VACON ARFIFF05V070 Liquid Cooled Enclosed Drive Instruction Manual

June 1, 2024
VACON

VACON ARFIFF05V070 Liquid Cooled Enclosed Drive

VACON-ARFIFF05V070-Liquid-Cooled-Enclosed-Drive-
product

Product Information

Specifications:

  • Product Name: AFE-II ARFIFF05
  • Model: Standard AFE-II
  • Date: 3.6.2021
  • Software Code: ARFIFF05V070

Product Usage Instructions

Introduction

The AFE unit is a regenerative power converter for the front-end of a common DC bus product line. It is utilized with inverter hardware and special software. An external L(CL)-filter and charging circuit are required. This unit is chosen for applications requiring low harmonics. The principle connection of the AFE drive is illustrated in Figure 1.

Regenerative Application

The Regenerative Application is user-friendly and adaptable due to its versatile fieldbus features. Detailed parameters of the Regenerative Application are explained in Chapter 6 of the manual.

I/O Configuration

The basic I/O-configuration of the AFE drive includes OPT-A1 and OPT-A2 option cards. The default control place (P3.1) of the AFE drive is Keypad. This application requires NXP3 control board VB00761.

Control IO

Refer to the manual for detailed information on CONTROL IO, including local contacts for support.

Keypad Control

Section 6.10 of the manual covers Keypad control. Follow the instructions provided for keypad operation.

Problem Solving and Fault Codes

Sections 8 and 9 of the manual address Problem Solving and Fault Codes respectively. Refer to these sections in case of troubleshooting needs.

FAQs

  • Q: How do I handle compatibility issues in parameters between versions?
    • A: Refer to the update notes in the manual for guidance on compatibility issues. It is recommended to use the compare function for parameter changes, especially when the version number change is significant.

vacon® nx
ac drives
active front end ii (afe-ii) arfiff05
application manual

Arfiff05 Standard AFE-II
Vacon Standard AFE-II application
INDEX

VACON® · 3
Document code: DPD01979A Software code: ARFIFF05V070
Date: 3.6.2021

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

6 · VACON®

arfiff05 Standard AFE-II

INTRODUCTION

The AFE unit is a regenerative power converter for the front-end of a common DC bus product line. The AFE unit is utilized by using inverter hardware with special software. An external L(CL)-filter and charging circuit is needed. This unit is selected when low harmonics are required. The principle connection of AFE drive has been described in Figure 1.
The Regenerative Application is easy and flexible to use due to its versatile fieldbus features. The parameters of the Regenerative Application are explained in Chapter 6 of this manual.
The basic I/O-configuration of the AFE drive consists of OPT-A1 and OPT-A2 option cards. The basic I/O configuration has been described in table 2-1. As a default the control place (P3.1) of the AFE drive is Keypad.
This application requires NXP3 control board VB00761.

Figure 1, AFE connection
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 7

1.1 Compatibility issues in parameters between versions
V025
· Compatibility Issue: MCB Force Open inverted. This to follow NXC cabinet default signals.

Update Note 1: This application parameters are not kept backwards compatible if new features or improvements would be difficult to implement by doing so. Read this change note and chapter “Compatibility issues in parameters between versions” from manual before updating the application.
Update Note 2: It’s recommended to use compare function for parameter changes when updating application, especially in cases when version number change is considerably high. Application is constantly developed; this includes changing parameter default values, and if parameters are directly downloaded to drive improved default values may be lost.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

8 · VACON®

arfiff05 Standard AFE-II

OPERATION

2.2 Charging of DC This AFE application has own charging control, P2.4.1.9 DC Charge (24 Vdc required for control board) and charging protection in case external charging can’t get DC voltage to required level within set time P2.7.1.5 Charge Max Time (provided that DC Voltage reach at least drive under voltage fault level).
Charging function is activated when P2.4.1.9 DC Charge is A.1 or higher. When control place is IO, Keypad or NCDrive charging is started from start command. Charging is not started if:
– Drive is in fault state. – P2.3.1.2 Enable MCB Close is FALSE – P2.3.1.6 Run Enable is FALSE – P2.3.1.7 Quick Stop is FALSE
Charging is also stopped if above conditions happens during charging or start command is removed.
For fieldbus control charging is started with B0 of FB Control Word on supporting FB profiles. Charging is also stopped if B0 goes low as is MCB opened if already closed.
DC Charge (F80) is given if 85 % of DC Nominal is not reached within P2.7.1.5 Charge Max Time and charging is stopped.
DC Charging is stopped when drive receives feedback from P2.3.1.5 MCB Status.
Note! Use suitably sized DC Charging resistor by checking Pulse loadability for time duration set in for Max Charge Time parameter
NOTE! The MCB feedback is necessary for the correct operation of the AFE application.
NOTE! Only the drive controls its own MCB. If additional interlocks or opening commands are needed, these commands must go through the drive.
NOTE! Missing feedback signal prevent drive going to ready state. MCB Feedback can be monitored from Status Word B10.
NOTE! If feedback is not used there will be three second forced delay on internally generated MCB feedback signal. MCB Feedback can be monitored from Status Word B10.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 9

2.3 Main Circuit breaker control (MCB control) The AFE application controls the MCB of the system with Relay Output RO2. When charging of the DC bus is ready the MCB will be closed. The status of the MCB is monitored via digital input P2.3.1.5 MCB Status (Default is DigIn: A.4). MCB feedback is required for correct AFE functionality,
NOTE! MCB feedback is required for correct AFE functionality.
Over Current (F1), Hardware IGBT (F31) and Software IGBT (F41) faults will open MCB immediately. Some fault can be programmed to open MCB if needed.
NOTE! For correct operation of AFE system, AFE unit needs to be in control of charging circuit and Main Circuit Breaker (MCB).
2.4 Quick Start instructions
NOTE! Before taking any commissioning actions read carefully the safety instructions in Vacon NX User’s Manual, chapter 1.
1. Connect the unit according to the Figure 1. 2. Power up the control unit. 3. Set parameters in G2.1 Basic Parameters. 4. Check that digital input parameters (G2.3.1) have been set according to connections. Note
that P2.3.1.5 MCB Status input is needed for correct operation of AFE unit. 5. Check the control place accordingly proves requirements (P3.1 Control Place). 6. Charge DC.
In case of parallel AFE:
1. Set Parallel AFE parameter (P2.1.5) = YES (in every AFE). (This will set also DC Drooping to 3,00 %
2. Set Start Up Delay in AFE units so that starting is in sequence with different intervals.

Run AFE 4
Stop
Run AFE 3
Stop
Run AFE 2
Stop
Run AFE 1
Stop

Time * 100 ms

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

10 · VACON® 2.5 Start Sequence

Init

Ready to switch on

No DC > 85 %

Yes

MCB close

No

enable

Yes

Close MCB

arfiff05 Standard AFE-II

No MCB Closed

Yes

Start

No

Command

Yes
No Synchronized

F64 A2 (Delayed)
No Trials >= 5

Yes Modulating

Yes F10: LineSynch

Figure 0-2. AFE start sequence

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II 2.6 Stop Sequence
Modulating

No MCB Closed

F64 A4

Yes

No

Stop Request

MCB Closed

Yes

F64 A2 (If DC > 75 %)
(Delayed)

VACON® · 11

Open MCB No
Yes
Stop Modulation (If Run State)

Open MCB

Yes MCB Closed
No End

F64 A3 (Delayed)

Figure 0-3. AFE stop sequence

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

12 · VACON® 2.7 Start Stop timing diagram

arfiff05 Standard AFE-II

P. Start Delay

Stable DC MCB Close level
DC Voltage

Control in FB Control

FB CW.B00 FB CW.B03

Contro in IO Control

IO Start
IO MCB Open Command
Charge Control

MCB Close Control MCB Feedback

Ready
Run
Above example when “Standard” state machine is used. With “Basic” state machine operation is like in IO Control.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 13

CONTROL IO

NXOPTA1
Terminal 1 +10Vref 2 AI1+
3 AI14 AI2+ 5 AI2-
6 +24V

Signal Reference voltage output Analogue input 1. Range 0-10V, Ri = 200 Range 0-20 mA Ri = 250 I/O Ground Analogue input 2. Range 0-10V, Ri = 200 Range 0-20 mA Ri = 250 Control voltage output

Description Voltage for potentiometer, etc. Analogue input 1 Input range selected by jumpers. Default range: Voltage 0 ­ 10 V
Ground for reference and controls Analogue input 2 Input range selected by jumpers. Default range: Current 0 ­ 20 mA Voltage for switches, etc. max 0.1 A

7 GND I/O ground 8 DIN1 Start Request
Programmable G2.3.1 9 DIN2
Programmable G2.3.1 10 DIN3 Fault Reset
Programmable G2.3.1 11 CMA Common for DIN 1–DIN 3

Ground for reference and controls Contact closed = Start Request No function defined at default
Contact closed = Fault Reset Connect to GND or +24V

12 +24V Control voltage output

Voltage for switches (see #6)

13 GND I/O ground

Ground for reference and controls

K1

14 DIN4 MCB feedback

Contact open = MCB open

Contact closed = MCB Closed

15 DIN5 Programmable G2.3.1

No function defined at default

220 VAC

16 DIN6 Programmable G2.2.1

17 CMB Common for DIN4–DIN6

mA

18 AOA1+ Analogue output 1 19 AOA1- Programmable P2.3.1.2

20 DOA1 Digital output Ready / Warning (Blinking)

Connect to GND or +24V Output range selected by jumpers. Range 0–20 mA. RL, max. 500 Range 0–10 V. RL > 1k Programmable Open collector, I50mA, U48 VDC

NXOPTA2

21 RO1 22 RO1 23 RO1

Relay output 1 Programmable G2.4.1

Switching capacity 24 VCD / 8 A 250 VAC / 8 A 125 VDC / 0.4 A

24 RO2 25 RO2 26 RO2

Relay output 2 MCB Contl
Cannot be reprogrammed

Fixed to MCB control. Closes when DC at 85 % of nominal DC. Opens when DC below 75 % of nominal DC

Table 4-2. Default I/O configuration.

Q1

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

14 · VACON®

arfiff05 Standard AFE-II

4. AFE APPLICATION ­ MONITORING VALUES
On the next pages you will find the lists of parameters within the respective parameter groups.

Column explanations:

Code

= Location indication on the keypad; Shows the operator the present parameter

number

Parameter = Name of parameter

Min

= Minimum value of parameter

Max

= Maximum value of parameter

Unit

= Unit of parameter value; Given if available

Default

= Value preset by factory

Cust

= Customer’s own setting

ID

= ID number of the parameter


= On parameter code: Parameter value can only be changed after the Drive has

been stopped.


= Monitoring value is possible to control from fieldbus by ID number

The manual presents signals that are not normally visible for monitoring. i.e. is not a parameter or standard monitoring signal. These signals are presented with [Letter]. e.g. [FW]MotorRegulatorStatus

Monitoring

[V] [P] [FW] [A] [R] [F] [DI] CB MCB

Normal monitoring signal Normal parameter in application. Firmware signal, Can be monitored with NCDrive when signal type is selected Firmware Application signal, can be monitored with NCDrive when signal type is selected Application. Reference type parameter on keypad. Function. Signal is received as a output of function. Digital input signal. Circuit Breaker Main Circuit Breaker = AFE controller Circuit Breaker

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 15

5.1 Monitoring values
The monitoring values are the actual values of parameters and signals as well as statuses and measurements. Monitoring values cannot be edited.

5.1.1 Monitoring 1

Code V1.1.1 V1.1.2 V1.1.3 V1.1.4
V1.1.5

Signal DC-Link Voltage
DC-Link Ref. DC Voltage Ref. DC Voltage Act.
Total Current

V1.1.6

Active Current

V1.1.7

Reactive Current

V1.1.8
V1.1.9 V1.1.10 V1.1.11 V1.1.12 V1.1.13 V1.1.14 V1.1.15 V1.1.16 V1.1.17 V1.1.18

Supply Frequency
Supply Voltage Unit Temperature
Status Word DIN 645. 321 Analogue Input 1 Analogue Input 2 Analogue Out 1 Operation Hours DC-Link Current DC-Link ActCurr

Unit

ID

Description

Vdc 1108 Measured DC Link voltage in Volts, filtered.

Vdc

25 DC Voltage Reference in Vdc

% 1200 Used DC Voltage Reference

%

7 Actual DC Voltage

A

3

Total current of the regenerative unit in Amperes.

Avtive current of the regenerative drive in % of

%

1125

Rated Line Current. > 0 power from AC side to DC side

< 0 power from DC side to AC side

Reactive current of the regenerative drive in % of

%

1157

Rated Line Current. > 0 Inductive current

< 0 Capacitive current

Hz

1

Supply frequency in ##.## Hz .The sign indicates the phase order.

V

6 Input AC voltage, RMS line to line Volts.

°C

8 Heat sing temperature

43

15

%

13

%

14

%

26

h

1856

A

72

% 1158

5.1.2 FieldBus Monitoring values

Code

Signal

Unit

V1.2.1

FB Control Word

V1.2.2

FB Status Word

V1.2.3

Fault Word 1

V1.2.4

Fault Word 2

V1.2.5

DIN Status Word 1

V1.2.6

DIN Status Word 2

V1.2.7

Warning Word 1

V1.2.8

DC Voltage

V1.2.9

Current

V1.2.10

Drive Power

kW

V1.2.11

Fault History

V1.2.12

Final DC Ref

%

V1.2.13

Cabin State Word

V1.2.14

Warning

5.1.3 Line Monitor OPT-D7

Code

Signal

Unit

V1.3.1

Line Voltage

V

V1.3.2

Line Frequency

Hz

V1.3.3

Synch Error D7

V1.3.4

Line Voltage THD

V1.3.5 Line Voltage HF rms

ID 1160
68 1172 1173
56 57 1174 44 1113 1508 37 1131 1884 74

Description Control word from fieldbus Status word to fieldbus
Unfiltered DC-Link voltage Unfiltered total current Electrical AFE terminal power

ID 1650 1654 1659 1670 1671

Description

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

16 · VACON®

arfiff05 Standard AFE-II

5.1.4 Master Follower

Code V1.4.1 V1.4.2 Code V1.4.3.1 V1.4.3.2 V1.4.3.3 V1.4.3.4 Code V1.4.4.1 V1.4.4.2 V1.4.4.3 V1.4.4.4

Parameter SB SystemStatus
Master CW Parameter Current D1 Current D2 Current D3 Current D4 Parameter Status Word D1 Status Word D2 Status Word D3 Status Word D4

Unit Form. ID

1601

93

Unit

ID

A

Varies 1820

A

Varies 1821

A

Varies 1822

A

Varies 1823

Unit

ID

1828

1829

1830

1831

Description Description
Description

5.1.5 Monitoring values 2

Code

Signal

Unit

V1.5.1 Measured temperature 1 Cº

V1.5.2 Measured temperature 2 Cº

V1.5.3 Measured temperature 3 Cº

V1.5.4 Measured temperature 4 Cº

V1.5.5 Measured temperature 5 Cº

V1.5.6 Measured temperature 6 Cº

V.1.5.7 PT-100 Temperature

ID

Description

50 4 s filtering.

