Solahart 180HAV Air Sourced Heat Pump Water Heaters User Guide
- June 1, 2024
- Solahart
Table of Contents
- Solahart 180HAV Air Sourced Heat Pump Water Heaters
- SOLAHART HEAT PUMP WATER HEATER WARRANTY AUSTRALIA ONLY
- SAFETY, WARNINGS, INSTALLATION NOTES
- ABOUT YOUR WATER HEATER
- DISPLAY PANEL
- MAINTENANCE REQUIREMENTS
- WATER SUPPLIES
- INSTALLATION
- CONNECTIONS – PLUMBING
- CONNECTIONS – ELECTRICAL
- COMMISSIONING
- DRAINING THE WATER HEATER
- INSTALLATION REPORT
- SOLAHART OFFICES
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Solahart 180HAV Air Sourced Heat Pump Water Heaters
This water heater must be installed and serviced by a qualified person. Please leave this guide with the householder.
An electronic copy of these Owner’s Guide and Installation Instructions can be downloaded from solahart.com.au. This water heater is manufactured by Rheem (China) Water Heater Co. Ltd.
PATENTS
This water heater may be protected by one or more patents or registered
designs in the name of Solahart Industries Pty Ltd Rheem Australia Pty Ltd or
Rheem (China) Water Heater Co. Ltd.
TRADEMARKS
Registered trademark of Solahart Industries Pty Ltd or Rheem Australia Pty
Ltd. ™ Trademark of Solahart Industries Pty Ltd or Rheem Australia Pty Ltd.
Note: Every care has been taken to ensure accuracy in preparation of this publication. No liability can be accepted for any consequences, which may arise as a result of its application.
HOUSEHOLDER
This booklet contains important information about your new water heater,
including the terms of the Solahart warranty. We recommend you read pages 7 to
29, and the terms of the Solahart warranty on pages 4 to 6. The other pages
are intended for the installer but may be of interest.
SOLAHART HEAT PUMP WATER HEATER WARRANTY AUSTRALIA ONLY
HEAT PUMP WATER HEATER MODELS 180HAV
THE SOLAHART WARRANTY – GENERAL
- This warranty is given by Solahart Industries Pty Limited ABN 45 064 945 848 of 1 Alan Street, Rydalmere New South Wales.
- Solahart offers national service through its Dealer network. Solahart will repair or replace components at the address of the water heater subject to the terms of the Solahart warranty. Solahart, in addition, can provide preventative maintenance and advice on the operation of your water heater.
- For details about this warranty, you can contact us on 1800 638 011.
- The terms of this warranty and what is covered by it are set out in sections 2 and 3 and apply to water heaters manufactured from the 1st of December 2022.
- If a subsequent version of this warranty is published, the terms of that warranty and what is covered by it will apply to water heaters manufactured after the date specified in the subsequent version.
TERMS OF THE SOLAHART WARRANTY AND EXCLUSIONS TO IT
- Solahart may reject a claim under this warranty in its sole discretion if:
- You do not arrange for a major service to be conducted on your water heater in the fifth year after installation, by Sola Hart’s recommendation in the Owner’s Guide and Installation Instructions; and
- The fault giving rise to the warranty claim would have been detected and rectified during that major service.
- The decision of whether to repair or replace a faulty component is at Solahart’s sole discretion.
- If you require a call-out and we find that the fault is not covered by the Solahart warranty, you are responsible for our standard call-out charge. If you wish to have the relevant component repaired or replaced by Solahart, that service will be at your cost.
- Where a failed component or cylinder is replaced under this warranty, the balance of the original warranty period will remain effective. The replacement does not carry a new Solahart warranty.
- Where the water heater is installed outside the boundaries of a metropolitan area as defined by Solahart or further than 30 km from a regional Solahart Dealer, the cost of transport, insurance, and traveling between the nearest Solahart Dealer’s premises and the installed site shall be the owner’s responsibility.
- Where the water heater is installed in a position that does not allow safe or ready access, the cost of that access, including the cost of additional materials handling and/or safety equipment, shall be the owner’s responsibility. In other words, the cost of dismantling or removing cupboards, doors, or walls and the cost of any special equipment to bring the water heater to floor or ground level or a serviceable position is not covered by this warranty.
- This warranty only applies to the original and genuine Solahart water heater in its original installed location and any genuine Solahart replacement parts.
- The Solahart warranty does not cover faults that are a result of:
- Accidental damage to the water heater or any component (for example (i) Acts of God such as floods, storms, fires, lightning strikes, and the like; and (ii) third party acts or omissions).
- Misuse or abnormal use of the water heater.
- Installation is not by the Owner’s Guide and Installation Instructions or with relevant statutory and local requirements in the State or Territory in which the water heater is installed.
- Connection at any time to a water supply that does not comply with the water supply guidelines as outlined in the Owner’s Guide and Installation Instructions.
- Repairs attempt to repair or modifications to the water heater by a person other than a Solahart Dealer or a Solahart Accredited Service Agent.
- Faulty plumbing or faulty power supply.
- Failure to maintain the water heater by the Owner’s Guide and Installation Instructions.
- Transport damage.
- Fair wear and tear from adverse conditions (for example, corrosion).
- Cosmetic defects.
- Ice formation in the waterways of a water heater system incorporating a freeze protection system where the electricity supply has been switched off or has failed.
- Solahart may reject a claim under this warranty at its sole discretion if a third-party solar diverter is connected to the water heater.
- Subject to any statutory provisions to the contrary, this warranty excludes any claims for damage to furniture, carpet, walls, foundations, or any other consequential loss either directly or indirectly due to leakage from the water heater, or due to leakage from fittings and/ or pipework of metal, plastic or other materials caused by water temperature, workmanship or other modes of failure.
- If the water heater is not sized to supply the hot water demand in the guidelines in the Solahart water heater literature, any resultant fault will not be covered by the Solahart warranty.
WHAT IS COVERED BY THE SOLAHART WARRANTY FOR THE WATER HEATERS DETAILED IN THIS DOCUMENT
- Solahart will repair or replace a faulty component of your water heater if it fails to operate by its specifications as follows:
What components are covered
| The period from the date of installation in which the fault must appear
to be covered| What coverage do you receive
---|---|---
180HAV models
All components| Year 1| Repair and/or replacement of the faulty
component, free of charge, including labor.
---|---|---
All components
(if the water heater is installed in a single-family domestic dwelling)
| ****
Year 2
| ****
Repair and/or replacement of the faulty component, free of charge, including labor.
Sealed System * components (if the water heater is installed in a single- family
domestic dwelling)
| ****
Years 2 & 3
| ****
Repair and/or replacement of the faulty component, free of charge, including labor.
The cylinder
(if the water heater is installed in a single-family domestic dwelling)
| Years 2 & 3| Repair and/or replacement of the cylinder, free of charge, including labor.
Years 4 to 7
| Replacement cylinder, free of charge. Installation and repair labor costs
are the responsibility of the owner.
The cylinder
(if the water heater is not installed in a single-family domestic dwelling)
| ****
Years 2 & 3
| Replacement cylinder, free of charge. Installation and repair labor costs are the responsibility of the owner.
- The Sealed System includes components that carry refrigerant only, e.g. Compressor, Condenser, TX Valve, Receiver / Drier, Evaporator, and associated pipe work.
HEAT PUMP WATER HEATER MODELS 180HAV
Without limiting the periods shown in the table in Clause 3.1, a 5-year whole- of-product warranty applies where a rebate has been received under Solar Victoria’s Solar Homes Program for a water heater installed from the 1st of July 2023. For further details, call 131 031. Proof of receipt of the rebate is required to be produced at the time of the service call.
ENTITLEMENT TO MAKE A CLAIM UNDER THIS WARRANTY
- To be entitled to make a claim under this warranty you need to:
- Be the owner of the water heater or have the consent of the owner to act on their behalf
- Contact Solahart without undue delay after detection of the defect and, in any event, within the applicable warranty period.
- You are not entitled to claim this warranty if your water heater:
- Does not have its original serial numbers or rating labels.
- Is not installed in Australia.
HOW TO MAKE A CLAIM UNDER THIS WARRANTY
- If you wish to claim this warranty, you need to:
- Contact Solahart on 1800 638 011 in Australia and provide the owner’s details, the address of the water heater, a contact number, and the date of installation of the water heater or if that’s unavailable, the date of manufacture and serial number (from the rating label on the water heater).
- Solahart will arrange for the water heater to be tested and assessed on-site.
- If Solahart determines that you have a valid warranty claim, Solahart will repair or replace the water heater with this warranty.
- Any expenses incurred in the making of a claim under this warranty will be borne by you.
THE AUSTRALIAN CONSUMER LAW
- Our goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or refund for a major failure and compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure.
- The Solahart warranty (set out above) is in addition to any rights and remedies that you may have under the Australian Consumer Law.
SAFETY, WARNINGS, INSTALLATION NOTES
You must read the following Safety Warnings and Relief Valves information.
SAFETY AND WARNINGS
-
The heat pump will operate until a water temperature of 60°C to 70°C is reached, depending upon the Hot Water Temperature Set Point. If the ambient air temperature is outside of the heat pump’s operating range and the heating of water is required, an electric heating unit will heat the water to this setting.
These temperatures are sufficiently hot to cause severe scalding. Water at this temperature may have been plumbed to fixtures where water hotter than 50°C is allowed, such as the kitchen and laundry. Refer to;- “How Hot Should the Water Be?” on page 11, and
- “Hotter Water Increases the Risk of Scald Injury” on page 11, and
- “Temperature Adjustment”.
-
This water heater is only intended to be operated by persons who have the experience or the knowledge and capabilities to do so.
-
This water heater is not intended to be operated by persons with reduced physical, sensory, or mental capabilities i.e. the infirm, or by children. Children should be supervised to ensure they do not interfere with or play with the water heater.
-
If the electrical supply conduit to the water heater is damaged, it must be replaced by a qualified person to avoid a hazard. Phone Your nearest Solahart Dealer to arrange for an inspection.
-
This water heater uses 220 V – 240 V a.c. electrical power for the operation of the control systems and the electrically operated components. The removal of the access covers will expose 220 V – 240 V a.c. wiring. They must only be removed by a qualified person. Do not operate the water heater with any of the covers removed.
-
This water heater is supplied with an electronic thermostat, an over-temperature energy cutout, and a combination temperature pressure relief valve. These devices must not be tampered with or removed. The water heater must not be operated unless each of these devices is fitted and is in working order. The Solahart warranty may not cover faults if the relief valve or other safety devices are tampered with or if the installation is not per these instructions.
-
DANGER: The operation of the over-temperature cut-out on the thermostat indicates a possibly dangerous situation. If the over-temperature cut-out operates, it must not be reset and the water heater must be serviced by a qualified person.
-
For the continued safety of this water heater, it must be installed, operated, and maintained per the Owner’s Guide and Installation Instructions.
-
The lever on the temperature pressure relief valve and expansion control valve (if fitted) requires to be operated every six (6) months to clear any deposits and to ensure the valve and its drain line are not blocked. Refer to;
- “Relief Valves” on page 8, and
- “Minor Maintenance Every Six Months” on.
-
Servicing of the water heater must only be carried out by qualified personnel. Phone Your nearest Solahart Dealer.
-
Only a person qualified to install or service a water heater can drain the water heater if this is required.
-
Do not modify this water heater.
-
In areas where there is a risk of freezing conditions, power must be available to the water heater at all times and the electrical supply to the water heater should not be switched off, otherwise damage could result. Refer to;
- “Freeze Protection” on page 10, and
- “To Turn Off the Water Heater”.
-
Do not use aerosols, stain removers, and household chemicals in the vicinity of this water heater while it is in operation. Gases from some aerosol sprays, stain removers, and household chemicals are corrosive to the materials used in the heat pump system.
-
Do not store swimming pool chemicals, household cleaners, etc., near the water heater.
-
Ensure the airflow, air inlet louvers, and outlet grille are not obstructed in any way at any time.
RELIEF VALVES
Temperature Pressure Relief Valve
This water heater incorporates a temperature pressure relief valve located
near the top of the water heater. This valve is essential for the water
heater’s safe operation. The valve can discharge a quantity of water through
the drain line during each heating period. This quantity should be equal to
approximately 1/50 of the hot water used, as water expands by this volume when
heated.
Expansion Control Valve
In many areas, including South Australia and Western Australia and scaling
water areas, an expansion control valve must be fitted to the cold water line
to the water heater. The expansion control valve will discharge the quantity
of water from its drain line during the heating period instead of the
temperature pressure relief valve as it has a lower pressure rating.
Valve Operation
Continuous leakage of water from either valve and its drain line may indicate
a problem with the water heater. Refer to “Temperature Pressure Relief Valve
or Expansion Control Valve Running”.
Warning: Never block the outlet of either valve or their drain lines for any reason. A relief valve drain must be left open to the atmosphere and be installed in a continuously downward direction. In locations where water pipes are prone to freezing, the relief valve drain line must be insulated and not exceed 300 mm in length before discharging into a tundish through an air gap .
Operate the easing lever on the temperature pressure relief valve and expansion control valve once every six (6) months to clear any deposits and ensure the valve and its drain line are not blocked. The lever must be raised and lowered gently. Refer to “Minor Maintenance Every Six Months”.
- Warning: Water discharged from the temperature pressure relief valve drain line will be hot. Exercise care to avoid any splashing of water by standing clear of the drain line’s point of discharge when operating either valve’s easing lever.
- DANGER: Failure to operate the easing lever on the relief valve once every six (6) months may result in the water heater cylinder failing, or under certain circumstances, exploding. If water does not flow freely from the drain line when the lever is lifted, then the water heater must be checked. Phone Your nearest Solahart Dealer to arrange for an inspection. The temperature pressure relief valve should be replaced at intervals not exceeding five (5) years and the expansion control valve should be checked for performance or replaced at intervals not exceeding five (5) years. The checking of the valve performance or replacement should occur more frequently in areas where there is a high incidence of water deposits. Refer to “Water Supplies”.
INSTALLATION NOTES
This water heater must be installed:
- by a qualified person,
- by the installation instructions,
- in compliance with the Plumbing Code of Australia (PCA) and Plumbing Standard AS/NZS 3500.4,
- This water heater is designed for outdoor installation only.
- This water heater is intended to be permanently connected to the water mains and not connected by a hose set. A braided flexible hose or semi-flexible connector may be used for connection to the water heater, where permitted by AS/NZS 3500.4.
- Refer to the dimensions diagram on page 34 for clearance requirements to provide adequate ventilation for the heat pump.
- in compliance with the Australian / New Zealand Wiring Rules AS/NZS 3000,
- Isolation switches must be installed in the electrical circuit to the water heater by the Wiring Rules, so the water heater can be switched off.
- The water heater must be directly connected to the mains power supply.
- in compliance with all local codes and regulatory authority requirements.
Installation and commissioning requirements and details for the installing plumber and licensed electrical worker are contained.
Mains pressure water supply
- The water heater is designed to operate at mains pressure by connecting directly to the mains water supply.
- The water heater is supplied with a temperature pressure relief valve with a pressure rating of 1000 kPa. If an expansion control valve has been installed on the cold water line to the water heater, this should have a pressure rating of 850 kPa.
- The maximum mains water supply pressure for the water heater is 800 kPa if an expansion control valve is not installed, or 680 kPa if an expansion control valve is installed. If the mains supply pressure in your area exceeds these values, a pressure limiting valve must be installed.
- The supply pressure should be greater than 350 kPa for true mains pressure operation to be achieved.
ABOUT YOUR WATER HEATER
WATER HEATER APPLICATION
This water heater is designed for use in a single-family domestic dwelling to
heat potable water. Its use in an application other than this may shorten its
life.
MODEL TYPE
Your Solahart® air-sourced heat pump water heater is designed for outdoor
installation only. The Solahart air-sourced heat pump water heater has a
vitreous enamel-lined steel cylinder. The model you have chosen is a 180HAV
water heater and is recommended for connection to an uninterrupted 24-hour
continuous tariff power supply. Depending upon the size of the household and
its hot water requirements and if the Electricity Retailer permits, an
extended off-peak (overnight and day) or Extended time-controlled power supply
connection of a minimum of 16 hours per day may also be suitable. A Solahart
heat pump water heater consumes less energy than an electric water heater. The
impact on an electricity account will depend on the tariff arrangement of the
water heater replaced and where you live. Contact your energy provider for
more information on tariff arrangements and cost comparisons. The water
heater’s evaporator absorbs heat from the surrounding air and transfers this
heat into the water. When hot water is drawn off and cold water enters the
tank, a sensor activates a fan, a compressor, and the heat pump control
system. The fan draws outside air in through the air inlet louvers at the top
of the water heater. Heat is absorbed from the air by an evaporator and
transferred into the water through a heat exchanger wrapped around the water
heater cylinder. The resulting cold air is then discharged through the air
outlouversvres back into the atmosphere. This process continues while every
heating is required until the water in the storage tank reaches a temperature
of 60°C to 70°C, depending upon the Hot Water Temperature Set Point.
Even on cloudy or cold days, heat is drawn from the surrounding air. The heat pump will operate when the ambient air temperature is from -7°C to 43°C. The electric heating unit will operate when the ambient air temperature falls below -7°C or rises above 43°C if heating is required. The efficiency of the heat pump increases as the surrounding ambient air temperature increases. Automatic safety controls are fitted to the water heater to provide safe and efficient operation.
ELECTRIC BOOSTING
Ice may begin to form on the evaporator reducing the heat pump efficiency,
when the ambient air temperature falls below 7°C and the heat pump has been
operating for an extended period. If the heat pump operates between -7°C and
7°C for longer than 3 hours 20 minutes, the electric heating unit will turn on
to assist in the heating of the water. At ambient air temperatures below -7°C,
the water heater deactivates the heat pump operation and switches to the
electric heating unit. During these periods the evaporator will defrost if
necessary. When operating at a temperature outside of the heat pump’s
operating range, the electric heating unit will heat the water in the water
heater. The water will be heated to the Hot Water Temperature Set Point.
FREEZE PROTECTION
The water heater has an active de-frost function so the heat pump operates
automatically to remove ice that may form on its evaporator coil. The water
heater also has a freeze protection function built in for extremely cold
conditions. When a power supply is available to the water heater and the
Display Panel is turned off at the water heater, the electric heating unit
will automatically turn on if the water temperature in the water heater falls
to 5°C. It will heat the water until the water temperature reaches 10°C and
then turn off. The water heater has NO WARRANTY for freeze damage if power is
unavailable at the water heater.
Warning: In areas where the ambient air temperature may fall below 4°C, power must be available to the water heater at all times.
HOW HOT SHOULD THE WATER BE?
The system controls (compressor, evaporator, and fan) will operate until a
water temperature of 60°C to 70°C is reached, depending upon the Hot Water
Temperature Set Point. If the ambient air temperature is outside of the heat
pump’s operating range, the water temperature is boosted automatically to the
Hot Water Temperature Set Point by the electric heating unit, if heating is
required.
HOTTER WATER INCREASES THE RISK OF SCALD INJURY
Warning: This water heater can deliver hot water at temperatures up to 70°C,
sufficiently hot to cause severe scalding. Water at this temperature may have
been plumbed to fixtures where water hotter than 50°C is allowed, such as the
kitchen and laundry. Check the water temperature before use, such as when
entering a shower or filling a bath or basin, to ensure it is suitable for the
application and will not cause scald injury.
We recommend and it may also be required by regulations that an apprtemperature-limiting device be fitted into the hot water pipework to the bathroom and ensuite when this water heater is installed. This will keep the water temperature below 50°C in the bathroom and ensuite. The risk of scald injury will be reduced and still allow hotter water in the kitchen and laundry.
TEMPERATURE ADJUSTMENT
The Hot Water Temperature Set Point for the heat pump and electric heating
unit is adjustable from 60°C to 70°C. This is the temperature to which the
Heat Pump and electric heating unit will heat the water and then cut out.
Refer to “Hot Water Temperature Set Point”.
DISPLAY PANEL
The water heater has a Display Panel to indicate the status of the water
heater. The Display Panel also allows the user to select the Hot Water
Temperature Set Point and use the Timer function. Refer to “Display Panel”.
TIMER CONTROL
A timer function on the Display Panel allows the hours of operation of the
water heater to be set. Refer to “Clock and Timer” on page 18. The clock and
timer functions were introduced to the 180HAV model water heaters manufactured
on the 29th of January 2024. It may be desirable for the water heater not to
operate between certain hours, such as during the peak period when connected
to a Time of Use electricity supply due to a more expensive tariff rate
applying. Setting the timer will affect the operating times of both the heat
pump circuit and the electric heating unit. Consideration must be given to the
time allowed to heat the water in the water heater in cold conditions.
Note: If there is a risk of freezing conditions, the electrical supply to the water heater should not be switched off, otherwise damage could result. Refer to “Freeze Protection”.
PRECAUTIONS
The water heater must be maintained by the Owner’s Guide and Installation
Instructions. Refer to “Maintenance Requirements” on page 22 and to “Anode
Inspection and Replacement”. If this water heater is to be used where an
uninterrupted hot water supply is necessary for your application or business
you should ensure that you have back-up redundancy within the hot water system
design. This should ensure the continuity of the hot water supply if this
water heater becomes inoperable for any reason. We recommend you seek advice
from your plumber or specifier about your needs and building backup redundancy
into your hot water supply system.
