Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units Instruction Manual

June 1, 2024
Schneider Electric

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip
Units

www.se.com/support

Retain instruction sheet for future use.
Visit our website at www.se.com to download the documents listed above (user guides or instruction sheets ) and other documents.

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
  • All pertinent state, regional, and local safety regulations must be observed when installing and using this product.

DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

  • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, NOM-029-STPS or local equivalent.
  • This equipment must only be installed and serviced by qualified electrical personnel. p Turn off all power supplying this equipment before working on or inside equipment.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Put back all devices, doors, and covers before turning on power to this equipment. p Beware of potential hazards, and carefully inspect the work area for tools and objects that may have been left inside the equipment.
  • Failure to follow these instructions will result in death or serious injury.

WARNING : This product can expose you to chemicals including lead and lead compounds, which are known to the State of California to cause cancer and birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov

DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Do not install a MicroLogic 7.2 trip unit on a network with a voltage above 440 Va. Failure to follow these instructions will result in death or serious injury.

WARNING ABSENCE OF EARTH-LEAKAGE PROTECTION
Do not use MicroLogic 7.2E-AL trip units to protect your equipment against earth-leakage faults. These trip units only indicate the presence of an earth- leakage fault.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Required for Installation

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
1

Use the wire A to connect the MicroLogic 7.2 trip unit to a BSCM, a 24Vcc terminal block, or an NSX cord.

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
2

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
3

Before Working on Equipment

  1. Turn off all power supplying this equipment before working on or inside equipment.
  2. Use push-to-trip button to trip the device.
  3. Use a properly rated voltage sensing device to confirm power is off.

Installation

WARNING HAZARD OF FIRE

  • When installing the MicroLogic trip unit, check that the snap-off screws break A when tightened.
  • It is mandatory to use snap-off screws LV429513 to install a MicroLogic trip unit.
  • In case of replacement of the trip unit by a trip unit with a different rating, you must:
  • re-define the trip unit settings
  • adapt the connection characteristics. Failure to follow these instructions can result in death, serious injury, or equipment damage.
  1. Loosen and remove screws of front cover or accessories as indicated in instruction sheet shipped with device.
  2. Install the trip unit into compartment.

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
5

Reinstall Front Cover

DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Put back front cover or accessories before energizing device to prevent access to live terminals.
Failure to follow these instructions will result in death or serious injury.

NOTICE HAZARD OF EQUIPMENT DAMAGE

  • Be careful not to pinch wires when installing front cover.
  • Tighten all front cover screws to stated torque.
  • Do not overtorque screws.
  • Do not use power equipment to torque screws.
  • Failure to follow these instructions can result in equipment damage.
  1. Put back front cover and accessories as indicated in instruction sheet shipped with device.
  2. Device is ready to be placed in service.

Trip Unit Adjustment

WARNING LOSS OF EARTH-LEAKAGE PROTECTION
Earth-leakage protection is inhibited when the IΔn dial is in the OFF position. Failure to follow these instructions can result in death, serious injury, or equipment damage.

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
6

Trip Unit Supply

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
7

Settings on HMI

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
8

Dielectric Test

WARNING LOSS OF EARTH-LEAKAGE PROTECTION
The dial must be in position while the B circuit breaker is in use.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
9

NOTICE HAZARD OF TRIP UNIT DETERIORATION

  • Turn the dial to the Test position A when performing a dielectric test.
  • Turn the dial back to the original position B after the dielectric test.
  • Do not close the transparent cover during the dielectric test.
  • Failure to follow these instructions can result in equipment damage.

Dielectric test authorized.

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
10

After the dielectric test.

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
11

After performing a dielectric test, carry out an earth-leakage test, see pages 13, 14 and 15

Earth-Leakage Protection Test

DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Take all measures necessary to avoid the risk of electrocution when the external power supply voltage is greater than 30 Va.
Failure to follow these instructions will result in death or serious injury.

Press the test button to simulate an earth-leakage fault, which allows the differential protection function to be tested.
This test is mandatory before commissioning.
Periodic test: In case of absence of local regulation, Schneider Electric recommends that the test is carried out (1) every 3 months or (2) once a month for devices in corrosive or harsh environment.

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
12

MicroLogic 7.2E

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
13

MicroLogic 7.2E-AL

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
14

Sealing

Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
15

To install the sealing accessory, consult the instruction sheet GHD16296AA.

Manufacturing Date

The product’s manufacture date is coded PP-YYYY-Www-D, where:

  • PP: plant code
  • YYYY: year of manufacture
  • Www: week of manufacture
  • D: weekday of manufacture
    (Monday = 1)

Eg: 7Q-2019-W20-3 = product manufactured at plant 7Q on Wednesday 15 May 2019

Schneider Electric Industries SAS 35, rue Joseph Monier
CS 30323
F – 92506 Rueil Malmaison Cedex www.se.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals