NAPOLEON B30NTR-1 Face Direct Urban Fireplaces Instruction Manual

June 1, 2024
Napoleon

NAPOLEON-logo

NAPOLEON B30NTR-1 Face Direct Urban Fireplaces

NAPOLEON-B30NTR-1-Face-Direct-Urban-Fireplaces-image

Product Information

Specifications:

  • Natural Gas Models: B30NTR-1 / BA3D0DNTPRREO-D1UCT
  • Propane Gas Models: B30PTR-1 / B30PTRE-1
  • For indoor use only
  • Certified to Canadian and American National Standards: CSA 2.22 and ANSI Z21.50 for vented decorative gas appliances

Product Usage Instructions

Safety Information:

! WARNING: Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

  • Do not store or use gasoline or other flammable vapors and liquids near the appliance.
  • Installation and service must be done by a qualified installer, service agency, or supplier.
  • This appliance must only be used with the gas type indicated on the rating plate.

Installation:

This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.

Operation:

Ensure the appliance is only used indoors. Never obstruct the front opening of the appliance. Do not connect 110 volts to the control valve. Install a viewing glass for protection of children and at-risk individuals.

Maintenance:

Follow all safety warnings. Disconnect the appliance main gas valve/control during pressure testing exceeding 1/2 psi (3.5 kPa). Isolate the appliance with its shut-off valve during pressure testing at or below 1/2 psi (3.5 kPa).

FAQs

  • Q: Can this appliance be used with other gases?
    • A: This appliance is not convertible for use with other gases unless a certified kit is used.
  • Q: What safety precautions should I take regarding hot glass?
    • A: Hot glass can cause burns. Do not touch the glass until it is cooled. Never allow children to touch the glass.
  • Q: Where can I get more information about potential hazards associated with this product?
    • A: For more information on potential hazards, including California Prop 65 warnings, visit www.P65Warnings.ca.gov.

“`

NATURAL GAS MODELS: B30NTR-1 / BA3D0DNTPRREO-D1UCT CODE HERE (TRADE GOTHIC LT STD FONT) PROPANE GAS MODELS: B30PTR-1 / B30PTRE-1

ENGLISH FRENCH PG. 71

OAPIDNEDSRTAMATALIOLNANUTAMIOLANTNIAUTNLAEDL

SAFETY INFORMATION

! WARNING
FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury, death, or property damage.

ProAduscct eNanmtTMe / C3od0e
(MUST use title from Price Book)
ADD ____ ILLUSTRATED

– Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
– WHAT TO DO IF YOU SMELL GAS: · Do not try to light any appliance. · Do not touch any electrical switch; do not
use any phone in your building. · Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s instructions. · If you cannot reach your gas supplier, call the fire department.
– Installation and service must be performed by a qualified installer, service agency, or the supplier.

ADSD PARFODEUTCTYIMBAGAERRIER

This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.

This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
INSTALLER: Leave this manual with the appliance
CONSUMER: Retain this manual for future reference

FOR INDOOR USE ONLY
CERTIFIED TO THE CANADIAN AND AMERICAN NATIONAL STANDARDS: CSA 2.22 AND ANSI Z21.50 FOR VENTED DECORATIVE GAS APPLIANCES

CSA / INTERTEK
LOGO

IF INSTALLATION + OPERATION, ADD SERIAL NUMBER LABEL HERE
IF SEPARATE MANUALS, ADD “PLACE BARCODE LABEL ON THE OWNER’S MANUAL”

Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada / 103 Miller Drive, Crittenden, Kentucky, USA, 41030 Phone 1 866-820-8686 · www.napoleon.com · hearth@napoleon.com

$10.00

W415-2351 / B / 12.09.20

EN safety information

! WARNING

· This appliance is hot when operated and can cause severe burns if contacted.
· Any changes or alterations to this appliance or its controls can be dangerous and is prohibited.

! DANGER HOT GLASS WILL CAUSE

· Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance according to operating instructions could cause fire or injury.

BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.

· Ensure the glass door is opened or removed when lighting the pilot for the first time and when the gas supply has run out.

NEVER ALLOW CHILDREN TO TOUCH GLASS.

· Risk of fire or asphyxiation, do not operate

A barrier designed to reduce the risk of burns from the hot

·

appliance with fixed glass removed and never obstruct the front opening of the appliance. Do not connect 110 volts to the control valve,

viewing glass is provided with this appliance and must be installed for the protection of children and other at-risk

with the exception of models; GSST8 and

individuals.

GT8.

· Risk of burns. The appliance should be turned off and cooled before servicing.

· Do not install damaged, incomplete or substitute components.

· Risk of cuts and abrasions. Wear protective gloves, protective footwear, and safety glasses during installation. Sheet metal edges may be sharp.

· Do not burn wood or other materials in this appliance.

· Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing and operating the appliance.

· High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at test pressures above 1/2 psig. Close the manual shut-off valve before pressure testing gas line at test pressures equal to or less than 1/2 psig (35mb).

· The appliance must not be operated at temperatures below freezing (32°F / 0°C). Allow the appliance to warm to above freezing prior to operation, with the exception of models; GSS36, GSS42; these appliances are suitable for 0°F / -18°C.

· Children and adults should be alerted to hazards of high surface temperature and should stay away to avoid burns or clothing ignition.

· Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to an appliance or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.

· Clothing or other flammable material should not be placed on or near the appliance.

· Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.

· Furniture or other objects must be kept a minimum of 4 feet (1.22m) away from the front of the appliance.

· Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.

· Even after the appliance is off, it will remain hot for an extended period of time.

· Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot surfaces. These screens and guards must be fastened to the floor.

· Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating the appliance.

· It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance and venting system are kept clean. The appliance and its venting system should be inspected before use and at least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials, gasoline and other flammable vapors and liquids.

· If the appliance shuts off, do not re-light until you provide fresh air. If appliance keeps shutting off, have it serviced. Keep burner and control compartment clean.

· Under no circumstances should this appliance be modified.

· Do not allow wind or fans to blow directly into the appliance. Avoid any drafts that alter burner flame patterns.

2

W415-2351 / B / 12.09.20

safety information EN ! WARNING
· Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this appliance.
· This appliance must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
· Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
· Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person, if equipped.
· Do not strike or slam shut the appliance glass door, if equipped. · Only doors / optional fronts certified with the appliance are to be installed on the appliance. · Keep the packaging material out of reach of children and dispose of the material in a safe manner. As
with all plastic bags, these are not toys and should be kept away from children and infants. · Carbon or soot should not occur in a vent free appliance as it can distribute into the living area of your
home. If you notice any signs of carbon or soot, immediately turn off your appliance and arrange to have it serviced by a qualified technician before operating it again. · If equipped, the screen must be in place (closed) when the appliance is in operation. · When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping through these openings can also cause the surrounding combustible materials to overheat and catch fire. · Carbon monoxide poisoning may lead to death; early signs of carbon monoxide poisoning resemble the flu, with headache, dizziness and/or nausea. If you have these signs, the appliance may not be working properly. Get fresh air at once! Have appliance serviced. Some people; pregnant women, persons with heart or lung disease, anemia, those under the influence of alcohol, those at high altitudes are more affected by carbon monoxide than others. Failure to keep the primary air opening(s) of the burner(s) clean may result in sooting and property damage. · As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon Monoxide (not applicable for outdoor appliances). · Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance. Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage to decorations, a TV or other electronic components. · For appliances equipped with a safety barrier; if the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this appliance. · Installation and repair should be done by a qualified service person. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean. · For outdoor products only: this appliance must not be installed indoors or within any structure that prevents or inhibits the exhaust gases from dissipating in the outside atmosphere. · If applicable, the millivolt version of this appliance uses and requires a fast acting thermocouple. Replace only with a fast acting thermocouple supplied by Wolf Steel Ltd.
Add California Prop 65 warning ! WARNING:This product can expose you to chemicals including lead and lead compounds,
which are known to the State of California to cause cancer, and chemicals including carbon monoxide, which are known to the State of California to cause birth defects or other reproductive harm. For more information, go to www.P65Warnings.ca.gov.
! WARNING !
FIRE RISK HAZARD / DELAYED IGNITION
High supply pressure will damage the valve / controls.
Disconnect the appliance main gas valve/control from the supply piping when pressure testing that system at pressures in excess of 1/2 psi (3.5 kPa).
Isolate the appliance with it’s shut off valve during any pressure testing of the supply piping at
pressures equal to or less than 1/2 psi (3.5 kPa).

W415-2351 / B / 12.09.20

note:
The information throughout this manual is believed to be correct at the time of printing. Wolf Steel Ltd. reserves the right to change or modify any information within this manual at any time without notice. Changes, other than editorial, are denoted by a vertical line in the margin.

4

W415-2351 / B / 12.09.20

standard checklist EN
Installer: please fill out the following information

Customer: Address: Date of Installation: Location of the appliance Installer: Dealer/Distributor contact number: Serial #:
Model:
Natural Gas: B30NTR-1
B30NTRE-1

Propane:

B30PTR-1 B30PTRE-1

general information

When the appliance is installed at elevations above 4,500ft (1372m), and in the absence of specific recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be reduced at the rate of 4% for each additional 1,000ft (305m). Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected. Change in flame appearance from “HI” to “LO” is more evident in natural gas than in propane.
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is certified for mobile home installation.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
note: A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance and must be installed.
The protective wrap on plated parts is best removed when the assembly is at room temperature but this can be improved if the assembly is warmed, using a hair dryer or similar heat source. This appliance is a decorative product. It is not a source of heat and not intended to burn solid fuel.

Batteries must be disposed of according to the local laws and regulations. Some batteries may be recycled, and may be accepted for disposal at your local recycling center. Check with your municipality for recycling instructions.

1.1 rates and efficiencies
Altitude (FT) Max. Input (BTU/HR) Min. Inlet Gas Supply Pressure Max. Inlet Gas Supply Pressure Manifold Pressure (Under Flow Conditions)

Natural Gas
4.5″ (11mb) w.c. 13″ (32mb) w.c. 3.5″ (9mb) w.c.

0-4,500 15,000

Propane
11″ (27mb) w.c. 13″ (32mb) w.c. 10″ (25mb) w.c.

W415-2351 / B / 12.09.20

5

EN general information ! WARNING
· Always light the pilot whether for the first time or if the gas supply has run out, with the glass door opened or removed.
· Provide adequate clearance for servicing and operating the appliance. · Provide adequate ventilation. · Never obstruct the front opening of the appliance. · Objects placed in front of the appliance must be kept a minimum of 48″ (121.9cm) from the front face of
the appliance. · Surfaces around and especially above the appliance can become hot. Avoid contact when appliance is
operating. · Fire risk. Explosion hazard. · High pressure will damage valve. Disconnect gas supply piping before pressure testing gas line at test
pressures above 1/2 PISG (35mb). Close the manual shut-off valve before pressure testing gas line at test pressures equal to or less than 1/2 PISG (35mb). · Use only Wolf Steel approved optional accessories and replacement parts with this appliance using nonlisted accessories (blowers, doors, louvres, trims, gas components, venting components, etc.) could result in a safety hazard and will void the warranty and certification. · The appliance must not be operated at temperatures below freezing (32ºF/0ºC). Allow the appliance to warm to above freezing prior to operation.

THIS GAS APPLIANCE MUST BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to conform with local codes. Installation practices vary from region to region and it is important to know the specifics that apply to your area, for example in the state of Massachusetts: · This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth of
Massachusetts. · The appliance damper must be removed or welded in the open position prior to installation of an appliance insert or gas
log. · The appliance off valve must be a “T” handle gas cock. · The flexible connector must not be longer than 36 inches (0.9m). · A carbon monoxide detector is required in all rooms containing gas fired appliances. · The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent sealed
combustion product.

The installation must conform with local codes or, in absence of local codes, the National Gas and Propane Installation Code CSA B149.1

We suggest that our gas

in Canada, or the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. Suitable for mobile home installation if installed in accordance with the current standard CAN/CSA Z240MH Series, for gas equipped mobile homes, in Canada or ANSI Z223.1 and NFPA 54 in the United States.

hearth products be installed and serviced by professionals who are certified in the U.S. by the National Fireplace

The appliance and its individual shutoff valve must be disconnected

Institute® (NFI) as NFI Gas

from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (35 mb).

Specialists
www.nficertified.org

The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any

pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (35 mb). When installed

with a blower or fan, the junction box must be electrically connected and grounded in accordance with local codes. In the

absence of local codes, use the current CSA C22.1 Canadian Electrical Code in Canada or the ANSI / NFPA 70 National

Electric Code in the United States. In the case where the blower is equipped with a power cord, it must be connected into a

properly grounded receptacle. The grounding prong must not be removed from the cord plug.

The following does not apply to inserts; as long as the required clearance to combustibles is maintained, the most desirable and beneficial location for an appliance is in the center of a building, thereby allowing the most efficient use of the heat created. The location of windows, doors and, the traffic flow in the room where the appliance is to be located should be considered. If possible, you should choose a location where the vent will pass through the house without cutting a floor or roof joist. If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth, unless otherwise tested.

6

W415-2351 / B / 12.09.20

1.2 rating plate information

general information EN

Certified to Canadian and American National Standards: CSA 2.22-XXXX / ANSI Z21.50-XXXX for Vented Decorative Gas Appliances Certifié selon les normes Nationales Canadiennes et Américaines: CSA 2.22-XXXX / ANSI Z21.50-XXXX pour les Appareils à gaz décoratif à évacuation

Direct vent, vented gas fireplaces. Approved for bedroom, bathroom and bed- sitting room installation. Suitable for mobile home installation, if installed in accordance with the current standard CAN / CSA Z240MH Series gas equipped mobile homes in Canada, or, in the United States, the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280. When this US Standard is not applicable, use the Standard for Fire Safety Criteria for Manufactured Home Installations, Sites and Communities, ANSI / NFPA 501A. This appliance must be installed in accordance with local codes, if any; if none, follow the current ANSI Z223.1 or CSA B149. For use with barrier WXXX-XXXX. Follow installation instructions. Foyer à gaz ventilé. Homologué pour installation dans une chambre à coucher, une salle de bain et un studio. Approprié pour installation dans une maison mobile si son installation conforme aux exigences de la norme CAN / CSA Z240MH Séries de maisons mobile équipées au gaz en vigueur au Canada, ou, aux États-Unis selon la norme 24 CFR, Part 3280, Manufactured Home Construction and Safety Standard. Dans le cas ou cette norme d’États-Unis n’est pas pertinentes, utiliser la norme NFPA 501A, Fire Safety Criteria for Manufactured Home Installations, Sites and Communities. Installer l’appareil selon les codes ou règlements locaux ou, en l’absence de tels règlements, selon les codes d’installation ANSI Z223.1 ou CSA B149 en vigueur. Utiliser uniquement avec l’écran WXXX-XXXX. Suivre les instructions d’installation.

VENTED DECHOAERAPAPTT,LIINVAOENEGAS APPLIANCE: NOT A SOURCE OF 9700539 (WSL)

4001658 (NAC)

4001657 (NGZ)

4001659 (WUSA)

T INTENDED FOR USE AS A HEATING MODEL / MODÈLE

XXXX

XXXX

XXXX

XXXX

REFERENCE# 161746

CE, NOT FOR USE WITH SOLID FUEL. XXXX

XXXX

XXXX

XXXX

APUPNAERUSETIOLILÀ GAZ DÉCORATIF À ÉVACUATION: N’EST PAS Altitude

0-XXXXft (0-XXXXm)

Élévation

URCE DE CHALEUR; N’EST PAS DESTINÉ À ÈTRE Input
Reduced Input
LISÉ COMME UN APPAREIL DE CHAUFFAGE; NE P4

XX,XXX XX,XXX XX.X%

XX,XXX XX,XXX XX.X%

Alimentation Alimentation Réduite
P4

Manifold Pressure: 3.5″ w.c. (NG)

Manifold Pressure: 10″ w.c. (P)

CONVIENT PAS AUX COMBUSTIBLES SOLIDES. Minimum Supply Pressure: 4.5″ w.c. (NG)

Minimum Supply Pressure: 11″ w.c. (P)

Maximum Supply Pressure: 7″* w.c. (NG)

Maximum Supply Pressure: 13″* w.c. (P)

P Pression au Collecteur: 3,5″ d’une colonne d’eau (GN)

Pression au Collecteur: 10″ d’une colonne d’eau (P)

Pression d’Alimentation Min.: 4,5″ d’une colonne d’eau (GN)

Pression d’Alimentation Min.: 11″ d’une colonne d’eau (P)

Pression d’Alimentation Max.: 7″ * d’une colonne d’eau (GN) Pression d’Alimentation Max.: 13″ d’une colonne d’eau (P)

** Maximum inlet pressure not to exceed 13″.

** Pression d’alimentation maximale ne devait pas dépasser 13″.

Minimum clearance to combustible materials:

Dégagements minimaux des matériaux combustibles:

Top, sides & back: per standoff spacers for framing and finishing Dessus, côtés et arrière: selon les espaceurs de dégagements

materials. For non-combustible framing and finishing materials,

pour les matériaux d’ossature selon le manuel du propriétaire

see installation manual.

pour les matériaux de finition.

Top X”

Dessus X”

M Floor X”

Plancher X”

Sides X”

Côtés X”

Back X”

Arrière X”

Vent top X”

Dessus du conduit d’évent X”

Vent sides & bottom X”

Côtés et dessous du conduit d’évent X”

Recessed depth X”

Profondeur d’encastré une face X”

*** Mantel X” from appliance opening

*** Tablette X” de l’ouverture de l’appareil

A *** Maximum horizontal extension:
X”. See installation manual for greater extensions, minimum vent lengths and maximum vent lengths. Electrical rating: 115V, 60HZ. Less than 12 amperes.

*** L’extension horizontale maximale: X”. Référez au manuel d’installation pour des
extensions plus grandes, les longueurs d’évacuation minimaux et maximum.
Spécifications électriques: 115V, 60HZ. Moins de 12 ampère.

S WOLF STEEL LTD. 24 Napoleon Road, Barrie, ON, L4M 0G8 Canada

FOR USE WITH GLASS DOORS CERTIFIED WITH THIS APPLIANCE ONLY. POUR UTILISATION UNIQUEMENT AVEC LES PORTES EN VERRE CERTIFIÉES AVEC L’APPAREIL.
For natural gas when equipped with No. XX drill size orifice. For propane when equipped with No. XX drill size orifice.
Convient au gaz naturel quand l’appareil est muni d’un injecteur de diamètre no. XX. Convient au propane quand l’appareil est muni d’un injecteur de diamètre no. XX.
WARNING: Do not add any material to the appliance which will come in contact with the
flames, other than that supplied by the manufacturer with the appliance.
AVERTISSEMENT: N’ajoutez pas à cet appareil aucun matériau devant entretien
contact avec les flammes autre que celui qui est fourni avec cet appareil par le fabricant.
The appliance must be vented using the appropriate Napoleon vent kits. See installation manual for venting specifications. Proper reinstallation and resealing is necessary after servicing
the vent-air intake system.
L’appareil doit être ventilé à l’aide de l’ensemble d’évacuation propre à Napoleon. Référez au manuel d’installation pour les spécifications d’évacuation. Il est nécessaire de bien réinstaller et
resceller l’évacuation après avoir executer l’entretien du système de prise d’air.

Serial Number / N° de Série: XXXX

W385-XXXX

This illustration is for reference only. Refer to the rating plate on the appliance for accurate information. note: The rating plate must remain with the appliance at all times. It must not be removed.
1.3 mobile home installation
This appliance must be installed in accordance with the manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only for use with the type(s) of gas indicated on the rating plate. This mobile/manufactured home listed appliance comes factory equipped with a means to secure the appliance. Built in appliances are equipped with 1/4″ (6.4mm) diameter holes located in the front left and right corners of the base. Use appropriate fasteners, inserted through the holes in the base to secure. For free standing products contact your local authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the appliance must be fastened in place. It is recommended that the appliance be secured in all installations. Always turn off the pilot and the fuel supply at the source, prior to moving the mobile home. After moving the mobile home and prior to lighting the appliance, ensure that the logs are positioned correctly. This appliance is certified to be installed in an aftermarket permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used. Conversion Kits This appliance is field convertible between Natural Gas (NG) and Propane (P). To convert from one gas to another, consult your Authorized dealer/distributor.

W415-2351 / B / 12.09.20

7

EN general information
1.4 dimensions

8

W415-2351 / B / 12.09.20

front view

side view

top view

SAFETY BARRIER

34 5/8″ 879mm

6 11/16″ 170mm

24 3/16″ 614mm

1 13/16″ 46mm

14″ 355mm

GAS INLET

12 3/4″ 324mm
8 5/8″ 136mm
30″ 762mm

7″ 178mm
4″ 102mm

! WARNING

venting requirements

· Risk of fire. Maintain specified air space clearances to vent pipe and appliance. · The vent system must be supported every 3′(0.9m) for both vertical and horizontal runs. Use support ring assembly W010-
0067 or equivalent non-combustible strapping to maintain the minimum clearance to combustibles for both vertical and horizontal runs. Spacers are attached to the inner pipe at predetermined intervals to maintain an even air gap to the outer pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this gap is maintained. These spaces must not be removed.

This appliance uses a 4″ (102mm) exhaust / 7″ (178mm) air intake vent pipe system. Refer to the section applicable to your installation.
For safe and proper operation of the appliance, follow the venting instructions exactly. Deviation from the minimum vertical vent length can create difficulty in burner start-up and/or carboning. Under extreme vent configurations, allow several minutes (5-15) for the flame to stabilize after ignition. Although not a requirement, it is recommended for vent lengths that pass through unheated spaces (attics, garages, crawl spaces) be insulated with the insulation wrapped in a protective sleeve to minimize condensation. Provide a means for visually checking the vent connection to the appliance after the appliance is installed. Use a firestop, vent pipe shield or attic insulation shield when penetrating interior walls, floor or ceiling.

The vent terminal may be painted with a high temperature paint to match exterior colours. Use an outdoor paint suitable for 400°F (200°C). Application and performance of paint is the consumer’s responsibility. Spot testing is recommended.
note:
If for any reason the vent air intake system is disassembled, re-install per the instructions provided for the initial installation.
This appliance must be installed with a continuous connection of exhaust and air intake vent pipes. Utilizing alternate constructions such as a chimney as part of the vent system is not permitted.
Use only Wolf Steel, Metal-Fab, BDM, Simpson Dura-Vent, or Selkirk Direct Temp venting components. Minimum and maximum vent lengths, for both horizontal and vertical installations, clearances from vent pipes to combustibles and air terminal locations as set out in this manual apply to all vent systems and must be adhered to. For Metal-Fab, BDM, Simpson Dura-Vent, or Selkirk Direct Temp, follow the installation procedure provided with the venting components or on the website for your venting supplier. A starter adaptor must be used with the following vent systems and may be purchased through Wolf Steel or from the corresponding supplier listed below:

Venting System Manufacturer

Starter Adapter Part Number Supplier

Website

SureSeal

Metal-Fab

4DNA

Wolf Steel

www.mtlfab.com

Direct Vent Pro Simpson DuraVent W175-0053

Wolf Steel

www.duravent.com

Pro-Form

BDM

DVR6-STA7

BDM

www.dalsinmfg.com

Direct Temp

Selkirk

4DT-AAN

Selkirk

www.selkirkcorp.com

Connections made by means of an adaptor at the appliance, as well as the connection at the vent terminal must be sealed. RTV sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems, except for the exhaust vent pipe connection to the appliance flue collar which must be sealed using the black high temperature sealant Mill Pac.
For all rigid vent systems is strongly recommend for all installations but required when power venting the appliance, that the outer air intake joints are sealed using either high temperature silicone (RTV) or a suitable aluminum tape that covers each joint in the vent system entirely around its circumference. This will ensure the best performance in every application and avoids performance or condensation concerns that may occur in “tightly” constructed homes, particularly those in cold climates.
When using Wolf Steel venting components, use only approved Wolf Steel rigid / flexible components with the following
treoTromfhtiniesarmttioeinnmakl ikptsitl:aGwtDeal-l1mte1r1um,sifnltaatbl rkeoitouGf tsDeer-m2d2in2ian,l GkciDtoG-n2D2ju- 21nR1c,2StoioTr4np7eUwrisoictrho1p/te1e2kmittoGp7Dla/-1t22e0sp1it(7cfoh.r1rwo.1oafllotperermn7ein.tr1aal.tk2ioit ,nGdbDeel-op1w1e0ng,rda8di/n1e2g). tWooin1th2/fl1e2xible vetnetrinmg,ininactoionjnunscthioanpweith(i.thee. vraoruionusdt,eromrinraotiuonnsd, uasne deithseqruthaere5)f.ooSte(1e.5amp) vpernotpkirtiGatDe-2t2e0mopr tlhaete1s0 ffoooltd(3e.r1.m) vent kit
GD-330. For stoves only: wall terminal kit GD-175 (venting included).
For optimum flame appearance and appliance performance, keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to verify that it is unobstructed and undamaged. Rigid and flexible venting systems must not be combined. Different venting manufacturer components must not be combined.

W415-2351 / B / 12.09.20

9

EN venting requirements
These vent kits allow for either horizontal or vertical venting of the appliance. The maximum allowable horizontal run is 20 feet (6.1m). The maximum allowable vertical vent length is 40 feet (12.2m). The maximum number of vent connections is two horizontally or three vertically (excluding the appliance and the air terminal connections) when using flexible venting. Horizontal runs may have a 0″ rise per foot or 0mm rise per meter however for optimum performance it is recommended that all horizontal runs have a minimum 1/4″ rise per foot or 21mm rise per meter using flexible venting. For safe and proper operation of the appliance, follow the venting instructions exactly. A terminal shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings. Local codes or regulations may require different clearances. Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1¼” (31.8mm) air gap all around between the inner liner and outer liner is required for safe operation. This appliance is certified for use with a power vent kit. Contact your local authorized dealer for more information.
2.1 typical vent installation
16″ (40.6cm) minimum

24″ (61cm) maximum
8″ (203mm) minimum

10

W415-2351 / B / 12.09.20

TOP VENT

40ft (12m) Maximum
3ft (1m) minimum
34 5/8″ (86cm)

venting requirements EN
16″ (40.6cm) minimum

20″ (50.8cm)
Max.

24 3/16″ (61.4cm) minimum plus rise *

  • See “venting” section

REAR VENT

40 ft (12m) Maximum 3 ft (1m) minimum

24 3/16″ (61.4cm)

W415-2351 / B / 12.09.20

11

EN venting requirements
2.2 special vent installations 2.2.1 periscope termination
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that when final grading is completed, the bottom air slot is located a minimum 12″ (305mm) above grade. The maximum allowable vent length (including both rise and run) is 10′ (3m) for a fireplace and 8′ (2m) for a stove. An insulation sleeve is illustrated in the top vent image below, use only when supplied with the appliance. (The insulation sleeve is not required with a stove appliance)

30″ (76.2cm) minimum

12″ (30.5cm) minimum to grade
30″ (76.2cm) minimum

12″ (30.5cm) minimum to grade

34 5/8″ (87.9CM)

REAR VENT

TOP VENT

2.2.2 corner termination

The maximum vent length for a corner installation is 20″ (50.8cm) of horizontal run, in addition to the 45° offset. In this case zero rise is acceptable. When using rigid venting, it is required to maintain a 6″ (152mm) rise. When using flexible venting, see illustrations below.

6″ (152mm) RISE MINIMUM

20″ (50.8cm) MAXIMUM

Flexible Venting

12

W415-2351 / B / 12.09.20

Rigid Venting

2.3 minimum air terminal location clearances

venting requirements EN
Covered balcony applications *

QS

P

R

G

INSTALLATIONS

CANADA

U.S.A.

QMIN = 3 feet (0.9m)

R MAX = 2 x QACTUAL

RMAX 15 feet (4.6m)

note:

Wall terminals are for illustration purposes only. Size and shapes may vary.

A 12″ (30.5cm) 12″ (30.5cm) Clearance above grade, veranda porch, deck or balcony.

B 12″ (30.5cm) 9″ (229mm) Clearance to windows or doors that open.

C 12″ (30.5cm) 12″ (30.5cm) Clearance to permanently closed windows.

D

18″ (45.7cm)**

18″ (45.7cm)**

Vertical clearance to ventilated soffits located above the terminal within a horizontal distance of 2′ (0.6m) from the center line of the terminal.

E 12″ (30.5cm) 12″ (30.5cm) Clearance to unventilated soffit.

F

0″ (0mm)

0″ (0mm)

Clearance to an outside corner wall.

0″ (0mm)***

0″ (0mm)*** Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney, etc.).

G

2″ (51mm)***

2″ (51mm)*** Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase, etc.).

H

3′(0.9m)

3′(0.9m)****

Clearance to each side of the center line extended above the meter / regulator assembly to a maximum vertical distance of 15′ (4.6m).

I

3′ (0.9m)

3′ (0.9m)**** Clearance to a service regulator vent outlet.

J 12″ (30.5cm)

9″ (229mm) Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other appliance.

K

6′ (1.8m)

3′ (0.9m) Clearance to a mechanical air supply inlet.

L

7′ (2.1m)

7′ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.

M 12″ (30.5cm) 12″ (30.5cm)**** Clearance under a veranda, porch, deck or overhang.

N 16″ (40.6cm) 16″ (40.6cm) Clearance above the roof.

O

2′ (0.6m)*

2′ (0.6m) * Clearance from an adjacent wall including neighbouring buildings.

P

8′ (2.4m)

8′ (2.4m)

Roof must be non-combustible without openings.

Q

3′ (0.9m)

3′ (0.9m)

See chart for wider wall dimensions.

R

6′ (1.8m)

6′ (1.8m)

See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an opening between the terminal and the open side of the structure.

S 12″ (30.5cm) 12″ (30.5cm) Clearance under a covered balcony

The terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.

  • Recommended to prevent condensation on windows and thermal breakage ** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits. * The periscope requires a minimum 18 inches clearance from an inside corner. ** This is a recommended distance. For additional requirements, check local codes. 3 feet above if within 10 feet horizontally.

note:
Clearances are to be in accordance with local installation codes and the requirements of the gas supplier. In their absence, clearances are to be as listed above and are based on national codes.

A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.

Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.

  • Recommended to prevent recirculation of exhaust products. For additional requirements, check local codes.

  • Permitted only if the balcony is fully open on a minimum of one side.

W415-2351 / B / 12.09.20

13

EN venting requirements
2.4 venting application flow chart

Horizontal Termination

TOP EXIT

Vertical Termination

Vertical rise is equal to or greater than the horizontal run

Vertical rise is less than horizontal run

Vertical rise is equal to or greater than the horizontal run

Vertical rise is less than horizontal run

Horizontal run + vertical rise to maximum of 35 feet (10.7m)

Horizontal run + vertical rise to maximum of 24.75
feet (7.5m)

Horizontal run + vertical rise to maximum of 35 feet (10.7m)

Horizontal run + vertical rise to maximum of 35 feet (10.7m)

4.2 times the vertical rise equal to or greater than the
horizontal run

3 times the vertical rise equal to or greater than the horizontal run

Horizontal Termination

REAR EXIT

Vertical Termination

Vertical rise is equal to or greater than the horizontal run

Vertical rise is less than horizontal run

Vertical rise is equal to or greater than the horizontal run

Vertical rise is less than horizontal run

Horizontal run + vertical rise to maximum of 40 feet
(12m)

Horizontal run + vertical rise to maximum of 24.75 feet (7.5m)

Horizontal run + vertical rise to maximum of 40 feet
(12m)

3.5 times the vertical rise equal to or greater than the
horizontal run
2.5 definitions
For the following symbols used in the venting calculations and examples are: > – greater than > – equal to or greater than < – less than < – equal to or less than HT – total of both horizontal vent lengths (Hr) and offsets (Ho) in feet HR – combined horizontal vent lengths in feet HO – offset factor: .03 (total degrees of offset – 90°*) in feet VT – combined vertical vent lengths in feet

14

W415-2351 / B / 12.09.20

Horizontal run + vertical rise to maximum of 40 feet
(12m)
3 times the vertical rise equal to or greater than the horizontal run

2.6 elbow vent length values

venting requirements EN

FEET

0.03

15° 0.45

30° 0.9

45° 1.35

90°* 2.7

INCHES 0.5 6.0 11.0 16.0 32.0

MILLIMETERS 12.7 152.4 279.4 406.4 812.8

  • The first 90° offset has a zero value and is shown in the formula as – 90°

2.7 top exit horizontal termination

(HT) < (VT) Simple venting configuration (only one 90° elbow)

See graph to determine the required vertical rise VT for the required horizontal run HT.

40 (12.2) 39 (11.9)

REQUIRED VERTICAL RISE IN FEET (METERS)V
T

30 (9.1) 20 (6.1) 10 (3.1)

0

2.5

5

7.5

10

12.5

15

17.5

20

(0.8)

(1.5)

(2.3)

(3.1)

(3.8)

(4.6)

(5.3)

(6.1)

HORIZONTAL VENT RUN PLUS OFFSET IN FEET

(METERS) H T

The shaded area within the lines represents acceptable values for HT and VT

For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: HT < VT Formula 2: HT + VT < 40 feet (12.2m)

Example: V1 = 3 FT (0.9m) V2 = 8 FT (2.4m) VT = V1 + V2= 3 FT (0.9m ) + 8 FT (2.4m) = 11 FT (3.4m) H1 = 2.5 FT (0.8m) H2 = 2 FT (0.6m) HR = H1 + H2 = 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m) HO = .03 (three 90° elbows – 90°) = .03 (270° – 90°) = 5.4 FT (1.7m) HT = HR + HO = 4.5 FT (1.4m) + 5.4 FT (1.6m) = 9.9 FT (3m) HT + VT = 9.9 FT (3m) + 11 FT (3.4m) = 20.9 FT (6.4m)

Formula 1: Formula 2:

HT < VT 9.9 FT (3m) < 11 FT (3.4m)
HT + VT < 40 FT (12.2m) 20.9 FT (6.4m) < 40 FT (12.2m)

Since both formulas are met, this vent configuration is acceptable.

90° H
2
V 2

90°

90°

H 1

V 1

W415-2351 / B / 12.09.20

15

EN venting requirements

Simple venting configuration (only one 90° elbow)

(HT) > (VT)
See graph to determine the required vertical rise VT for the required horizontal run HT.
150 (381) 147 (373)

REQUIRED VERTICAL RISE IN INCHES (CENTIMETERS) VT

100 (254)

57 (145) 50 (127)

8 (20.3)

0

5

2 (1.5)

(0.6)

10

15

(3.1) 12.5 (4.6)

(3.8)

20 (6.1)
19.5 (5.9)

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) HT The shaded area within the lines represents acceptable values for HT and VT

For vent configurations requiring more than one 90° elbow, the following formulas apply:

Formula 1: HT < 4.2 VT Formula 2: HT + VT < 24.75 feet (7.5m)
Example:
V1 = VT = 6 FT (1.8m) H1 = 3 FT (0.9m) H2 = 5 FT (1.5m) HR = H1 + H2 = 3FT (0.9m) + 5FT (1.5m) = 8FT (2.4m) HO = .03 (two 90° elbows – 90°) = .03 (180° – 90°) = 2.7FT (0.8m) HT = HR + HO = 8FT (2.4m) + 2.7FT (0.8m) = 10.7FT (3.3m) HT + VT = 10.7FT (3.3m) + 6FT (1.8m) = 16.7FT (5.1m)

90° V1

H1

H2

90°

Formula 1:

HT < 4.2 VT

4.2 VT = 4.2FT (1.3m) x 6FT (1.8m) = 25.2FT (7.7m)

Formula 2:

HT + VT < 24.75 FT (7.5m)

16.7 FT (5.1m) < 24.75 FT (7.5m)

90°

Since both formulas are met, this vent configuration is acceptable.

90°

H1 90°

H4 V2

Example:

V1 = 4 FT (1.2m) V2 = 1.5 FT (0.5m)

90° V1

VT = V1 + V2 = 4 FT (1.2m) + 1.5 FT (0.5m) = 5.5 FT (1.7m)

H1 = 2 FT (0.6m)

H2 = 1 FT (0.3m)

H3 = 1 FT (0.3m)

H4 = 1.5 FT (0.5m)

HR = H1 + H2 + H3 + H4 = 2FT (0.6m) + 1FT (0.3m) + 1FT (0.3m) + 1.5FT (0.5m) = 5.5 FT (1.7m)

HO = .03 (four 90° elbows – 90°) = .03 (360° – 90°) = 8.1 FT (2.5m)

HT = HR + HO = 5.5 FT (1.7m) + 8.1 FT (2.5m) = 13.6 FT (4.2m)

HT + VT = 13.6 FT (4.2m) + 5.5 FT (1.7m) = 19.1 FT (5.8m)

H2 H3

Formula 1:

HT < 4.2 VT 4.2 VT = 4.2 FT (1.3m) x 5.5 FT (1.7m) = 23.1 FT (7m)
13.6 FT (4.2m) < 23.1 FT (7m)

Formula 2:

HT + VT < 24.75 FT (7.5m) 19.1 FT (5.8m) < 24.75 FT (7.5m)

Since both formulas are met, this vent configuration is acceptable.

16

W415-2351 / B / 12.09.20

venting requirements EN

2.8 rear exit horizontal termination

(HT) < (VT)

Simple venting configuration (only two 90° elbows)

See graph to determine the required vertical rise VT for the required horizontal run HT.
40 (12.2) 38.3 (11.7)

REQUIRED 30 (9.1)

VERTICAL

RISE IN

20 (6.1)

FEET

(METERS) VT 10 (3.1)

1.6 (0.5)
0

2.5 1.6 (0.8) (0.5)

5 (1.5)

7.5 (2.3)

10 (3.1)

12.5 (3.8)

15 (4.6)

17.5 (5.3)

20 (6.1)

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) HT
The shaded area within the lines represents acceptable values for HT and HT

For vent configurations requiring more than two 90° elbows, the following formulas apply:

Formula 1: HT < VT Formula 2: HT + VT < 40 feet (12.2m)

Example:

V1 = 9 FT (2.7m)

V2 = 6 FT (1.8m)

VT = V1 + V2 = 9FT (2.7m) + 6FT (1.8m) = 15FT (4.6m)

H1 = 3 FT (0.9m)

H2 = 2 FT (0.6m)

H3 = 1.5 FT (0.5m)

HR = H1 + H2 + H3 = 3FT (0.9m) + 2FT (0.6m) + 1.5FT (0.5m) = 6.5FT (2m)

HO = .03 (four 90° elbows – 90°) = .03 (360° – 90°) = 8.1 FT (2.5m)

HT = HR + HO = 6.5FT (2m) + 8.1FT (2.5m) = 14.6FT (4.5m)

HT + VT = 14.6FT (4.5m) + 15FT (4.6m) = 29.6 FT (9m)

H1

Formula 1:

HT < VT 14.6 FT (4.5m) < 15 FT (4.6m)

Formula 2:

HT + VT < 40 FT (12.2m) 29.6 FT (9m) < 40 FT (12.2m)

Since both formulas are met, this vent configuration is acceptable.

90° V1

90° H3
V2 H2 90°
90°

W415-2351 / B / 12.09.20

17

EN venting requirements
Simple venting configuration (only two 90° elbows)

(HT) > (VT)
See graph to determine the required vertical rise VT for the required horizontal run HT.
12.5 (3.8) 12.25 (3.7)

REQUIRED VERTICAL RISE IN
FEET (METERS)VT

8.3 (2.54)
5.5 (1.68)
4.2 (1.3)

1 (0.3)

0

2.5

5

(0.8)

(1.5)

1 (0.3)

3.5 (1.1)

7.5 (2.3)

10 (3.1)

12.5 (3.8)

15 (4.6)

17.5 (5.3)

20 (6.1)
19.25 (5.9)

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) HT The shaded area within the lines represents acceptable
values for HT and HT

For vent configurations requiring more than two 90° elbows, the following formulas apply:
Formula 1: HT < 3.5VT Formula 2: HT + VT < 24.75 feet (7.5m)

Example:
V1 = 4 FT (1.2m) V2 = 1.5 FT (0.5m) VT = V1 + V2 = 4FT (1.2m) + 1.5FT (0.5m) = 5.5 FT (1.7m) H1 = 2 FT (0.6m) H2 = 1 FT (0.3m) H3 = 1 FT (0.3m) H4 = 1.5 FT (0.5m) HR = H1+ H2+H3+H4= 2FT(0.6m) + 1FT(0.3m) + 1FT(0.3m) + 1.5FT(0.5m) = 5.5 FT(1.7m) HO = .03 (four 90° elbows + one 45° elbow – 90°)
= .03 (90 + 90 + 90 + 90 + 45 – 90) = 9.45 FT (2.9m)
HT = HR + HO = 5.5FT (1.7m) + 9.45FT (2.9m) = 14.95FT (4.6m) HT + VT = 14.95FT (4.6m) + 5.5FT (1.7m) = 20.45FT (6.2m)

90° H3
V2 90°
H2
90° V1

Formula 1:

HT < 3.5VT 3.5VT = 3.5FT (1.1m) x 5.5FT (1.7m) = 19.25FT (5.9m)
14.95 FT (4.6m) < 19.25 FT (5.9m)

Formula 2:

HT + VT < 24.75 FT (7.5m) 20.45 FT (6.2m) < 24.75 FT (7.5m)

Since both formulas are met, this vent configuration is acceptable.

H1 90°

18

W415-2351 / B / 12.09.20

2.9 top and rear exit vertical termination

venting requirements EN

Simple venting configurations.

(HT) < (VT)
See graph to determine the required vertical rise VT for the required horizontal run HT.
40 (12.2)

REQUIRED VERTICAL RISE
IN FEET (METERS)VT

30 (9.1) 20 (6.1)

10 (3.1)

3 (0.9)

0

5

10

15

20

(1.5)

(3.1)

(4.6)

(6.1)

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) HT
The shaded area within the lines represents acceptable values for HT and HT

For vent configurations requiring one or more 90° elbows (top exit) or one or more 90° elbows (rear exit), the following formulas apply:

Formula 1: HT < VT Formula 2: HT + VT < 40 feet (12.2m)

Example:
V1 = 5 FT (1.5m) V2 = 6 FT (1.8m) V3 = 10 FT (3.1m) VT = V1 + V2 + V3 = 5FT (1.5m) + 6FT (1.8m) + 10FT (3.1m) = 21 FT (6.4m) H1 = 8 FT (2.4m) H2 = 2.5 FT (0.8m) HR = H1+ H2 = 8FT (2.4m) + 2.5FT (0.8m) = 10.5FT (3.2m) HO = .03 (four 90° elbows – 90°)
= .03 (360° – 90°) = 8.1 FT (2.5m)
HT = HR + HO = 10.5FT (3.2m) + 8.1FT (2.5m) = 18.6FT (5.7m) HT + VT = 18.6FT (5.7m) + 21FT (6.4m) = 39.6FT (12.1m)

Formula 1:

HT < 3.5VT 18.6 FT (5.7m) < 21 FT (6.4m)

Formula 2:

HT + VT < 40 FT (12.2m) 39.6FT (12.1m) < 40 FT (12.2m)

Since both formulas are met, this vent configuration is acceptable.

W415-2351 / B / 12.09.20

19

EN venting requirements
Simple venting configurations.

(HT) > (VT)

See graph to determine the required vertical rise VT for the required horizontal run HT.
20 (6.1) 19 (5.8)
REQUIRED

VERTICAL RISE IN

10 (3.1)

FEET (METERS)VT 3 (0.9)
0

5 (1.5)

10 (3.1)

15 (4.6)

20 (6.1)

25 (7.6)

30 (9.1)

HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS)HT
The shaded area within the lines represents acceptable values for HT and HT

20

For vent configurations requiring more than two 90° elbows (top exit) or one 90° elbow (rear exit), the following formulas apply:

Formula 1: HT < 3 VT Formula 2: HT + VT < 40 feet (12.2m)
Example:

V1 = 2 FT (0.6m)

90°

V2 = 1 FT (0.3m)

V3 = 1.5 FT (0.5m)

VT = V1 + V2 + V3 = 2FT (0.6m) + 1FT (0.3m) + 1.5FT (0.5m) = 4.5 FT (1.4m) H1 = 6 FT (1.8m)

V1

H2 = 2 FT (0.6m)

H1

HR = H1 + H2 = 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)

HO = .03 (four 90° elbows – 90°)

= .03 (360° – 90°) = 8.1 FT (2.5m)

90° H2 V2
90°

V3 90°

HT = HR + HO = 8FT (2.4m) + 8.1FT (2.5m) = 16.1FT (4.9m) HT + VT = 16.1FT (4.9m) + 4.5FT (1.4m) = 20.6FT (6.3m)

Formula 1:

HT < 3.5 VT 3.5 VT = 3FT (0.9m) x 4.5FT (1.4m) = 13.5 FT (4.1m)
16.1FT (4.9m) < 13.5 FT (4.1m)

Since this formula is not met, this vent configuration is unacceptable.