TO TURN OFF THE WATER HEATER
If it is necessary to turn off the water heater:
- Switch off the electrical supply at the water heater isolating switch on the switchboard or at the isolating switch at the water heater.
- Close the cold water isolation valve at the inlet to the water heater.
Note: If there is a risk of freezing conditions, the electrical supply to the water heater should not be switched off at the isolating switch, otherwise damage could result. Refer to “Freeze Protection”.
TO TURN ON THE WATER HEATER
- Open the cold water isolation valve fully on the cold water line to the water heater.
- Switch on the electrical supply at the water heater isolating switch on the switchboard and at the isolating switch at the water heater.
- Check and if required turn the water heater on at the Display Panel.
Note: When the electrical supply is switched on, there will be a knocking sound coming from the heat pump for a short period. This is the electronic expansion valve operating. This is normal and not a fault with the heat pump.
HEAT PUMP OPERATION
The heat pump may take up to 5 minutes to commence operating when the power
supply is switched on. The heat pump will only operate when:
- power is available at the water heater, and
- the water in the storage tank requires heating, and
- the water temperature in the lower part of the water heater is greater than 11°C below the Hot Water Temperature Set Point.
If the ambient air temperature is below -7°C or above 43°C and the system calls for heating, the heat pump will not operate, and the electric heating unit will operate instead. When the heat pump is operating, the system may switch to the electric heating unit if it detects that the ambient air temperature is below the minimum operating temperature of -7°C or above the maximum operating temperature of 43°C. It may also switch back to heat pump operation from the electric heating unit if it detects the ambient air temperature has moved back to within the heat pump’s operating temperature range.
Note: The heat pump may not turn on after having just completed a heating cycle and more hot water is drawn from the water heater, or whilst the heat pump was operating and either power was switched off or it was turned “Off” at the Display Panel. The heat pump will wait a few minutes before operating and the conditions for start-up are favorable.
GOING ON HOLIDAYS
- If you plan to be away from home for a few nights, we suggest you leave the water heater switched on.
- If you plan to be away for a longer period, you can conserve energy by turning the water heater off at the Display Panel. The electrical supply remains available to the water heater. The heat pump and electric heating unit are prevented from operating under normal operation. The electric heating unit will operate as part of the freeze protection function if the water in the water heater falls to 5°C. Refer to “Turn the water heater “Off” at the Display Panel” on page 17 and “Freeze Protection Function” on page 21.
- It is not advised to switch off the water heater at the isolating switch if there is a risk of freeze conditions. Refer to “To Turn Off The Water Heater”.
VICTORIAN CUSTOMERS
Notice to Victorian Customers from the Victorian Building Authority. This
water heater must be installed by a licensed person as required by the
Victorian Building Act 1993. Only a licensed person will give you a Compliance
Certificate, showing that the work complies with all the relevant Standards.
Only a licensed person will have insurance protecting their workmanship for 6
years. Make sure you use a licensed person to install this water heater and
ask for your Compliance Certificate.
DOES THE WATER CHEMISTRY AFFECT THE WATER HEATER?
The water heater is suitable for most public water supplies, however, some
water chemistries may have detrimental effects on the water heater, its
components, and fittings. Refer to “Water Supplies” on page 24. If you are in
a known harsh water area or you are not sure of your water chemistry, have
your water checked against the conditions described.
HOW LONG WILL THE WATER HEATER LAST?
The water heater is supported by a manufacturer’s warranty (refer to page 4).
There are several factors that will affect the length of service the water
heater will provide. These include but are not limited to the water chemistry,
the water pressure, the water temperature (inlet and outlet), and the water
usage pattern. Refer to “Precautions”.
ENVIRONMENT
At the end of the service life of the heat pump water heater and before the
water heater being disposed of, a person qualified to work with refrigerants
must recover the refrigerant from within the sealed system. The refrigerant
must not be vented to the atmosphere. Phone Your nearest Solahart Dealer to
arrange for an inspection.
DISPLAY PANEL
DISPLAY PANEL AND ICONS
The water heater has a Display Panel to allow the user to view the current
operational status of the water heater and to enable user input functionality.
LEDs on the Display Panel illuminate to display icons when there is power to
the water heater and the water heater is turned on at the Display Panel. The
display icons provide information on the water heater’s current operational
status and mode setting, average water temperature in the water heater, water
temperature setting of the heat pump and electric heating unit, usable hot
water quantity available, the time, timer function settings, and fault codes.
The Display Panel also has printed Selection Keys to enable the user to change
the Hot Water Temperature Set Point, turn the water heater on or off at the
Display Panel, set or change the time setting, and set the Timer.
- Refer to “Display Panel – Display Icons and Selection Keys” on page 15 to view the Display icons and Selection Keys that display on the Display Panel.
- Refer to “Display Icons and Selection Keys Explained” on page 16 for an explanation of each of the icons and keys.
Memory – The water heater has a memory function. When the electricity supply is switched on to the water heater after having been switched off, or if electricity is reinstated to the water heater after a time-controlled electricity supply period, previous settings remain stored. The water heater and heat pump will return to the programmed state at the time the electricity supply is interrupted. It is necessary to turn the water heater “On” at the Display Panel after the electricity supply is switched on to the water heater at the water heater isolating switch for the first time. The water heater must be “On” at the Display Panel for the heat pump and electric booster unit to operate and heat the water and for the Display icons to illuminate.
FUNCTIONS AND OPERATIONAL MODES OF THE WATER HEATER
Hot Water Temperature Set Point
The Hot Water Temperature Set Point is the water temperature to which the Heat
Pump and electric heating unit will heat the water. It is user-adjustable from
60°C to 70°C. Refer to “Hot Water Temperature Set Point”.
Water Temperature Display
The average water temperature in the water heater is displayed in the Main
Display Area of the Display Panel. Refer to “Display Panel – Display Icons and
Selection Keys” on page 15 for the Main Display Area.
ECO Mode
This is the standard heating mode. The ECO (Energy Conservation Only) Mode
allows the Heat Pump to operate when heating is required, and the ambient
temperature is within the heat pump’s operating range of -7°C to 43°C. Refer
to “ECO Mode”.
Useable Hot Water Quantity Display
The Display Panel features a Useable Water Quantity display icon. This icon
indicates the quantity of usable hot water in the water heater. Refer to
“Useable Water Quantity Display”.
Clock and Timer Function
- The water heater has a clock function to enable the time to be displayed. It is necessary to set the clock to use the timer setting function of the water heater.
- The Timer function enables one time period to be set in 24 hours. The Timer can be used to control the time of operation of the heat pump.
- The clock and timer functions were introduced to the 180HAV model water heaters manufactured on the 29th of January 2024.
- Refer to “Clock and Timer”.
Fault Codes
In the event the water heater develops a fault, a code will display in the
Main Display Area This function of the water heater indicates to the user a
service call is required. Refer to “Fault Codes”.
Freeze Protection Function
The water heater has a freeze protection function built in for extremely cold
conditions to protect the water heater when the Display Panel is turned off at
the water heater. Refer to “Freeze Protection Function”.
DISPLAY PANEL – DISPLAY ICONS AND SELECTION KEYS
DISPLAY ICONS AND SELECTION KEYS EXPLAINED
Note – On / Off Key : The On / Off key only turns the Heat Pump and electric heating unit “Off” at the Display Panel. It does not switch off or isolate the electricity supply to the water heater or Display Panel. If it is necessary to switch off the electricity supply to the water heater, then this must be done at the water heater isolating switch on the switchboard or at the isolating switch adjacent to the water heater.
TURNING THE WATER HEATER “ON” OR “OFF” AT THE DISPLAY PANEL Turn the water heater “On” at the Display Panel
- Press the “On / Off” key.
- The average water temperature in the water heater illuminates in the Main Display Area.
- The time (if set) illuminates in the Timer / Clock Display Area.
- The ECO Operational Mode icon illuminates.
- The Useable Water Quantity icon bars illuminate (if the water is hot).
- The Timer / Clock icon illuminates if the Timer is set.
- The Display Panel will remain fully illuminated for three (3) minutes if a key is not pressed or after a key is pressed. It will then dim.
Note: When the water heater is turned on at the Display Panel after the electrical supply is switched on at the isolating switch, there may be a knocking sound coming from the heat pump for a short period. This is the electronic expansion valve operating. This is normal and not a fault with the heat pump. This knocking sound may also occur when the water heater is reconnected to power from a time-controlled electrical supply after having been off.
Reilluminating the Display Panel
- To reilluminate the Display Panel fully after it has dimmed, press the “On / Off” key.
Turn the water heater “Off” at the Display Panel
- Press the “On / Off” key.
- The average water temperature display in the Main Display Area goes out.
- The Time display and ECO Operational Mode icon go out.
- The Useable Water Quantity icon bars go out.
Note: If the Display Panel is in the ‘dimmed’ state, it will be necessary to press the “On / Off” key twice. The first press reilluminates the Display Panel fully, the second press turns off the water heater at the Display Panel.
HOT WATER TEMPERATURE SET POINT
The Hot Water Temperature Set Point is the temperature to which the Heat Pump
and/or the electric heating unit will heat the water and then cut it out.
- The default Hot Water Temperature Set Point is 60°C.
- The maximum Hot Water Temperature Set Point is 70°C.
- The minimum Hot Water Temperature Set Point is 60°C.
To change the Hot Water Temperature Set Point:
- Ensure the water heater is turned On at the Display Panel. The current average water temperature in the water heater is displayed in the Main Display area. The time, ECO Mode icon, and Useable Hot Water Quantity Display icon are also displayed.
- Press the “Up Arrow” or “Down Arrow” Key to display the Temperature Set Point.
- Each press of the “Up Arrow” or the “Down Arrow” Key will increase or decrease the Temperature Set Point in 1°C increments.
The selected temperature will flash five times before turning solid.
ECO MODE
The ECO (Energy Conservation Only) Mode is the standard day-to-day operational
and heating mode by the heat pump. This mode allows for the Heat Pump to
operate during normal operation when heating is required. The ECO icon
illuminates on the Display Panel.
The heat pump will operate when there is:
- electricity supply to the water heater, and
- the water heater is turned “On” at the Display Panel, and
- the water temperature in the lower part of the water heater is greater than 11°C below the Hot Water Temperature Set Point, and
- the ambient temperature is between the heat pump’s operating range of -7°C to 43°C.
If the heat pump operates between -7°C and 7°C for an extended period, the electric heating unit may turn on to assist in the heating of the water. The electric heating unit will operate if the ambient air temperature is outside of the heat pump’s operating range of -7°C to 43°C and heating of the water is required.
