Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units Instruction Manual
- June 1, 2024
- Schneider Electric
Table of Contents
- Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
- Required for Installation
- Before Working on Equipment
- Installation
- Reinstall Front Cover
- Trip Unit Adjustment
- Dielectric Test
- Earth-Leakage Protection Test
- Sealing
- Manufacturing Date
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Schneider Electric ComPacT NSX100-250 MicroLogic 7.2 Trip Units
Retain instruction sheet for future use.
Visit our website at www.se.com to download the
documents listed above (user guides or instruction sheets ) and other
documents.
PLEASE NOTE
- Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
- No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
- All pertinent state, regional, and local safety regulations must be observed when installing and using this product.
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
- Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E, CSA Z462, NOM-029-STPS or local equivalent.
- This equipment must only be installed and serviced by qualified electrical personnel. p Turn off all power supplying this equipment before working on or inside equipment.
- Always use a properly rated voltage sensing device to confirm power is off.
- Put back all devices, doors, and covers before turning on power to this equipment. p Beware of potential hazards, and carefully inspect the work area for tools and objects that may have been left inside the equipment.
- Failure to follow these instructions will result in death or serious injury.
WARNING : This product can expose you to chemicals including lead and
lead compounds, which are known to the State of California to cause cancer and
birth defects or other reproductive harm.
For more information go to
www.P65Warnings.ca.gov
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Do not install a MicroLogic 7.2 trip unit on a network with a voltage above
440 Va. Failure to follow these instructions will result in death or serious
injury.
WARNING ABSENCE OF EARTH-LEAKAGE PROTECTION
Do not use MicroLogic 7.2E-AL trip units to protect your equipment against
earth-leakage faults. These trip units only indicate the presence of an earth-
leakage fault.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Required for Installation
Use the wire A to connect the MicroLogic 7.2 trip unit to a BSCM, a 24Vcc terminal block, or an NSX cord.
Before Working on Equipment
- Turn off all power supplying this equipment before working on or inside equipment.
- Use push-to-trip button to trip the device.
- Use a properly rated voltage sensing device to confirm power is off.
Installation
WARNING HAZARD OF FIRE
- When installing the MicroLogic trip unit, check that the snap-off screws break A when tightened.
- It is mandatory to use snap-off screws LV429513 to install a MicroLogic trip unit.
- In case of replacement of the trip unit by a trip unit with a different rating, you must:
- re-define the trip unit settings
- adapt the connection characteristics. Failure to follow these instructions can result in death, serious injury, or equipment damage.
- Loosen and remove screws of front cover or accessories as indicated in instruction sheet shipped with device.
- Install the trip unit into compartment.
Reinstall Front Cover
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Put back front cover or accessories before energizing device to prevent access
to live terminals.
Failure to follow these instructions will result in death or serious injury.
NOTICE HAZARD OF EQUIPMENT DAMAGE
- Be careful not to pinch wires when installing front cover.
- Tighten all front cover screws to stated torque.
- Do not overtorque screws.
- Do not use power equipment to torque screws.
- Failure to follow these instructions can result in equipment damage.
- Put back front cover and accessories as indicated in instruction sheet shipped with device.
- Device is ready to be placed in service.
Trip Unit Adjustment
WARNING LOSS OF EARTH-LEAKAGE PROTECTION
Earth-leakage protection is inhibited when the IΔn dial is in the OFF
position. Failure to follow these instructions can result in death, serious
injury, or equipment damage.
Trip Unit Supply
Settings on HMI
Dielectric Test
WARNING LOSS OF EARTH-LEAKAGE PROTECTION
The dial must be in position while the B circuit breaker is in use.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTICE HAZARD OF TRIP UNIT DETERIORATION
- Turn the dial to the Test position A when performing a dielectric test.
- Turn the dial back to the original position B after the dielectric test.
- Do not close the transparent cover during the dielectric test.
- Failure to follow these instructions can result in equipment damage.
Dielectric test authorized.
After the dielectric test.
After performing a dielectric test, carry out an earth-leakage test, see pages 13, 14 and 15
Earth-Leakage Protection Test
DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Take all measures necessary to avoid the risk of electrocution when the
external power supply voltage is greater than 30 Va.
Failure to follow these instructions will result in death or serious injury.
Press the test button to simulate an earth-leakage fault, which allows the
differential protection function to be tested.
This test is mandatory before commissioning.
Periodic test: In case of absence of local regulation, Schneider Electric
recommends that the test is carried out (1) every 3 months or (2) once a month
for devices in corrosive or harsh environment.
MicroLogic 7.2E
MicroLogic 7.2E-AL
Sealing
To install the sealing accessory, consult the instruction sheet GHD16296AA.
Manufacturing Date
The product’s manufacture date is coded PP-YYYY-Www-D, where:
- PP: plant code
- YYYY: year of manufacture
- Www: week of manufacture
- D: weekday of manufacture
(Monday = 1)
Eg: 7Q-2019-W20-3 = product manufactured at plant 7Q on Wednesday 15 May 2019
Schneider Electric Industries SAS 35, rue Joseph Monier
CS 30323
F – 92506 Rueil Malmaison Cedex www.se.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>