Formula 2:

HT + VT < 40 FT (12.2m) 16.1FT (4.9m) < 13.5 (4.1m)

Since only formula 2 is met, this vent configuration is unacceptable and a new fireplace location or vent configuration will

need to be established to satisfy both formulas. Example:

18.2_2B

V1 = 1.5 FT (0.5m)

V2 = 5 FT (1.5m)

VT = V1 + V2 = 1.5FT (0.5m)+ 5FT (1.5m) = 6.5 FT (2m)

H1 = 1 FT (0.3m)

H2 = 1 FT (0.3m)

H3 = 10.75 FT (3.3m)

HR = H1 + H2 + H3 = 1FT (0.3m) + 1FT (0.3m) + 10.75FT (3.3m) = 12.75FT (3.9m)

V2

HO = .03 (three 90° elbows + one 45° elbow – 90°)

90°

= .03 (270° + 45° – 90°) = 6.75 FT (2.1m)

H2

HT = HR + HO = 12.75FT (3.9m) + 6.75FT (2.1m) = 19.5 FT (5.9m)

45°

HT + VT = 19.5FT (5.9m) + 6.5FT (2m) = 26 FT (7.9m)

Formula 1: HT < 3 VT

V1

H3

90°

3 VT = 3FT (0.9m) x 6.5FT (2m) = 19.5FT (5.9m) 19.5FT (5.9m) = 19.5FT (5.9m)

H1

Formula 2:

90°

HT + VT < 40 FT (12.2m) 26 FT (7.9m) < 40 FT (12.2m)

Since both formulas are met, this vent configuration is acceptable.
W415-2351 / B / 12.09.20

2.10 rear exit

venting requirements EN

! WARNING

· Failure to create a seal to the firebox with the exhaust collar assembly will cause the appliance to function improperly and can cause injury or property damage.

A.

Remove the safety barrier and glass front, refer to “safety

barrier & door removal/installation” section.

Fig. 1

B.

Remove the contents from the firebox and set aside, you will

need the exhaust flue collar from the top of the log carton.

C.

To ease assembly, remove the four hex head screws

securing the deflector from inside the top front of the firebox,

refer to Figure 1.

D.

Place the gasket (provided) over the 4″ (102mm) flue collar

assembly and bend along perforation.

DEFLECTOR DÉFLECTEUR
Fig. 2

E.

From inside the firebox, insert the 4″ (102mm) flue collar through the back

of the firebox. Install the rear exit shield onto the 4″ (102mm) flue collar, see

“rear exit shield” section for installation instructions.

F.

Secure the flue collar assembly, gasket and rear exit shield using the four hex

head 3/8″ thread cutting screws, refer to Figure 2.

note:
Do not overtighten. The gasket needs only to be snug against the firebox.

G.

Reattach the deflector using the four screws and

install the log set, glass door and safety barrier.

H.

Install the 7″ collar assembly, complete with

gasket, onto the rear panel around the 4″

(101.6mm) collar with the screws provided (FIG

3).

Fig. 3
GASKET INTAKE COLLAR ASSEMBLY

2.11
A.

rear exit shield (for rear vent only)
Remove the safety barrier assembly and door from the appliance, refer to the “safety barrier & door removal / installation” section of the manual for detailed instructions.

B.

Loosen the two screws, that secure the exhaust plate, and slide the shield in place by sliding its slotted

openings behind the screwheads,

tighten the two previously loosened

screws. Refer to the illustration .

C.

Reinstall the door and safety barrier

assembly on the appliance, see to

the “safety barrier & door

removal / installation” section.

note:
This shield is used to block the view through the venting to the outdoors.

W415-2351 / B / 12.09.20

21

EN venting requirements
2.12 top exit
! WARNING
· Failure to install the cover plate and gasket will cause the appliance to function improperly and can cause injury or property damage.

This appliance is factory shipped as a rear vent model equipped with a #50 burner orifice. This orifice size is suitable for rear vent installations with 0″ vertical rise only. For top exit applications, the main burner orifice should be changed to the #49 burner orifice (supplied) for natural gas. For propane models, the appliance is converted to a #58 burner orifice for rear vent applications or a #57 burner orifice for top vent applications.

A.

Remove the safety screen and glass front, refer to ” SAFETY

SCREEN / DOOR REMOVAL AND INSTALLATION” section.

B.

Remove the contents from the firebox and set aside, you will

need the exhaust collar from the top of the log carton.

C.

To ease assembly, remove the four hex head screws securing

the deflector from inside the top front of the firebox.

D.

Remove the single screw from the outer cover on the

back of the appliance.

DEFLECTOR DÉFLECTEUR
GASKET E

E.

Remove the four screws on the 7″ (178mm) intake collar

assembly; set the intake collar and gasket aside. Careful

not to damage gasket.

F.

Remove the single screw from the outer cover with

knockout intact, on the top of the appliance and set aside.

INTAKE COLLAR E
ASSEMBLY
OUTER COVER D

G.

Remove the inner cover plate and gasket by removing the

four screws. Reinstall the inner cover plate and gasket

onto the back of the appliance.

H.

Take the outer cover (with knockout intact) and secure

onto the back of the appliance.

I.

Remove and discard the 1 1/2″ thick batt of insulation

from the top opening.

J.

Place the 7″ (178mm) intake collar and gasket onto the top of the appliance and secure with the four

screws.

K.

Reinstall the outer cover (without knock out) over the 7″ (178mm) exhaust collar assembly and secure.

L.

From inside the firebox, install the 4″ (102mm) exhaust collar up through the top of the firebox and

secure with the the four hex head 3/8″ thread cutting screws. NOTE: Do not overtighten. The gasket

needs only to be snug against the firebox.

M.

Reattach the top deflector, log set, glass door and safety screen.

FLUE PIPE WITH GASKET

OUTER

COVER

F

PLATE (without

knockout)

INNER
G COVERPLATE
GASKET

I

EXHAUST FLUE COLLAR

22

W415-2351 / B / 12.09.20

3.0 rough framing EN
note: When using optional finishing accessories, the framing dimensions and finishing materials may differ from what is outlined in the section below; refer to the leaflet instructions supplied in the accessory kit for specific framing and finishing specifications.
! WARNING
· Risk of fire! · In order to avoid the possibility of exposed insulation or vapour barrier coming in contact with the appliance
body, it is recommended that the walls of the appliance enclosure be “finished” (i.e. drywall / sheetrock), as you would finish any other outside wall of a home. This will ensure that clearance to combustibles is maintained within the cavity. · Do not notch the framing around the appliance stand offs. Failure to maintain air space clearance may cause over heating and fire. Prevent contact with sagging or loose insulation or framing and other combustible materials. Block opening into the chase to prevent entry of blown- in insulation. Make sure insulation and other materials are secured. · When constructing the enclosure, allow for finishing material thickness to maintain clearances. Framing or finishing material closer than the minimums listed must be constructed entirely of non-combustible materials. Materials consisting entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or any combination thereof are suitable. Materials that are reported as passing ASTM E136, standard test method for behaviour of materials in a vertical tube furnace at 1382ºF (750ºC) and UL763 shall be considered non-combustible materials. · Minimum clearance to combusibles must be maintained or a serious fire hazard could result. · The appliance requires a minimum enclosure height. Measure from the appliance base. · If steel stud framing kits with cement board are provided, or specified in the installation instructions, they must be installed. · If specified in the installation instruction, finishing must be done using a non-combustible board, ceramic tile, marble, etc. Do NOT use wood or drywall. Any fire rated drywall is not acceptable.
It is best to frame your appliance after it is positioned and the vent system is installed. Frame to local building codes.
It is not necessary to install a hearth extension with this appliance.
When roughing in the appliance, raise the appliance to accommodate for the thickness of the finished floor materials, i.e. tile, carpeting, hard wood, which if not planned for will interfere with the opening of the lower access door and the installation of many decorative flashing accessories.
Combustible materials may be installed flush with the front of the appliance but must not cover any of the black face-areas of the appliance. Non- combustible material (brick, stone or ceramic tile) may protrude in these areas.

W415-2351 / B / 12.09.20

23

EN rough framing
3.1 minimum framing dimensions
SIDE WALL 2″
(51mm)

29 1/2″ (75cm)

30 1/2″ (77.5cm)

(1064c1m3()7/47″.53c0m1)/2″

14 1/2″ (36.8cm)

Do not put objects in front of the appliance (minimum distance of 4 feet)

  • HORIZONTAL VENT SECTIONS: A minimum of 1″ (25mm) at the bottom and sides and 3″ (76mm) at the top of the vent pipe on all horizontal runs to combustibles is required.
    NOTE: The minimum clearances from the top of the horizontal vent pipe to combustible materials may be reduced from 3″(76mm) to 1″(25mm) in those installations with a minimum 38″ (965mm) vertical vent rise made immediately off the fireplace collar.
  • VERTICAL VENT SECTIONS: A minimum of 1″ (25mm) all around the vent pipe on all vertical runs to combustibles is required except for clearances in appliance enclosures. See “minimum enclosure clearances” section.

24

W415-2351 / B / 12.09.20

3.2 minimum enclosure clearances TOP VENT

rough framing EN
COMBUSTIBLE NON-COMBUSTIBLE

3″ [76mm] MINIMUM *

54″ [1372mm] CEILING
(MIN)

15 5/8″ 3″ [76mm] [403mm] 2″ [51mm]

BRICK 0″(0MM) IF 3″ [76mm] NON-COMBUSTIBLE
FINISHING IS USED SUCH AS BRICK AND STONE.
1″ [25mm]

50 1/2″ [1283mm]

14 1/2″ [368mm]

42 5/8″ [1083mm] MINIMUM PLUS RISE*

1″ [25mm] TOP EXIT ENCLOSURE The appliance requires a minimum non-combustible enclosure height of 50 1/2″ (1283mm). For temperature requirements, the enclosure space around and above the appliance must be left unobstructed. NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall penetration.

  • See “MINIMUM FRAMING DIMENSION” section for details on reducing vent pipe top clearances.
    These parameters also apply to the illustrations found in the “MINIMUM ENCLOSURE CLEARANCES” section.

W415-2351 / B / 12.09.20

25

EN rough framing
REAR VENT
For rear vent termination not exceeding 10″ (254mm) of horizontal vent run.

NON-COMBUSTIBLE

COMBUSTIBLE

BRICK

41 5/8″ [105.7cm]

7″ [178mm]

34 5/8″ [87.9cm]

3″ [76mm]

0″ (0MM) IF NON-COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE.

1″ [25mm]

24 3/16″ [61.4cm] MINIMUM PLUS RISE*

1″-10″ [25mm-254mm] VENT RUN
REAR EXIT ENCLOSURE The appliance requires a minimum enclosure height of 41 5/8″ (1057mm). For temperature requirements, the enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall penetration.

  • See “VENTING” section.

26

W415-2351 / B / 12.09.20

MAXIMUM REAR VENT CLEARANCES (EXAMPLE 1)

rough framing EN

NON-COMBUSTIBLE COMBUSTIBLE
BRICK

41 5/8″ [105.7cm]

7″ [178mm]

34 5/8″ [87.9cm]

11 1/2″ [292mm]

3″ [76mm]

0″ (0MM) IF NON-COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE.

1″ [25mm]

2244 33/1166″ ” (6[611..44ccmm] ) MINIMUM PLUS RISE*

10″-20″ [254mm-508mm] VENT RUN
REAR EXIT ENCLOSURE The appliance requires a minimum enclosure height of 41 5/8″ (1057mm). For temperature requirements, the enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall penetration.

W415-2351 / B / 12.09.20

27

EN rough framing
MAXIMUM REAR VENT CLEARANCES (EXAMPLE 2)

41 5/8″ [105.7cm]

7″ [178mm]

34 5/8″ [87.9cm]

11 1/2″ [292mm]

3″ [76mm]

0″ (0MM) IF NON-COMBUSTIBLE FINISHING IS USED SUCH AS BRICK AND STONE.

COMBUSTIBLE NON-COMBUSTIBLE

1″ [25mm] BRICK

242431//186″ ” (6[161..43ccmm]) MINIMUM PLUS RISE*

10″-20″ [254mm-508mm] VENT RUN
REAR EXIT ENCLOSURE The appliance requires a minimum enclosure height of 41 5/8″ (1057mm). For temperature requirements, the enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall penetration.

28

W415-2351 / B / 12.09.20

rough framing EN
note: For heavier finishing materials such as marble, we recommend adding extra support to the frame. Ensure there is adequate floor support for the appliance and finishing material.
Before framing your appliance, determine vent requirements before deciding the final location of the appliance. After rough framing, place the appliance in its final position.

A B

Ref

Minimum rough framing dimensions

A

14 1/2″* (36.8cm)

B

30 1/2″ (77.5cm)

  • Based on 1/2″ finishing material thickness.

W415-2351 / B / 12.09.20

29

EN 4ve.0ntvinegntiinnsgtainllasttaiollnation ! WARNING
· Ensure to unpack all loose materials from inside the firebox prior to connecting the gas and electrical supply · If your appliance is supplied with a remote, ensure the remote receiver is in the “OFF” position prior
to connecting the gas and electrical supply to the appliance. · For safe and proper operation of the appliance, follow the venting instructions exactly. · The appliance exhaust flue collar must be sealed using Mill Pac. All exhaust and intake vent pipe joints
must be sealed using red RTV high temp silicone sealant (W573-0002) (not supplied) or black high temp Mill Pac (W573-0007) (not supplied). · If using pipe clamps to connect rigid vent components, a minimum of 3 screws must also be used to ensure the connection cannot slip off. · Do not clamp the flexible vent pipe. · Risk of fire, explosion, or asphyxiation. Improper support of the entire venting system may allow vent to sag and separate. Use vent run supports and connect vent sections per installation instructions. · Risk of fire, do not allow loose materials or insulation to touch the vent pipe. Remove insulation to allow for the installation of the attic shield and to maintain clearances to combustibles. · Do not fill the space between the vent pipe and enclosure with any type of material. Do not pack insulation or combustibles between ceiling firestops. Always maintain specified clearances around venting and firestop systems. Install wall shields and firestops as specified. Failure to keep insulation or other materials away from vent pipe may cause fire. · For gas stoves only: If the appliance is installed directly on carpeting, vinyl tile, or other combustible material other than wood flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth, unless otherwise tested.
For optimum performance, it is recommended that all horizontal runs have a minimum of 1/4″ (6mm) rise per foot using flexible venting. For safe and proper operation of the appliance, follow the venting instructions exactly.

30

W415-2351 / B / 12.09.20

Installation

4.1 horizontal installation

venting installation EN

! WARNING

· The firestop assembly must be installed with the vent shield to the top. · Terminals must not be recessed into a wall or siding more than the depth of the return flange of the mounting
plate. · The vent shield must be fixed in place by fastening the extended vent shield to the bend tabs using the
supplied fasteners.

This application occurs when venting through an exterior wall. Having determined the correct height for the air terminal location, cut and frame a hole in the exterior wall, as illustrated, to accommodate the firestop assembly. Dry fit the firestop assembly before proceeding to ensure the brackets on the rear surface fit to the inside surface of the horizontal framing.
The vent shield must be installed to the full depth of the combustible wall. The length of the vent shield may cut shorter for combustible walls that less than 8 1/2″ (216mm) thick.
note:
Bend the tabs for reduced side clearances or move the shield for reduced top clearances (dependent on specific appliance clearances). Do not fill the air space between the firestop spacer and the exterior wall with any type of insulating material (i.e. spray foam).

VENT
SHIELD CAULKING

11 1/8″ (28.2CM)

14 1/2″ (36.8CM)

FIRESTOP SPACER

CAULKING

FINISHING MATERIAL

DETERMINE THE CORRECT HEIGHT

The above is for illustrative purposes only. Vents do not always pass through
center of frame.

A. Fold the vent shield up so that it is perpendicular to the spacer plate.

C

B. Bend the tabs located on either side of the vent shield so that they are just shy of 90º to the spacer plate.

C. On both sides of the firestop, fasten the (W570-0018)

screws through the clearance holes in the bend tabs and

threaded into the holes in the vent shield.

C

D. Apply a bead of caulking around the outer edge of the

firestop assembly. E. Screw the firestop onto the wall/framing, using 4 screws.

A

F. Once the vent pipe is installed in its final position, apply red RTV silicone (W573-0002) (not supplied) between the pipe and the firestop.

note:
Where the venting passes horizontally through a wall, you MUST use a Wolf Steel firestop for all rigid and flex vent systems. The gap between the outside diameter of the vent and the firestop MUST be completely sealed with high temperature RTV. When using flex venting, use firestop assembly W010-3440 (not supplied). When using rigid venting, use firestop assembly 4DHFSN (not supplied).

W415-2351 / B / 12.09.20

31

EN venting installation

4.2 vertical installation

This application occurs when venting through a roof. Installation kits for various roof pitches are available from your authorized dealer / distributor. See the “accessories” section to order specific kits required.

A. Determine the air terminal location, cut and frame a square opening, as illustrated, in the ceiling and the roof to provide the minimum 1″ (25mm) clearance between the vent pipe and any combustible material. Try to center the vent pipe location midway between two joists to prevent having to cut them. Use a plumb bob to line up the center of the openings. A vent pipe shield will prevent any materials such as insulation, from filling up the 1″ (25mm) air space around the pipe. Nail headers between the joist for extra support.

Firestop underside
of joist

B. Apply a bead of caulking (not supplied) to the framework or to the Wolf Steel vent pipe shield plate or equivalent (in the case of a finished ceiling), and secure over the opening in the ceiling. A firestop must be placed on the bottom of each framed opening in a roof or ceiling that the venting system passes through. Apply a bead of caulking all around and place a firestop spacer over the vent shield to restrict cold air from being drawn into the room or around the fireplace. Ensure that both spacer and shield maintain the required clearance to combustibles. Once the vent pipe is installed in its final position, apply red RTV silicone (W573-0002) (not supplied) between the pipe and the firestop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will prevent any materials, such as insulation, from filling up the 1″ (25mm) air space around the pipe.

Vent Pipe Shield

Caulking

Vent Pipe Shield

Vent Pipe Collar

note:

Where the venting passes vertically through a wall you use MUST use a Wolf Steel firestop for all rigid and flex vent systems. The gap between the outside diameter of the vent and the firestop MUST be completely sealed with high temperature RTV. For 4″/7″ appliances: When using flex venting, use firestop assembly W500-0292 (not supplied). When using rigid venting, use firestop assembly 4DFS (not supplied). For 5″/8″ appliances: When using flex venting, use firestop assembly W500-0028 (not supplied). When using rigid venting, use firestop assembly 5DFS (not supplied).

32

W415-2351 / B / 12.09.20

4.3 using either flexible or rigid vent components

venting installation EN

! WARNING
· Do not allow the inner flex pipe to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. · Spacers are attached to the inner flex pipe at predetermined intervals to maintain an even air gap to the outer
flex pipe. This gap is required for safe operation. A spacer is required at the start, middle, and end of each elbow to ensure this gap is maintained. These spacers must not be removed.

Elbow

Spacers

For safe and proper operation of the appliance, follow the venting instructions exactly. The vent system must be supported approximately every 3 feet (0.9m) for both vertical and horizontal runs. Use Wolf Steel Ltd. support ring assembly or equivalent noncombustible strapping to maintain the minimum clearance to combustibles for both vertical and horizontal runs. All inner flex pipe and outer flex pipe joints may be sealed using high temperature red RTV silicone W573-0002 (not supplied) or the high temperature sealant W5730007 Mill Pac (not supplied). However, the high temperature sealant W573-0007 Mill Pac (not supplied) must be used on the joint connecting the inner flex pipe and the exhaust flue collar.
Use only approved flexible vent pipe kits marked:

“Wolf Steel Approved Venting” or “E2″ as identified by the stamp only on the flex pipes.

4.3.1 horizontal air terminal installation

A.

Stretch the inner flex pipe to the required length taking

into account the additional length needed for the finished ADD FASTENER TYPE

wall surface. Apply a heavy bead of the red RTV silicone

(W573-0002) (not supplied) to the inner sleeve of the air

terminal. Slip the vent pipe a minimum of 2″ (50.8mm)

Caulking

over the inner sleeve of the air terminal and secure with a minimum of 3 screws.

B.

Using the outer flex pipe, slide over the outer combustion

air sleeve of the air terminal and secure with a minimum

of 3 screws. Seal using red RTV silicone (W573-0002)

InnePripFelex
Outer Flex Pipe 2″ (50.8mm) Overlap

(not supplied).

C.

Insert the vent pipes through the firestop maintaining

the required clearance to combustibles. Holding the air

Screws (Supplied)

Red RTV Silicone

terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing

ADD GRAPHIC

with caulking (not supplied).

D.

If more vent pipe needs to be used to reach the fireplace, Red RTV Silicone

couple them together, as illustrated. The vent system

Screws Inner Coupler Outer Coupler

must be supported approximately every 3 feet (0.9m) for

both vertical and horizontal runs. Use non-combustible strapping to maintain the minimum clearance to combustibles.

E.

Stove Appliances Only: From inside the house, using

Outer Flex Pipe

Inner Flex Pipe

Outer Flex Pipe

Red RTV Silicone (W573-0002) (not supplied), seal

between the vent pipe and the firestop. Then slide the black trim collar over the vent pipe up to the

firestop.

The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its return flange.

W415-2351 / B / 12.09.20

33

EN venting installation
4.3.2 vertical air terminal installation

! WARNING
· Maintain a minimum 2″ (51mm) space between the air inlet base and the storm collar.

note: Fastening hardware provided with appropriate roof terminal and liner kits.

A. Fasten the roof support to the roof using 6 screws. The roof support is optional. In this case, the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.

B. Stretch the inner flex pipe to the required length. Slip the inner flex pipe a minimum of 2″ (51mm) over the inner pipe of the air terminal connector and secure with a minimum of three screws, when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws when using 8/10 or 8/11 venting. Seal using a heavy bead of red RTV silicone sealant (W573-0002) (not supplied).

Roof Support

C. Repeat using the outer flex pipe, using a heavy bead of red RTV silicone sealant (W573-0002) (not supplied) and a minimum of three screws, when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws when using 8/10 or 8/11 venting.

Inner Pipe

D. Thread the air terminal connector / vent pipe assembly down through the roof. The air terminal must be positioned vertically and plumb. Attach the air terminal connector to the roof support, ensuring that the

Air Terminal Connector

top of the air terminal is 16″ (40.6cm) above the highest point that it

Red RTV

penetrates the roof.

Silicone (W572-0002)

E. Remove nails from the shingles, above and to the sides of the air terminal connector. Place the flashing over the air terminal connector leaving a min. 3/4″ (19mm) of the air terminal connector showing above

Inner Flex Pipe Outer Flex Pipe

the top of the flashing. Slide the flashing underneath the sides and

upper edge of the shingles. Ensure that the air terminal connector is

properly centered within the flashing, giving a 3/4″ (19mm) margin all

around. Fasten to the roof. Do not nail through the lower portion of the

flashing. Make weather-tight by sealing with caulking. Where possible,

cover the sides and top edges of the flashing with roofing material.

Air Inlet

F. Aligning the seams of the terminal and air terminal connector, place the 2″ (51mm)

Base

terminal over the air terminal connector making sure the vent pipe goes into the hole in the terminal. Secure with a minimum of three screws, when 4/7, 5/8 and 3/5 venting is used and a minimum of six screws

Caulking Storm Collar

when using 8/10 or 8/11 venting.

Weather

G. Apply a heavy bead of weatherproof caulking 2” (51mm) above the

Sealant

flashing. Install the storm collar around the air terminal and slide down

to the caulking. Tighten to ensure that a weather-tight seal between the

Flashing

air terminal and the collar is achieved.

H. If more vent pipe needs to be used to reach the appliance, see “horizontal air terminal installation” section.

4.3.3 applianceAvDenDt cFoAnnSeTctEioNn ER TYPE

A. Install the inner flex pipe to the appliance. Secure with a minimum of three screws when installing 3″/5″, 4″/7″ or 5″/8″ venting, or six screws when installing 8″/10″ or 8″/11″ venting. Seal the joint and screw holes using Mill Pac sealant (W573-0007) (not supplied).

INSERT #8 X 1/2″
Self Drilling Screws
IMAGE HERE 21″1(/541″ m(31m.8)mm) Overlap

B. Install the outer flex pipe to the appliance. Secure with a minimum of three screws when installing 3″/5″, 4″/7″ or 5″/”8 venting, or six screws when installing 8″/10″ or 8″/11″ venting. Seal the joints using high temperature red RTV silicone (W573-0002) (not supplied).

Mill-Pac Sealant
Red RTV Silicone

34

W415-2351 / B / 12.09.20

4.3.4 horizontal air terminal installation

venting installation EN

A. Move the appliance into position. Measure the vent length required between terminal and appliance taking into account the additional length needed for the finished wall surface and any 2″ (50.8mm) overlaps between venting components.

10×2″ SCREWS

B. Apply a heavy bead of Mill Pac sealant (W573-0007) (not supplied) to the outer edge of the inner collar of the appliance. Attach the first inner rigid pipe component and secure using a minimum of three screws. Repeat using the outer rigid pipe. Seal using Red RTV Silicone (W573-0002) (not supplied).

CAULKING
INNER OUTER RIGID RIGID PIPE PIPE
2″ (50.8mm) OVERLAP
HI-TEMP SEALANT

C. Insert the vent pipes through the firestop maintaining the required clearance to combustibles. Apply a heavy bead of Red RTV Silicone (W573-0002) (not supplied) to both the inner sleeve and outer sleeve of the air terminal. Slide the terminal sleeves into the rigid pipes a minimum of 1 1/4″. Holding the air terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).

The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of the return flange.

W415-2351 / B / 12.09.20

35

EN venting installation
4.3.5 vertical air terminal installation

! WARNING

· Maintain a minimum 2″ (51mm) space between the air inlet base and the storm collar.

note: Fastening hardware provided with appropriate roof terminal and liner kits.
Before attaching elbows to the collars on the back of the appliance, 1 1/2″ (38.1mm) will need to be trimmed off the 4″ (101.6mm) collar.

REAR VENT APPLICATIONS ONLY: Attach 4″ (101.6mm) and 7″ (177.8mm) elbows to the appliance. Secure with 3 screws and seal the joints and screw heads using high temperature sealant. Proceed to step A below.

TOP AND REAR VENT APPLICATIONS: A. Move the appliance into position.

INNER PIPE

B. Fasten the roof support to the roof using the screws provided. The roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.

AIR TERMINAL CONNECTOR

C. Apply high temperature sealant W573-0007 (not supplied) to the outer edge of the inner sleeve of the air terminal. Slip the inner coupler a minimum of 2″ (51mm) over the sleeve and secure using 3 screws.

HIGH TEMPERATURE SEALANT

D. Apply high temperature sealant W573-0002 (not supplied) to the outer edge of the of the outside sleeve of the air terminal connector. Slip the outer coupler over the sleeve and secure as before. Trim the outer coupler even with the inner coupler end.

INNER RIGID PIPE
OUTER RIGID

E. Thread the air terminal connector / vent pipe assembly down through the roof support and attach, ensuring that a minimum 16″ (40.6cm)of air terminal connector will penetrate the roof when fastened. If the attic space is tight, we recommend threading the Wolf Steel vent pipe collar or equivalent loosely onto the air terminal connector / vent pipe assembly as it is passed through the attic. The air terminal connector must be positioned vertically and plumb.

PIPE
VENT PIPE COLLAR VENT

F. Remove nails from the shingles, above and to the sides of the air terminal

PIPE

connector. Place the flashing over the air terminal connector and slide it

SHIELD

underneath the sides and upper edge of the shingles. Ensure that the air

terminal connector is properly centered within the flashing, giving a 3/4″

(19.1mm) margin all around. Fasten to the roof. Do NOT nail through the lower portion of the flashing.

Make weather-tight by sealing with caulking. Where possible, cover the sides and top edges of the flashing

with roofing material.

G. Apply a heavy bead of waterproof caulking 2″ (51mm) above the flashing. Install the storm collar around the air terminal and slide down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal connector and the collar is achieved.

H. Continue adding rigid venting sections, sealing and securing as above. Attach the inner collapsed telescopic sleeve to the last section of rigid piping. Secure with screws and seal. Repeat using the outer telescopic sleeve.

I. Run a bead of high temperature sealant W573-0007 (not supplied) around the outside of the inner elbow for rear vent applications or the inner collar for top vent applications. Pull the telescopic sleeve a minimum of 2″ (51mm) onto the elbow. Secure with three screws. Repeat with the outer telescopic sleeve.

TOP VENT APPLICATIONS ONLY:

K. In the attic, slide the vent pipe collar down to cover up the open end of the shield and tighten. This will prevent any materials, such as insulation, from filling up the 1″ (25mm) air space around the pipe.

36

W415-2351 / B / 12.09.20

4.4 vertical through existing chimney

venting installation EN

! WARNING
· Risk of fire. · Co-axial to co-linear venting configurations must only be used in a non-combustible chimney or enclosure.
Installation in a combustible enclosure could result in a fire.

This appliance is designed to be attached to a 3″ (76.2mm) co-linear aluminum flex vent system running the full

length of a masonry chimney.

TERMINATION

The flex liners accommodate any contours of a

masonry chimney, however, it is necessary to keep

the flexible liners as straight as possible. The inlet

air collar of the termination cap must be connected

to the air intake flex liner and the exhaust collar

must be connected to the exhaust flexible liner.

AIR

INTAKE

Both Simpson Duravent and Selkirk co-linear to

co-axial adaptors have been approved on this

appliance

EXHAUST FLUE
FLEX LINER

note: A vent adaptor will be required directly off the appliance.
Follow vent manufacturer’s installation instructions.

  • 40 FT (12.2m)
    MAX.
    10 FT (3.1m) MIN

Different manufacturer’s venting components must not be combined. Once the preferred manufacturer’s appliance adaptor has been attached, the remainder of the system must be that of the same manufacturer.
The only exception to this rule is to use Wolf Steel’s approved 3″ (76.2mm) flex liner and co-linear termination.

COAXIAL TO CO-LINEAR ADAPATOR
APPLIANCE VENT ADAPTOR

  • Measured from appliance flue collar to termination flue collar

W415-2351 / B / 12.09.20

37

EN venting installation
4.4.1 restricting vertical vents
! WARNING
· Turn off gas and electrical supply before servicing the appliance. · Appliance may be hot, do not service until appliance is cool. · For safe and proper operation of the appliance, follow the venting instruction exactly. · To avoid danger of suffocation, keep the packaging bag away from babies and children. Do not use in
cribs, beds, carriages or play pens. This bag is not a toy. Knot before throwing away.

Vertical installations may display a very active flame. If this appearance is not desirable, the exhaust outlet may be restricted with a Wolf Steel approved restrictor kit. This kit is not recommended for short vertical vent runs.

Depending on the model and/or year of your appliance, mounting holes may not exist.

A.

If mounting holes exist, remove the screws from the firebox top, align the restrictor plate as illustrated

and secure.

B.

If mounting holes do not exist, align the restrictor plate as illustrated and secure using the 2

8×1/2 hex head sheet metal screws supplied.

C.

Ensure the plate will pivot at the slot up into the exhaust outlet.

D.

Depending on the amount of restriction desired, the restrictor plate can be left flat for most restriction

or bent up for varying degrees of restriction.

Top view

Mounting screws

Restrictor

Firebox top

Restrictor

Exhaust collar

3

2

1

8x½ hex head sheet metal screw

1. Most restriction 2. Moderate restriction 3. Least restriction

Firebox top

38

W415-2351 / B / 12.09.20

! WARNING
· Do not wire 110 volts to the valve or wall switch.
ACS (where applicable)
ON / OFF SWITCH

5.0 electrical information EN

ORANGE

GREEN

TRANSFORMER

ON / OFF

IPI / CPI

OFF ON

BATTERY HOUSING

DISCONNECT THESE CONNECTIONS TO THE ON/OFF SWITCH. CONNECT AN OPTIONAL THERMOSTAT OR REMOTE CONTROL AND (IF ALLOWED WITH THIS APPLIANCE) A “B” VENT
ADAPTOR.

VALVE

ELECTRONIC VALVE

GROUND

GROUND EYELET

DFC DC SUPPLY

WHERE APPLICABLE, APPLIANCES WITH “B” VENT ADAPTORS MUST HAVE THE SPILL SWITCH WIRED IN SERIES WITH EITHER THE EXISTING SWITCH OR OPTIONAL WALL SWITCH, THERMOSTAT OR REMOTE.
note:
This appliance comes equipped with a battery back-up. If this backup is used, install 4 `AA’ batteries (not supplied) into the holder and connect to the wire harness. Connect the battery holder to the wire harness before using the appliance. Place near the DFC board. If the backup is used, it must be connect to this 6 volt batterypack (supplied).

DFC DC IPI CPI ACS

Legend Digital Fireplace Control Direct Current Intermittent Pilot Ignition Continuous Pilot Ignition (with 7-day timer) Anti-Condensation Switch (IPI / CPI)

W415-2351 / B / 12.09.20

39

EN

Electrical information

5.1 battery back-up installation
note: In the event of a power failure, your appliance can be operated using the battery back-up supplied.

A.

Remove the safety barrier by lifting it up and off of the four shoulder screws.

B.

Locate your battery holder, this would have been supplied in the manual baggie.

C.

Locate the red and black wires from the control module to connect to the battery holder, as shown below.

D.

Connect the red wire from the control module to the red wire of the battery back-up. Ensure the protective

sleeve covers the connections, as shown below.

E.

Connect the black wire from the control module to the black wire of the battery back-up. Ensure the

protective sleeve covers the connections, as shown below.

F.

Install 4 “AA” size batteries, ensure the positive and negative ends correspond with those identified on the

holder.

G.

Place the battery holder either onto the hearth, or in the front left corner of the control area, for the

duration of the power failure, as shown below.

H.

Ensure the safety barrier is reinstalled onto the appliance during operation.

note:
Once the power has been restored, you must disconnect the battery back-up or remove the batteries from the holder.

Red wire

Black wire

Control module

Battery housing

40

W415-2351 / B / 12.09.20

5.2 optional wall switch

electrical information EN

! WARNING

· Do not connect either the wall switch, thermostat or gas valve directly to 110 volt electricity.

For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient

location. Route a 2 strand, solid core millivolt wire from the valve to the wall switch or millivolt thermostat. The

recommended maximum lead length depends on wire size:

SIT MILLIVOLT

WIRE SIZE 14 gauge (1.8mm)

MAX. LENGTH 100 feet (30.5m)

3 ADD IMAGE

16 gauge (1.5mm) 18 gauge (1.2mm)

60 feet (18.3m) 40 feet (12.2m)

2 HERE

1
Disconnect the existing wires from terminals 1 and 3 (from the ON/OFF switch) and replace with the leads from the wall switch / millivolt thermostat.

6.0 gas installation ! WARNING
· Risk of fire, explosion, or asphyxiation. Ensure there are no ignition sources such as sparks or open flames. · Support gas control when attaching gas supply pipe to prevent damaging gas line. · Always light the pilot whether for the first time or if the gas supply has run out with the glass door opened
or removed. Purging of the gas supply line should be performed by a qualified service technician. Ensure that a continuous gas flow is at the burner before closing the door. Ensure adequate ventilation. For gas and electrical locations, see “dimensions” section. · All gas connections must be contained within the appliance when complete (gas fireplaces only). · High pressure will damage valve. Disconnect gas supply piping before testing gas line at test pressures above 1/2 PSIG. · Valve settings have been factory set, do not change.
Installation and servicing to be done by a qualified installer. · Move the appliance into position and secure. · If equipped with a flex connector, the appliance is designed to accept a 1/2″ (13mm) gas supply. Without the
connector, it is designed to accept a 3/8″ (9.5mm) gas supply. The appliance is equipped with a manual shut off valve to turn off the gas supply to the appliance. · Connect the gas supply in accordance to local codes. In the absence of local codes, install to the current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United States. · When flexing any gas line, support the gas valve so that the lines are not bent or kinked. · The gas line flex-connector should be installed to provide sufficient movement for shifting the burner assembly on its side to aid with servicing components. · Check for gas leaks by brushing on a soap and water solution. Do not use open flame.
After installing the electrical wiring and gas lines, ensure to test the appliance before finishing the framing and finishing the appliance.

W415-2351 / B / 12.09.20

41

EN 7e.l0ecotrpicearlaitniofonr(melaetciotrnonic) ! WARNING

· If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
· If applicable, always light the pilot whether for the first time or if the gas supply has run out with the glass door opened or removed.

Ensure that a continuous gas flow is at the burner before installing the door. When lit for the first time, the appliance will emit an odor for a few hours. This is a normal temporary condition caused by the “burn-in” of paints and lubricants used in the manufacturing process and will not occur again. After extended periods of non-operation, such as, following a vacation or warm weather season, the appliance may emit a slight odor for a few hours. This is caused by dust particules in the heat exchanger burning off. In both cases, open a window to sufficiently ventilate the room.

FOR YOUR SAFETY READ BEFORE LIGHTING

· Do not turn on if children or other at risk individuals are near the appliance. · This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the
pilot by hand. · Before operating, smell all around the appliance area for gas and next to the floor because some gas is
heavier than air and will settle on the floor. · Do not use this appliance if any part has been under water. Immediately call a qualified service technician
to inspect the appliance and replace any part of the control system and any gas control which has been underwater.

WHAT TO DO IF YOU SMELL GAS

· Turn off all gas to the appliance. · Open windows. · Do not try to light any appliance. · Do not touch any electric switch; do not use
any phone in your building

· Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.

LIGHTING INSTRUCTIONS

note: This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.

A. Stop! Read the above safety information on this label. B. Remove batteries from the transmitter and set thermostat to lowest setting, if
equipped. C. Turn off all electrical power to the appliance. D. Open the glass door, if equipped. E. Turn the manual shut-off valve clockwise to the “OFF” position. (Shut-off valve is
located on the flex connector). F. Wait five (5) minutes to clear out any gas. If you smell gas including near the
floor, STOP! Follow the instructions above in the “WHAT TO DO IF YOU SMELL GAS” section. If you don’t smell gas; close the glass door and go to the next step. G. Turn the manual shut-off valve counter clockwise to the “ON” position. H. Turn on all electrical power to the appliance and re-install the batteries into the transmitter. Set thermostat to desired setting, if equipped. I. Turn on the remote wall switch to the appliance. J. If the appliance will not operate, follow instructions “TO TURN OFF GAS” and call your service technician or gas supplier.
TO TURN OFF GAS A. Set thermostat to lowest setting, if equipped. B. Turn off the remote wall switch to the appliance. C. Turn off all electric power to the appliance if service is to be performed. D. Turn manual shutoff valve clockwise to the “OFF” positon. Do not force.

L O

add gas knob add gas valve

HI

42

W415-2351 / B / 12.09.20

7.1 pilot on demand

operation (electronic) EN

This appliance is equipped with an “On Demand” intermittent pilot ignition system (IPI) which also includes a continuous pilot ignition (CPI) mode with an integrated seven day timer. This system minimizes your appliance’s carbon footprint as well as reducing its annual fuel consumption and operating costs.

In IPI mode, the pilot will ignite prior to the main burner, when the appliance is turned on using a switch, remote or from a call for heat with the thermostat (if equipped). Once the appliance is turned off (or the call for heat is satisfied), the main burner and pilot flame will shut down.

The continuous (CPI) mode is intended to enhance the performance of the appliance during the startup phase in colder climates and extreme weather by keeping the system warm when the main burner is not in use. However, the timer feature provides the convenience that the appliance automatically switches off the pilot when the appliance has not been used for seven days to save unnecessary fuel consumption.

When the CPI function is turned on, the pilot will remain on after the main burner is turned off. A timer will then begin the countdown for approximately seven days before shutting off the pilot if the appliance is not used. This countdown will reset anytime the appliance main burner is used. Therefore, if the appliance is regularly used day to day, the pilot will remain on. However, this system does not require the user to remember to turn the pilot off as summer approaches and avoids unnecessary fuel consumption while still readily turned back on when the cold weather returns.

Your appliance may be equipped with an ACS or remote control device which enables you to select IPI or CPI modes.

If your appliance is equipped with an ACS switch, it has the option to change modes. If installed with the blue wire facing up, flipping the switch UP turns on the continuous pilot with timer and flipping the switch DOWN turns on the intermittent pilot ignition. If installed with the white wire facing up, the opposite is true.

If your appliance is equipped with a remote control device capable of selecting IPI / CPI modes, refer to remote operating instructions.

In order to start your pilot, turning the main burner on with the switch, remote or thermostat and then turning it off will reactivate the continuous pilot mode and reset the seven day timer.

For further information, refer to www.napoleon.com/pilotondemand.

W415-2351 / B / 12.09.20

43

EN o8.p0eroaptieornation (millivolt) ! WARNING

· If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
· If applicable, always light the pilot whether for the first time or if the gas supply has run out with the glass door opened or removed.

Ensure that a continuous gas flow is at the burner before installing the door. When lit for the first time, the appliance will emit an odor for a few hours. This is a normal temporary condition caused by the “burn-in” of paints and lubricants used in the manufacturing process and will not occur again. After extended periods of non-operation such as following a vacation or a warm weather season, the appliance may emit a slight odor for a few hours. This is caused by dust particles in the heat exchanger burning off. In both cases, open a window to sufficiently ventilate the room. For vent free appliances ONLY: if the appliance shuts off, do not relight until you provide fresh air. If appliance keeps shutting off, have it serviced. Keep burner and control compartment clean.

FOR YOUR SAFETY READ BEFORE LIGHTING

· Do not turn on if children or other at risk individuals are near the appliance. · This appliance is equipped with a pilot which must be lit by hand while following these instructions exactly. · Before operating, smell all around the appliance area for gas and next to the floor because some gas is heavier
than air and will settle on the floor. · Use only your hand to turn the gas control knob. Never use tools. If the knob will not turn by hand, do not try
to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion. · Do not use this appliance if any part has been under water. Immediately call a qualified service technician
to inspect the appliance and replace any part of the control system and any gas control which has been underwater.

WHAT TO DO IF YOU SMELL GAS

· Turn off all gas to the appliance. · Open windows. · Do not try to light any appliance. · Do not touch any electric switch; do not use
any phone in your building

· Immediately call your gas supplier from a neighbour’s phone. Follow the gas supplier’s instructions.
· If you cannot reach your gas supplier, call the fire department.

LIGHTING INSTRUCTIONS

note:
When lighting and re-lighting, the gas knob cannot be turned from pilot to off unless the knob is depressed.

A. Stop! Read the above safety information on this label.

B. Remove batteries from the transmitter and set thermostat to lowest setting, if equipped. C. Turn off all electrical power to the appliance.

add gas knob

D. Open the glass door, if equipped.

E. Turn the gas knob clockwise

to the “OFF” position.

F. Wait five (5) minutes to clear out any gas. If you smell gas including near the floor, STOP! Follow the instructions above in the “WHAT TO DO IF YOU SMELL GAS” section. If you don’t smell gas; close the glass door and go to the next step.

G. If the appliance is equipped with flame adjustment valve turn clockwise

to “OFF”.

H. Turn gas knob counter-clockwise

to the “PILOT” position. (If the appliance is equipped

with an “ON/OFF” switch, ensure it is in the “ON” position.

I. Depress and hold gas knob while lighting the pilot with the push button ignitor. Keep knob add gas valve
fully depressed for one minute, then release. If pilot does not continue to burn, repeat steps E through I.

J. With pilot lit, turn gas knob counter-clockwise

to the “ON” position.

K. If equipped with the flame adjustment valve, push and turn the knob to high.

L. Turn on all electrical power to the appliance and re-install the batteries into the transmitter, if equipped. Set thermostat to desired setting, if equipped.

TO TURN OFF GAS

A. Set thermostat to desired setting, if equipped.

B. Turn off all electrical power to the appliance if service is to be performed.

C. Push in gas knob slightly and turn clockwise

to the “OFF” position. Do not force.

44

W415-2351 / B / 12.09.20

9.1 minimum framing dimensions

9.0 finish framing EN

ENCLOSURE TOP

ELECTRICAL CONNECTION
14 1/2″ 368mm

FINISHING MATERIAL

35″ 889mm

GAS INLET LOCATION

1 13/16″ 46mm 6 1/2″ 192mm
30 1/2″ 775mm

W415-2351 / B / 12.09.20

45

EN 1fi0n.i0shfiinigshing ! WARNING
· Risk of fire! · Never obstruct the front opening of the appliance. · The front of the appliance must be finished with any non-combustible materials such as brick, marble, granite,
etc., provided that these materials do not go below the specified dimension, as illustrated. · Do not strike, slam, or scratch. Do not operate appliance with glass removed, cracked, or scratched. · Facing and/or finishing material must never overhang into the appliance opening. · The glass door assembly is designed to pivot forward when relieving excess pressure that might occur. Finishing
or other materials must not be located in the opening surrounding the door as this will interfere with the doors ability to relieve pressure.
10.1 safety barrier / door removal and installation
! WARNING
· Glass may be hot. Do not touch glass until cooled. · If equipped with door latches that are part of a safety system, they must be properly engaged. Do not
operate the appliance with latches disengaged. · Facing and/or finishing materials must not interfere with air flow through air openings, louvre openings,
operation of louvres, or doors/access for service. Observe all clearances when applying combustible materials. · Before door is removed, turn the appliance off and wait until appliance is cool to the touch. Doors are heavy and fragile so handle with care.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided for the appliance and shall be installed. Before the glass door can be removed, the safety barrier must be removed. Lift the safety barrier off the 4 pins, tilt the top forward and remove from the appliance.

Safety barrier

Safety barrier

Leave a hand on the glass door during entire door removal. The glass door is secured to the firebox with 2 spring latches along the top and 2 along the bottom. Pull the handles of the latches forward, then lift the latches out from the door frame to release the top of the door. Repeat the same step for the 2 bottom latches. Next, pivot the door forward until the top edge clears the front of the appliance. Carefully grip the sides of the door lifting it off the appliance. note: These spring latches make up the spring relief system for the appliance. Ensure they open freely and close sealed.
Reverse these steps to re-install the safety barrier and door. Ensure safety barrier is installed correctly.

46

W415-2351 / B / 12.09.20

10.2 front hood installation
note: This hood must be installed, if it has not already been factory installed.

A.

Safety door and screen must be removed.

B.

Remove the securing screws from the top of the firebox, as shown.

C.

Install the front hood, ensure it is angled downward when installed.

D.

Reinstall the previously removed securing screws.

finishing EN

SIDE VIEW
HOOD

X5

W415-2351 / B / 12.09.20

47

EN finishing
10.3 non-combustible facing material
! WARNING
Non-combustible facing material must not project more than 4″ (101.6mm) from the face of the door (all four sides). If greater projections are desired, increase the clearance to the sides, bottom and top by 2″ (50.8mm) for every additional 1″ (25.4mm) of projection. If using an optional surround, the same rule applies, starting from the top of the surround. Ensure clearances are maintained for surround removal, as it must lift off the appliance for maintenance.

A

B

A

B

4″ (101.6mm) 2″ (50.8mm)
Optional surround

6″ (152.4mm) 5″ (127mm) 4″ (101.6mm)
Top of appliance
Door

3″(76.2mm) 2″ (50.8mm)
0″ (0mm)

6″ (152.4mm) 5″ (127mm) 4″ (101.6mm)
Top of appliance
Door

Section A – A

Section B – B

48

W415-2351 / B / 12.09.20

10.4 minimum mantel clearances

finishing EN

! WARNING

· Risk of fire. Maintain all specified air space clearances to combustibles. Failure to comply with these instructions may cause a fire or cause the appliance to overheat. Ensure all clearances (i.e. back, side, top, vent, mantel, front, etc.) are clearly maintained.
· When using paint or lacquer to finish the mantel, the paint or lacquer must be heat resistant to prevent discolouration.

Combustible mantel clearance can vary according to the mantel depth. Use the graph to help evaluate the clearance needed. These same requirements apply to any combustibles protruding on either side of the appliance.

8″ 203.2mm MANTEL

12″ (30.5cm)

M H 10″ (254mm)

A E 8″ (203.2mm)

NI TG

6″ (152.4mm)

E H 4″ (101.6mm)

L T 2″ (50.8mm)

8″ 203.2mm
6″ 152.4mm 4″
101.6mm

6″ 152.4mm 4″ 101.6mm 2″ 50.8mm
2″ 50.8mm

TOP OF APPLIANCE

34 5/8″ [88cm]

0 2 4 6 8 10 12 MANTEL DEPTH (INCHES)

W415-2351 / B / 12.09.20

49

EN finishing
10.5 recessed installation
! WARNING
· Installing a television or other electronics above the appliance may cause discolouration, melting, or damage to the electronics. Use clearances as guidelines and refer to your TV manufacturer’s instructions for further information

A
Add Image SAFETY BARRIER
B

Before placing anything above a heat source, it is advisable to follow proper clearances and manufacturer’s instructions.
note:
Recesses or alcoves above the appliance must be made with non-combustible material and regular minimum clearances, as defined for combustible materials, must still be applied.
The minimum enclosure volume must be increased by no less than the volume of the recess. This adjustment can be made by increasing any or all of the height, width and depth of the enclosure.
Installing a mantel between this appliance and electronics or other materials that may be sensitive to heat, will reduce the effect of direct heat on them. Follow mantel height and depth instructions for proper clearance information. Refer to the “minimum mantel clearances” section for detailed mantel clearance information.
note:
Installing electronics or other materials that may be sensitive to heat on a recessed wall will also reduce the effect of direct heat.

MINIMUM CLEARANCES CHART

A

6″ (152mm) MAX

B

41 5/8″ (1057mm) (REAR VENT)

B

50 1/2″ (1283mm) (TOP VENT)

50

W415-2351 / B / 12.09.20

10.6 log placement

finishing EN

! WARNING

· Failure to position the logs in accordance with these diagrams or failure to use only logs specifically approved with this appliance may result in property damage or personal injury.
· Logs must be placed in their exact location in the appliance. Do not modify the proper log positions, since appliance may not function properly and delayed ignition may occur.
· The logs are fragile and should be handled with care.

PHAZERTM logs exclusive to Napoleon, provide a unique and realistic glowing effect that is different in every installation. Log colours may vary. During the initial use of the appliance, the colours will become more uniform as colour pigments burn in during the heat activated curing process.

PINS

A

A B

A.

Place the rear log (W135-0575) firmly onto the B.

Place the left log (W135-0576) onto the two studs

two studs at the rear of the support tray.Ensure

located on the left side of the log support.

the log sits flat and does not cover the pilot

opening. Place two pins in the holes located

on the top rear of the rear log.

PIN

A

B

C

D

A

B

C

C.

Position the right log (W135-0577) onto the

D.

Place the left crossover log (W135-0578) onto

two studs located on the right side of the log

the pin located in the left side of the rear log,

support. Place one pin into the hole located

allow it to rest in the notch of the left log.

on the top of the right log.

W415-2351 / B / 12.09.20

51

EN finishing

D

E

A

B

C

F.

Reinstall the door and safety screen.

E.

Place the right crossover log (W135-0579) onto

the two remaining pins.

10.7 logo placement

Remove the backing of the logo supplied and place, as illustrated.

1/2″(12.7mm)
INLSOGEORT IMAGE 1/2″(12.7mm)
HERE

52

W415-2351 / B / 12.09.20

11.0 adjustments EN

11.1 pilot burner adjustment

Adjust the pilot screw to provide properly sized flame. Turn in a clockwise direction to reduce the gas flow.

ELECTRODE
3/8″ – 1/2″ (9.5mm – 12.7mm)

Check Pressure Readings:

FLAME SENSOR

Inlet pressure can be checked by turning screw (A) counter-

clockwise 2 or 3 turns and then placing pressure gauge tubing

over the test point. Gauge should read as described on the chart

below. Check pressure with main burner operating on “HI”.

PILOT BURNER

ELECTRONIC ILLUSTRATED

FLAME MUST ENVELOP UPPER 3/8″ (9.5mm) TO 1/2″ (12.7mm) OF FLAME SENSOR

Outlet pressure can be checked the same as above using screw (B). Gauge should read as described on the chart below. Check pressure with main burner operating on “HI”.
After taking pressure readings, be sure to turn screws clockwise firmly to reseal. Do not overtorque.
Leak test with a soap and water solution.

INSERT

PILOT ASSEMBLY 3/8″ – 1/2″ (9.5mm – 12.7mm)

FLAME MUST ENVELOP UPPER
3/8″ TO 1/2″ (12.7mm – 9.5mm) OF THERMOCOUPLE &
THERMOPILE

MILLIVOLT ILLUSTRATED

Prior to pilot adjustment, ensure that the pilot assembly has not been painted. If overspray or painting of the pilot assembly has occurred remove the paint from the pilot assembly, or replace. Fine emery cloth or a synthetic scrub pad (such as Scotch-BriteTM) can be used to remove the paint from the pilot hood, electrode and flame sensor.

Pressure

Natural Gas (inches)

Natural Gas (millibars)

Propane (inches)

Propane (millibars)

Inlet

*7″ (minimum 4.5″)

17.4mb (minimum 11.2mb)

13″ (minimum 11″)

32.4mb (minimum 27.4mb)

Outlet

3.5″

8.7mb

10″

24.9mb

*Maximum inlet pressure not to exceed 13″

AB

PILOT SCREW
ELECTRONIC

MILLIVOLT

11.2 venturi adjustment
This appliance has an air shutter that has been factory set open according to the chart below:
Regardless of venturi orientation, closing the air shutter will cause a more yellow flame, but can lead to carbonization. Opening the air shutter will cause a more blue flame, but can cause flame lifting from the burner ports. The flame may not appear yellow immediately; allow 15 to 30 minutes for the final flame colour to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED INSTALLER.

VENTURI BURNER
ORIFICE

AIR SHUTTER OPENING

note: It is important that the orifice is securely inserted into the venturi.

VENTURI ADJUSTMENT CHART

FUEL

B30-1

NG

1/16″ (1.5mm)

P

3/8″ (9.5mm)

W415-2351 / B / 12.09.20

53

EN adjustments
11.3 flame characteristics
It’s important to periodically perform a visual check of the pilot and burner flames. Compare them to the illustration provided. If any flames appear abnormal, call a service person.

3/8″ – 1/2″ (9.5mm – 12.7mm)
ADD IMAGE Flame must envelop upper HERE 3/8″ to 1/2″ (12.7mm – 9.5mm) of
thermocouple & thermopile

MILLIVOLT ILLUSTRATED

54

W415-2351 / B / 12.09.20

! WARNING

12.0

Maintenance

· Turn off the gas and electrical power before servicing the appliance. · Appliance may be hot. Do not service until appliance has cooled. · Do not use abrasive cleaners on glass. · Do not paint the pilot assembly.
This appliance and its venting system should be inspected before use and at least annually by a qualified service person. The following suggested checks should be performed by a qualified technician. The appliance area must be kept clear and free of combustible materials, gasoline, or other flammable vapors and liquids. The flow of combustion and ventilation air must not be obstructed.
note:
Caution: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.

In order to properly clean the burner and pilot assembly, remove the logs, rocks and/or glass to ex-

pose both assemblies.

Keep the control compartment, media, burner, air shutter opening and the area surrounding the appli-

ance clean by vacuuming or brushing, at least once a year.

Check to see that all burner ports are burning. Clean out any of the ports which may not be burning

or are not burning properly.

Check to see that the pilot flame is large enough to engulf the flame sensor and/or thermocouple /

thermopile as well as it reaches the burner.

If your appliance is equipped with a safety barrier, cleaning may be necessary due to excessive lint /

dust from carpeting, pets, etc. simply vacuum using the brush attachment.

If your appliance is equipped with relief doors, ensure the system performs effectively. Check that the

gasket is not worn or damaged. Replace if necessary.

Replace the cleaned logs, rocks or glass. Failure to properly position the media may cause carboning

which can be distributed in the surrounding living area, inside the firebox and on exterior surfaces sur-

rounding vent termination.

Check to see that the main burner ignites completely on all ports when turned on. A 5 to 10 second

total light-up period is satisfactory. If ignition takes longer, consult your local authorized dealer / dis-

tributor.

Visually inspect the appliance for carbon build up. Using a small whisk or brush, brush off the carbon

and vacuum up or sweep into garbage.

10. This step is not applicable for Vent Free appliances: Check to see that the appliance is venting correctly. Ensure chimney system is safe and unobstructed. (If for any reason the vent air intake system is disassembled, re-install and re-seal per the instructions provided for the initial installation).

W415-2351 / B / 12.09.20

55

EN maintenance
12.1 annual maintenance
! WARNING
· Annual maintenance should be performed by a qualified service technician · The firebox becomes very hot during operation. Let the appliance cool completely or wear heat resistant
gloves before conducting service. · Never vacuum hot embers. · Do not paint the pilot assembly
· This appliance will require maintenance which should be planned on an annual basis. · Service should include cleaning, battery replacement, venting inspection and inspection of the burner,
media, and firebox. Refer to the door removal section and remove the door as instructed. · Carefully remove media if necessary (logs, glass, brick panels, etc.). · Using a vacuum with soft brush attachment, gently remove any dirt, debris, or carbon build up from the
logs, firebox, and burner. For glass media, follow the installation instructions for pre-cleaning. · Gently remove any build-up on the pilot assembly including thermopile, thermocouple, flame sensor, and
igniter (if equipped). note: Clean flame sensor using a fine emery cloth or a synthetic scrub pad (such as Scotch-BriteTM) to remove any oxides. Clean the pilot assembly using a vacuum with a soft brush attachment. It is important that the pilot assembly is not painted.
· Inspect all accessible gaskets and replace as required. · If equipped with a blower, access the blower and clean using a soft brush and vacuum. · Re- assemble the various components in reverse order. · Inspect the relief system. The appliance relieves through the main glass door or through the flaps on the
firebox top. Ensure they open freely, and close sealed. · Check the gas control valve pilot and Hi / Lo knobs move freely, if equipped. Replace if any stiffness in
movement is experienced. · Check for gas leaks on all gas connections up and downstream from the gas valve including pilot tube
connections.

56

W415-2351 / B / 12.09.20

12.2 door glass replacement

maintenance EN

! WARNING
· Do not use substitute materials. · Glass may be hot. Do not touch glass until cooled. · Care must be taken when removing and disposing of any broken door glass or damaged components. Be
sure to vacuum up any broken glass from inside appliance before operation. · Do not strike, slam, or scratch. Do not operate appliance with glass removed, cracked, broken, or scratched.