USEABLE HOT WATER QUANTITY DISPLAY
The Display Panel features a Useable Hot Water Quantity display icon. This
icon indicates the quantity of usable hot water in the water heater. The more
bars illuminated, the more hot water there is available. The display ranges
from no illumination of bars, which indicates the average temperature of the
water in the water heater is below 36°C, to the illumination of twenty-five
bars, which indicates the water heater is full of hot water. The number of
bars illustrates the average water temperature in the water heater calculated
from the water temperature in both the upper part and lower part of the water
heater. It is an approximation only.
The first solid vertical bar represents an average tank temperature of 36°C. Each subsequent solid bar represents an increase of average water temperature in the water heater by 1°C. When all 25 bars are illuminated solid, the average tank temperature is 60°C or above. It may be above 60°C if the Hot Water Temperature Set Point is greater than 60°C. Whilst the water heater is heating water, the illuminated bars will fluctuate back and forth from left to right.
CLOCK AND TIMER
The clock and timer functions were introduced to the 180HAV model water
heaters manufactured on the 29th of January 2024.
Clock
The water heater has a clock function. The clock must be set to use the timer
setting function of the water heater. The setting of the clock includes hours
and minutes only. It does not include day, month, or year. Once the clock is
set, the time in hours and minutes is displayed in the Timer / Clock Display
when the water heater is “On” at the Display Panel. The clock is a 24-hour
clock, i.e. if the time is 4:30 PM, it will show as 16:30 on the clock.
Timer
The water heater has a Timer function. One timed period can be set within 24
hours. The Timer operates over 24 hours, it does not allow for days or months
to be programmed. It may be desirable for the water heater not to operate
between certain hours, such as during the peak period when connected to a Time
of Use electricity supply due to a more expensive tariff rate applying.
Setting the timer will affect the operating times of both the heat pump
circuit and the electric heating unit. The Timer displays use 24-hour clock,
i.e. if the time being set is 4:30 PM, it will show as 16:30.
Notes
- If a Timer period is not set, the Timer / Clock icon does not illuminate.
- When setting the Timer period, sufficient time must be allowed for the heat pump to operate and heat up all the water in the water heater to its hot water set point. The heat pump will take longer to heat water in the cooler winter months than in the warmer summer months.
- The Timer period may need to be reset at the start and finish of Daylight Saving.
- The clock and Timer period can only be set when the water heater is “Off” at the Display Panel.
- If the Timer OFF setting is earlier in the day than the Timer ON setting, then the Timer will turn OFF the following day.
- If the Timer is set and the scheduled power ON and scheduled power OFF times are the same, the scheduled power OFF setting will override the scheduled power ON setting. The heat pump will remain off and will not operate. The Display Panel and Timer / Clock icon will remain illuminated.
- If there is no action for 10 seconds during the setting of the Clock or the Timer period, the Display Panel exits the clock or Timer programming. The last programmed Clock time or Timer setting will be saved.
To set the Clock
-
Turn the water heater “Off” at the Display Panel.
- Press the “On / Off” key. The displays and icons go out. The Display Screen is blank.
Note: If the Display Panel is in the ‘dimmed’ state, it will be necessary to press the “On / Off” key twice. The first press reilluminates the Display Panel fully, the second press turns off the water heater at the Display Panel.
- Press the “On / Off” key. The displays and icons go out. The Display Screen is blank.
-
Activate the Clock setting screen.
- Press the “MODE” key 3 times. A beeping sound will be heard with each press of the key. If the beeping sound is not heard at the press of the key, then press the key again. Use the sound feedback to help with the press count. The current Time setting illuminates in the Timer / Clock Display and the hour digits commence to flash. A colon separates the hour digits (on the left) and minute digits (on the right) on the display.
-
Set the Clock time.
- Press the “Up” key or “Down” key to select the hour digits.
- Press the “Mode” key to save the hour digits. The minute digits commence to flash.
- Press the “Up” key or “Down” key to select the minute digits.
- Press the “Mode” key to save the minute digits.
Note: The display switches to the Timer setting. Proceed to Step 1 of “To set the Timer” on page 20 if a Timer period is to be set. Either ‘oN’ or ‘oF’ will flash in the Main Display Area. The Timer / Clock icon will also flash. If a Timer period is not to be set and ‘oN’ is flashing in the Main Display area, then:
- Press the “Down” key. ‘oF’ will commence flashing in the Main Display Area.
- Press the “Mode” key.
The ‘oF’ icon goes out and the Display Panel is blank. The water heater remains “OFF” at the Display Panel. It will be necessary to turn the water heater “ON” again at the Display Panel.
To set the Timer
-
Set the Timer ON time.
- If a Timer period is to be set and ‘oF’ is flashing in the Main Display area, then:
- Press the “Up” key. ‘oN’ will commence flashing in the Main Display Area.
- Press the “Mode” key. The hour digits flash in the Timer / Clock Display Area. The Timer ON and Timer / Clock icons illuminate and flash.
- Press the “Up” key or “Down” key to select the hour digits.
- Press the “Mode” key to save the hour digits. The minute digits commence to flash.
- Press the “Up” key or “Down” key to select the minute digits.
- Press the “Mode” key to save the minute digits. The Timer ON icon goes out. The Timer OFF and Timer / Clock icons illuminate and flash. The hour digits flash in the Timer / Clock Display Area.
-
Set the Timer OFF time.
- Press the “Up” key or “Down” key to select the hour digits.
- Press the “Mode” key to save the hour digits. The minute digits commence to flash.
- Press the “Up” key or “Down” key to select the minute digits.
- Press the “Mode” key to save the minute digits.
The Display returns to an off-state. The displays and icons go out. The Display Screen is blank.
-
Turn the water heater “On” at the Display Panel
- Refer to “Turn the water heater “On” at the Display Panel”.
To turn the Timer Function Off
To turn the Timer function off, so power is available to the heat pump 24
hours a day :
- Turn the water heater “Off” at the Display Panel and activate the Clock setting screen.
- Follow Steps 1 and 2 of the procedure “To Set the Clock” on page 19. The hour digits in the Timer / Clock Display commence to flash.
- Turn the Timer Function off.
- Press the “Mode” key. The minute digits commence to flash.
- Press the “Mode” key a second time. The Timer / Clock Display goes out. ‘oN’, displayed in the Main Display Area, and the Timer / Clock icon both commence to flash. If ‘oF’ is flashing in the Main Display Area instead of ‘oN’, there is no need to press the “Down” key.
- Press the “Down” key. ‘oF’ flashes in the Main Display Area and the Timer / Clock icon continues to flash.
- Press the “Mode” key a third time. The Timer / Clock icon and ‘oF’ in the Main Display Area go out and the Display Panel is blank. The Timer is no longer set. The water heater remains “OFF” at the Display Panel. It will be necessary to turn the water heater “ON” again at the Display Panel.
FAULT CODES
The Main Display Area will display a fault code in the event the water heater
develops a fault. In addition, a one off six (6) second beeping alarm will
sound from the Display Panel if a fault code is displayed. The fault code will
display alternately with the average water temperature in the water heater. If
there is more than one fault code, each code will display alternately with the
other fault code(s) and the average water temperature.
The fault codes that may appear are:
- E0, E2, E3, E4, E5, E6, E7, E8, EF – The heat pump will not operate. The electric heating unit will operate to heat the water when heating is required, to provide hot water until a service call is made to repair the fault.
- EA – The heat pump and electric heating unit will not operate and there will be no heating of the water.
- EC – The heat pump and electric heating unit will not operate. This is an over-temperature fault which will reset when the water in the bottom two-thirds of the tank is replaced with cold water as hot water is drawn off. If the fault reoccurs, a service call must be made.
If one or more of the above codes is displayed on the Display Panel, make a note of the fault code(s) and phone Your nearest Solahart Dealer to arrange for an inspection.
FREEZE PROTECTION FUNCTION
The water heater has a freeze protection function built in to protect the
water heater in extremely cold conditions and the water temperature in the
water heater falls to 5°C. This condition will only occur if the Display Panel
is turned off at the water heater. The power supply to the water heater must
be turned on at the isolating switch and power must be available to the water
heater. The electric heating unit will automatically turn on if the water
temperature in the water heater falls to 5°C. It will heat the water until the
water temperature reaches 10°C and then turn off. The code Fd and the Heating
Indicator Icon will illuminate solid in the Display area of the Display Panel.
MAINTENANCE REQUIREMENTS
MINOR MAINTENANCE EVERY SIX MONTHS
It is recommended minor maintenance be performed every six (6) months. Minor
maintenance can be performed by the dwelling occupant. Switch off the
electrical supply at the power outlet to the water heater prior to performing
general maintenance. This will prevent the water heater from operating while
you clean or spray around the water heater. Switch on the electrical supply at
the power outlet to the water heater when finished performing the general
maintenance.
The minor maintenance includes
-
Operate the easing lever on the temperature pressure relief valve. The lever must be raised and lowered gently. Refer to “Relief Valves”.
- Warning: Water discharged from the temperature pressure relief valve drain line will be hot. Exercise care to avoid any splashing of water by standing clear of the drain line’s point of discharge when operating the valve’s easing lever.
-
Operate the easing lever on the expansion control valve. The lever must be raised and lowered gently. Refer to “Relief Valves”.
If water does not flow freely from the drain line of either the temperature relief valve or expansion control valve when the easing lever is operated, phone Your nearest Solahart Dealer to arrange for an inspection. -
The jacket of the water heater can be cleaned with a soft cloth and warm mild soapy water if required. Under no circumstances should abrasive materials or powders be used.
-
Inspect around the air inlet and outlet louvres and the water heater in general for plant growth.
-
Trim back any shrubs, bushes or other plants which have encroached around the water heater. Plant growth across the air inlet and outlet louvers can interfere with the performance of the water heater.
-
Inspect around the water heater for infestations of insects, such as ants. Insects encroaching into or nesting in the water heater can interfere with the operation of the water heater and also damage components. The area around the water heater can be sprayed with insecticide to rid the area of insects.
- Warning: Do not spray insecticide near the water heater while the heat pump is operating.
-
If necessary to rid the area of insects:
- Ensure the electrical supply at the power outlet to the water heater has been switched off.
- Spray the affected are, taking care not to spray into the air inlet or outlet louvers or onto the surface of the water heater.
- Wait a few minutes to allow any aerosol gases to dissipate before switching on the electrical supply at the power outlet to the water heater.
-
Inspect and check the condensate drain hose.
- Remove the drain hose from the drain spigot towards the rear of the heat pump. Use a garden hose to run water through the drain hose and dislodge any foreign bodies. Reconnect the drain hose to the drain spigot. Ensure the garden hose and drain hose are well clear of the heat pump and its components.