51 4 s filtering.

52 4 s filtering.

69 4 s filtering.

70 4 s filtering.

71 4 s filtering.

42

Highest temperature of OPTB8/OPTBH board. 4 s filtering.

4.7.1 PID Control

Code V1.6.1 V1.6.2 V1.6.3

Parameter PID Reference PID Actual Value
PID Output

Unit Form. ID

,

20

,

21

,## 23

Description

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 17

5.2 Monitoring Values description

5.2.1 Monitoring 1 values

V1.1.1 DC-Link Voltage

Vdc ID44

Measured DC voltage, filtered.

V1.1.2

DC-Link Ref. Vdc ID25 DC-Link voltage reference in Vdc.

V1.1.3

DC Voltage Ref.

% ID1200

Used DC Voltage reference in %

V1.1.4 DC Voltage Act.

% ID7

Actual DC Voltage in %

V1.1.5

Total Current

A ID3

Total current of the regenerative unit in Amperes, filtered

V1.1.6

Active Current

% ID1125

Active current in % of System Rated Current. Negative value means that current is flowing to AC side from DC side i.e. regenerating.

V1.1.7

Reactive Current

% ID1157

Reactive current of the regenerative drive in % of System Rated Current. Positive is Inductive current. Negative is capacitive current.

V1.1.8

Supply Frequency Hz ID1
Supply frequency in ##.## Hz .The sign indicates the phase order. Updated when drive in run state. Updated also in stop state when OPT-D7 is used or Regen Options B9 is activated.

V1.1.9

Supply Voltage

V

ID6

Input AC voltage, RMS line to line Volts. Updated when drive in run state. Updates also when OPT-D7 is used.

V1.1.10 Unit Temperature

°C ID8

Temperature of the unit in degrees Celsius

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

18 · VACON®

arfiff05 Standard AFE-II

V1.1.11 Status Word

ID43

Application Status Word combines different drive statuses to one data word.

Application Status Word ID43

FALSE

TRUE

b0 b1 Not in Ready state b2 Not Running b3 No Fault

Ready Running Fault

b4 b5 Quick Stop Active b6 Run Disabled b7 No Warning

Quick Stop Not Active Run Enable Warning

b8

Charging Switch closed (internal)

b9

MCB Control (DO Final)

b10

MCB Feedback

b11

DO Charging Active

b12 No Run Request b13 b14 b15

Run Request

V1.1.12

DIN 645. 321

ID15

DIN1/DIN2/DIN3 status B0 DIN1 B1 DIN2 B2 DIN3 B3 DIN4 B4 DIN5 B5 DIN6

V1.1.13 V1.1.14

Analogue Input 1

% ID13

Analogue Input 2

% ID14

Unfiltered analogue input level. 0 % = 0 mA / 0 V, -100 % = -10 V, 100 % = 20 mA / 10 V. Monitoring scaling is determined by the option board parameter.

V1.1.15 Analogue Out 1

% ID26

Analogue Output value 0 % = 0 mA / 0 V, 100 % = 20 mA / 10 V

V1.1.16 Operation HoursID1856 Run state hours

V1.1.17 V1.1.18

DC-Link Current

[A] ID72

Calculated DC-Link Current in Amps.

DC-Link ActCurr

[%] #,#

Calculated DC-Link Current in %.

ID1158

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 19

5.2.2 Fieldbus monitoring values

V1.2.1 FB Control Word

ID 1160

Control word from fieldbus. Below table is for bypass operation for such fieldbus board that natively supports this or can be parameterized to bypass mode.

FB Control Word ID1160

Signal

Comment

SM

0= Open MCB.

B00

DC Charge

1= Close DC charge contactor, MCB closed automatically, see 1,2,3

B01.

0= Disable Closing of MCB (Also opens if Control

B01

MCB Close Enable Options.B0=TRUE)

3

1= Enable Closing of MCB (Works also for reclosing)

B02

Quick Stop

0= Quick Stop 1= No Quick Stop

3

B03

Run

0= AFE is stopped 1= AFE is started

1,2,3

B04

Output Power Limit to 0= Output Power Limit to Zero (7%)

Zero

1= Output Power Limit = P2.5.2.1

3

Disable Power

B05

Increase.

0= Disable increase of power.

3

Input or Output

1= Power limits defined by G2.5.2

B06

Input Power Limit to 0= Input Power Limit to Zero (7%)

Zero

1= Output Power Limit = P2.5.2.2

3

B07

Reset

0>1 Reset fault.

1,2,3

B08

DC Voltage Ref B00 B00 | B01

2,3

0 | 0 = FB Reference. P2.2.1, if not FB Control & FB Ref > 50,00

%

B09

DC Voltage Ref B01 0 | 1 = 110 %

2,3

1 | 0 = 115 %

1 | 1 = 120 %

B10

Fieldbus Control

0= No control from fieldbus 1=Control from fieldbus

2,3

B11

Watchdog

0>1>0>1…0,5 sec square wave clock. This is used to check data communication between fieldbus master and the drive.

2,3

B12

FB DIN2

Can be used to control RO or directly parameter by ID number. G2.4.1

1,2,3

B13

FB DIN3

Can be used to control RO or directly parameter by ID number. G2.4.1

1,2,3

B14

FB DIN4

Can be used to control RO or directly parameter by ID number. G2.4.1

1,2,3

B15

Reserved for future use.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

20 · VACON®

arfiff05 Standard AFE-II

V1.2.2 FB Status Word

ID 68

FB Status word to fieldbus. Below table is for bypass operation for such fieldbus board that natively supports this or can be parameterized to bypass mode.

FB Status Word ID68

Signal

Comment

b0

Ready On

0=Drive not ready to switch on 1=Drive ready to start charging

b1

Ready Run

0=Drive not ready to run 1=Drive ready and MCB is ON

b2

Running

0=Drive not running 1=Drive in Run state (Modulating)

b3

Fault

0=No active fault 1=Fault is active

b4

Run Enable Status

0= Run Disabled. Drive in stop state 1= Run Enabled. Drive can be started.

b5

Quick Stop Active

0=Quick Stop Active 1=Quick Stop not Active

b6

MCB Control NOT OK

0= MCB Control OK 1= MCB Requested open but DC stays high

b7

Warning

0= No active warnings 1= Warning active

b8

At Reference

0= DC Voltage Ref and Act DC Voltage are not same.

b9

Fieldbus Control Active

0=Fieldbus control not active 1=Fieldbus control active

b10

Above Limit

0= DC Voltage is below P2.5.5.1 level 1=The DC Voltage is above the P2.5.5.1 level

b11

MCB Control (DO Final)

0= Drive is controlling MCB to be Open. 1= Drive is controlling MCB to be Closed

b12

MCB Feedback

0= Feedback indicates MCB to be Open 1= Feedback indicates MCB to be Closed

b13

Reserved for future use.

b14

DC Charge DO Control

0= DC not charged 1= DC Charging Active

b15

Watchdog

Same as received on bit 11 of the FB Control Word.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

V1.2.3

Fault Word 1
Bit B0 B1 B2 B3 B4 B5 B6
B7
B8 B9 B10 B11 B12 B13 B14 B15

ID 1172
Fault Word 1 ID1172 Fault(s)
F1 Over current, F31 IGBT, F41 IGBT F2 Over Voltage F9 Under Voltage F91 Short Circuit F3 Earth Fault
F14 Unit Over Temperature F29 Thermistor, F56 Measured Temperature 1, F65 Measured Temperature 2 F71 LCL Over Temperature F10 Line Synch fault F11 Supply Phase
Device faults: F37, F38, F39, F40

V1.2.4

Fault Word 2

ID 1173

Fault Word 2 ID1173

Bit

Fault(s)

B0

B1

F5 Charging Fault, F80 Charge Fault

B2

B3

Hardware faults: F7

B4

F13 Under Temperature

B5

F22 EPROM, F49 Zero Division

B6

B7

B8

B9

F31 IGBT, F41 IGBT

B10

F32 Fan Fault,

B11

F70 LCL Fan Fault,

F60 LC Cooling Warning/Fault

B12

F8 System,

B13

F26 Start Up Prevented,

F36 Control Unit

B14

F64 MCB State Fault

B15

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

VACON® · 21

22 · VACON®

arfiff05 Standard AFE-II

V1.2.5 V1.2.6

DIN Status 1 DIN Status 2

ID 56 ID 57

DIN Status Word 1 b0 DIN: A.1 b1 DIN: A.2 b2 DIN: A.3 b3 DIN: A.4 b4 DIN: A.5 b5 DIN: A.6 b6 DIN: B.1 b7 DIN: B.2 b8 DIN: B.3 b9 DIN: B.4 b10 DIN: B.5 b11 DIN: B.6 b12 DIN: C.1 b13 DIN: C.2 b14 DIN: C.3 b15 DIN: C.4

DIN Status Word 2 DIN: C.5 DIN: C.6 DIN: D.1 DIN: D.2 DIN: D.3 DIN: D.4 DIN: D.5 DIN: D.6 DIN: E.1 DIN: E.2 DIN: E.3 DIN: E.4 DIN: E.5 DIN: E.6

V1.2.7 Warning Word 1

ID 1174

Warning Word 1 ID1174

Bit

Warning(s)

B0

W29 Thermistor

B1

F56 Measured Temperature 1, F65 Measured Temperature 2

F71 LCL Over Temperature

B2

B3

W11 Supply Phase

B4

B5

B6

B7

B8

W14 Unit Over Temperature

B9

B10

F32 Fan Fault, F70 LCL Fan Fault

B11

B12

B13

B14

B15

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 23

V1.2.8

DC Voltage

[Vdc] ID44

Unfiltered DC-Link Voltage

V1.2.9

Current [A] ID1113 Total unfiltered current

V1.2.10 Drive Power [kW] ID 1508 Drive input terminal electrical power.

V1.2.11

Fault History ID37
Last active fault. If drive has several fault at the same time see from fault history what was the first fault.

V1.2.12 Final DC Ref [%] ID1131 Final DC Reference, including offset control.

V1.2.13 Cabin State Word

ID1884

Fault b0 Main Fuse b1 Aux voltage b2 STO Fuse b3 Insulation Fault
b4 Earthswitch Fault b5 Arc Relay b6 high Amb Temp. b7 Leakage
b8 Not used b9 Not used b10 Not used b11 Not used
b12 Not used b13 Not used b14 Not used b15 Not used

Cabin State Word ID1884 Fault Codes
W81 W82 W83 W84
W85 W86 W88 W89

V1.2.14 Warning

ID74

Last active warning. If drive has several warning at the same time see from fault history what was the first warning.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

24 · VACON®

arfiff05 Standard AFE-II

5.2.3 Line monitoring OPT-D7

V1.3.1 V1.3.2 V1.3.3
V1.3.4

Line Voltage V

ID1650

The measured line voltage rms value when using the OPT-D7 option board in slot C.

Line Frequency Hz ID1654 The measured line voltage frequency when using the OPT-D7 option board in slot C.

Synch Error D7

ID1659

An error on voltage angles between the drive and the measurement taken by OPT-D7. -3072…+3071 = -180…180 degrees. If the value is not near to zero when running in AFE mode, the phase order may be wrong even if the OPT-D7 frequency is correct (Error about 2047 = 120 degree). If measurement is after Dyn11 transformer error is usually about 512 (30,0 Degree).

Line Voltage THD

ID1670

V1.3.5 LineVoltageHFrms ID1671

5.2.4 Master/Follower Here are gathered relevant signals in Master follower system.

V1.4.1 SB SystemStatus

ID 1601

System Bus Status Word ID1601

FALSE

TRUE

b0

Not used

b1

Drive 1 Ready

b2

Drive 1 Running

b3

Drive 1 Fault

b4

Not used

b5

Drive 2 Ready

b6

Drive 2 Running

b7

Drive 2 Fault

b8

Not used

b9

Drive 3 Ready

b10

Drive 3 Running

b11

Drive 3 Fault

b12

Not used

b13

Drive 4 Ready

b14

Drive 4 Running

b15

Drive 4 Fault

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 25

V1.4. 2

Master CW

ID93

Master Drive Control Word. Master Sending, Follower receiving.

.4.7.1.1 Currents

V1.4.3.1 V1.4.3.2 V1.4.3.3 V1.4.3.4

Current D1 A Current D2 A Current D3 A Current D4 A

Varies 1820 Varies 1821 Varies 1822 Varies 1823

4.7.2 Statuses

V1.4.4.1 V1.4.4.2 V1.4.4.3 V1.4.4.4

Status Word D1 Status Word D2 Status Word D3 Status Word D4

1828

1829

1830

1831

5.2.5 Monitoring values 2

V1.5.1 Measured temperature 1

Cº ID 50

V1.5.2 Measured temperature 2

Cº ID 51

V1.5.3 Measured temperature 3

Cº ID 52

V1.5.4 Measured temperature 4

Cº ID 69

V1.5.5 Measured temperature 5

Cº ID 70

V1.5.6 Measured temperature 6

Cº ID 71

V1.5.7 PT-100 Temperature

Cº ID 42

Highest temperature of OPTB8/OPTBH board. 4 s filtering.

4.7.3 PIC Controller Monitoring values for power controller in AFE mode

V1.6.1

PID Reference

20

Active Current reference

V1.6.2 PID Actual Value

21

Active current

V1.6.3

PID Output

23

PID controller output for DC Voltage reference, gives an offset for DC Voltage Reference.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

26 · VACON®

arfiff05 Standard AFE-II

5. PARAMETER LIST

6.1 Basic parameters

Code
P2.1.1
P2.1.2 P2.1.3 P2.1.4

Parameter
Grid Nominal Voltage
Grid Nominal Frequency
System Rated Current System Rated Power

Min 500V: 380V
690V: 525V
48
0,0 0

Max 500V: 500V
690V: 690V
63
Ih 32000

Unit
V
Hz A kW

Default
400
50 Ih 0

P2.1.5

Parallel AFE

0

3

0

Table 4-2. Basic parameters

ID Note

110

Set here the nominal voltage of the grid.

