Danfoss 027R9797 ICAD Actuators Owner’s Manual

June 1, 2024
Danfoss

Danfoss-logo

Danfoss 027R9797 ICAD Actuators

Danfoss-027R9797-ICAD-Actuators-product-image

Specifications:

  • Model: ICAD Actuators
  • Generation: 1st and 2nd
  • Power Supply: 19-24 V d.c.
  • Connector Type: 4-pin and 8-pin male connectors
  • Input/Output: Digital and Analogue

Product Usage Instructions

  1. Installation Guide:
    Follow the colour code connection diagram provided for ICAD actuators to ensure correct installation.

  2. Power Supply:
    Connect the ICAD actuators to a 19-24 V d.c. fail-safe supply using 3 x 0.25 mm2 (3 x 24 AWG) wires.

  3. Connector Setup:
    For 0/4 – 20 mA Input, use the A (Black), B (Brown), and C (Red) connections. For 0/2 – 10 V Input, use E (Yellow) and F (Green).

  4. Analog In/Output:
    Connect G (Blue) for 0/4 – 20 mA Output.

  5. Fail-Safe Supply:
    For fail-safe supply and battery/UPS connection, use the 8-pin male connector with the specified wiring setup.

FAQ :

Q: What should I do if the ICAD actuator is not responding?
A: Check the power supply connection and ensure that the wiring follows the colour code diagram provided in the manual. If the issue persists, contact customer support for further assistance.

Installation Guide

Colour code connection diagram for ICAD actuators

| 1 st genration ICAD| 2 nd generation ICAD
---|---|---
|

Danfoss-027R9797-ICAD-Actuators-fig- \(2\)

3 x 0,25 mm 2 (3 x 24 AWG)| + 19-24 V d.c. fail safe supply| White (+)| Black (+)
+ 24 V d.c.| Brown (+)| White (+)
–24 C d.c. (GND)| Green (–)| Brown (–)
7 x 0,25 mm 2 (7 x 24 AWG)| Digital output (common alarm)| White (–)| Black (–)
Digital output (ICM fully open)| Brown (–)| Brown (–)
Digital output (ICM fully closed)| Green (–)| Red (–)
GND – Ground| Yellow (–)| Orange (–)
Analog input 0/4-20 mA| Grey (+)| Yellow (+)
Analog input 0/2-10 V / Digital ON/OFF input| Pink (+)| Green (+)
Analog output 0/4-20 mA| Blue (+)| Blue (+)

Danfoss-027R9797-ICAD-Actuators-fig-04

I Black + Fail safe supply Battery / UPS* 19 V d.c.
II White + Supply voltage 24 V d.c.
III Brown
  • Uninterruptable Power SupplyDanfoss-027R9797-ICAD-Actuators-fig- \(3\)

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products all era marren this material are property of the respectide companies. bantos and the Dantos goes are trademarts of Santos Als. Al rights reserved.

Info for UK customers only:Danfoss Ltd. Oxford Road, UB9 4LH Denham, UK
© Danfoss A/S (MWA), 2021-01