MAJOR SERVICE EVERY FIVE YEARS
It is recommended a major service be conducted on the water heater every five
(5) years.
- Warning: Servicing of a water heater must only be carried out by qualified personnel. Phone Your nearest Solahart Dealer.
- Note: The major service and routine replacement of any components, such as the anode and relief valve(s), are not included in the Solahart warranty. A charge will be made for this work. Only genuine replacement parts should be used on this water heater.
The major service include:
- Replace the temperature pressure relief valve.
- Inspect and flush the expansion control valve (if fitted). If required, replace the valve.
- Inspect and if required, replace the anode. If the anode is not replaced, it should be replaced within three years of this service. Refer to “Anode Inspection and Replacement”.
- Check the electric heating unit for excessive calcium build-up or corrosion and replace if necessary.
- Flush the water heater tank (if required).
- Check and clean the heat pump of dust and residue.
- Check and inspect the heat pump for operation.
- Visually check the unit for any potential problems.
- Inspect all connections.
- Inspect the air inlet and outlet louvers and the water heater in general for plant growth.
- Inspect the water heater for infestations of insects, such as ants.
- Inspect and check the condensate drain hose.
- Check the items covered in the minor maintenance
Note: The water heater may need to be drained during this service. After the completion of the service, the water heater will take some time to reheat the water. Depending upon the power supply connection, hot water may not be available until the next day.
HEAT PUMP SYSTEM
It is recommended the evaporator and refrigeration system is checked every
five years. In particularly dusty environments, it may be necessary to have
the heat pump system checked and cleaned of dust and residue on a more regular
basis.
WATER SUPPLIES
This water heater must be installed by this advice to be covered by the Solahart warranty. This water heater is manufactured to suit the water conditions of most public reticulated water supplies. However, some known water chemistries can have detrimental effects on the water heater and its operation and / or life expectancy. If you are unsure of your water chemistry, you may be able to obtain information from your local water supply authority. This water heater should only be connected to a water supply that complies with these guidelines for the Solahart warranty to apply.
CHANGE OF WATER SUPPLY
Changing or alternating from one water supply to another can have a
detrimental effect on the operation and/or life expectation of a water heater
cylinder, a temperature pressure relief valve, and a heating unit. Where there
is a changeover from one water supply to another, e.g. a rainwater tank
supply, bore water supply, desalinated water supply, public reticulated water
supply or water brought in from another supply, then water chemistry
information should be sought from the supplier or it should be tested to
ensure the water supply meets the requirements given in these guidelines for
the Solahart warranty to apply.
ANODE
The vitreous enamel-lined cylinder of the water heater is only covered by the
Solahart warranty when the total dissolved solids (TDS) content in the water
is less than 2500 mg/L and when the correct color-coded anode is used. If an
incorrect color-coded anode is used in the water heater, any resultant faults
will not be covered by the Solahart warranty. In addition, the use of an
incorrect color-coded anode may shorten the life of the water heater cylinder.
The correct color-coded anode is as shown in the following table:
Total Dissolved Solids | Anode colour code |
---|---|
0 – 40 mg/L | Green |
40 – 150 mg/L | Green or Black |
150 – 400 mg/L | Black |
400 – 600 mg/L | Black or Blue |
600 – 2500 mg/L | Blue |
2500 mg/L + | Blue (no cylinder warranty) |
The changing of anodes must be carried out by a qualified person.
Note: Some water analysis reports may state the conductivity of the water rather than the level of total dissolved solids. Conductivity, measured in micro siemens per centimetre (µS / cm), is directly proportional to the TDS content of the water. TDS, in mg / L, is approximately 70% of the conductivity in µS / cm.
ANODE INSPECTION AND REPLACEMENT
The anode installed in your water heater will slowly dissipate whilst
protecting the cylinder. The life of the cylinder may be extended by replacing
the anode. For water supplies which are either softened or desalinated, or
where the water supply may alternate between a water tank and a reticulated
public supply or another supply, or where there is a variable supply (e.g.
from a bore or public reticulated supply from various water sources), the
anode must be inspected (and replaced if there is any sign of depletion)
within five (5) years of its installation. For all water supplies, if the
anode is not replaced during a major service (refer to “Major Service Every
Five Years” on page 23) then the maximum time after installation when the
anode should be replaced for this water heater is eight (8) years.
CAUTION
If the water supply has a TDS greater than 150 mg/L and a green anode has not
been changed to a black anode, or if the TDS is greater than 600 mg/L and the
anode has not been changed to a blue anode, there is the possibility the anode
may become overactive and hydrogen gas could accumulate in the top of the
water heater during long periods of no use. If, under these conditions, the
water heater has not been used for two or more weeks the following procedure
should be carried out before using any electrical appliances (automatic
washing machines and dishwashers) which are connected to the hot water supply.
The hydrogen, which is highly flammable, should be vented safely by opening a
hot tap and allowing the water to flow. There should be no smoking or naked
flame near the tap whilst it is turned on. Any hydrogen gas will be
dissipated. This is indicated by an unusual spurting of the water from the
tap. Once the water runs freely, any hydrogen in the system will have been
released.
SATURATION INDEX
The saturation index (SI) is used as a measure of the water’s corrosive or
scaling properties. The saturation index figures stated are calculated using a
water temperature of 80°C. In a corrosive water supply, the water can attack
copper parts and cause them to fail. Where the saturation index is less than
–1.0, the water is very corrosive, and the Solahart warranty does not apply to
a copper-sheathed heating unit. An Incoloy sheathed heating unit is supplied
with this water heater. In a scaling water supply calcium carbonate is
deposited out of the water onto any hot metallic surface. Where the saturation
index exceeds +0.40, the water is very scaling. An expansion control valve
must be fitted on the cold water line after the non-return valve to protect
and for the Solahartwarranty to apply to the temperature pressure relief valve
and water heater cylinder. Where the saturation index exceeds +0.80, the
Solahart warranty does not apply to a standard watts density heating unit. A
low-watt-density heating unit is supplied with this water heater. Water that
is scaling may be treated with a water-softening device to reduce the
saturation index of the water. Refer to the Saturation Index chart on page 26.
Refer to the cold water connection diagram on page 37 for the position of the
expansion control valve.
SUMMARY OF WATER CHEMISTRY ADVICE AFFECTING WARRANTY
The water heater is not suitable for certain water chemistries. Those
chemistries are listed below. If the water heater is connected at any time to
a water supply with the following water chemistry, the Solahart warranty will
not cover any resultant faults:
Water Chemistry /Component
- Total Dissolved Solids (TDS) > 2500 mg/L water heater cylinder
- Total Dissolved Solids (TDS) are not suitable for anode-type water heater cylinder
- Saturation Index (SI) < -1.0 copper sheathed heating unit
- Saturation Index (SI) > +0.4 (if the expansion control valve is not fitted)
- water heater cylinder temperature pressure relief valve
- Saturation Index (SI) > +0.8 standard watts density heating unit
Check the items below before making a service call. You will be charged for attending to any condition or fault that is not related to manufacture or failure of a part.
NOT ENOUGH HOT WATER (OR NO HOT WATER)
Is the electricity switched on?
Inspect the isolating switch marked “HOT WATER” or “WATER HEATER” at the
switchboard and the isolating switch at the water heater and ensure they are
turned on. Check the fuse or circuit breaker marked “HOT WATER” or “WATER
HEATER” at the switchboard.
Has the Timer been set?
If the Timer has been set, ensure sufficient time has been allowed to reheat
the storage tank.
Are you using more hot water than you think?
Is one outlet (especially the shower) using more hot water than you think?
Very often it is not realized the amount of hot water used, particularly when
showering. Carefully review the family’s hot water usage. As you have
installed an energy saving appliance, energy saving should also be practised
in the home. Adjust your water usage pattern to take advantage of maximum
energy gains. Have your plumber install a flow control valve to each shower
outlet to reduce water usage.
Heat pump fault
Is the ‘EA’ fault code is displayed on the Display Panel? The heat pump has
developed a fault. The heat pump and electric heating unit will not operate
and there will be no heating of the water. Phone Your nearest Solahart Dealer
to arrange for an inspection. Refer to “Fault Codes”. Also refer to “Heat Pump
Is Not Operating”.
Relief valve running
- Is the relief valve discharging too much water?
- Refer to “Temperature Pressure Relief Valve or Expansion Control Valve Running”.
THE WATER IS NOT HOT ENOUGH
You may find that due to heavy hot water usage, the water temperature may be
lower than normally expected, due to insufficient heating time being allowed.
You will need to carefully plan your use of the hot water on such occasions.
WATER TOO HOT
The heat pump and electric heating unit operation will heat the water to a
temperature of 60°C up to 70°C, depending upon the Hot Water Temperature Set
Point. This is a normal operation. If the water heater Display Panel shows a
fault code ‘EC’, this indicates the water heater has developed an over-
temperature fault. The water would have been heated to 85°C. The water heater
will reset when the water in the bottom two-thirds of the tank is replaced
with cold water as hot water is drawn from the water heater. If the fault
reoccurs, a service call must be made. Refer to “Fault Codes”. Phone Your
nearest Solahart Dealer to arrange for an inspection.
HEAT PUMP IS NOT OPERATING
-
Power must be available at the water heater and the water heater switched on.
If there is power to the water heater, check the water heater has been turned “On” at the Display Panel. Refer to “Turning the Water Heater “On” or “Off” at the Display Panel” on page 15. -
Time-controlled power supply
If the water heater is connected to a time controlled power supply, then during periods of no power supply at the water heater, the heat pump and electric heating unit will not operate. This is not a fault condition, but a result of no power being available to operate the water heater. Check the hours of supply from the electricity retailer. The Display Panel will illuminate again when power is available again at the water heater.
Note: If power was cut to the heat pump whilst it was operating, it may wait for a few minutes before recommencing to operate when power is restored and if heating is required. -
Heat pump operating range
The heat pump’s operating range is when the ambient air temperature is from -7°C to 43°C. It will not operate outside of this temperature range. The electric heating unit will operate if the ambient air temperature is outside of the heat pump’s operating range and heating of the water is required. The water in the water heater will be heated to the Hot Water Temperature Set Point. -
Possible fault condition
If the heat pump has developed a fault, the heat pump will not operate, and a fault code will be displayed on the Display Panel in the Main Display Area. In this condition and depending upon the fault code, if heating of the water is required, the electric heating unit will operate automatically to heat the water in the water heater. Refer to “Fault Codes”.Take note of the fault code and phone Your nearest Solahart Dealer to arrange for an inspection.