1532 113 116
1501

Set here the nominal frequency of the grid. Capacity of supply, used if oversized AFE.
0 = Single AFE 1 = Parallel AFE 1 = Master 1 = Follower

6.2
Code

Reference Handling

Parameter

Min

Max Unit Default

P2.2.1

DC Voltage Ref.

105 Varies % 110,00

P 2.2.2 DC Voltage Drooping 0,00 100,00

0,00

P2.2.3

Reactive Current Reference

-100,0 100,0 %

0,0

P2.2.4 DC Reference Offset -5,00 5,00 %

0,00

Table 1- 1, Reference Handling

ID 1462 620 1459 1777

Note DC Voltage reference as % of Nominal DC Voltage
Nominal DC voltage = 1,35 * Supply voltage AFE drooping DC-voltage. Set to 3,00 % when parallel AFE operation is selected Regenerative reactive current reference 100,0 = nominal current. Positive =Inductive Negative = Capacitive

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 27

5.8 PIC Function

Code P2.2.5.1 P2.2.5.2 P2.2.5.3 P2.2.5.4 P2.2.5.5 P2.2.5.6 P2.2.5.7

Parameter PIC Enable PIC Control Mode PIC Reference
PIC Kp PIC Ti PID DC Low PIC DC High

Min 0.1 0 -320 1 0 -50 -50

Max E.10
2 320 3200 3200 50 50

Unit
% % ms % %

Default

ID 1905 1914 167 19111 1906 1903 1906

Description

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

28 · VACON®

arfiff05 Standard AFE-II

5.9 Input signals 6.2.1 Digital inputs

Code

Parameter

Min

P2.3.1.1

Start Signal 1

0.1

P2.3.1.2 Enable MCB Close 0.1

P2.3.1.3

Open MCB Power Dawn

0.1

P2.3.1.4 LCL Temp. X51

0.1

P2.3.1.5 LCL Temp. X52

0.1

P2.3.1.6

MCB Status

0.1

P2.3.1.7

Run Enable

0.1

P2.3.1.8

Quick Stop

0.1

P2.3.1.9

Ext. Fault 1

0.1

P2.3.1.10

Ext. Fault 2

0.1

P2.3.1.11

Fault Reset

0.1

P2.3.1.12

LC Cooling

0.1

P2.3.1.13 MCB Trip State

0.1

P2.3.1.14

Control from I/O terminal

0.1

P2.3.1.15

Control from keypad

0.1

P2.3.1.16

Control from fieldbus

0.1

Table 4-3. Digital inputs parameters

Max E.10
E.10
E.10
E.10 E.10 E.10 E.10
E.10 E.10 E.10 E.10 E.10 E.10
0.1
0.1
0.1

Unit DigIn:
DigIn:
DigIn:
DigIn: DigIn: DigIn: DigIn:
DigIn: DigIn: DigIn: DigIn: DigIn: DigIn
DigIn
DigIn
DigIn

Default A.1
0.2
0.2
0.2 0.2 A.4 0.2
0.2 0.1 0.1 0.1 0.2 0.1
0.1
0.1
0.1

ID 403
1619

Description
With CO.B00; Opens MCB also

1600 Power down command

1179 1125 1453 407
1213
405 406 414 750 1706
409
410
411

Power down with a warning
Force control place to I/O terminal (cc) Force control place to keypad (cc) Force control place to fieldbus (cc)

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 29

6.2.2 Analogue Input 1

Code P2.3.2.1 P2.3.2.2 P2.3.2.3 P2.3.2.4 P2.3.2.5 P2.3.2.6
P2.3.2.7 P2.3.2.8

Parameter AI1 signal selection
AI1 filter time AI1 custom minimum setting AI1 custom maximum setting AI1 signal inversion AI1 reference scaling, minimum
value AI1 reference scaling, maximum
value AI1 Controlled ID

Min 0.1 0,000 -160,00 -160,00 0 -32000
-32000 0

Table 1- 2, ANALOG INPUT1,

Max E.10 32,000 160,00 160,00
1 32000
32000 10000

Unit AnIN:
s %
%

Default 0.1
0,000 0,00 100,00
0 0
0 0

ID Note 377 324 321 322 387 303
304 1507

6.2.3 Analogue Input 2

Code

Parameter

P2.3.3.1 AI2 signal selection

P2.3.3.2 AI2 filter time

P2.3.3.3
P2.3.3.4 P2.3.3.5

AI2 custom minimum setting
AI2 custom maximum setting AI2 signal inversion

P2.3.3.6 P2.2.3.7

AI2 reference scaling, minimum
value
AI2 reference scaling, maximum
value

P2.3.3.8 AI2 Controlled ID

Table 1- 3, ANALOG INPUT2

Min 0.1 0,000 -160,00
-160,00 0
-32000
-32000
0

Max E.10 32,000 160,00
160,00 1
32000
32000
10000

Unit AnIN:
s %
%

Default 0.1
0,000 0,00
100,00 0
0
0
0

ID Note 388 329 326
327 398
393
394
1511

6.2.4 Cabin State DI

Code

Parameter

Min

P2.3.4.1

Main Fuse

0.1

P2.3.4.2

Aux Voltage

0.1

P2.3.4.3

STO Fuse

0.1

P2.3.4.4 Insulation Fault

0.1

P2.3.4.5 Earthswitch Fault 0.1

P2.3.4.6

Arc Relay

0.1

P2.3.4.7 High Amb Temp. 0.1

P2.3.4.8

Leakage

0.1

P2.3.4.9

Klixon In 1

0.1

P2.3.4.10

Klixon In 2

0.1

P2.3.4.11

Input Switch

0.1

Max E.10 E.10 E.10 E.10 E.10 E.10 E.10 E.10 E.10 E.10 E.10

Unit DigIn: DigIn: DigIn: DigIn: DigIn: DigIn: DigIn: DigIn: DigIn DigIn DigIn

Default 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2

ID 1700 1703 1702 1704 1732 1733 1734 1735 780 781 1209

Description

6.2.5 Options

Code

Parameter

Min

P2.3.5.1 Start/Stop Logic

0

P2.3.5.2 Input Inversion

0

Table 1- 4, Digital input options

Max

Unit

2

65535

Default 0 0

ID 300 1091

Note 0/Static 1/ Rising edge 2/ Pulse

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

30 · VACON®

arfiff05 Standard AFE-II

6.3 Output signals 6.3.1 Digital Outputs

Code

Parameter

Min Max

P2.4.1.1
P2.4.1.2
P2.4.1.3 P2.4.1.4 P2.4.1.5 P2.4.1.6 P2.4.1.7

MCB Control (Close)
MCB Control Open Ready Run Fault
Fault,Inverted Warning

B.2

B.2

0.1 E.10
0.1 E.10 0.1 E.10 0.1 E.10 0.1 E.10 0.1 E.10

P2.4.1.8 DC Above Limit 0.1 E.10

P2.4.1.9

DC Charge

0.1 E.10

P2.4.1.10 Ready To Start

0.1

E.10

P2.4.1.11 FB Dig Input 1

0.1

E.10

P2.4.1.12 FB Dig 1 Input Par 0

P2.4.1.13 FB Dig Input 2

0.1

P2.4.1.14 FB Dig 2 Input Par 0

P2.4.1.15 FB Dig Input 3

0.1

P2.4.1.16 FB Dig 3 Input Par 0

P2.4.1.17 FB Dig Input 4

0.1

P2.4.1.18 FB Dig 4 Input Par 0

P2.4.1.19 FB Dig Input 5

0.1

10000 E.10 10000 E.10 10000 E.10 10000 E.10

P2.4.1.20 FB Dig 5 Input Par 0

10000

Table 4-4. Digital outputs parameters

Unit
DigOUT:
DigOUT:
DigOUT: DigOUT: DigOUT: DigOUT: DigOUT: DigOUT: DigOUT: DigOUT: DigOUT:
ID DigOUT:
ID DigOUT:
ID DigOUT:
ID DigOUT:
ID

Default
B.2
0.1
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0 0.1 0 0.1 0 0.1 0 0.1 0

ID
1218
1219
432 433 434 435 436 451 1668 1686 455 891 456 892 457 893 169 894 170 895

Description
Static if ID1219 < DigOUT:A.1 Pulse, if used also ID1218 is pulse control.

6.3.2 ANALOG OUTPUT 1

Code

Parameter

Min

P2.4.2.1 Iout 1 signal

0.1

P2.4.2.2 Iout Content

0

P2.4.2.3

Iout Filter Time

0

P2.4.2.4

Iout Invert

0

P2.4.2.5 Iout Minimum

0

P2.4.2.6

Iout Scale

10

P2.4.2.7

Iout Offset

-100

Table 1- 5, Output signals, G2.3.4

Max E.10
4
10 1 1 1000 100

Unit AnOUT
s
% %

Default A.1
1 0 0 100 0

ID Note 464
0 = 4 mA 1 = DC-Link Voltage 307 2 = Current 3 = Power 4 = +- Power

308 0=No filtering

309

0=Not inverted 1=Inverted

310

0=0 mA 1=4 mA

Percentage

multiplier.

311 Defines output when

content is it maximum value

375

Add -1000 to 1000% to the analogue output.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 31

6.3.3 Options

Code

Parameter

Min

P2.4.3.1

Output Inversion

0

P2.4.3.2

MCB Close Mode

0

P2.4.3.3

MCB At Stop Command

0

Max 1 2 1

Unit

Default ID Note

0

1806

0 = DC Voltage

0

1607 1 = DC or Start command

2 = Start Command.

0

1685

0 = Keep CB Closed 1 = Open CB

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

32 · VACON®

arfiff05 Standard AFE-II

6.5 Limit Settings 5.9.1 Current Limit

Code

Parameter

Min

Max

Unit

P2.5.1.1

Current Limit

0

Varies

A

P2.5.1.2

Output Active Current Limit

0

300,0

%

P2.5.1.3

Input Active Current Limit

0

300,0

%

5.9.2 Power Limit

Code

Parameter

Min

Max

Unit

P 2.5.2.1 Output Power Lim

0

300,0

%

P 2.5.2.2 Input Power Lim

0

300,0

%

Default Varies 150,0 150,0
Default 150,0 150,0

ID 107 1290
1289

Note Total current limit Generating Active Current limit in AFE mode to grid. Motoring active current limit in AFE mode to DC-link.

ID 1288 1287

Note Generating power limit Motoring power limit

5.9.3 Frequency Limit

Code

Parameter

Min

Max

Unit

Default

ID Note

P 2.5.3.1

Low Frequency Trip Limit

42

120

%

80

1717

P 2.5.3.2

High Frequency Trip Limit

42

120

%

120

1716

5.9.4 AC Voltage Limit

Code

Parameter

Min

Max

Unit

Default

ID Note

P 2.5.4.1

Low AC Voltage Trip Limit

50

150

%

80

1711

P 2.5.4.2

High AC Voltage Trip Limit

50

150

%

120

1710

5.9.5 DC Voltage Limit

Code

Parameter

Min

Max

Unit

P2.5.5.1

DC Super Vision Limit

0

1300

Vdc

P2.5.5.2

High MCB Close Limit

0

1300

Vdc

Default 600
0

ID Note 1454
1251

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 33

5.10 Drive Control parameters

Code
P2.6.1 P2.6.2
P2.6.3

Parameter
AFE Options 1 AFE Options 2
Control Options

P2.6.4

Start Delay

P2.6.5

Modulator Type

P2.6.6

Operation Time

Min

Max

Unit

Default

ID

Description

0

65535

544 1463

0

65535

0

1464

0

65536

0

1707

Control word for activating special features.

Starting delay when run

command is given. When

0,00 320,00

s

0,50

1500

programming different delay to paralleled units,

the units will start in

sequence.

0

4

Single: 2
Parallel 1

1516

0 = Hardware 1 = Software 1 2 = Software 2 3 = Software 3 4 = Software 4

0

2^32

1855

Table 4-6. Drive control parameters G2.4

5.10.1

Control

Code

Parameter

Min

Max

Unit

Default

ID

P2.6.7.1 Capacitor Size

0

100

%

6,3 1460

P2.6.7.2

Inductor Size

0

100

%

15,5 1461

P2.6.7.3 Dynamic Support Kp

0

32000

0

1797

P2.6.7.4

Synch Kp

0

32000

2000 1457

P2.6.7.5

Synch Ti

0

1000

50

1458

P2.6.7.6 Active Current Kp

0

4000

400 1455

P2.6.7.7 Active Current Ti

0,0

100,0

1,5 1456

P2.6.7.8 Synch. Kp Start

0

10000

4000 1300

P2.6.7.9 Voltage Ctrl Kp

0

32000

200 1451

P2.6.7.10 Voltage Ctrl Ti

0

1000

ms

50

1452

P2.6.7.11 Switching Frequency 3,4

Varies

Hz

3,6

601

P2.6.7.12 DCLinkMeasCalib -2,00 2,00

%

0,00 549

P2.6.7.13

Modulator #2 DPWM Optimization

0

1

1

1682

Table 4-6. Drive control parameters G2.4

Description

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

34 · VACON®

arfiff05 Standard AFE-II

5.11 Protections

5.11.1

General

Code

Parameter

Min

Max

Unit

P2.7.1.1

Response to Thermistor fault

0

3

Input Filter Over

P2.7.1.2 Temperature

0

3

Response

P2.7.1.3 MCB At Fault

0

1

P2.7.1.4 Charge Max Time

0,00

60,00

s

P2.7.1.5

Fault/Warn Indication

0

2

P2.7.1.6

Quick Stop Response

0

2

P2.7.1.7

Run Enable Indication

0

2

Table 4-9. General Protections parameters G2.7.1

Default
2
2 0 10,00 1 1 1

ID
732
1505 1699 1522 1940 1758

Description
0=No response 1=Warning 2=Fault 3=Fault, DC OFF 0=No response 1=Warning 2=Fault 3=Fault, DC OFF
Charging time limit when drive charging options are used. 0=Static 1=Toggle 2=Marine

