COMPLIANCE
This device complies with part 15 of the FCC. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference,
and (2) this device must accept any interference received, including
interference that may cause undesired operation.
FCC NOTE : The manufacturer is not responsible for any radio or TV
interference caused by unauthorized modifications to this equipment. Such
modifications could void the user’s authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in
accordance with the instructions may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and the receiver.
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Important note: To comply with the FCC RF exposure compliance
requirements, no change to the antenna or the device is permitted. Any change
to the antenna or the device could result in the device exceeding the RF
exposure requirements and void the user’s authority to operate the device.
This Class B digital apparatus complies with ICES-005 of Canada.
WARNINGS/SAFETY
WARNING
Risk of Fire or Electric Shock
- Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
- Installation and/or wiring must be in accordance with national and local electrical code requirements.
- Only use copper conductors rated 105°C minimum.
- For INDOOR USE ONLY.
RATINGS1
Operating Voltage – 120-277 VAC, 50/60 Hz
Operating Temperature – 0° – 55° C (32° – 131° F)
Dimensions – 2 3/4″ H x 1 3/4″ W x 1 2/3″ D
1Type 1 action, Operating Control, Pollution degree PD2, Impulse Voltage 4000V
PRODUCT OVERVIEW
The ALC-DT-BT-WH is a Dual Technology (PIR and Ultrasonic) Sensor designed for use with the ARISTA Lighting Controls System by Intermatic and will control lighting based on occupancy/vacancy. If the space is configured for Occupancy and movement is detected, the sensor informs the ARISTA controller(s) in the space and the lights will illuminate. The lights will turn off after the ARISTA controller(s) deem the space vacant and the timeout period completes. If the space is configured for Vacancy, the ARISTA controller(s) in the space will only react when they are manually activated. The lights will turn off after the ALC-DT-BT-WH deems the space vacant and the timeout period completes. The ALC-DT-BT-WH also utilizes a built-in switch that can be used as a manual override to the programmed ARISTA controller(s).
INSTALLATION
- Turn off the power to the controlling circuit.
- Connect wires as shown in the wiring diagram.
- Attach ALC-DT-BT-WH to the electrical box with provided screws.
- Install wall plate
- Turn the power ON to the controlling the circuit.
- Once powered, a Green LED indicator light will start flashing for 1minute..
NOTES: For Programming instructions please visit www.Intermatic. com. The Arista App is available on Apple App and Google Play stores. (Search for Arista by Intermatic) Bluetooth Operations have a maximum range of 100′.
WIRING DIAGRAM
Wire | Description |
---|---|
White | Connects to Neutral/Line 2 from Power Source |
Black | Connects to Line from Power Source |
Green | Connects to ground |
NOTE: To be installed in single- or double-gang applications with 2-1/2″
minimum depth. Please consult a qualified electrician for specific wiring
details.
SWITCH INTERFACE
COVERAGE AREA
TROUBLESHOOTING
Symptom|
---|---
During installation, the ARISTA Mobile App can’t find the sensor when scanning
for devices in the area| Verify power is supplied to the sensor. Make sure the
Blue LED is blinking slowly. If not, the sensor could already be provisioned
into another area. If this is correct, factory reset the device by pressing
the reset button for more than 10 seconds. Make sure you are within range of
the sensor
The sensor is energizing the lights without motion being detected in the
space| Verify zone configuration using the ARISTA Mobile App is correct.
Sensitivity may be set too high. Using the ARISTA Mobile App, lower the
sensor’s sensitivity setting.
The sensor doesn’t detect motion when a person enters the space| Verify power
is supplied to the sensor. If Blue LED is blinking slowly, the sensor hasn’t
been provisioned into the zone using the ARISTA Mobile App and will not
operate properly. Verify the sensor is detecting motion by walking by the
sensor and verifying the Green LED blinks briefly. The sensitivity setting may
be set too low. Using the ARISTA Mobile App, increase the sensor’s sensitivity
setting. Verify sensor configuration (i.e. — time delay). Make certain zone
configuration is set to Occupancy and not Vacancy. Change mounting location.
The sensor’s Red LED is on solid| Replace Sensor
The sensor is de-energizing the lights while still in the space| The
sensitivity setting may be set too low. Using the ARISTA Mobile App, increase
the sensor’s sensitivity setting. Change mounting location.
Sensor leaves the lights energized after having left the space| Verify sensor
configuration (i.e. — time delay).
LIMITED WARRANTY
This warranty service is available by either (a) returning the product to the
dealer from whom the unit was purchased or (b) completing a warranty claim
online at www.intermatic.com. This warranty is
made by: Intermatic Incorporated, Customer Service, 1950 Innovation Way Suite
300, Libertyville, IL 60048. For warranty service go to:
www.intermatic.com or call
815-675-7000.
For complete information on Intermatic products, literature, and Contractors
Guides visit www.intermatic.com.
158–02258REF
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>