TEMPERATURE PRESSURE RELIEF VALVE OR EXPANSION CONTROL VALVE RUNNING
-
Normal Operation
It is normal and desirable the temperature pressure relief valve or expansion control valve (if fitted) allows a quantity of water to escape during the heating cycle. This quantity should be equal to approximately 1/50 of the hot water used, as water expands by this volume when heated. However, if it discharges more than a bucket full of water in 24 hours, there may be another problem. The expansion control valve (if fitted) will discharge water instead of the temperature pressure relief valve as it has a lower pressure rating. A benefit is that energy is conserved as the discharged water is cooler. This valve is installed in the cold water line to the water heater. Refer to the cold water connection diagram. -
Continuous dribble
Try gently raising the easing lever on the relief valve for a few seconds (refer to “Relief Valves” on page 8). This may dislodge a small particle of foreign matter and clear the fault. Release the lever gently. -
Steady flows for long periods (often at night)
This may indicate the mains water pressure sometimes rises above the designed pressure of the water heater. Ask your installing plumber to fit a pressure limiting valve.
Warning: Never replace the relief valve with one of a higher pressure rating.
- Heavy flows of hot water from the temperature pressure relief valve until the water heater is cold -then stops until the water reheats The water heater must be switched off at the isolating switch or switchboard. Phone Your nearest Solahart Dealer to arrange for an inspection.
HIGHER THAN EXPECTED ELECTRICITY BILLS
With the installation of your new air-sourced heat pump water heater,
electrical energy savings can be achieved. Should you at any time, feel your
electricity bill is higher than expected, we suggest you check the following
points:
- Is the water heater operating for extended periods with the electric heating unit? Prolonged periods of use where the ambient air temperature is outside of the heat pump’s operating range when heating is required will increase the amount of heating required by the electric heating unit to ensure a supply of hot water, increasing running costs. Refer to “Heat Pump Is Not Operating”.
- Has the water heater developed a fault? Check if an error code is displayed on the Display Panel. If the water heater has developed a fault, it may be operating with the electric heating unit only, which will increase the amount of purchased energy used. Refer to “Fault Codes”.
- Is the relief valve running excessively? Refer to “Temperature Pressure Relief Valve or Expansion Control Valve Running”.
- Is one outlet (especially the shower) using more hot water than you think? Refer to “Not Enough Hot Water”.
- Is there a leaking hot water pipe, dripping hot water tap, etc? Even a small leak will waste a surprising quantity of hot water and energy. Replace faulty tap washers, and have your plumber rectify any leaking pipe work.
- Has there been an increase in hot water usage? An increase in hot water usage will increase heat pump operation.
- Has your water heating tariff rate been increased by your electricity retailer since your previous bill?
- Is the heat pump water heater on the same tariff as the water heater replaced? The impact on an electricity account will depend upon the tariff arrangement of the water heater replaced and where you live. Contact your energy provider for more information on tariff arrangements and cost comparisons.
IF YOU HAVE CHECKED ALL THE FOREGOING AND STILL BELIEVE YOU NEED ASSISTANCE, PHONE YOUR NEAREST SOLAHART DEALER.
INSTALLATION
THIS WATER HEATER IS FOR OUTDOOR INSTALLATION ONLY. THIS WATER HEATER IS NOT SUITABLE FOR POOL HEATING.
INSTALLATION STANDARDS
The water heater must be installed:
- by a qualified person, and
- by the installation instructions, and
- in compliance with the Plumbing Standard AS/NZS 3500.4 and the Australian / New Zealand Wiring Rules AS/NZS 3000,
- in compliance with all local codes and regulatory authority requirements.
Warning: This water heater may deliver water at high temperatures. Refer to the Plumbing Code of Australia, local requirements, and these installation instructions to determine if additional delivery temperature control is required. Refer to “Hot Water Delivery”.
Victorian Installers
Notice to Victorian Installers from the Victorian Building Authority if this
solar water heater is installed in a new Class 1 dwelling in the State of
Victoria. The system model number is to be recorded on the Certificate of
Compliance. It is also a requirement to provide the householder with permanent
documentation recording the system model number exactly as it is shown in the
‘VEET Product Register’ published by the Essential Services Commission in
Victoria. See www.veu-
registry.vic.gov.au/Public/ProductRegistrySearch.aspx. This documentation may
be in the form of an indelible label adhered to the heat pump storage tank, or
other suitable form placed in an accessible location, such as the meter box,
for later inspection.
WATER HEATER APPLICATION
This water heater is designed for use in a single-family domestic dwelling to
heat potable water. Its use in an application other than this may shorten its
life. If this water heater is to be used where an uninterrupted hot water
supply is necessary for the application or business, then there should be
backup redundancy within the hot water system design. This should ensure the
continuity of the hot water supply if this water heater becomes inoperable for
any reason. We recommend you provide advice to the system owner about their
needs and build backup redundancy into the hot water supply system. The water
heater is recommended for connection to an uninterrupted 24-hour continuous
tariff power supply. Depending upon the size of the household and its hot
water requirements and if the Electricity Retailer permits, an extended off-
peak (overnight and day) or Extended time-controlled power supply connection
of a minimum 16 hours per day may also be suitable.
A Solahart heat pump water heater consumes less energy than an electric water
heater. The impact on an electricity account will depend on the tariff
arrangement of the water heater replaced and the installation location.
Contact the energy provider for more information on tariff arrangements and
cost comparisons.
TRANSPORTING AND HANDLING THE WATER HEATER
- Take care when handling the water heater. The jacket surrounding the heat pump at the top of the water heater needs to be handled gently so as not to cause damage.
- Do not tilt the water heater more than 30° from the vertical. Care must be taken during transportation and handling as the water heater is top-heavy. It will become unstable if tilted more than 30° from the vertical. The water heater must be secured during transport to avoid tipping over. To prevent injury or damage, the water heater must also be placed on a level surface. In addition, tilting the water heater more than 30° from the vertical during handling will unsettle the refrigerant gas and compressor lubricating oil. If the water heater has been tilted, it will need one hour to settle before the power to the water heater can be switched on, otherwise damage to the compressor may result. All packaging materials must be removed from the water heater prior to its installation. This includes the removal of the packaging base of the carton from the underside of the water heater.
WATER HEATER LOCATION
The water heater is suitable for outdoor installation only. The water heater should be installed close to the most frequently used outlet and its position chosen with noise, safety and service in mind. Make sure people (particularly children) will not accidentally touch the air inlet and outlet louvres and that they are clear of obstructions and shrubbery. It is advisable to install the water heater away from bedroom or living room windows as the system controls can generate a level of noise whilst they are operating. Consider the location with neighbors’ bedrooms and living room windows. Clearance must be allowed for servicing of the water heater. The water heater must be accessible without the use of a ladder or scaffold. Make sure the temperature pressure relief valve lever is accessible and the top and front cover, air inlet and outlet louvers, system controls and thermostat can be removed for service.
To maintain the designed performance, air flow and air discharge from the heat pump, and service access, the minimum distances to a wall or obstruction from the water heater are:
- 80 mm from a wall behind the water heater, and
- 850 mm on the right hand side and 500 mm on the left hand side from the air inlet louvres, and
- 700 mm above the water heater to an awning or covering, and
- 500 mm to the front of the water heater.
It is recommended to leave a minimum distance of 900 mm in front of and to the left-hand side of the water heater, where this is possible, for service access. Refer to the dimensions diagram on page 34. You must be able to read the information on the rating plate. If possible, leave headroom of one water heater height so the anode can be inspected or replaced. Remember you may have to remove the entire water heater later for servicing. The heat pump water heater is to be installed at ground or floor level and must stand vertically upright on a level, stable and impervious base designed to avoid ponding in accordance to AS/NZS 3500.4 and as acceptable to local authorities. The base of the water heater is supported on three feet, which allows for free circulation of air under the base of the water heater. The water heater must not be installed in an area with a corrosive atmosphere where chemicals are stored or where aerosol propellants are released, as exposure to the corrosive atmosphere may attack the materials used in the water heater and heat pump system.
FREEZE PROTECTION
The water heater has a freeze protection function built in for extremely cold
conditions. When a power supply is available to the water heater and the
Display Panel is turned off at the water heater, the electric heating unit
will automatically turn on if the water temperature in the water heater falls
to 5°C. It will heat the water until the water temperature reaches 10°C and
then turn off.
The water heater has NO WARRANTY for freeze damage if power is unavailable at the water heater.
Warning: In areas where the ambient air temperature may fall below 4°C, power must be available to the water heater at all times.
MAINS WATER SUPPLY
Where the mains water supply pressure exceeds that shown in the table below,
an approved pressure limiting valve is required and should be fitted as shown
in the cold water connection diagram.
Model | 180HAV |
---|---|
Temperature pressure relief valve setting | 1000 kPa |
Expansion control valve setting * | 850 kPa |
Maximum mains supply pressure | |
With expansion control valve | 680 kPa |
Without expansion control valve | 800 kPa |
- Expansion control valve not supplied with the water heater.
TANK WATER SUPPLY
If the water heater is supplied with water from a tank supply and a pressure
pump system is not installed, then the bottom of the supply tank must be at
least 1 m above the highest point of the hot water plumbing system, including
the water heater. Care must be taken to avoid air locks. The cold water line
to the water heater should be adequately sized and fitted with a full flow
gate valve or ball valve.
REDUCING HEAT LOSSES
The cold water line to and the hot water line from the water heater must be
insulated under the requirements of AS/NZS 3500.4. The insulation must be
weatherproof and UV-resistant if exposed.
ANODE TYPES
The vitreous enamel-lined cylinder of the water heater is only covered by the
Solahart warranty when the total dissolved solids (TDS) content in the water
is less than 2500 mg/L and when the correct color-coded anode is used. If an
incorrect colour-coded anode is used in the water heater, any resultant faults
will not be covered by the Solahart warranty. In addition, the use of an
incorrect color-coded anode may shorten the life of the water heater cylinder.
The correct color-coded anode for the water supply being used must be selected
and fitted to the water heater for the Solahart warranty to apply to the water
heater cylinder. Refer to “Water Supplies” on page 24 and the Anode Selection
table on page 24. The black anode is typically fitted as standard.
If an incorrect anode is used, there is also the possibility the anode may
become overactive and hydrogen gas could accumulate in the top of the water
heater during long periods of no use. In areas where this is likely to occur,
the installer should instruct the householder on how to dissipate the gas
safely. Refer to “Caution” on page 25.
SADDLING – PIPEWORK
To prevent damage to the cylinder when attaching pipe clips or saddles to the
water heater jacket, we recommend the use of self-drilling screws with a
maximum length of 13 mm. Should pre-drilling be required, extreme caution must
be observed when penetrating the jacket of the water heater.