1177

5.11.2
Code

Temperature sensor protections

Parameter

Min Max Unit Default

P2.7.2.1

No. of used inputs on board 1

0

5

0

P2.7.2.2

Response to temperature fault

0

3

P2.7.2.3

Board 1 warning limit

­30,0 200,0

P2.7.2.4 Board 1 fault limit ­30,0 200,0 Cº

P2.7.2.5

No. of uses inputs on board 2

0

5

2 120,0 130,0
0

P2.7.2.6

Response to temperature fault

0

3

P2.7.2.7

Board 2 warning limit

­30,0 200,0

P2.7.2.8 Board 2 fault limit ­30,0 200,0 Cº

P2.7.2.9.1 Channel 1B Warn -30,0 200,0 Cº

P2.7.2.9.2 Channel 1B Fault -30,0 200,0 Cº

P2.7.2.9.3 Channel 1C Warn -30,0 200,0 Cº

P2.7.2.9.4 Channel 1C Fault -30,0 200,0 Cº

P2.7.2.9.5 Channel 2B Warn -30,0 200,0 Cº

P2.7.2.9.6 Channel 2B Fault -30,0 200,0 Cº

P2.7.2.9.7 Channel 2C Warn -30,0 200,0 Cº

P2.7.2.9.8 Channel 2C Fault -30,0 200,0 Cº

2
120,0
130,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0 0,0

Cust

ID

Note

0=Not used (ID Write)

1 = Sensor 1 in use

739

2 = Sensor 1 & 2 in use 3 = Sensor 1 & 2 & 3 in use

4 = Sensor 2 & 3 in use

5 = Sensor 3 in use

0=No response

740

1=Warning 2=Fault,stop acc. to 2.3.2

3=Fault,stop by coasting

741

742

0=Not used (ID Write)

1 = Sensor 1 in use

743

2 = Sensor 1 & 2 in use 3 = Sensor 1 & 2 & 3 in use

4 = Sensor 2 & 3 in use

5 = Sensor 3 in use

0=No response

766

1=Warning 2=Fault,stop acc. to 2.3.2

3=Fault,stop by coasting

745

746 764 765 768 769 770 771 772 773

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 35

5.11.3

Fieldbus

Code

Parameter

Min

Max

Unit

2.7.3.1 FB Fault Response

0

2

2.7.3.2 FB WD Delay

0,00

30,00

Table 4-9. Fieldbus Protections parameters G2.7.2

Default
2 0,00

ID
733 1354

Description
0=No response 1=Warning 2=Fault 0,00 = Disabled WD

5.11.4

OPT-D7 protections

Code

Parameter

Min

Max

Unit

2.7.4.1 THD Response

0

2

2.7.4.2 THD Warn. Limit

0,00

50,00

%

2.7.4.3 THD Fault Limit

0,00

50,00

%

2.7.4.4 HF rms Response

0

2

2.7.4.5 HF rms Warn Limit

0,0

400,0

V

2.7.4.6 HF rms Fault Limit

0

400,0

V

Table 4-9. OPT-D7 Protection parameters G2.7.3

Default
0 6,00 10,00
0 20,0 60,0

ID
1672 1673 1674 1675 1676 1677

Description

5.11.5

External Fault

Code

Parameter

Min

Max

P2.7.5.1

External Fault 1 Response

0

2

P2.7.5.2

External Fault 2 Response

0

2

Table 4-9. Options parameters G2.7.2

Unit

Default

ID

Description

0=No response

2

701 1=Warning

2=Fault

0=No response

2

1504 1=Warning

2=Fault

5.11.6

Cooling protection

Code

Parameter

Min Max Unit

P2.7.6.1

Cooling Fault Response

1

2

P2.7.6.2 Cooling Fault delay 0.00 7.00

s

Table 5-29. Cooling Protections parameters

Default 2
2.00

Cust

ID

Note

0= No Action, Warning

762

1= Warning, Warning 2= Warning, Fault

3= No Action, Fault

751

5.11.7
Code

Cabin protection

Parameter

Min Max Unit

P2.7.7.1 Klixon Response

0

3

P2.7.7.1

Ambient Temp Response

0

2

P2.7.7.1

Input Switch Response

0

2

Table 5-29. Cabin Protections parameters

Default 2 1 2

Cust

ID

Note

0 = No Action

782

1 = Warning, Warning 2 = Warning, Fault

3 = Fault, Fault

0 = No Action

784 1 = Warning

2 = Fault

0 = No Action

785 1 = Warning

2 = Fault

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

36 · VACON®

arfiff05 Standard AFE-II

5.11.8

Options

Code

Parameter

Min

P2.7.7 Fault Simulation

0

P2.7.8 Reset Datalogger

0

P2.7.9 Disable Run Lock

0

Max
65535
1
1

Unit

Default

ID

Description

0

1569

0

1857

Resets datalogger to defaults.

0

1086

Table 4-9. Options parameters G2.7.2

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 37

5.12 Fieldbus parameters

Code

Parameter

Min

P2.8.1

FB Actual Value Selection

0

P2.8.2

Fieldbus data out 1 selection

0

P2.8.3

Fieldbus data out 2 selection

0

P2.8.4

Fieldbus data out 3 selection

0

P2.8.5

Fieldbus data out 4 selection

0

P2.8.6

Fieldbus data out 5 selection

0

P2.8.7

Fieldbus data out 6 selection

0

P2.8.8

Fieldbus data out 7 selection

0

P2.8.9

Fieldbus data out 8 selection

0

P2.8.10

Fieldbus data in 1 selection

0

P2.8.11

Fieldbus data in 2 selection

0

P2.8.12

Fieldbus data in 3 selection

0

P2.8.13

Fieldbus data in 4 selection

0

P2.8.14

Fieldbus data in 5 selection

0

P2.8.15

Fieldbus data in 6 selection

0

P2.8.16

Fieldbus data in 7 selection

0

P2.8.17

Fieldbus data in 8 selection

0

P2.8.18

GSW ID

0

P2.8.19

State Machine

0

P2.8.20 FB Control Slot Sel.

0

Table 4-8. Fieldbus parameters G2.6

Max

Unit

Default

ID

Description

65535

ID

7

1853

65535

ID

0

852

Choose monitoring data with parameter ID

65535

ID

0

853

65535

ID

0

854

65535

ID

0

855

65535

ID

0

856

65535

ID

0

857

65535

ID

0

858

65535

ID

0

859

65535

ID

0

876

Choose controlled data with parameter ID

65535

ID

0

877

65535

ID

0

878

65535

ID

0

879

65535

ID

0

880

65535

ID

0

881

65535

ID

0

882

65535

ID

65535

ID

3

5

0

883

68

897

1

896

0

1440

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

38 · VACON®

arfiff05 Standard AFE-II

5.13 ID Control Functions

5.13.1

Value control

Table 1. Power reference input signal selection, G2.2.8

Code

Parameter

Min

Max Unit

P2.9.1.1

Control Input Signal ID

0

10000 ID

P2.9.1.2

Control Input Off Limit

-32000 32000

P2.9.1.3

Control Input On Limit

-32000 32000

P2.9.1.4

Control Output Off Value

-32000 32000

P2.9.1.5

Control Output On Value

-32000 32000

P2.9.1.6

Control Output Signal ID

0

10000 ID

P2.9.1.7

Control Mode

0

5

P2.9.1.8

Control Output Filtering rime

0.000 32.000 s

Default 0 0 0 0 0 0
0
0.000

Cust

ID Description 1580

1581

1582

1583

1584

1585 1586 1721

0 = SR ABS 1 = Scale ABS 2 = Scale INV ABS 3 = SR 4 = Scale 5 = Scale INV

5.13.2
Code P2.9.2.1 P2.9.2.2 P2.9.2.3 P2.9.2.4

DIN ID Control 1 Table 2. DIN ID control parameters, G2.2.8

Parameter ID Control DIN
Controlled ID False value True value

Min

Max

0.1

E.10

0
-32000 -32000

10000
32000 32000

Unit Default Cust ID Description

Slot Board input No.

0.1

1570 If 0.1 ID61 can be

controlled from FB

ID

0

1571

Select ID that is controlled by digital input

0

1572 Value when DI is low

0

1573 Value when DI is high

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 39

5.14 Keypad control (Control keypad: Menu M3)

Code
P3.1

Parameter
Control place

Default

Min

2

0

Table 4-11. Keypad control parameters M3

Max

Unit

ID

Description

0=Fieldbus

2

125 1=I/O terminal

2=Keypad (Default)

5.15 System menu (Control keypad: Menu M6)
For parameters and functions related to the general use of the frequency converter, such as application and language selection, customised parameter sets or information about the hardware and software, see Chapter 7.3.6 in the Vacon NX User’s Manual.
5.16 Expander boards (Control keypad: Menu M7)
The M7 menu shows the expander and option boards attached to the control board and boardrelated information. For more information, see Chapter 7.3.7 in the Vacon NX User’s Manual and Vacon I/O option board manual.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

40 · VACON®

arfiff05 Standard AFE-II

DESCRIPTION OF PARAMETERS

6.1 Basic parameters

2.1.1 2.1.2 2.1.3
2.1.4

Grid Nominal Voltage

[# V]

ID110

This parameter sets the incoming line voltage for the regenerative drive. The maximum value is 690 V, Set this parameter to the nominal line voltage at the installation site.

Grid Nominal Frequency

[#,## Hz] ID1532

Grid Nominal frequency. Used for frequency protection functions and initial guess for synchronization frequency.

System Rated Current

[A]

ID113

Rated current capacity of the supply or the transformer. May need to be set if AFE is oversized compared to LCL or feeding transformer capacity. For testing purposes, the feeding transformer should not be less than 20% of the unit nominal current or following breakers or fuses. Recommended not to increase System Rated Current above IH Current.

System Rated Power

[kW]

ID116

Set here the rated active power of the system.

2.1.5

Parallel AFE

ID1501

0 = Single AFE

1 = Parallel AFE

When selecting parallel, AFE DC Drooping is set to 3,00 %, Software Modulation 1 is activated (Default Software Modulator 2) and modulation is automatically synchronized between AFE units in common DC bus.

2 = Master

When selecting Master, AFE DC Drooping is set to 3,00 %, Software Modulation 1 is activated (Default Software Modulator 2) and modulation is automatically synchronized between AFE units in common DC bus. Start Command is send trough system bus to follower drives

3 = Follower

When selecting follower, AFE DC Drooping is set to 3,00 %, Software Modulation 1 is activated (Default Software Modulator 2) and modulation is automatically synchronized between AFE units in common DC bus. Follower drive revives start command from master drive through system bus.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 41

6.2 Reference Handling

P2.2.1

DC Voltage Reference

[#,## %]

ID1462

This parameter sets the DC Voltage reference in % of Nominal DC voltage (Nominal DC voltage = 1,35 * Grid Nominal Voltage). The DC Voltage will be maintained at this level when regenerative unit is running. Ramp rate for reference is 5 % / 100 ms.

NOTE! DC-link voltage should not exceed the following values:

· 797 Vdc for 500V unit · 1099 Vdc for 690V unit

DC Voltage is limited to these values regardless of reference.

In fieldbus control DC Voltage Reference can be given in FBSpeedReference signal. If FBSpeedReference is below 50,00 % keypad reference is used instead but minimum is always limited to 105,00 %.

P2.2.2 P2.2.3 P2.2.4

DC Droop

ID620

When AFEs are used in parallel, drooping can be used for current balancing. The DCV voltage reference drooping is set as % of active current reference.

E.g. if drooping is 3.00% and active current is 50% then DC voltage reference is reduced 1,5%.

Reactive Current Reference ID1459 This parameter sets the reference for the reactive current in % of the rated current. This can be used for power factor correction of AFE system or reactive power compensation.
Positive value makes inductive power to the grid Negative value makes capacitive power to the grid.
DC Reference Offset Offset for DC Reference, used to balance parallel unit active current while using same DC Reference P2.2.1. in all units.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

42 · VACON®

arfiff05 Standard AFE-II

6.2.1 PIC Function

P2.2.5.1

PIC Enable

ID1905

Select digital input to activate PID Power control function. Use ID1914 to select control mode.

P2.2.5.2 PIC Control Mode

ID1914

This parameter is used to select control mode.

0 = Disabled

1 = Drive will control AC side active current

2 = Drive will control DC Current

P2.2.5.3 PIC Reference ID167 PIC Reference parameter

P2.2.5.4 PIC Kp PIC Control Gain

ID1911

P2.2.5.5 PIC Ti

ID1906

PIC Controller integration time in ms.

P2.2.5.6 PID DC Low

ID1903

Limit for PIC controlled how much DC Reference can be lowered to maintain reference.

P2.2.5.7 PIC DC High

ID1906

Limit for PIC controlled how much DC Reference can be increased to maintain reference.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 43

6.3 Input signals

6.3.1 Digital inputs

P2.3.1.1 Start Signal 1

ID403

Start signal, See Start/Stop Logic ID 300.

P2.3.1.2

Enable MCB Close

ID1619

Enables MCB closing, false keeps MCB open even if required DC Voltage level has been reached. With Control Options B00 MCB is also opened without need to discharge DC link.

P2.3.1.3

Open MCB PowerDown ID1600
Signal FALSE status will stop the AFE unit and discharge DC. System is powered down.

On keypad control pressing Stop button more than a 2 second will open the MCB.

P2.3.1.4

LCL Temp. X51

ID1179

This parameter defines if the drive monitors the status of the LCL Fan of the unit. If the monitoring function is used, the unit will give a warning if the LCL fan stops working and LCL temperature reaches warning level.

Check from hardware if LCL is using X51 for fan monitoring or for LCL Temperature monitoring. If hardware uses X51 for fan monitoring use this parameter if it is used for LCL temperature monitoring use P2.3.1.10 LCL Temperature Monitoring X51.

This signal is normally used in cabinet installations. If status of the LCL fan is not monitored in the system the option “0 = Not used” must be chosen.

P2.3.1.5

LCL Temp. X52

ID1125

This parameter defines if the drive monitors the status of the LCL over temperature
switch signal. This wire is marked as “X52” when not using integrated DC/DC power supply.

This signal is normally used in cabinet installations. If LCL Over temperature monitoring signal is not used in the system the option “0 = Not used” must be chosen.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

44 · VACON®

arfiff05 Standard AFE-II

P2.3.1.6

MCB Status

ID1453

This parameter defines what input is used to monitor status of the MCB of the unit. If feedback does not correspond the control signal within 4 second time delay drive will indicate MCC Fault and will not be able to start until proper feedback is give. If feedback is lost during run state fault is immediate and MCB Open command is given.

NOTE! AFE needs feedback signal for correct operation. If feedback is not used there will be 3 second delay after closing command before drive can be started.

NOTE! Missing feedback signal prevent drive going to ready state. MCB Feedback can be monitored from Status Word B10.
NOTE! If feedback is not used there will be three second forced delay on internally generated MCB feedback signal. MCB Feedback can be monitored from Status Word B10.

