ASFIFF11 VACON NXP Air Cooled User Manual

June 16, 2024
VACON

user’s manual
nx frequency converters

fire mode pid application
asfiff11

INTRODUCTION

The application is functionally the same as the PID application (ASFIFF05) with the addition of the fire mode features. Fire mode is selected via a digital input (programmable). The frequency is set according to logic in Figure 1. When fire mode is active, a fire mode warning (A81) is brought up on the display. When running in fire mode, the converter is programmed to enable the user to run the converter until either the digital input is removed or the converter is damaged.

Additional features when fire mode is selected:

  • Run enable always active
  • Run request always active
  • Direction change not allowed
  • Fault signal on digital outputs inactive
  • Possible to connect fire mode signal to digital outputs
  • Software generated faults are changed to warnings (Drive does not stop)
  • Forced reset of hardware system faults (Delay time is set with parameter P2.10.5)
  • Fire Mode frequency reference can be PID-output or two selectable preset speeds
  • Monitor value V1.22 is stored if fire mode have been used (Counter)

FIRE MODE PID APPLICATION – PARAMETER LISTS

On the next pages you will find the lists of parameters within the respective parameter groups. The parameter descriptions are given on pages 9.

Column explanations:

Code| Location indication on the keypad; Shows the operator the present parameter number
---|---
Parameter| Name of parameter
Min| Minimum value of parameter
Max| Maximum value of parameter
Unit| Unit of parameter value; Given if available
Default| Value preset by factory
Cust| Customer’s own setting
ID| ID number of the parameter (used with PC tools)
| On parameter code: Parameter value can only be changed after the frequency converter has been stopped.

2.1 Monitoring values (Control keypad: menu M1)
The monitoring values are the actual values of parameters and signals as well as statuses and measurements. Monitoring values cannot be edited.
See Vacon NX User’s Manual, Chapter 7 for more information.

Code Parameter Unit ID Description
V1.1 Output frequency Hz 1 Output frequency to motor
V1.2 Frequency reference Hz 25 Frequency reference to motor control
V1.3 Motor speed rpm 2 Motor speed in rpm
V1.4 Motor current A 3
V1.5 Motor torque % 4
V1.6 Motor power % 5 Motor shaft power
V1.7 Motor voltage V 6
V1.8 DC link voltage V 7
V1.9 Unit temperature °C 8 Heatsink temperature
V1.10 Voltage input V 13 AI1
V1.11 Current input mA 14 AI2
V1.12 Analogue input 3 27 AI3
V1.13 Analogue input 4 28 AI4
V1.14 DIN1, DIN2, DIN3 15 Digital input statuses
V1.15 DIN4, DIN5, DIN6 16 Digital input statuses
V1.16 DO1, RO1, RO2 17 Digital and relay output statuses
V1.17 Analogue Iout mA 26 AO1
V1.18 PID Reference % 20 In percent of the maximum frequency
V1.19 PID Actual value % 21 In percent of the max actual value
V1.20 PID Error value % 22 In percent of the max error value
V1.21 PID Output % 23 In percent of the max output value
V1.22 Fire mode used x 1510 Counter, how many times fire mode have been in

use

Table 1. Monitoring values

2.2 Input signals (Control keypad: Menu M2 ⇒G2.2)

Code| Parameter| Min| Max| Unit| Default| Cust| ID| Note
---|---|---|---|---|---|---|---|---
P2.2.1| DIN2 function| 0| 15| | 1| | 319| 0=Not used 1=External fault cc 2=External fault oc
3=Run enable
4=Acc/Dec time selection
5=CP: I/O terminal
6=CP: Keypad
7=CP: Fieldbus
8=Forward/Reverse
9=Jogging frequency (cc)
10=Fault reset (cc)
11=Acc/Dec prohibit (cc)
12=DC braking command
13=Motor pot. UP (cc)
14=Fire Mode
15=Fire mode preset reference selection, 1
(oc) or 2 (cc)
P2.2.2| DIN3 function| 0| 15| | | | 301| 0=Not used 1=External fault cc
2=External fault oc
3=Run enable
4=Acc/Dec time selection
5=CP: I/O terminal
6=CP: Keypad
7=CP: Fieldbus
8=Forward/Reverse
9=Jogging frequency (cc)
10=Fault reset (cc)
11=Acc/Dec prohibit (cc)
12=DC braking command
13=Motor pot.DOWN (cc)
14=Fire Mode
15=Fire mode reference selection, PID or Preset
P2.2.3| DIN5 function| 0| 15| | | | 330| 0=Not used
1=External fault cc
2=External fault oc
3=Run enable
4=Acc/Dec time selection
5=CP: I/O terminal
6=CP: Keypad
7=CP: Fieldbus
8=Forward/Reverse
9=Jogging frequency (cc)
10=Fault reset (cc)
11=Acc/Dec prohibit (cc)
12=DC braking command
13=Enable PID reference
14=Fire Mode
15=Fire mode reference selection, PID or Preset

Table 2. Digital input functions, G2.2

2.3 Output signals (Control keypad M2⇒G2.3)

Code| Parameter| Min| Max| Unit| Default| Cust| ID| Note
---|---|---|---|---|---|---|---|---
P2.3.6| Digital output 1 function| 0| 21| | 1| | 312| 0=Not used
1=Ready
2=Run
3=Fault
4=Fault inverted
5=FC overheat warning
6=Ext. fault or warning
7=Ref. fault or warning
8=Warning
9=Reversed
10=Preset speed
11=At speed
12=Mot. regulator active
13=OP freq. limit superv.1
14=OP freq. limit superv.2
15=Torque limit superv.
16=Ref. limit supervision
17=External brake control
18=Control place: IO
19=FC temp. limit superv. 20=Unrequested direction
21=Ext. brake control inv. 22=Thermistor Fault/Warn.
23=Fieldbus digital input.
24=Fire mode selected.
P2.3.7| Relay output 1 function| 0| 21| | 2| | 313| As parameter 2.3.6
P2.3.8| Relay output 2 function| 0| 21| | 3| | 314| As parameter 2.3.6

Table 3. Digital output functions, G2.3

2.4 Fire Mode (Control keypad M2 - > G2.10) 

Code| Parameter| Min| Max| Unit| Default| Cust| ID| Note
---|---|---|---|---|---|---|---|---
P2.10.1| Fire mode function| 0| 1| | 0| | 1501| 0=Closing contact
1=Opening contact
P2.10.2| Fire mode preset reference selection| 0| 1| | 0| | 1502| 0=Not inverted 1=Inverted
P2.10.3| Fire mode min frequency| Par 2.1.1| Par. 2.1.2| Hz| 15,00| | 1503| Min frequency when in fire mode
P2.10.4| Fire mode preset frequency 1| Par 2.1.1| Par 2.1.2| Hz| 35,00| | 1504| Fire mode preset frequency reference 1
P2.10.5| Fire mode preset frequency 2| Par 2.1.1| Par 2.1.2| Hz| 50,00| | 1505| Fire mode preset frequency reference 2
P2.10.6| Fire mode forced reset delay| 0,50| 10,00| s| 5,00| | 1506| Delay time for forced reset when in fire mode

Table 4. Fire Mode parameters, G2.10

Tel. +358 (0)201 2121 • Fax +358 (0)201 212 205

DESCRIPTION OF PARAMETERS

3.1 Fire mode parameters

2.10.1 Fire mode function
0 Closing contact
1 Opening contact
2.10.2 Fire mode preset reference selection
0 Not inverted
1 Inverted
2.10.3 Fire mode min frequency
Sets the min frequency when the Fire Mode is active
2.10.4 Fire mode preset frequency 1
Parameter value is automatically limited between the minimum ad maximum frequencies (P2.1.1, P2.1.2)
2.10.5 Fire mode preset frequency 2
Parameter value is automatically limited between the minimum ad maximum frequencies (P2.1.1, P2.1.2)
2.10.6 Fire mode forced reset delay
Time delay before forced reset after a hardware generated fault.

FREQUENCY REFERENCE SIGNAL LOGIC IN FIRE MODE PID APPLICATION

Figure 1. Frequency reference logic of the Fire Mode PID Application when running in Fire Mode

Vaasa
Vacon Plc (Head office and production)
Runsorintie 7
65380 Vaasa
[email protected]
telephone: +358 (0)201 2121
fax: +358 (0)201 212 205| Helsinki
Vacon Plc
Äyritie 12
01510 Vantaa
telephone: +358 (0)201 212 600
fax: +358 (0)201 212 699| Tampere
Vacon Plc
Vehnämyllynkatu 18
33700 Tampere
telephone: +358 (0)201 2121
fax: +358 (0)201 212 750| Vacon Traction Oy
Vehnämyllynkatu 18
33700 Tampere
telephone: +358 (0)201 2121
fax: +358 (0)201 212 710
---|---|---|---

sales companies and representative offices:

Austria
Vacon AT Antriebssysteme GmbH
Aumühlweg 21
2544 Leobersdorf
telephone: +43 2256 651 66
fax: +43 2256 651 66 66
Belgium
Vacon Benelux NV/SA
Interleuvenlaan 62
3001 Heverlee (Leuven)
telephone: +32 (0)16 394 825
fax: +32 (0)16 394 827
France
Vacon France s.a.s.
1 Rue Jacquard – BP72
91280 Saint Pierre du Perray CDIS
telephone: +33 (0)1 69 89 60 30
fax: +33 (0)1 69 89 60 40
Germany
Vacon GmbH
Gladbecker Strasse 425
45329 Essen
telephone: +49 (0)201 806 700
fax: +49 (0)201 806 7099
Great Britain
Vacon Drives (UK) Ltd.
18, Maizefield
Hinckley Fields Industrial Estate Hinckley
LE10 1YF Leicestershire
telephone: +44 (0)1455 611 515
fax: +44 (0)1455 611 517| Italy
Vacon S.p.A.
Via F.lli Guerra, 35
42100 Reggio Emilia
telephone: +39 0522 276811
fax: +39 0522 276890
The Netherlands
Vacon Benelux BV
Weide 40
4206 CJ Gorinchem
telephone: +31 (0)183 642 970
fax: +31 (0)183 642 971
Norway
Vacon AS
Langgata 2
3080 Holmestrand
telephone: +47 330 96120
fax: +47 330 96130
PR China
Vacon Suzhou Drives Co. Ltd.
Blk 11A
428 Xinglong Street
Suchun Industrial Square
Suzhou 215126
telephone: +86 512 6283 6630
fax: +86 512 6283 6618
Vacon Suzhou Drives Co. Ltd.
Beijing Office
A205, Grand Pacific Garden Mansion
8A Guanhua Road
Beijing 100026
telephone: +86 10 6581 3734
fax: +86 10 6581 3754| Russia
ZAO Vacon Drives
Bolshaja Jakimanka 31,
stroenie 18
109180 Moscow
telephone: +7 (095) 974 14 47
fax: +7 (095) 974 15 54
ZAO Vacon Drives
2ya Sovetskaya 7, office 210A
191036 St. Petersburg
telephone: +7 (812) 332 1114
fax: +7 (812) 279 9053
Singapore
Vacon Plc
Singapore Representative Office
102F Pasir Panjang Road

02-06 Citilink Warehouse Complex

Singapore 118530
telephone: +65 6278 8533
fax: +65 6278 1066
Spain
Vacon Drives Ibérica S.A.
Miquel Servet, 2. P.I. Bufalvent
08243 Manresa
telephone: +34 93 877 45 06
fax: +34 93 877 00 09
Sweden
Vacon AB
Torget 1
172 67 Sundbyberg
telephone: +46 (0)8 293 055
fax: +46 (0)8 290 755
---|---|---

24-hour support +358 (0)40 837 1150 • Email: [email protected]
Vacon distributor:

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

VACON User Manuals

Related Manuals