Note: If the cylinder is damaged as a result of attaching pipe clips or saddles to the jacket, any resultant faults will not be covered by the Solahart warranty.
HOT WATER DELIVERY
Warning: This water heater can deliver hot water at temperatures up to 70°C, sufficiently hot to cause severe scalding. Water at this temperature may be plumbed to fixtures where water hotter than 50°C is allowed, such as the kitchen and laundry.
The installing plumber may have a legal obligation to ensure the installation
of this water heater meets the water temperature delivery requirements of the
Plumbing Code of Australia (PCA) so that heated water delivered to fixtures
and appliances used primarily for personal hygiene is at a temperature which
is unlikely to scald.
It is necessary and we recommend that a temperature-limiting device be fitted
between the water heater and the fixtures and appliances used primarily for
personal hygiene such as in a bathroom, ensuite, public amenities or other
ablution areas, to reduce the risk of scalding. The temperature limiting
device used with a heat pump water heater should have a specified ‘minimum
temperature differential’ between the hot water inlet and the tempered water
outlet of no greater than 10°C. Refer to the manufacturer’s specifications of
the temperature limiting device. If a pressure limiting valve is installed on
the cold water line to the water heater and the cold water line to a
temperature limiting device branches off before this valve or from another
cold water line in the premises, then a pressure limiting valve of an equal
pressure setting may be required before the temperature limiting device. Where
a temperature limiting device is installed adjacent to the water heater, the
cold water line to the temperature limiting device can be branched off the
cold water line either before or after the isolation valve, pressure limiting
valve and non-return valve to the water heater. If an expansion control valve
is required, it must always be installed after the non-return valve and be the
last valve prior to the water heater.
CIRCULATED HOT WATER FLOW AND RETURN SYSTEM
This model heat pump water heater is not recommended to be installed as part
of a circulated hot water flow and return system in a building.
DIMENSIONS AND TECHNICAL DATA Dimensions
Technical Data
Model number| | 180HAV|
---|---|---|---
Product number – with black anode (magnesium)| | 180HAV24| | Refrigerant type|
R134a
Product number – with blue anode (aluminium)| | 180HAV24/B| Refrigerant
circuit pressure| 2600 kPa
Storage capacity| litres| 178| IP Rating| IP24
Boost capacity| litres| 168| Average COP @
19°C Ambient air temp & 11.5°C to 60°C water temp
| 4.5
Weight system cartoned| kg| 116
Weight system full| kg| 284| Avg HP Heating Capacity 19°C
Ambient air temp & 11.5°C to 60°C water temp| 3.1 kW
Noise Level @ 1 metre| dB(A)| 48
Rated heat pump power input @ 240 V| watts| 683| | |
Electric element rating @ 240 V| watts| 2400| | |
Maximum power input @ 240 V| watts| 3500| | Technical data is|
Electrical circuit| Amps| 15| | subject to change|
Heat Pump 180HAV Performance Specifications
Ambient Air Temperature| Relative Humidity| Average Heat Pump Heating Capacity
(kW)| Recovery Rate @ 45°C rise (L / hr)| Coefficient of Performance (COP)
---|---|---|---|---
9°C| 88%| 2.3| 44| 3.8
19°C| 66%| 3.1| 60| 4.5
32°C| 38%| 3.6| 69| 4.6
34°C| 54%| 4.0| 77| 4.9
Back-Up Heating Unit Recovery Rate @ 240 V
Heating Unit Rating| Recovery Rate @ 30°C rise (L / hr)| Recovery Rate @ 40°C
rise (L / hr)| Recovery Rate @ 50°C rise (L / hr)
---|---|---|---
2400 watts| 69| 52| 41
Noise Level – A noise level of 48 dB(A) was measured at 1 m from the water heater during a Noise Test conducted to Standard GB/T 23137-2008 in a hemi-anechoic chamber of a test laboratory. The noise level when installed may be higher due to sound reflections from adjacent walls and structures. COP – The Coefficient of Performance (COP) for a heat pump is the ratio of how much useful heat it produces for water heating to the power input into the water heater. The higher the COP number, the more efficient the heat pump is. The actual COP of the product at any given time will be impacted by a number of factors, including the ambient air and cold-water inlet temperatures at the place of installation and time of day/season of operation. The COP of 4.5 is the average value measured under test conditions with an ambient air temperature of 19˚C/15˚C (Dry Bulb/Wet Bulb) over the entire heat-up process, heating of the water from 11.5˚C to 60˚C during water heater operation and a power supply of 240 V~ 50 Hz. The Heat Pump average heating capacity in Watts and its water heating capacity in liters/hour were calculated from the results of this test. The heat pump water heater performance tests were conducted to AS/NZS 5125.1:2014.
Ambient Air Temperature & Humidity – The performance of a Heat Pump changes with ambient air temperature, humidity, and incoming water temperature. The warmer the air temperature, the higher the Relative Humidity and the cooler the water temperature, the higher is the heating rate of the heat pump. Performance specifications stated with the heat pump are measured at predefined conditions during its testing.
Average Heating Capacity kW or Watts – This is how much heating power is put into the water during the heating cycle. It is expressed as an average due to the changes in heating power from the refrigeration cycle as the water is being heated and its temperature increases during the heating cycle.
Recovery Rate @ 45°C rise L/hr – Is the number of litres of water that can be heated through a 45°C temperature rise in one hour, e.g. when the air temperature is 19°C, the heat pump can heat 57 litres of water from 15°C to 60°C in one hour.
TYPICAL INSTALLATION – OUTDOOR LOCATION
CONNECTIONS – PLUMBING
All plumbing work must be carried out by a qualified person and by the Standard AS/NZS 3500.4 and all local codes and regulatory authority requirements.
CONNECTION SIZES
- Hot water connection: Rp 3/4
- Cold water connection: Rp 3/4
- Relief valve connection: Rp 1/2
WATER INLET AND OUTLET
The pipe work must be cleared of foreign matter before connection and purged
before attempting to operate the water heater. All olive compression fittings
must use brass or copper olives. Use an approved thread sealant such as Teflon
tape on all threaded joints. An isolation valve and non-return valve must be
installed on the cold water line to the water heater. An acceptable
arrangement is shown in the diagram. Refer also to “Hot Water Delivery” on
page 33 and to “Mains Water Supply. A disconnection union must always be
provided at the cold water inlet and hot water outlet on the water heater to
allow for disconnection of the water heater. This water heater has either a
plastic dip tube or fitting liner in the inlet and outlet fittings (see
diagram). These must be in place for the water heater to function properly. Do
not remove or damage them by using heat nearby. They will be pushed into the
correct position as the fitting is screwed in. This water heater is intended
to be permanently connected to the water mains and not connected by a hose
set. A braided flexible hose or semi-flexible connector may be used for
connection to the water heater, where permitted by AS/NZS 3500.4.
CONDENSATE DRAIN
A condensate drain hose is supplied with the water heater.
- Securely connect the condensate drain hose to the condensate drain spigot at the rear of the heat pump,
- Position the drain hose so it has a continuous fall to the discharge outlet and there are no bends or distortions in it after it is installed,
- It may be necessary to use hose clips to secure the drain hose in position,
- Locate the discharge outlet of the drain hose such that the flow out of the pipe can be easily seen and not cause damage or nuisance.
PIPE SIZES
To achieve true mains pressure operation, the cold water line to the water
heater should be the same size or bigger than the hot water line from the
water heater. The pipe sizing for hot water supply systems should be carried
out by persons competent to do so, choosing the most suitable pipe size for
each individual application. Reference to the technical specifications of the
water heater and local regulatory authority requirements must be made.
TEMPERATURE PRESSURE RELIEF VALVE
The temperature pressure relief valve is shipped with the water heater. The
temperature pressure relief valve must be fitted before the water heater is
operated. Before fitting the relief valve, make sure the probe has not been
bent.
To fit the relief valve:
- Seal the thread with an approved thread sealant such as Teflon tape – never hemp. Make sure the tape does not hang over the end of the thread.
- Hand tighten the valve into the opening marked “Relief Valve”. Refer to the dimensions diagram.
- Using a spanner engaged on the valve’s spanner flats and applying medium pressure to tighten, turn the relief valve an additional ½ to 1 ½ turns to secure and make the joint watertight, leaving the valve drain pointing downwards.
- Warning: Do not use a pipe wrench or poor fitting tool on the valve body nor over-tighten the valve, as this could damage the valve and prevent safe operation.
- Operate the easing lever on the valve to check the smooth operation of the valve plunger. The lever must be raised and lowered gently. The lever should move smoothly and without undue force.
- If the lever cannot be moved or is jerky in its movement, then the valve has been damaged and must be replaced.
- A copper drain line must be fitted to the temperature pressure relief valve. Refer to “Relief Valve Drain”.
- The valve must be insulated with closed cell polymer insulation or similar (minimum thickness 9 mm) and the insulation installed so as not to impede the operation of the valve. The insulation must be weatherproof and UV-resistant if exposed.
EXPANSION CONTROL VALVE
In South Australia and Western Australia, it is mandatory to install an
expansion control valve (ECV) in the cold water line to the water heater. In
other areas, an ECV is required if the saturation index is greater than +0.4.
Refer to “Water Supplies” on page 24. The expansion control valve must always
be installed after the non-return valve and be the last valve installed prior
to the water heater. Refer to the diagram on page 37. A copper drain line must
be fitted to the expansion control valve. Refer to “Relief Valve Drain” on
page 39. The valve, if installed within 500 mm of the water heater, must be
insulated with closed cell polymer insulation or similar (minimum thickness 9
mm) and the insulation installed so as not to impede the operation of the
valve. The insulation must be weatherproof and UV-resistant if exposed.
RELIEF VALVE DRAIN
- DN15 copper drain lines must be fitted to the temperature pressure relief valve and expansion control valve (if one is installed) to carry the discharge clear of the water heater. Connect the drain lines to the valves using disconnection unions. The drain line from the valve to the point of discharge should be as short as possible, have a continuous fall all the way from the water heater to the discharge outlet and have no tap, valves or other restrictions in the pipe work.
- A drain line from a relief valve must comply with the requirements of AS/NZS 3500.4.
- A drain line must have the number of changes in direction plus the length of the relief drain (in meters) not exceeding 12. The maximum length of 12 metres for a drain line is reduced by 1 metre for each bend or change of direction required. Where the distance to the point of final discharge exceeds this length, the drain line can discharge into a tundish. For example, a relief drain of 9 metres must have no more than three bends before discharging at an outlet or air break.
- The drain lines from the temperature pressure relief valve and expansion control valve from an individual water heater may be interconnected where freezing is unlikely. The combined drain line must have a minimum size of DN20 and discharge via a minimum air break of 25 mm.