Replacement glass/frame assembly shall be replaced as a complete unit as supplied by the appliance manufacturer.
12.3 care of glass
! WARNING
· Do not clean glass when hot! Do not use abrasive cleaners to clean glass.
Buff lightly with a clean dry soft cloth to remove accumulated dust or fingerprints. Clean both sides of the glass after the first 10 hours of operation with an ammonia-free glass cleaner.
note: Vinegar-based glass cleaners have demonstrated an ability to provide a clean, streak free glass surface.
Thereafter, clean as required. If the glass is not kept clean permanent discoloration and / or blemishes may result. Contact you local authorized dealer / distributor for complete cleaning instructions.
Razor blades, steel wool, or other metallic objects must not be used on both surfaces of the glass. Doing so can remove a thin layer of metal from the razor blades, steel wool, or other metallic objects that may then be deposited onto the coating. This can result in a discoloured stain or scratch-like mark. More importantly, this can scratch the glass surface, thereby reducing its strength.
Do not operate the appliance with broken glass, as leakage of flue gases may result.
Contact your local authorized dealer / distributor for complete cleaning instructions.
If the glass should ever crack or break while the fire is burning, do not open the door until the fire is out. Do not operate the appliance until the glass has been replaced. Contact you local authorized dealer / distributor for replacement parts. DO NOT SUBSTITUTE MATERIALS.
This appliance is factory equipped with 4mm tempered glass. Use only replacement parts as supplied by the appliance manufacturer. DO NOT SUBSTITUTE MATERIALS.

W415-2351 / B / 12.09.20

57

EN r1e3p.0lacemrepnltapcaermtsent parts ! WARNING
· Failure to position the parts in accordance with this manual or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
Contact your dealer for questions concerning prices and policies on replacement parts. Normally, all parts can be ordered through your Authorized dealer / distributor.
For warranty replacement parts, a photocopy of the original invoice will be required to honour the claim. When ordering replacement parts always give the following information: · Model & Serial Number of appliance · Installation date of appliance · Part number · Description of part · Finish Parts, part numbers, and availability are subject to change without notice. Parts identified as stocked will be delivered within 2 to 5 business days for most delivery destinations. Parts not identified as stocked will be delivered within a 2 to 4 week period, for most cases. Parts identified as `SO’ are special order and can take up to 90 days for delivery.

58

W415-2351 / B / 12.09.20

13.1 overview

Safety barrier assembly

17

18

116

19

117

118

1

11

1

10

112

119

1

1

13

15

14

1

GL-694

1

2

3

4

5

6

For replacement parts, refer to “valve train assembly”

Items may not appear exactly as illustrated

Ref. No. 1 2 3 4 5 6 7 8 9 10

Part number Description

W565-0266

Safety screen

W010-3246-SER Safety barrier assembly

W385-2010

Napoleon logo

W010-3244 W667-0018

Door assembly Gasket tape (X4)

W562-0009

Door gasket

W715-1045

Top finishing trim

W335-0067

Hood

W018-0157

Front baffle

W135-0578

Left crossover log (GL-694)

Stocked Yes Yes Yes Yes
Yes

Ref. No. 11 12 13 14 15 16
17 18
19

Part number Description

W135-0575 W135-0579

Rear log (GL-694) Right crossover log (GL-694)

W135-0576

Left side log (GL-694)

W485-0042

Log locating pin (X4)

W135-0577

Right side log (GL-694)

W290-0282

Gasket flue pipe assembly

W010-3490-SER 4″ exhaust flue pipe assembly

W010-3070

Door latches (X4)

W570-0135

Shoulder screws (X4)

Stocked Yes Yes Yes Yes Yes Yes Yes
Yes

replacement parts EN

W415-2351 / B / 12.09.20

59

EN replacement parts

60

W415-2351 / B / 12.09.20

13.2 electronic valve train assembly

28

Ref. No.
21 22 22 22 22 23 24 25
26
27 28

Part number W100-0162 W456-0050 W456-0058 W456-0049 W456-0057 W290-0248 W432-0046 W190-0175 W350-0702 W707-0010 W335-0039

221

29

232

320

4345

253

331

2264

432

3285

353

376

354 4206

4217 Items may not appear exactly as illustrated

Description Burner assembly Burner orifice #50 (NG – rear) Burner orifice #58 (P – rear) Burner orifice #49 (NG – top) Burner orifice #57 (P – top) Valve train gasket Manifold flex pipe Control board
Battery back-up Transformer Pilot hood

Stocked Yes Yes Yes Yes Yes
Yes Yes Yes Yes Yes

Ref. No. 29 30 30 31 32 33 34 35 35 36 36

Part number W455-0070 W455-0068 W720-0062 W240-0013 W245-0025 W290-0029 W725-0062 W725-0063 W010-2763 W010-2808 W750-0270

Description Pilot orifice #62 (NG) Pilot orifice #35 (P) Pilot tube (w/ fittings) Ignitor (w/ wire) Thermosensor
Pilot gasket 886 Proflame valve (NG) 886 Proflame valve (P) Pilot assembly (NG) Pilot assembly (P) Wire assembly

Stocked Yes Yes Yes Yes YeEsS Yes Yes Yes Yes Yes

13.3 millivolt valve train assembly

289 221
2390

232

340

3463

3411 2348
321

253

332

2264

3442

3474

354

2379

Items may not appear exactly as illustrated

Ref. No. Part number Description

Stocked

Ref. No. Part number Description

Stocked

21

W100-0162

Burner assembly

Yes

32

W240-0006

Ignitor (w/ wire)

Yes

22

W456-0050

Burner orifice #50 (NG – rear) Yes

34

W290-0029

Pilot gasket

22

W456-0058

Burner orifice #58 (P – rear) Yes

38

W357-0001

Push button ignitor

Yes

22

W456-0049

Burner orifice #49 (NG – top) Yes

39

W725-0025

Valve (NG)

Yes

22

W456-0057

Burner orifice #57 (P – top) Yes

39

W725-0043

Valve (P)

Yes

23

W290-0248

Valve train gasket

Yes

40

W010-0801

Pilot (NG)

Yes

24

W432-0078

Manifold flex pipe

Yes

40

W010-0800

Pilot (P)

Yes

29

W335-0039

Pilot hood

Yes

41

W680-0004

Thermopile

Yes

30

W455-0070

Pilot orifice #62 (NG)

Yes

42

W680-0005

**Thermocouple

Yes

30

W455-0068

Pilot orifice #35 (P)

Yes

43

W010-0798

Pilot assembly (NG)

31

W720-0062

Pilot tube (w/ fittings)

Yes

43

W010-0799

Pilot assembly (P)

44

W750-0112

Wire assembly

** THIS IS A FAST ACTING THERMOCOUPLE. IT IS AN INTEGRAL SAFETY COMPONENT. REPLACE ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD.

replacement parts EN

W415-2351 / B / 12.09.20

61

EN 1a4c.c0essoraicecsessories

62

W415-2351 / B / 12.09.20

1

45

1

46

SAFETY SCREEN

Z30F

SAFETY SCREEN
50

H30F
521 532 543

47 48 49
TK30

PRPB30

AUB

Ref. No.
1
45 46 47 48 49

Part number W565-0154 Z30F H30F W430-0003 W715-0981 W715-0952

Items may not appear exactly as illustrated

Description Safety screen (Z30F / H30F) Black Zen Decorative Safety Barrier Black Heritage Decorative Safety Barrier Magnet (x16) (TK30) Top / bottom trim (x2) (TK30) Side trim (x2) (TK30)

Stocked Yes
Yes

Ref. No. 50 51 52 53

Part number PRPB30-1 W062-0051 KB-35 W690-0002

Description Porcelain Reflective Panels
Blower (AUB) Variable speed switch Thermodisc

Stocked Yes Yes Yes
03.08.19 / D

! WARNING

Troubleshooting

· Always light the pilot whether for the first time or if the gas supply has run out, with the glass door open or removed.
· Turn off gas and electrical power before servicing the appliance. · Appliance may be hot. Do not service until appliance has cooled. · Do not use abrasive cleaners

symptom

problem

test solution

Main burner flame is a blue, lazy, transparent flame.
(This is not applicable in outdoor appliances)

Blockage in vent. Incorrect installation.

– Remove blockage. In really cold conditions, ice buildup may occur on the terminal and should be removed as required. (To minimize this from reoccuring, the vent lengths that pass through unheated spaces (attics, garages, crawl spaces) should be wrapped with an insulated mylar sleeve).
– Refer to “venting” section to ensure correct installation.

Flames are consistently too large or too small. Carboning occurs.

Appliance is over-fired or underfired.

AB
INSERT
PHOTO

– Check pressure readings: Inlet pressure can be checked by turning screw (A) counter-clockwise 2 or 3 turns and then placing pressure gauge tubing over the test point. Gauge should read as described on the chart below. Check that main burner is operating on HI’. Outlet pressure can be checked the same as above using screw (B). Gauge should read as described on the chart below. Check that main burner is operating onHI’. After taking pressure readings, be sure to turn screws clockwise firmly to reseal. DO NOT OVER TORQUE.
Leak test with a soap and water solution.

OF VALVE PILOT SCREW HERE

Pressure Natural Gas (inches)

Inlet

*7″ (minimum 4.5″)

Natural Gas (millibars)
17.4mb (minimum 11.2mb)

Propane (inches)

Propane (millibars)

13″

32.4mb

(minimum 11″) (minimum 27.4mb)

Outlet

3.5″

8.7mb

10″

24.9mb

*Maximum inlet pressure not to exceed 13″ w.c.

Carbon is being deposited on glass, logs, rocks, media, or combustion chamber surfaces.
White / grey film forms.
Exhaust fumes smelled in room, headaches.

Air shutter improperly adjusted. –

Air shutter is blocked.

Flame is impinging on the glass, –

logs, rocks, media or combus-

tion chamber.

Sulphur from fuel is being depos- –

ited on glass, logs, or combus-

tion chamber surfaces.

Appliance is spilling.

(This is not applicable in outdoor –

appliances).

Return air shutter to specified opening, see “venturi adjustments” section in the installation manual.
Ensure air shutter opening is free of lint or other obstructions.
Ensure the media is positioned correctly in the appliance. Open air shutter to increase the primary air. Check the input rate: check the manifold pressure and orifice size as specified by the rating plate. Ensure door gaskets are not broken or missing and the seal is tight. Ensure vent liners are free of holes and well sealed at all joints. Check that minimum rise per foot (meters) has been adhered to for any horizontal venting.
Clean the glass with a recommended gas fireplace glass cleaner. DO NOT CLEAN GLASS WHEN HOT. If deposits are not cleaned off regularly, the glass may become permanently marked.
Check door seal. Check for exhaust damage. Check that venting is installed correctly. Room is in negative pressure; increase fresh air supply.

W415-2351 / B / 12.09.20

63

EN troubleshooting (electronic)

symptom

problem

Pilot will not light. Makes noise with no spark at pilot burner.

Wiring: short, loose, or damaged –

connections

(poor flame rectification).

Pilot sparks but will not light.

No signal from remote with no

pilot ignition.

Poor grounding.

Improper switch wiring.

Dirty, painted, or damaged pilot and/or dirty sensor rod.

Gas supply.

Out of propane gas.

Pilot supply line may contain air.

Incorrect wiring / grounding. –

Receiver (if equipped).

Valve.

Burner continues to

Short or loose connection in –

spark and pilot lights sensor rod.

but main burner

does not light.

Dirty, painted, or damaged

pilot assembly components.

Remote wall switch is in “off” position; burner comes on.
Remote and / or receiver is not functioning properly.

Wall switch mounted upside down.

Remote wall switch and/or

wire is grounding.

Faulty wire

Remote controls lights but

no spark or flame. (Remote is

locked out).

Receiver or remote has low battery. –
Appliance functions but does not respond to receiver / remote

Error with synchronizing.

Remote too far away from receiver. –

Wire connector pins are bent.

Valve wiring is damaged.

test solution
Verify the thermocouple/sensor is clean and the wiring is undamaged. Verify the interrupter block is not damaged or too tight. Verify connections from pilot assembly are tight; also verify the connections are not grounding out to any metal. (Remember, the flame carries the rectification current, not the gas. If flame lifts from pilot hood, the circuit is broken. A wrong orifice or too high of an inlet pressure can cause the pilot flame to lift)*. The sensor rod may need cleaning.
Reprogram receiver code. Replace receiver.
Verify the valve / pilot assembly are properly grounded
Troubleshoot the system with the simplest on/off switch.
Clean sensor rod with a green Scotch-BriteTM pad to remove any contamination that may have accumulated. Verify continuity with multimeter with ohms set at the lowest range.
Verify that the incoming gas line ball valve is “open”. Verify that the inlet pressure reading is within acceptable limits, inlet pressures must not exceed 13″ W.C. (32.4mb).
Fill the tank.
Repeat ignition process several times or purge the pilot supply line.
Ensure correct polarity of wiring of thermocouple (if equipped). Verify pilot assembly / valve are properly grounded.
Reset program: hold reset button on receiver and wait for 2 beeps. Release after second beep. Press small flame button on remote within 20 seconds, you will hear an additional beep (this signals a successful reset). Replace receiver.
Check valve and replace if necessary (Do not to overtighten thermocouple).
Verify all connections. Verify the connections from the pilot assembly are tight. Also, verify these connections are not grounding out to any metal.
Clean using a green Scotch-BriteTM pad to remove any contamination that may have accumulated on the sensor rod, pilot hood, ignitor, or flame sensor. Verify continuity with multimeter with ohms set at the lowest range.
Reverse.
Replace. Check for ground (short); repair ground or replace wire.
Replace.
Reset by turning power source off then on.
note:
If back up batteries are installed, they must also be removed to re-program
Replace batteries.
Ensure appliance is being operated by the same device that turned it on. Remote controls function if appliance was turned on by remote. Receiver controls function if appliance was turned on by receiver.
Reset receiver and remote.
Refer to “wiring diagram” section.
Straighten pins.
Replace valve.

64

W415-2351 / B / 12.09.20

symptom
Lights or blower won’t function (if equipped).
Flames are very aggressive.
Appliance won’t perform any functions.

problem
Control module switch in wrong position. COM switch is unplugged.
Door is ajar. Venting action is too great.
No power to the system. Receiver switch in wrong position (if equipped). Transmitter isn’t operational.

troubleshooting (electronic) EN
test solution
– Verify ON/OFF switch is in the “I” position which denotes on.
– Verify “COM” switch is plugged into the front of the control module.
– Ensure door is secured properly. – Check to ensure venting is properly sealed or restrict vent
exit with restrictor plate. (Not available in all appliances). – Check breaker to verify it’s in the “on” position. – Verify that the 3 position switch on the receiver is in the
remote position (middle). – Check battery power and battery orientation.

symptom

problem

test solution

The following applies specifically to the SIT system only:

Pilot will not light. Makes no noise with no spark at pilot burner. (Lights and blower operate, if equipped).

Ignition box has been locked out.

Choose one of the 3 methods below to reset the system. 1. To reset ignition box when locked out. Turn off power supply
and remove batteries (if used) from the back up battery pack. 2. To reset the DFC Board when the board goes into a lock
out condition and the LED is blinking 3 times using the transmitter on/off button:
Step 1: Turn the system off by pressing the on/off button to turn

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals