Model
240HX3
340HX3
100074230 100074217
100074227
100074528 100074616 100074526
N/A 100074533 100074242 100074678
100074679
100342435 100074624
N/A 100074377 100074381 100074382
100074398
100074680
100320527 N/A 100074412
100074334 100074682 100074683 100074684
100342423 100074629 100074700 100074701 100310706 100348805
N/A
N/A
N/A N/A 100074273 100074310 100074251 100074331 100076303 100076305 100076306 100076307
100076308
100074282 100074290 100074410 100074389 100074297 100074686
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>