- The outlet of a drain line must be in such a position that flow out of the pipe can be easily seen, but arranged so discharge will not cause injury, damage or nuisance. The termination point of a drain line must comply with the requirements of AS/NZS 3500.4. Drain lines must not discharge into a safe tray.
- In locations where water pipes are prone to freezing, drain lines from the temperature and pressure relief valve and expansion control valve shall not be interconnected, must be insulated with a minimum thickness of 13 mm insulation, must not exceed 100 mm in length, and are to discharge into a tundish through an air gap of 25 mm before the drain line enters a zone where freezing is likely.
- If a drain line discharges into a tundish, the drain line from the tundish must be not less than DN20. The drain line from a tundish must meet the same requirements as for a drain line from a relief valve.
Warning: As the function of the temperature pressure relief valve on this water heater is to discharge high-temperature water under certain conditions, it is strongly recommended the pipework downstream of the relief valve be capable of carrying water exceeding 93°C. Failure to observe this precaution may result in damage to pipework and property.
CONNECTIONS – ELECTRICAL
The power supply to the water heater must not be switched on until the water heater is filled with water and a satisfactory megger reading is obtained. There is NO WARRANTY for the dry firing of the electric heating unit. Ensure the water heater has been in the installed position for a minimum of 30 minutes before switching on the electricity supply to the water heater. Refer to “To Fill and Turn On The Water Heater”.
MEGGER READING
When a megger test is conducted on this water heater, then the following
should be noted.
Warning: This water heater contains electronic equipment and 500 V insulation tests must only be conducted between active and earth and between neutral and earth. An active to neutral test WILL damage the electronics. An insulation test result of greater than 1 MΩ for this water heater is normal.
ELECTRICAL CONNECTION
All electrical work and permanent wiring must be carried out by a qualified
person and under the edition of the Wiring Rules AS/NZS 3000 in force in the
state or territory at the time of installation, and all local codes and
regulatory authority requirements. The water heater must be directly connected
to a 220 V – 240 V a.c. 50 Hz mains power supply. The water heater must be on
its circuit with an isolating switch installed at the switchboard. The Wiring
Rules require a second and lockable isolating switch be installed adjacent to
but not on or attached to the water heater, and a residual current device
(RCD) installed in the electrical circuit to the water heater. The electrical
power supply cable from the switchboard to the isolation switch adjacent to
the water heater must be correctly sized to safely carry the maximum current
draw of the heat pump and electric heating unit operating together on the
water heater. The power supply must be able to supply a minimum of 17 Amps.
This water heater is fitted with a 2.5 m supply cord and bootlace wire
terminals and must be directly connected to the mains electricity supply with
an Earth, Live, and Neutral wire connection. This supply cord can be connected
to the isolating switch adjacent to the water heater. A flexible 20 mm conduit
is required for the electrical cable to the water heater. The conduit is to be
secured to the unit at the lower front cover with the cable clamp supplied.
Note: It is not recommended to connect this water heater via a power- switching device that allows an alternative supply of grid power and photovoltaic (PV) power. The water heater is recommended for connection to a 24-hour continuous tariff power supply. Depending upon the size of the household and its hot water requirements and if the Electricity Retailer permits, an extended off-peak (overnight and day) or Extended time-controlled power supply connection of a minimum of 16 hours per day may also be suitable. The water heater will only operate on a sine wave at 50 Hz. Devices generating a square wave cannot be used to supply power to the water heater.
ELECTRIC HEATING UNIT AND THERMOSTAT SETTING
The water heater has an electric heating unit and thermostat and is controlled
by an electronic controller. The electric heating unit will be automatically
activated during periods when the ambient air temperature falls below -7°C or
above 43°C and heating of the water is required. In addition, if the heat pump
operates between -7°C and 7°C for longer than 3 hours 20 minutes, the electric
heating unit will turn on to assist in the heating of the water. The Hot Water
Temperature Set Point of the heat pump and the electric heating unit can be
adjusted from 60°C to 70°C. Refer to “Hot Water Temperature Set Point.
TIMER
A timer function on the Display Panel allows the hours of operation of the
water heater to be set. Refer to “Clock and Timer”.It may be desirable for the
heat pump not to operate between certain hours, such as during the peak period
when connected to a Time of Use electricity supply due to a more expensive
tariff rate applying. A timer will affect the operating times of both the heat
pump circuit and the electric heating unit.
Note: If there is a risk of freezing conditions, the electrical supply to the water heater should not be switched off, otherwise damage could result. Refer to “Freeze Protection”.
WIRING DIAGRAM
COMMISSIONING
TO FILL AND TURN ON THE WATER HEATER
The power supply to the water heater must not be switched on until the water
heater is filled with water and a satisfactory megger reading is obtained.
-
Open all of the hot water taps in the house (don’t forget the shower).
-
Open the cold water isolation valve fully to the water heater. Air will be forced out of the taps and the air bleed valve.
-
Close each tap as water flows freely from it.
-
Check the pipe work for leaks.
-
Inspect for leaks at the temperature pressure relief valve connection to the water heater. If a leak is detected, close the cold water isolation valve fully and relieve pressure from the water heater by either operating the easing lever on the temperature pressure relief valve or opening a hot tap. Remove the valve and all of its thread sealant from the threads of the valve. Reapply new thread sealant and refit the valve. Refer to the procedure in “Temperature Pressure Relief Valve”.
-
Operate the easing lever on the temperature pressure relief valve to check the smooth operation of the valve plunger and that water discharges freely from the drain line. The lever must be raised and lowered gently. The lever should move smoothly and without undue force. If the lever cannot be moved or is jerky in its movement, then the valve has been damaged and must be replaced.
-
Ensure the water heater has been in the installed position for a minimum of 30 minutes before switching on the electricity supply to the water heater.
-
Switch on the electrical supply at the water heater isolating switch on the switchboard and at the isolating switch at the water heater.
Note: When the electrical supply is switched on, there will be a knocking sound from the heat pump for a short period. This is the electronic expansion valve operating. This is normal and not a fault with the heat pump. -
Turn the water heater “On” at the Display Panel. Refer to “Turn the Water Heater “On” at the Display Panel”.
-
Set the Clock on the Water Heater, and if required, set the Timer period. Refer to “Clock and Timer”.
The heat pump may take up to 5 minutes to commence operating when the power supply is switched on. The heat pump will only operate when the water in the storage tank requires heating and power is available at the water heater. If the ambient air temperature is below -7°C or above 43°C and the system calls for heating, the heat pump will not operate and the electric heating unit will operate instead. When the heat pump is operating, the system may switch to the electric heating unit if it detects that the ambient air temperature is below the minimum operating temperature of -7°C or above the maximum operating temperature of 43°C. It may also switch back to heat pump operation from the electric heating unit if it detects the ambient air temperature has moved back to within the heat pump’s operating temperature range.
Note: The heat pump may not turn on after having just completed a heating cycle and more hot water is drawn from the water heater, or whilst the heat pump was operating and either power was switched off or it was turned “Off” at the Display Panel. The heat pump may wait a few minutes before operating and the conditions for start-up are favourable.It is important to wait for five minutes after the heat pump has activated to ensure it continues to operate and is functioning correctly. Explain to the householder or a responsible officer the functions and operation of the heat pump water heater. Upon completion of the installation and commissioning of the water heating system, leave this guide with the householder or a responsible officer.
TO TURN OFF THE WATER HEATER
If it is necessary to turn off the water heater on completion of the
installation, such as on a building site or where the premises are vacant,
then:
- Turn the water heater off at the Display Panel.
- Switch off the electrical supply at the water heater isolating switch on the switchboard and at the isolating switch at the water heater.
- Close the cold water isolation valve at the inlet to the water heater.
Notes
- The freeze protection system will be rendered inoperable if electrical power is not available at the water heater.
- Damage caused by freezing due to the unavailability of power at the water heater is not covered by the Rheem warranty. Refer to “Terms of the Rheem Warranty”.
- If the power has been switched off to the water heater and there is a risk of freezing, then it is necessary to drain the water heater. Refer to “Draining The Water Heater”.
DRAINING THE WATER HEATER
Warning: Exercise care, as water discharged from the water heater may be of a very high temperature. To drain the water heater:
- Turn off the water heater. Refer to “To Turn Off The Water Heater”.
- Close all hot water taps.
- Operate the relief valve lever – do not let the lever snap back or you will damage the valve seat. The lever must be raised and lowered gently. Operating the lever will release the pressure in the water heater.
- Undo the union at the cold water inlet to the water heater and attach a hose to the water heater side of the union. Let the other end of the hose go to a drain.
- Open the relief valve by holding the lever in the raised position. This will let air into the water heater and allow the water to drain through the hose.
INSTALLATION REPORT
Dear Installer / Customer
A copy of this installation report filled out in full and signed can be
attached to an STC Assignment Form (where applicable) as a method to
demonstrate proof of installation. It can be copied and kept for your records.
An electronic version may be provided by the Dealer instead.
Installer, please complete all details below
Owner’s Name|
---|---
Installation Address|
Suburb| | Telephone Home|
State| | Work|
Postcode| | Mobile|
Email Address|
Dealership / Agent| | No. of Stories of Install| Single| Other|
Installer’s Name| | Installation Date|
Type of Installation
(please circle)
| Replace Complete Solar System| Replace Solar Tank| Replace Electric or Gas| Replace Heat Pump| ****
New Building
| New Install on Existing Building (not replacing a unit)| ****
Other
System Model No| | System Type|
Tank Model No| | Tank Serial No|
Electric Booster
(please circle)
| ****
Electric continuous
| Off Peak 1 (night)| Off Peak 2 (night & day)| ****
Other
If replacing a water heater, please give details
Brand | Model No | Electric | Gas | ||
---|---|---|---|---|---|
If a Solahart unit | Tank Serial No | Date of manufacture | |||
Collector Serial No’s | 1) | 2) | 3) | 4) |
Comments
Signature:| Installer:| Customer:
Date| |
- This page is intentionally blank.
- This page is intentionally blank.
SOLAHART OFFICES
International Headquarters
Solahart Industries Pty Ltd (ABN 45 064 945 848) Registered and Head Office 1
Alan Street Rydalmere, New South Wales, 2116 Australia Postal Address: PO Box
7508 Silverwater, New South Wales, 2128 Australia Principal Manufacturing
Facility 55 Brodie Street Rydalmere, New South Wales, 2116 Australia
www.solahart.com.au
Australia
For SERVICE Telephone – 1800 638 011 or your nearest Solahart Dealer For Sales
Telephone – 1300 769 475 or your nearest Solahart Dealer
International Sales
- Telephone International Sales : + 61 8 9351 4600
- Facsimile International Sales : + 61 8 9351 4698
- Email: solahart@solahart.com.au
- Web: www.solahart.com