Panasonic S-140MH1H5 H1 Type High-Fresh Air Ducted Instruction Manual
- June 1, 2024
- Panasonic
Table of Contents
Panasonic S-140MH1H5 H1 Type High-Fresh Air Ducted Instruction Manual
**Self-diagnosing Function
Automatic Fan Operation
Automatic Restart Function
**
Technical focus
- 100% fresh Air intake for ventilation purpose
- Design flexibility thanks to high static pressure and large air volume
- Discharge air temperature control to reduce cold drafts during heating operation
- Configurable air temperature control
High Fresh System
High Fresh system enables delivery of fresh outside air at almost the same
temperature and humidity as indoor air without putting a burden on air
conditioning.
- Capable of treating outdoor air only. Indoor air conditioner units are required to adjust indoor air temperature.
Mix operation unit with standard indoor units
Possible to combine High Fresh Air dusted indoor unit and standard air dusted
indoor units.
When other indoor units are connected in same circuit, keep following capacity
ratio.
H1 type/Outdoor unit < 30%, and Total of indoors(incl. H1)/outdoor <100%
Remark For High Static Ducted Series
Model| Operation| Rap valve kit CZ-P160RVK2
| 3way control PCB CZ-CAPE2
| 3way valve kit CZ-P160HR3
| Distribution Joint kit<2pipes> CZ-P160BK2 for 22.4kW unit or less
CZ-P680BK2 for more than 22.4kW| Distribution Joint kit<3pipes> CZ-
P224BH2 for 22.4kW unit CZ-P680BH2 for 28.0kW unit
---|---|---|---|---|---|---
H1 Type High-Fresh Air Ducted| Cooling Only| –| –| –| –| –
Cool or Heat| 2pcs| –| –| 2pcs| –
Heat Recovery| –| –| 2pcs| 1pc| 1pc
Model Name| S-140MH1H5| S-224MH1H5| S-280MH1H5
---|---|---|---
Power source| 220/230/240 V, 1 phase – 50 Hz
Cooling capacity| kW| 14.0| 22.4| 28.0
BTU/h| 47,800| 76,400| 95,500
Heating capacity| kW| 13.2| 21.2| 26.5
BTU/h| 45,000| 72,300| 90,400
Power input| Cooling| kW| 0.430/0.430/0.430| 0.670/0.670/0.670|
0.730/0.730/0.730
Heating| kW| 0.430/0.430/0.430| 0.670/0.670/0.670| 0.730/0.730/0.730
Running current| Cooling| A| 2.0/1.9/1.9| 3.2/3.1/3.0| 3.6/3.4/3.3
Heating| A| 2.0/1.9/1.9| 3.2/3.1/3.0| 3.6/3.4/3.3
Fan| Type| Sirocco fan| Sirocco fan| Sirocco fan
Air flow rate| m³/h| 1,560| 1,800| 2,100
L/s| 433| 500| 583
Motor output| kW| 0.3| 0.38| 0.38
Sound power level (H/M/L)| dB| 75/76/76| 78/79/79| 79/80/80
Sound pressure level (H/M/L)| dB(A)| 43/44/44| 46/47/47| 47/48/48
Dimensions H x W x D| mm| 420 x 1,065 x 620| 479 x 1,428 x 1,230| 479 x
1,428 x 1,230
Pipe connections| Liquid| mm (inches)| Ø9.52 (Ø3/8)| Ø12.7 (Ø1/2)| Ø12.7
(Ø1/2)
Gas| mm (inches)| Ø15.88 (Ø5/8)| Ø25.4 (Ø1)| Ø25.4 (Ø1)
Drain piping| VP-25| VP-25| VP-25
Net weight| kg| 50| 110| 110
GLOBAL REMARKS| Rated conditions| Cooling| Heating
---|---|---|---
Outdoor air temperature| 33˚C DB / 28˚C WB| 0˚C DB / -2.9˚C WB
Specifications are subject to change without notice
H1TYPE HIGH-FRESH AIR DUCTED Dimensions
- Refrigerant liquid line
- Refrigerant gas line
- Power supply entry
- Drain connection
- Duct connection for suction
- Duct connection for discharge
SIZE 140
SIZE 224-280
Read User Manual Online (PDF format)