BOXED Ats System
Specifications
- Product Name: BOXED ATS System
- Function: Automatically starts generator for emergency power supply
- Charge Current: 1A
- Operation Modes: Automatic and Manual
Product Usage Instructions
Operation Steps
- Connect the ATS box to the generator control panel using the provided cable.
- Switch the position to AUTO.
Automatic Position Setup
Press the AUTO button to activate automatic mode. The AUTO indicator light
will turn on, indicating that the ATS system is working automatically.
ATS System Working
When the mains power supply is off, the ATS system will open the air damper
control and start the generator within 2 seconds. After the generator runs for
5 seconds, the system will switch the load to the generator power supply.
ATS System Start 3 Times
If the generator fails to start initially, the ATS system will attempt to
start it three times before indicating a fault.
Generator Stop
When the mains power supply is restored, the ATS system will transfer the
load back to the mains power and stop the generator after running for 5
seconds without a load.
Manual Start
To manually control the generator, switch the position to MANUAL.
Automatic Air Damper Control
If your generator has air damper control, the ATS system will automatically
open and close it when starting and stopping the generator.
PRODUCT INSTRUCTION
ATS system is designed for the main power supply off and start the generator
for emergency power supply.
When the mains power supply is off, the generator will start in 2-6 seconds
and then supply power to load. When the main power supply is on, the ATS
system will automatically transfer the switch to the main power supply, and
then stop the generator in 2-6 seconds.
- This system uses SCM core and digital techniques to control and manage the automatic working system.
- Easy installation and operation
- Automatic working without people inspection. When the transfer is broken the system will remain an error record and indicate engineer to inspect and re-setup. Don’t worry about the mains power supply and generator power supply action same time.
- There is a battery charger inside, and the battery of the generator automatically.
OPERATION STEPS
Use the cable to connect the ATS box to the generator control panel, and switch the “AUTO” position.
Automatic postion setup
Press the AUTO button, the indicator light AUTO will be on, ATS system will
work automatically.
ATS system working
When the ATS system works automatically, if the main power supply is off,
the ATS system will automatically open the air damper control start the
generator in 2 seconds, and wait for the generator to run 5 seconds, the
system will switch the load to the generator power supply.
The ATS system starts 3 times
When the generator can not start well, the ATS system will start the
generator circularly 3 times as below Mains power supply off→ generator starts
3 seconds first time→ start unsuccessfully and wait for 5 seconds→ generator
starts 4 seconds second time→start unsuccessfully and wait seconds→ generator
start 5 seconds third time
NOTICE: When the generator can not start successfully in 3 times, the indicator light “FAULT” will be on.
Generator stop
When the mains power supply is on again, the ATS system will transfer the
load to the mains power supply, and the generator will stop after running 5
seconds without load.
Manual start
If you don’t need the ATS system to work automatically, please put the
switch to the “MANUAL” position.
Automatic air damper control
If the generator has air damper control, when the generator starts, the ATS
system will automatically open it and close it after the generator start
successfully.
OPERATION INSTRUCTION
Battery maintenance
ATS system will charge the battery automatically,the charge current is 1A.
ATS access to power system diagram
Access ATS system
Wiring diagram
Single-phase. single voltage wiring diagram:
Three-phase. Double voltage wiring diagram:
Notice
- ATS power must be bigger than load power.
- Must add an AIR-BREAKER to protect the ATS system, when you connect the main power cable to the ATS box.
- Please run the generator successfully at the “OFF” position first, then you can use “AUTO” to work automatically.
- Please turn the air-breaker switch to the “ON” position when using the ATS system.
- Only electrician can open the box for inspection and repair, there is high voltage danger,
Frequently Asked Questions
- Q: What should I do if the generator fails to start after three attempts?
- A: If the generator fails to start successfully after three attempts, the indicator light FAULT will illuminate.
- Q: Can I manually start the generator?
- A: Yes, you can switch the ATS system to MANUAL position for manual control of the generator.