P2.3.1.7

Run Enable

ID407

This parameter defines which digital input is used for external Run Enable signal. If Run Enable is used the drive does not go to Ready state until the Run Enable goes high.

P2.3.1.8

Quick Stop (Power Down)

ID1213

Drive is stopped and MCB is opened immediately and DC needs to go zero to make restart. Power Down command with a warning indication (Recorded to fault history).

P2.3.1.9 Ext. Fault 1

ID405

P2.3.1.10 Ext. Fault 2

ID406

This parameter defines if the drive monitors the status of the External fault input. The response to the fault can be selected with the parameter P2.7.2.

P2.3.1.11 Fault Reset

ID414

This parameter defines which digital input is used to reset faults.

P2.3.1.12 LC Cooling

ID750

OK input from the cooling unit. Warning indication if unit is not in run state or there is not active run request. Response is fault within 3 second if unit is in run state or there is an active run request.

P2.3.1.13 MCB Trip State

ID1706

Input signal for Main Circuit Breaker trip state. Gives F64 with and subcode.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 45

.6.3.1.1 Forced control place
Digital inputs can be used to bypass parameter P3.1 Control Place, for example, in an emergency situation when PLC is not able to send command to the drive.

P Control Place

DI KP Control

DI FB Control C FB Control

SEL G IN 0 IN 1

C KP Control

PC PC Control

DI IO Control
SEL G IN 0 IN 1
C IO Control

SEL G IN 0 IN 1
C PC COntrol

SEL G IN 0 IN 1

Final Control Place

Figure 6-1. Control place selection priority order

P2.3.1.14 Control from I/O terminal

ID409 “I/O Term Control”

Contact closed: Force control place to I/O terminal

P2.3.1.15 Control from keypad

ID410 “Keypad Control”

Contact closed: Force control place to keypad

P2.3.1.16 Control from Fieldbus

ID411 “Fieldbus Control”

Contact closed: Force control place to fieldbus

NOTE: When the control place is forced to change the values of Start/Stop, Direction and Reference valid in the respective control place are used. The value of parameter ID125 (Keypad Control Place) does not change. When the input opens the control place is selected according to keypad control parameter P3.1 Control Place

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

46 · VACON®

arfiff05 Standard AFE-II

6.3.2 Analogue Inputs

2.3.2.1 2.3.2.1

AI1 signal selection ID377 “AI1 Signal Sel”
AI2 signal selection ID388 “AI2 Signal Sel”
Connect the AI1/AI2 signal to the analogue input of your choice with this parameter. When analogue input selection parameter is set to 0.1 you can control analogue input monitoring variable from Fieldbus by assign process data input ID number to monitoring signal thus allowing making of scaling function in drive side to PLC input signals.

2.3.2.2 2.3.2.2

Analogue input 1 signal filtering time ID324 “AI1 Filter Time” Analogue input 2 signal filtering time ID329 “AI2 Filter Time” First order filtering is used for analogue inputs signals 3 and 4.

12000 10000
8000 6000 4000 2000
0

Unfiltered 1 s filter time 63 %

-0,045 0,545 1,135 1,725 2,315 2,905 3,495 4,085 4,675 5,265 5,855 6,445

2.3.2.3 2.3.2.4
2.3.3.3 2.3.3.4

AI1 custom setting minimum ID321 “AI1 Custom Min” AI1 custom setting maximum ID322 “AI1 Custom Max”
AI2 custom setting minimum ID326 “AI2 Custom Min” AI2 custom setting maximum ID327 “AI2 Custom Max”
Set the custom minimum and maximum input levels for the AI1/AI2 signal within 160…160%.

100 %

AI3/AI4 Output

0 % 0 %

40 % Custom
Min

Analogue Input

80 % Custom
Max

100 %

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 47

2.3.2.5 2.3.3.5

AI1 signal inversion ID387 “AI1 Signal Inv”
AI2 signal inversion ID398 “AI2 Signal Inv”
Signal inversion function is useful in situation when e.g. PLC is sending power limit to the drive by using analogue inputs, if PLC is unable to communicate to the drive power limit would be normally zero, by using inverted signal logic zero value from PLC would mean maximum power limit thus allowing drive running e.g. from keypad without changing power limit function parameters.
0 = No inversion 1 = Signal inverted

AI3/AI4 Output

0 %

40 % Analogue 80 % 100 %

Custom

Input Custom

Min

Max

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

48 · VACON®

arfiff05 Standard AFE-II

.6.3.2.1 Analogue input to any parameter
This function allows control of any parameter by using analogue input. with parameters it is selected what will be range of control area and ID number for paramter that is controller

2.3.2.6 2.3.2.7 2.3.3.6 2.3.3.7

Analogue input 1, minimum value Analogue input 1, maximum value Analogue input 2, minimum value Analogue input 2, maximum value

ID303 “AI1 Scale Min”
ID304 “AI1 Scale Max” ID393 “AI2 Scale Min”
ID394 “AI2 Scale Max”

These parameters are defining range for controlled parameter. All the values are considered to be integers thus when controlling FWP as in example you need to set also numbers for decimals. e.g. FWP 100,00 needs to be set as 10000.

2.3.2.8 2.3.3.8

AI1 Controlled ID

ID1507

“AI1 Control. ID”

AI2 Controlled ID

ID1511

“AI2 Control. ID”

These parameters define what controller parameter is. Example: You want to control motor field weakening point voltage by analogue input from 70,00 % to 130,00 %. Set Scale min to 7000 = 70,00 % Set Scale max to 13000 = 130,00 % Set Controlled ID to 603 Voltage at filed weakening point

13000 Scale Max

AI3/AI4 Output = Field weakening point voltage ID603

7000 Scale Min

0 %

40 % Analogue 80 % 100 %

Custom

Input Custom

Min

Max

Now analogue input 3 signal 0 V to 10 V (0 mA to 20 mA) will control field weakening point voltage between 70,00 % – 130,00 %. When setting value, decimals are handled as

integer.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 49

6.3.3 Cabin State DI

P2.3.4.1 Main Fuse

ID1700

P2.3.4.2 Aux Voltage

ID1703

P2.3.4.3 STO Fuse

ID1702

P2.3.4.4 Insulation Fault

ID1704

P2.3.4.5 Earth switch Fault ID1732

P2.3.4.6 Arc Relay

ID1733

P2.3.4.7 High Amb. Temp

ID1734

Ambient temperature monitoring input Low signal will generate waring W88 Ambien Temp.

P2.3.4.8 Leakage

ID1735

P2.3.4.9 Klixon In 1

ID780

Klixon type temperature monitoring input 1. Low signal will generate warning W66 Klixon.

P2.3.4.10 Klixon In 2

ID781

Klixon type temperature monitoring input 2. Low signal will generate fault F66 Klixon.

P2.3.4.11 Input Switch

ID1209

Selects the digital input for the status of input switch. The input switch is normally switch fuse unit or main contactor with which the power is fed to the drive. If the input switch feedback is missing, the drive trips on “F55 Input Switch” fault.

6.3.4 Options

P2.3.5.1 Stat/Stop Logic

ID300

Start Signal 1 ID 403 command 0 = Static 1 = Rising Edge 2 = Pulse

P2.3.5.2

Input Inversion

ID1091

B00 = +1 = Inv. Open MCB (Force) B01 = +2 = Inv. External Fault 1 B02 = +4 = Inv. External Fault 2 B03 = +8 = Inv. Enable MCB Close B04 = +16 = Inv. MCB Trip input. B05 = +32 = Inv. High Amb Temp. B06 = +64 = B07 = +128 = Inv. Input Switch B08 = +256 = Inv. Klixon Input 1 B09 = +512 = Inv. Klixon Input 2

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

50 · VACON®

arfiff05 Standard AFE-II

6.4 Output signals 6.4.1 Digital outputs

P2.4.1.1

MCB Close Control

ID1218

“MCB CloseControl”

AFE MCB control, fixed to the relay output B.2. When P2.4.1.2 is not activated, this output will stay high as long as MCB must be closed. When the signal goes low, MCB must be open.

P2.4.1.2

MCB 1 Open Control

ID1219

“MCB OpenControl”

When this output is selected above 0.9, the drive will use pulse control for the MCB breaker. P2.5.1.1 is used to close the breaker with a 2 s pulse.

The opening command is given by with a 2 s pulse.

P2.4.1.3 Ready

ID432

The AC drive is ready to operate.

P2.4.1.4 Run

ID433

The AC drive operates (the drive is modulating).

P2.4.1.5 Fault

ID434

Drive is in fault state

P2.4.1.6 Fault, Inverted No active faults.

ID435

P2.4.1.7 Warning

ID436

Warning is active.

P2.4.1.8 DC Above Limit

ID451

DC Voltage is above P2.5.5.1 DC Supervision limit.

P2.4.1.9

DC Charge

ID1668

This output function is used to charge DC. When run enable is HIGH and there are no active faults, the rising edge on the start command will start the DC charging and if charging is successful, the drive will go to Run State. In fieldbus control, charging is started by FB Control Word B0. If MCB feedback is not received within P:Max Charge Time, fault F80 is generated.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 51

P2.4.1.10 Ready To Start Drive is ready for charge and start command. No active fault or warnings.
P2.4.1.11 FB Dig Input 1 455 P2.4.1.13 FB Dig Input 2 456 P2.4.1.15 FB Dig Input 3 457 P2.4.1.17 FB Dig Input 4 169 P2.4.1.19 FB Dig Input 5 170
The data from the fieldbus main control word can be led to the digital outputs of the drive. See the fieldbus board manual for the location of these bits.

P2.4.1.12 FB Dig 1 Input Par 891
P2.4.1.14 FB Dig 2 Input Par 892
P2.4.1.16 FB Dig 3 Input Par 893
P2.4.1.18 FB Dig 4 Input Par 894
P2.4.1.20 FB Dig 5 Input Par 895
With these parameters you can define the parameter to be controlled by using FB digital input. Example: All option board inputs are already in use, but you want to give a DI: External Fault 1 (ID405) and drive has a fieldbus board.
Set parameter ID892 (Fieldbus Digital Input 2) to 405. Now you are able to control External Fault 1 command from the fieldbus by Profibus control word (bit 11).
It is possible to control any parameter in the same way if values 0 = FALSE and 1 = TRUE are significant for that parameter. For example, P2.1.5 Parallel AFE (ID1501) can be switched on and off using this function (Parallel AFE: 0 = No, 1 = Yes).

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

52 · VACON®

arfiff05 Standard AFE-II

6.4.2 Analogue outputs P2.4.2.1 Iout 1 signal ID464
Connect the AO signal to the analogue output of your choice with this parameter.

P2.4.2.2 Iout Content 0 = Not used

ID307

P2.4.2.3

Iout Filter Time ID308
Defines the filtering time of the analogue output signal. Setting this parameter value 0 will deactivate the filtering. First order filtering is used for the analogue output signals.

12000 10000
8000 6000 4000 2000
0

Unfiltered 1 s filter time 63 %

-0,045 0,545 1,135 1,725 2,315 2,905 3,495 4,085 4,675 5,265 5,855 6,445

P2.4.2.4

Iout Invert

ID309

Inverts the analogue output signal:

· Maximum output signal = Minimum set value.

· Minimum output signal = Maximum set value.

100 %

Analogue Output

0 % 0 %

Function Signal

100 %

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

P2.4.2.5

Iout Minimum ID310 0 = Set minimum value to 0 mA (0%)
1 = Set minimum value to 4 mA (20%)

100 %

VACON® · 53

Analogue Output

P2.4.2.6

20 %

0 % 0 %

Function Signal

Iout Scale

ID311

A scaling factor for an analogue output.

Inverted
100 %

100 % Analogue
Output 50 %
20 % 0 %
0 %

Scaling 200 %

Scaling 50 %

50 %

Function 100 % Signal

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

54 · VACON®

arfiff05 Standard AFE-II

P2.4.2.7 Iout Offset

ID375

Add ­100.0 to 100.0% to the analogue output.

100 % Analogue
Output 50 %
20 % 0 %
0 %

Scaling 200 %

Scaling 50 %

50 %

Function 100 % Signal

6.4.3 Options outputs

P2.4.3.1

Output Inversion

ID1806

With this parameter it is possible to select which output signals are inverted.

B01 = +2 = Invert Common Warning

P2.4.3.2

MCB Close Mode
This parameter defines how the closing of circuit breaker is handled.
0 = DC Voltage
Normal AFE operation type circuit breaker control. The circuit breaker is closed when DC voltage is at a required level.
1 = DC Voltage or Start Command
The circuit breaker is closed when DC voltage is at the required level, or from a start command if DC is at a required level. This can be used when the breaker is opened, for example, by a stop command but DC remains high. It is useful when used in a battery system.
2 = Start Command
The circuit breaker is closed from a start command if DC is at a required level.

P2.4.3.3

MCB At Stop Command

ID 1685

The parameter defines the action for MCB when a stop command has been given.

0 = Keep closed

1 = Open CB when drive has stopped

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 55

6.5 Limit Settings 6.5.1 Current limits

P2.5.1.1

Current Limit

[A]

ID107

Sets the current limit for the regenerative supply unit. Set this to correspond to the maximum required load or peak overload for the unit, bearing in mind that the load might consist of several motor drive units.

Maximum value 2 * IH depends on the unit size.

P2.5.1.2

Output Active Current Limit [%] ID1290

“OutputActCurLim”

This parameter sets the active current limit for the generator side operation of the regenerative unit. 100.0% is equal to nominal current. Generator Side operations is when power flows from DC side to AC side. Setting too low value may lead to over voltage fault even on situation when power is not mend to regenerate to grid side.

P2.5.1.3

Input Active Current Limit [%] ID1289

“InputActCurrLim”

This parameter sets the active current limit for the motor side operation of the regenerative unit. 100.0% is equal to nominal current. Motoring Side operations is when power flows from AC side to DC side.

6.5.2 Power Limits

P2.5.2.1 Output Power Limit

ID1288

This parameter sets the power limit for the generator side operation of the regenerative unit. 100.0% is equal to nominal current at nominal voltage. Generator Side operations is when power flows from DC side to AC side. Setting too low value may lead to over voltage fault even on situation when power is not mend to regenerate to grid side.

P2.5.2.2

Input Power Limit

ID1287

This parameter sets the power limit for the motor side operation of the regenerative unit. 100.0% is equal to nominal current at nominal voltage. Motoring Side operations is when power flows from AC side to DC side.

6.5.3 Frequency limits
P2.5.3.1 Line Low Frequency Trip Limit
If the drive output frequency goes below this level, the drive will trip to a line synch fault (F10). Use this limit as a final protection function for the grid or generator. .

P2.5.3.2

Line High Frequency Trip Limit
If the drive output frequency goes above this level, the drive will trip to a line synch fault (F10). Use this limit as a final protection function for the grid or generator.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

56 · VACON®

arfiff05 Standard AFE-II

6.5.4 AC Voltage limits
P2.5.4.1 Low AC Voltage Trip Limit ID1711
Trip limit for low supply voltage (F92). Note that this is AFE unit terminal voltage; voltage losses in LCL may affect actual drive terminal voltage compared to grid voltage.

P2.5.4.2

High AC Voltage Trip Limit ID1710
Trip limit for high supply voltage (F92). Note that this is AFE unit terminal voltage; voltage losses in LCL may affect actual drive terminal voltage compared to grid voltage.

6.5.5 DC Voltage limit parameters

P2.5.5.1

DC Voltage supervision limit

ID1454

This parameter sets a supervision limit for the DC link voltage. If the voltage increases above this, this signal goes HIGH. This signal can be connected to digital output and it is copied to Main Status Word, Bit 10. This value does not limit the DC-link voltage but it can be used for monitoring purposes.

P2.5.5.2

High MCB Close Limit

ID1251

This parameter can be used to increase normal MCB closing level. Example case of use is when there is high capacitance in DC-Link and closing the MCB at normal level will cause current spike.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 57

6.6 Drive control

P2.6.1 P2.6.2

AFE Options 1

ID1463

This packed bit word is made for enabling/disabling different control options for regeneration control:

B0 = Disable DCV reduction with reactive reference generation with high line voltage.

B1 = Disable LCL reactive power compensation.

B5 = Disable all harmonic elimination compensation This is active by default. When activated, this function will reduce little 5th and 7th
harmonics. This will not reduce harmonics of the grid, only own harmonics.

B8 = Enable longer synchronization pulse This option will make longer synchronization pulse to help synchronization on weak grid.

B9 = Enable soft synchronization (>= FI9) This function enables hardware frequency detection on FI9 and bigger units. When active and there is connection to grid, Supply Frequency is updated by detected frequency. Recommended to disable when Battery or Photovoltaics system.

B12 = Enable floating DC reference. DC-link voltage will follow line voltage. DC Voltage is increased when supply voltage is higher than set Grid Nominal Voltage. While run state drive can detect the Supply Voltage, if supply voltage changes also internal DC Reference is changed so that DC Voltage is:
= ( , ) 1,35

B13 = Enable use of D7 board for start synchronization. When OPT-D7 board is installed this bit will activate synchronization by using voltage angle and frequency information from D7 board. Note that phase order needs to be same in both OPT-D7 and input phases. It is also recommended to keep frequency on positive side. Note that Frequency of D7 board can be same as a Supply Frequency but phase order can be still wrong,

AFE Options 2
This packed bit word is made for enabling/disabling different control options for the regeneration control.

B00 = Reserved

P2.6.3

Control Options

ID1798

B00 = +1 = Enable MCB Close (DI and FB), will also open MCB, without need of discharge DC link.
B10 = +1024 = Disable internal F80 DC Charge fault operation.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

58 · VACON®

arfiff05 Standard AFE-II

P2.6.4

Start Delay

ID1500

This parameter defines a starting delay when run command is given. When programming different delay to paralleled units, the units will start in sequence. This is needed in parallel units so that synchronization does not happen simultaneously with all drives. Simultaneous starting may lead to failed synchronization. Recommended to set value so that AFE units following start attempts do not happen at the same time with the other units.

Run AFE 4
Stop
Run AFE 3
Stop
Run AFE 2
Stop
Run AFE 1
Stop

Time * 100 ms

P2.6.5

Modulator type

ID1516

This Parameter is for changing the modulator type. With ASIC (HW) modulator the current distortion is lower, but losses are higher compared to software modulator. It is recommended to use Software modulator.

0 = Hardware modulator: ASIC modulator, which is classical third harmonic injection. Spectrum is slightly better compared to Software 1 modulator.

1 = Software modulator 1: Symmetric vector modulator with symmetrical zero vectors. Current distortion is less than with software modulator 2 if boosting is used.

2 = Software modulator 2: Symmetric BusClamb, in which one switch always conducts 60 degrees either to negative or positive DC-rail. Switching losses are reduced without different heating of upper and lower switches. Spectrum is narrow. Not recommended for parallel units.

3 = Software modulator 3: Unsymmetric BusClamb, in which one switch always conducts 120 degrees to negative DC-rail to reduce switching losses. Drawback is that upper and lower switches are unevenly loaded and spectrum is wide. Not recommended for parallel units.

4 = Software modulator 4: Pure sine wave, sinusoidal modulator without harmonic injection. Dedicated to be used in back to back test benches etc. to avoid circulating third harmonic current. Drawback is that required DC voltage is 15% higher compared to other modulator types.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 59

P2.6.6

Operation Time

ID1855

Stored Operation Time. When application is reloaded operation hours will go zero if this parameter is not updated. Monitoring signal is in hours with two decimal. Parameter is in format of:

xx (Years) XX (Monts) XX (Days) XX (Hours) XX Minutes

1211292359 -> 12 years, 11 months, 29 days, 23 hours and 59 minutes.

6.6.1 Control

P2.6.7.1

Capacitor Size [%] (ID1460)
This parameter defines the reactive current going to the LCL filter capacitor. It compensates the LCL effect to the reactive current by adjusting the reactive current reference internally. The inductor size is also added to compensation. If set correctly, the power factor on the grid side will be 1.

P2.6.7.1

Inductor Size [%] (ID1461)
This parameter defines voltage losses in percentage of the nominal voltage at 100% active current. This value is internally added to the reactive current reference thus giving power factor 1 on the grid side, if set correctly together with Capacitor Size. The transformer and feeding cables can be compensated by increasing this value.

P2.6.7.3

Dynamic Support Kp #,# [%/%] ID1797
This function supports weak grid by generating or consuming reactive current in grid under- and over-voltage situations. Reactive current is generated/consumed with gradient by set parameter value by every 1 % decrease/ increase in grid voltage to stabilize voltage in the point of coupling.

P2.6.7.4

Synch Kp

ID1457

This parameter sets the gain of the synchronisation controller used to synchronise the switching to the supply.

P2.6.7.5

Synch Ti

ID1458

This parameter sets the time constant of the controller used to synchronise the switching to the supply (15 equals 7ms).

P2.6.7.6

Active Current Kp

ID1455

This parameter sets the gain of the controller for the active current of the regenerative unit.

P2.6.7.7

Active Currnt Ti

ID1456

This parameter sets the time constant of the controller for the active current of the regenerative unit (15 equals 1.5ms).

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

60 · VACON®

arfiff05 Standard AFE-II

P2.6.7.8 Synch. Kp Start

ID1300

P2.6.7.9 Voltage Control Kp ID1451 This parameter sets the gain for the DC link PI voltage controller.

P2.6.7.10 Voltage Control Ti ID1452 This parameter sets the time constant in ms of the DC link PI controller.

P2.6.7.11 Switching frequency ID601
The switching frequency of the IGBT bridge in kHz. Changing the default value may impact on the LCL filter operation.

P2.6.7.12 DCLinkMeasCalib

ID549

To increase the DC-voltage accuracy you may use ID549 to adjust the DC-link voltage measurement shown by the converter. This parameter will add a small gain offset to the measured DC-link voltage value. This feature helps to balance the load sharing for parallel converters.

P2.6.7.13 Modulator #2 DPWM Optimization ID1682
This function enables use of Grid Converter Modulator used with parallel Grid Converters. Active only when Software Modulator #2 is used. Operation is same as software modulator 2 when mindex > 75 % and same as software modulator 1 when mindez < 25 %.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 61

6.7 Protections

6.7.1 General

P2.7.1.1 Response to thermistor fault

ID732

0 = No response 1 = Warning 2 = Fault (the drive will stop modulation leaving MCB closed) 3 = Fault, DC off (MCB open)

Setting the parameter to 0 will deactivate the protection.

P2.7.1.2

Response to Input Filter over temperature ID1505
This parameter defines a response to LCL over temperature fault. LCL fault is monitored through digital input defined in parameter P2.2.1.3.

0 = No response 1 = Warning 2 = Fault (the drive will stop modulation leaving MCB closed) 3 = Fault, DC off (MCB open)

P2.7.1.4 MCB on Fault

ID1510

This parameter defines response to ANY fault what occurs in the AFE.

0 = MCB is kept closed in case of fault – Faults that have been defined to open MCB are still active.
1 = Any fault in the drive will open the MCB. – Auto reset of MCC fault will be disabled with this selection.

P2.7.1.5

Charge Max Time

ID1522

When drive charging options is used this parameter defines maximum time limit for charging. Use suitably sized DC Charging resistor by checking Pulse loadability for time duration set in for Max Charge Time parameter

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

62 · VACON®

arfiff05 Standard AFE-II

P2.7.1.6

FaultWarnIndicat

ID1940

With this parameter its possible to select how warning and fault indication as handled to digital outputs and to fieldbus 0 = Static

Static signal, as long as warning or fault is active

1 = Toggle New fault or warning toggles signal for one second.

2 = Marine
Signal toggles in new fault or warning and status needs to be reset to get signal down.

P2.7.1.6

Quick Stop Response

ID1758

This function will stop the drive at any case. This parameter is used to select which action is shown on keypad. 0 = No response 1 = Warning 2 = Fault

P2.7.1.7

Run Enable Indication

ID1177

Select the response for Run Enable low signal, drive will lose ready status regardless what response has been selected here.

0 = No Action

1 = Warning

2 = Fault

6.7.2 Temperature sensor protections
The temperature protection function is used to measure temperatures and issue warnings and/or faults when the set limits are exceeded. The AFEII application supports two OPT-BH and OPT-B8 board simultaneously.

P2.7.2.1

Number of used inputs in board 1

ID739 “Board1 Channels”

Select used temperature sensor combination with this parameter. See also the Vacon I/O boards manual.

0 = Not used (ID Write, value of maximum temperature can be written from fieldbus) 1 = Sensor 1 in use 2 = Sensor 1 & 2 in use 3 = Sensor 1 & 2 & 3 in use 4 = Sensor 2 & 3 in use 5 = Sensor 3 in use

Note: If the selected value is greater than the actual number of used sensor inputs, the display will read 200ºC. If the input is short-circuited the displayed value is ­30ºC.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 63

P2.7.2.2

Board 1 Temperature response

ID740 “Board1 Response”

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to Stop Function 3 = Fault, stop mode after fault always by coasting

P2.7.2.3

Board 1 warning limit ID741 “Board1Warn.Limit”
Set here the limit at which the PT100 warning will be activated. When individual warning and fault limits are activated this is first board first channel (1A).

P2.7.2.4

Board 1 fault limit

ID742 “Board1 Fault Lim.”

Set here the limit at which the PT100 fault (F56) will be activated. When individual warning and fault limits are activated this is first board first channel (1A).

P2.7.2.5

Number of used inputs in board 2 ID743 “Board2 Channels”
If you have two temperature sensor boards installed in your frequency converter you can choose here the combination inputs in use in the second board. See also the Vacon I/O boards manual.

0 = Not used (ID Write, value of maximum temperature can be written from fieldbus) 1 = Sensor 1 in use 2 = Sensor 1 & 2 in use 3 = Sensor 1 & 2 & 3 in use 4 = Sensor 2 & 3 in use 5 = Sensor 3 in use

P2.7.2.6

Board 2 Temperature response

ID766 “Board2 Response”

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to Stop Function 3 = Fault, stop mode after fault always by coasting

P2.7.2.7

Board 2 warning limit ID745 “Board2 Warn. Lim”
Set here the limit at which the second temperature sensor board warning will be activated. When individual warning and fault limits are activated this is second board first channel (2A).

P2.7.2.8

Board2 fault limit

ID746 “Board2 FaultLim”

Set here the limit at which the second temperature sensor board fault (F61) will be activated. When individual warning and fault limits are activated this is second board first channel (2A).

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

64 · VACON®

arfiff05 Standard AFE-II

.6.7.2.1 Individual channel monitoring Individual channel monitoring is activated by setting one of the warning limits (per board) different than zero. Common limits in above parameters will be channel A warning and fault limits. Channel B and C limits are set with below parameters.
P2.7.2.9.1 Channel 1B Warn ID764 P2.7.2.9.2 Channel 1B Fault ID765
First board second (1B) channel warning and fault limits.
P2.7.2.9.3 Channel 1C Warn ID768 P2.7.2.9.4 Channel 1C Fault ID769
First board third (1C) channel warning and fault limits.
P2.7.2.9.5 Channel 2B Warn ID770 P2.7.2.9.6 Channel 2B Fault ID771
Second board second (2B) channel warning and fault limits.

P2.7.2.9.7 Channel 2C Warn ID772 P2.7.2.9.8 Channel 2C Fault ID773
Second board third (2C) channel warning and fault limits.

6.7.3 Fieldbus

2.7.3.1 Fieldbus Fault Slot D Response

ID733

Set the response for a fieldbus fault if the active control place is fieldbus. For more information, see the relevant Fieldbus Board Manual.

0 = No response 1 = Warning 2 = Fault, stop mode after fault according to Stop Function

2.7.3.2

FB WD Time
Delay time to a fieldbus fault when the pulse from PLC is missing. Setting the time to zero will disable the monitoring function.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 65

6.7.4 OPT-D7 Protections

2.7.4.1 THD Response

ID1672

2.7.4.2 THD Warn. Limit

ID1673

2.7.4.3 THD Fault Limit

ID1674

2.7.4.4 HF rms Response

ID1675

2.7.4.5 HF rms Warn Limit ID1676

2.7.4.6 HF rms Fault Limit ID1677

6.7.5 External Fault

P2.7.5.1 Response to external fault 1

ID701

P2.7.5.2 Response to external fault 2

ID1504

This parameter defines a response to external fault 1 and 2t. If the drive monitors the state of external fault input (ID405 and ID406) and a fault occurs the drive can be set to respond to the fault.

0 = No response 1 = Warning 2 = Fault (the drive will stop modulation leaving MCB closed)

6.7.6 Cooling protection
Protection for liquid cooled units. An external sensor is connected to the drive (DI: Cooling Monitor) to indicate if cooling liquid is circulating.
P2.10.7.1 Cooling fault delay ID751 “Cooling F Delay” This parameter defines the delay after which the drive goes to fault state when `Cooling OK’ signal is missing.
P2.10.7.2 Cooling fault response ID762 “CoolingFaultREsp” In some cases it is more important to allow the drive to run even if the cooling liquid is not circulating. Then it is possible to select warning as the response. The drive will then continue running until its internal protection will stop it. If cooling signal loss happens on stop state indication is not stored to fault history if previous fault is already Cooling Fault. In Run State indication is always stored to fault history
0 = Stop State: No Action, Run State: Warning 1= Stop State: Warning, Run State: Warning 2= Stop State: Warning, Run State: Fault 3= Stop State: No Action, Run State: Fault

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

66 · VACON®

arfiff05 Standard AFE-II

6.7.7 Cabin Protection

P2.7.7.1

Klixon Response

ID782

Select the response for klaxon inputs.

0 = No Action

1 = Warning, Warning

Both klixon inputs give a warning

2 = Warning, Fault

Klixon input 1 will generate warning and klixon input 2 will generate fault

3 = Fault, Fault

Both klixon inputs give a fault

P2.7.7.2 Ambient Temp Response ID784 Select the response for ambient temperature digital input.

P2.7.7.3 Input Switch Response ID785 Select the response for input switch digital input.

6.7.8 Options

2.7.6

Fault Simulation

ID1569

“Fault Simulation”

With this parameter it is possible to simulate different faults without actually making, for example, an over current situation. In the point of view of the drive interface, the operation is identical to actual fault situation.

B00 = +1 = Simulates an over current fault (F1) B01 = +2 = Simulates an over voltage fault (F2) B02 = +4 = Simulates an under voltage fault (F9) B03 = +8 = Simulates an output phase supervision fault (F11) B04 = +16 = Simulates an earth fault (F3) B05 = +32 = Simulates a system fault (F8)
This fault simulation covers a wide range of different faults in drive. See the fault description for details. B06 = +64 = Free B07 = +128 = Simulates an over temperature warning (W14) B08 = +256 = Simulates an over temperature fault (F14) The warning bit must be active for a fault to appear in simulation. If the fault bit is left active, the drive will go FAULT state at warning limit when the drive temperature rises to the warning level. B09 = +512 = Reserved

2.7.7

Reset Datalogger

ID1857

This parameter reset datalogger setting back to factory defaults.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 67

6.8 Fieldbus parameters
FBSpeedReference is used as DC Voltage Reference when control place is Fieldbus. If FBSpeedRefernce is below 50,00 % keypad DC Voltage Reference is used. But is always limited to 105 %.

2.8.1

FB Actual Value Sel Select ID for monitoring signal that will be located in FBSpeedActual.

2.8.2 2.8.9

Fieldbus data out 1-8 selection

ID1490-ID1497

Using these parameters, you can monitor any monitoring or parameter value from the fieldbus. Enter the ID number of the item you wish to monitor for the value of these parameters.

2.8.10 2.8.17

Fieldbus data in 1-8 selection

ID876-ID883

Using these parameters, you can control any parameter from the fieldbus. Enter the ID number of the item you wish to control for the value of these parameters.

2.8.18

GSW ID ID897 With this parameter it is possible to select which data is sent in FBGeneralStatusWord.

2.8.19

State Machine
The application provides a possibility to select what kind of state machine is used. See details from chapter Status and Control Words in detail.

0: Basic This mode makes fieldbus control behave as is explained in the fieldbus board manual.

1: Standard A simple control word that is used in modes where the control word from fieldbus is used as such. For some fieldbus boards this requires a bypass operation.

2: Vacon AFE 1 This mode uses a ProfiDrive type state machine in the application level. You can use this mode on fieldbus boards that do not have a state machine or have a possibility to bypass the state machine function in the option board.

3: Vacon AFE 2 This mode uses a ProfiDrive type state machine in the application level. You can use this mode on fieldbus boards that do not have a state machine or have a possibility to bypass the state machine function in the option board. More extensive control than Vacon AFE 1 state machine selection.

P2.8.20

Control Slot selector ID1440

“ControlSlotSel.”

This parameter defines which slot is used as the main control place when two fieldbus boards have been installed in the drive

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

68 · VACON®

arfiff05 Standard AFE-II

6.9 ID Functions Here you will find the functions that use the parameter ID number to control and monitor the signal.

6.9.1 Value Control The value control parameters are used to control an input signal parameter.

P2.9.1.1 P2.9.1.2 P2.9.1.3 P2.9.1.4 P2.9.1.5 P2.9.1.6 P2.9.1.7

Control Input Signal ID ID1580

“ContrInSignal ID”

With this parameter you can select which signal is used to control the selected

parameter.

Control Off Limit

ID1581

“Contrl Off Limit”

This parameter defines the limit when the selected parameter value is forced to Off

value.

Control On Limit

ID1582

“Contrl On Limit”

This parameter defines the limit when the selected parameter value is forced to On

value.

Control Off Value

ID1583

“Contrl Off Value”

This parameter defines the value that is used when the used input signal is below Off

limit.

Control On Value

ID1584

“Contrl On Value”

This parameter defines the value that is used when the used input signal is above On

limit.

Control Output Signal ID

ID1585

“ContrlOutSignID”

This parameter defines which parameter is forced to On and Off values when selected

input signal exceeds the set limits.

Control Mode ID1586

“Control Mode”

This parameter defines how the value control output behaves. 0 = SR ABS
Absolute input value is used to make a step change in the output between On and Off values.

Control On
Value

Control Off
value

On Negative value

Off value

Off Positive value

On value

Figure 1.
1 = Scale ABS Absolute input value is scaled linearly between On and Off values.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 69

Control On
Value

Control Off
value

On Negative value

Off value

Off value

Positive

On value

Figure 2.

2 = Scale ABS Inverted Inverted absolute value is scaled linearly between On and Off values.

Control On
Value

Control Off
value

On Negative value

Off value

Off value

Positive

On value

Figure 3.

3 = SR Input value is used to make a step change in the output between On and Off values.
4 = Scale ABS Input values is scaled linearly between On and Off values.
5 = Scale Inverted Inverted value is scaled linearly between On and Off values

P2.9.1.8

Control Signal Filtering TC ID1721

“Control Filt TC”

This parameter is used to filter the scaling function output. This can be used, for example, when unfiltered torque is used to control a parameter that needs stabilisation.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

70 · VACON®

arfiff05 Standard AFE-II

6.9.2 DIN ID Control
This function is used to control any parameter between two different values with a digital input. Different values are given for DI LOW and DI HIGH.

DI ID Control Digital Input P Value for LOW P Value for High

SEL
G IN 0 IN 1

P DIN Controlled ID

Figure 4.

P2.9.2.1 P2.9.3.1 P2.9.4.1

ID Control Digital Input ID1570

“ID Control DIN”

ID Control Digital Input ID1590

“ID Control DIN”

ID Control Digital Input ID1578

“ID Control DIN”

Select a digital input to be used for controlling the parameter selected by ID1571.

P2.9.2.2 P2.9.3.2 P2.9.4.2

DIN Controlled ID

ID1571

“Controlled ID”

DIN Controlled ID

ID1575

“Controlled ID”

DIN Controlled ID

ID15719

“Controlled ID”

Select a parameter ID controlled by ID1570.

P2.9.2.3 P2.9.3.3 P2.9.4.3

Value for Low digital input (FALSE) ID1572

“FALSE Value”

Value for Low digital input (FALSE) ID1592

“FALSE Value”

Value for Low digital input (FALSE) ID15794

“FALSE Value”

Set the controlled parameter value when the digital input (ID1570) is LOW for the parameter selected by ID1571. The function does not recognise decimals. For example, give the value 10.00 Hz as 1000.

P2.9.2.4 P2.9.3.4 P2.9.4.4

Value for High digital input (TRUE) ID1573

“TRUE Value”

Value for High digital input (TRUE) ID1593

“TRUE Value”

Value for High digital input (TRUE) ID1596

“TRUE Value”

Set the controlled parameter value when the digital input (ID1570) is HIGH for the parameter selected by ID1571. The function does not recognise decimals. For example, give the value 10.00 Hz as 1000.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 71

6.10 Keypad control

3.1

Control place

ID125

The active control place can be changed with this parameter.

NOTE! Keypad is the default control place.

0 = PC Control, Activated by NCDrive 1 = I/O terminal 2 = Keypad 3 = Fieldbus (4 = SystemBus)

On keypad control pressing Stop button more than a 2 second will open the MCB.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

72 · VACON®

arfiff05 Standard AFE-II

7. STATUS AND CONTROL WORDS IN DETAIL

P2.10.19 machine 0 / Basic 1 / Standard
2 / Vacon AFE 1
3 / Vacon AFE 2

State

This mode makes fieldbus control behave as in explained in used fieldbus board manual. Simple control word that is used in modes where control word from fieldbus is used as such, for some fieldbus board this requires bypass operation. This mode uses ProfiDrive type state machine in application level. This mode is possible to use on fieldbus boards that does not have state machine itself or has possibility to bypass state machine functionality in option board. This mode uses ProfiDrive type state machine in application level. This mode is possible to use on fieldbus boards that does not have state machine itself or has possibility to bypass state machine functionality in option board.

8.1 Basic In ByPass (0)

Signal

FB Control Word ID1160 Description

B00

Run

0= AFE is stopped 1= AFE is started

B01

B02

Fault Reset 0>1 Reset fault.

B03

FB DIN1 Can be used to control RO or directly parameter by ID number. G2.4.1

B04

FB DIN2 Can be used to control RO or directly parameter by ID number. G2.4.1

B05

FB DIN3 Can be used to control RO or directly parameter by ID number. G2.4.1

B06

FB DIN4 Can be used to control RO or directly parameter by ID number. G2.4.1

B07

FB DIN5 Can be used to control RO or directly parameter by ID number. G2.4.1

B08

B09

B10

B11

B12

B13 B14 B15

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 73

8.2 FB Control Word

8.2.1 Standard (1)

FB Control Word ID1160

Signal

Comment

B00

DC Charge

0= Open MCB. 1= Close DC charge. MCB closed automatically.

B01

B02

B03

Run

0= AFE is stopped 1= AFE is started

B04

B05

B06

B07

Reset

0>1 Reset fault.

B08

B09

B10

B11

FB DIN1 Can be used to control RO or directly parameter by ID number. G2.4.1

B12

FB DIN2 Can be used to control RO or directly parameter by ID number. G2.4.1

B13

FB DIN3 Can be used to control RO or directly parameter by ID number. G2.4.1

B14

FB DIN4 Can be used to control RO or directly parameter by ID number. G2.4.1

B15

B00: FALSE = Open MCB, TRUE = PreCharge DC Open MCB: Opens MCB if closed, stops precharging if not closed. PreCharge DC: Drive will start precharge if function activated by digital output and control place is fieldbus. When control place is not fieldbus precharging is started from normal start command.
B03: FALSE = Stop Request, TRUE = Start Request Stop Request: Drive will stop . Start Request: Start Command to the drive. Rising edge needed for start.
B07: FALSE = No significance, TRUE = Fault Acknowledge
Fault Acknowledge: The group signal is acknowledged with a positive edge.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

74 · VACON®

arfiff05 Standard AFE-II

8.2.2 Vacon AFE 1 profile (2)

FB Control Word ID1160

Signal

Comment

B00

DC Charge

0= Open MCB. 1= Close DC charge contactor, MCB closed automatically.

B01

B02

B03

Run

0= AFE is stopped 1= AFE is started

B04

B05

B06

B07

Reset

0>1 Reset fault.

B00 | B01 B08 DC Voltage Ref B00 0 | 0 = FB Reference. P2.2.1, if not FB Control & FB Ref > 50,00 %

0 | 1 = 110 %

B09 DC Voltage Ref B01 1 | 0 = 115 % 1 | 1 = 120 %

B10

Fieldbus Control

0= No control from fieldbus 1=Control from fieldbus

B11

Watchdog

0>1>0>1…0,5 sec square wave clock. This is used to check data communication between fieldbus master and the drive.

B12

FB DIN2

Can be used to control RO or directly parameter by ID number. G2.4.1

B13

FB DIN3

Can be used to control RO or directly parameter by ID number. G2.4.1

B14

FB DIN4

Can be used to control RO or directly parameter by ID number. G2.4.1

B15

Reserved for future use.

B00: FALSE = Open MCB, TRUE = PreCharge DC Open MCB: Opens MCB if closed, stops precharging if not closed. PreCharge DC: Drive will start precharge if function activated by digital output and control place is fieldbus. When control place is not fieldbus precharging is started from normal start command.
B03: FALSE = Stop Request, TRUE = Start Request Stop Request: Drive will stop . Start Request: Start Command to the drive. Rising edge needed for start.
B07: FALSE = No significance, TRUE = Fault Acknowledge
Fault Acknowledge: The group signal is acknowledged with a positive edge.

B08: FALSE = No Function, TRUE = DC Ref 1 B09: FALSE = No Function, TRUE = DC Ref 2

DC Ref B08 B09

FB Reference FALSE FALSE

110,00 % TRUE FALSE

115,00 % FALSE TRUE

120,00 % TRUE TRUE

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 75

B10: FALSE = FB Control disabled TRUE = FB Control Enabled
FB Control Disabled: Drive will not follow main control word from Fieldbus. If removed while running drive will stop. FB Control Enabled: Drive follows control word from fieldbus
B11: FALSE = FB WD Pulse Low, TRUE = FB WD Pulse High
Watch Dog pulse: This pulse is used to monitor that PLC is alive. If pulse is missing drive will go to fault state. This function is activated by P2.7.6 FB WD Delay. When value is zero pulse si not monitored.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

76 · VACON®

arfiff05 Standard AFE-II

8.2.3 Vacon AFE 2 Profile (3)

FB Control Word ID1160

Signal

Comment

B00

DC Charge

0= Open MCB. 1= Close DC charge contactor, MCB closed automatically, see B01.

0= Disable Closing of MCB (Also opens if Control

B01

MCB Close Enable Options.B0=TRUE)

1= Enable Closing of MCB (Works also for reclosing)

B02

Quick Stop

0= Quick Stop 1= No Quick Stop

B03

Run

0= AFE is stopped 1= AFE is started

B04

Output Power Limit to 0= Output Power Limit to Zero (7%)

Zero

1= Output Power Limit = P2.5.2.1

B05

Disable Power Increase. 0= Disable increase of power.

Input or Output

1= Power limits defined by G2.5.2

B06

Input Power Limit to Zero

0= Input Power Limit to Zero (7%) 1= Output Power Limit = P2.5.2.2

B07

Reset

0>1 Reset fault.

B00 | B01

B08

DC Voltage Ref B00 0 | 0 = FB Reference. P2.2.1, if not FB Control & FB Ref > 50,00 %

0 | 1 = 110 %

1 | 0 = 115 %

B09

DC Voltage Ref B01 1 | 1 = 120 %

B10

Fieldbus Control

0= No control from fieldbus 1=Control from fieldbus

B11

Watchdog

0>1>0>1…0,5 sec square wave clock. This is used to check data communication between fieldbus master and the drive.

B12

FB DIN2

Can be used to control RO or directly parameter by ID number. G2.4.1

B13

FB DIN3

Can be used to control RO or directly parameter by ID number. G2.4.1

B14

FB DIN4

Can be used to control RO or directly parameter by ID number. G2.4.1

B15

Reserved for future use.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 77

B00: FALSE = Open MCB, TRUE = PreCharge DC Open MCB: Opens MCB if closed, stops precharging if charging is active trough the drive. PreCharge DC: Drive will start precharge if function activated by digital output and control place is fieldbus. When control place is not fieldbus precharging is started from normal start command.

B01: MCB Close Enable
FALSE: MCB Closing is disabled in fieldbus control. MCB Remains open when if DC voltage is above closing limit. TRUE: MCB Closing is enabled in fieldbus control. This bit can be true all the time if function is not needed.

B02: Quick Stop
FALSE: Drive will stop modulation immediately and open MCB immediately. TRUE: Quick stop is not active and normal operation is possible.
B03: FALSE = Stop Request, TRUE = Start Request Stop Request: Drive will stop . Start Request: Start Command to the drive. Rising edge needed for start.

B04: Output Power Limit to Zero FALSE: Output power limit is reduced to 7 % if parameter limit is higher. TRUE: Power limit is defined by power limit parameters.
B05: Disable Power Increase. Input or Output FALSE: Power is limited to actual power, power can’t increase when this bit is active, TRUE: Power limit is defined by power limit parameters.

B06: Input Power Limit to Zero FALSE: Input power limit is reduced to 7 % if parameter limit is higher TRUE: Power limit is defined by power limit parameters.

B07: FALSE = No significance, TRUE = Fault Acknowledge Fault Acknowledge: The group signal is acknowledged with a positive edge. B08: FALSE = No Function, TRUE = DC Ref 1 B09: FALSE = No Function, TRUE = DC Ref 2

DC Ref B08 B09

FB Reference FALSE FALSE

110,00 % TRUE FALSE

115,00 % FALSE TRUE

120,00 % TRUE TRUE

B10: FALSE = FB Control disabled TRUE = FB Control Enabled
FB Control Disabled: Drive will not follow main control word from Fieldbus. If removed while running drive will make coasting stop. FB Control Enabled: Drive follows control word from fieldbus

B11: FALSE = FB WD Pulse Low, TRUE = FB WD Pulse High
Watch dog pulse: This pulse is used to monitor that PLC is alive. If pulse is missing drive will go to fault state. This function is activated by P2.7.6 FB WD Delay. When value is zero pulse si not monitored.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

78 · VACON®

arfiff05 Standard AFE-II

8.3 FB Status Word

FB Status Word ID68

Signal

Comment

b0

Ready On

0=Drive not ready to switch on 1=Drive ready to start charging

b1

Ready Run

0=Drive not ready to run 1=Drive ready and MCB is ON

b2

Running

0=Drive not running 1=Drive in Run state (Modulating)

b3

Fault

0=No active fault 1=Fault is active

b4

Run Enable Status

0= Run Disabled. Drive in stop state 1= Run Enabled. Drive can be started.

b5

Quick Stop Active

0=Quick Stop Active 1=Quick Stop not Active

b6

MCB Control OK

0= Status opposite of control 1= Status and control OK

b7

Warning

0= No active warnings 1= Warning active

b8

At Reference

0= DC Voltage Ref and Act DC Voltage are not same.

b9

Fieldbus Control Active

0=Fieldbus control not active 1=Fieldbus control active

b10

Above Limit

0= DC Voltage is below P2.5.5.1 level 1=The DC Voltage is above the P2.5.5.1 level

b11

MCB Control (DO Final)

0= Drive is controlling MCB to be Open. 1= Drive is controlling MCB to be Closed

b12

MCB Feedback

0= Feedback indicates MCB to be Open 1= Feedback indicates MCB to be Closed

b13

Reserved for future use.

b14

DC Charge DO Control

0= DC not charged 1= DC Charging Active

b15

Watchdog

Same as received on bit 11 of the main control word.

B00: FALSE = Not Ready to Switch On, TRUE = Ready to Switch On Not Ready to Switch On: Fault active, DI: Run Enable low, MCB Forced open command active, Quick Stop Active. Ready to Switch On: No Faults, DI: Run Enabled, DI: MCB not forced open, Quick Stop not active.
B01: FALSE = Not Ready To Operate, TRUE = Ready To Operate Not Ready To Operate: CW.B0 = FALSE, DC Not Ready, MCB Control Open, MCB Status Low. Ready To Operate: CW.B0 = TRUE, DC Ready, MCB Control closed, MCB Status High.
B02: FALSE = Drive is not operating, TRUE = Drive is operational Drive is not operating: Drive is not run state (modulating) Drive is operational: Drive is in run state and modulating.

B03: FALSE = No Fault, TRUE = Fault Present No Fault: Drive is not on fault state. Fault Present: Drive is in fault state.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 79

B04: FALSE = Coast Stop Activated, TRUE = Coast Stop Not Activated Coast Stop Activated: DI: Run Enable False, Quick Stop Active, MCB Status Open, MCB Control Open, Enable MCB Close, MCB Forced Open. Coast Stop Not Activated: Running Enabled
B05: FALSE = Quick Stop Activated, TRUE = Quick Stop Not Activated Quick Stop Activated: Quick Stop command is active. Quick Stop Not Activated: Quick stop command is not active.
B06: FALSE = MCB Control OK, TRUE = MCB Control Not OK MCB Control OK: MCB Control and Drive internal status are the same. MCB Control Not OK: Drive internal status to close the MCB is high but application logic request MCB open. This can be case when MCB has been opened but DC is connected to battery system. DC needs to be discharged or MCB is needed to close.
B07: FALSE = No Warning, TRUE = Warning Present No Warning: There is no warning or the warning has disappeared again. Warning Present: Drive still works; warning in the service/maintenance parameter; no acknowledgement.
B08: FALSE = DC Voltage out of tolerance TRUE = DC Voltage within tolerance DC Error Out Of Tolerance Range: DC Error Within Tolerance Range:
B09: FALSE = No Control Requested, TRUE = Control Requested No Control Requested: Control by the automation system is not possible. Control Requested: The automation system is controlling.
B10: FALSE = DC Not Reached, TRUE = DC Reached Or Exceeded DC Not Reached: DC Voltage is below P2.5.5.1 level DC Reached Or Exceeded: DC Voltage is above the P2.5.5.1 level
B11: MCB Control (DO Final) FALSE: Drive is controlling MCB to be Open. TRUE: Drive is controlling MCB to be Closed
B12: MCB Feedback FALSE: Feedback indicates MCB to be Open TRUE: Feedback indicates MCB to be Closed
B14: FALSE = Charge DO Open, TRUE = Charge DO Closed Charge DO Open: Charging Command not active Charge DO Closed: Charging Command Active
B15: FALSE = FB DW Feedback Low, TRUE = FB DW Feedback High FB DW Feedback: FB Control Word B11 is echoed back to the Fieldbus. Can be used to monitor communication status from the drive. 7.11 Fault Word 1

Fault Word 1 ID1172

Bit

Fault(s)

B0

F1 Over current, F31 IGBT, F41 IGBT

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

80 · VACON®

B1

F2 Over Voltage

B2

F9 Under Voltage

B3

F91 Short Circuit

B4

F3 Earth Fault

B5

B6

F14 Unit Over Temperature

F29 Thermistor,

B7

F56 Measured Temperature 1, F65 Measured Temperature 2

F71 LCL Over Temperature

B8

F10 Line Synch fault F11 Supply Phase

B9

B10

Device faults: F37, F38, F39, F40

B11

B12

B13

B14

B15

7.12 Fault Word 2

Fault Word 2 ID1173

Bit

Fault(s)

B0

B1

F5 Charging Fault, F80 Charge Fault

B2

B3

Hardware faults: F7

B4

F13 Under Temperature

B5

F22 EPROM, F49 Zero Division

B6

B7

B8

B9

F31 IGBT, F41 IGBT

B10

B11

F32 Fan Fault, F70 LCL Fan Fault

B12

B13

F8 System, F26 Start Up Prevented, F36 Control Unit

B14

F64 MCB State Fault

B15

arfiff05 Standard AFE-II

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

7.13 Warning Word 1

Warning Word 1 ID1174

Bit

Warning(s)

B0

W29 Thermistor

B1

F56 Measured Temperature 1, F65 Measured Temperature 2

F71 LCL Over Temperature

B2

B3

W11 Supply Phase

B4

B5

B6

B7

B8

W14 Unit Over Temperature

B9

B10

F32 Fan Fault, F70 LCL Fan Fault, F60 Cooling Fault

B11

B12

B13

B14

B15

Table 8. Alarm Word 1

VACON® · 81

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

82 · VACON® 8.4 Auxiliary Control Word

arfiff05 Standard AFE-II

FALSE

TRUE

b0

Reserved for future use.

b1

Reserved for future use.

b2

Reserved for future use.

b3

Reserved for future use.

b4

Reserved for future use.

b5

Reserved for future use.

b6

Reserved for future use.

b7

Reserved for future use.

b8

Reserved for future use.

b9

Reserved for future use.

b10

Reserved for future use.

b11

Reserved for future use.

b12

Reserved for future use.

b13

Reserved for future use.

b14

Reserved for future use.

b15

Reserved for future use.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 83

8.5 Status Word (Application) ID 43 Application Status Word combines different drive statuses to one data word.

Application Status Word ID43

FALSE

TRUE

b0 b1 Not in Ready state b2 Not Running

Ready Running

b3 No Fault

Fault

b4 b5 b6 Run Disabled b7 No Warning

Run Enable Warning

b8

Charging Switch closed (internal)

b9

MCB Control (DO Final)

b10

MCB Feedback

b11

DO Charging Active

b12 No Run Request b13 b14 b15

Run Request

B01: FALSE = Not Ready, TRUE = Ready Not Ready: DC Voltage low, Fault active Ready: Drive in ready state, start command can be given.
B02: FALSE = Not Running, TRUE = Running Not Running: Drive is not modulating Running: Drive is modulating.
B03: FALSE = No Fault, TRUE = Fault Active No Faults: Drive do not have active faults. Fault: Drive has an active faults.
B06: FALSE = Run Enable Low, TRUE = Run Enable High Run Enable Low: Run Enable command to motor control is low Run Enable High: Run Enable command to motor control is high.
B07: FALSE = No Warning, TRUE = Warning Active No Warning: No warning signals active in the drive Warning: Drive has active warning signal. Warning signal not stop the operation.
B08: FALSE = Charging Switch Open, TRUE = Charging Switch closed Charging Switch Open: DC voltage level is nor reached closing level or has drop below the opening level. This information is from drive motor control. Charging switch Closed: DC voltage level is above closing limit and no interlock active internally.

B09: FALSE = MCB Open command, TRUE = MCB closed command MCB Open Command: Final command to open the MCB from application logic.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

84 · VACON®

arfiff05 Standard AFE-II

MCB Close Command: Final close command to MCB from application logic.
B10: FALSE = Main contactor Open, TRUE = Main contactor closed MCB Open: Feedback from MCB, open. MCB Closed: Feedback from MCB, closed.
B11: FALSE = Charge Control Open, TRUE = Charge Control Closed Charge Control Open: Charging Contactor is not controlled. Charge Control Closed: Charging contactor controlled closed.
B12: FALSE = No Run Request, TRUE = Run Request No Run Request: Final Run Request command has not been given to motor control. Run Request: Final Run Request command has been given to motor control.

Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

Arfiff05 Standard AFE-II

VACON® · 85

PROBLEM SOLVING

While proper information is needed form the problem, it’s also recommended to try with latest application- and system software versions available. Software is continuously developed and default settings are improved (See Chapter 1.1 Compatibility issues in parameters between versions).

Figure 5. The recommended signals for NCDrive
Use the fastest communication speed (Baudrate: 57 600) and a 50 ms update interval for signals for the RS232 communication.
For the CAN communication, use a 1 Mbit communication speed and 7 ms update interval for signals.
When you contact the support, send the .trn, .par and Service info (*.txt) files with a description of the situation. If the situation is caused by a fault, take also the Datalogger data from the drive.
Note that Datalogger settings can be changed to catch correct situation and it’s also to possible make manual force trig for Datalogger.
Before storing the parameter file, upload the parameters from the drive and save when NCDrive is in the ON-LINE state. If it is possible, do this while the problem is active.
It’s also helpful to have single line diagram from the system where problem is faced.

Figure 1. Datalogger window opening and Service Info upload.
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
Classified as Public

86 · VACON®

arfiff05 Standard AFE-II

FAULT CODES

The fault codes, their causes and correcting actions are presented below.
Note: When contacting distributor or factory because of a fault condition, always write down all texts and codes on the keypad display. Best way is to send parameter file and service info to Vacon technical support This chapter includes all fault codes that are possible. but some faults are not possible in AFE application. And some faults description may be different when compared to standard frequency converter.
F1 Over current fault Drive has detected a high current in the output phase.
S1 = Hardware trip: Current above 4*Ih
Possible cause and solutions 1. Sudden increase in load
· Check motor load. 2. Short circuit in cables
· Check cables.
F2 Overvoltage fault DC-link voltage has exceeded the drive protection limits.
S1 = Hardware trip. 500 Vac unit DC voltage above 911 Vdc 690 Vac unit DC voltage above 1200 Vdc
S2 = Overvoltage control supervision (only 690 Vac unit). DC voltage has been above 1100 Vdc for too long.
Possible cause and solutions 1. Too short a deceleration time
· Increase deceleration time. · Use brake chopper and brake resistor. · Use Brake chopper unit. 2. High overvoltage spikes in supply · Check input voltage.
F3 Earth fault Earth fault protection ensures that the sum of the phase currents is zero. The over current protection is always working and protects the frequency converter from earth faults with high currents.
S1 = Sum of output phase current is not zero
Possible cause and solutions 1. Insulation failure in cables

Local contacts: http://drives.danfoss.com/d

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals