aparian A-DNTR-B DeviceNet Router User Guide
- June 2, 2024
- aparian
Table of Contents
DeviceNet Router/B
Quick Start Guide
A-DNTR/B
A-DNTR-B DeviceNet Router
NOTE: Before installing, configuring, operating, or maintaining Aparian products, please review this information and the information located on www.aparian.com for the latest software, documentation, and installation files specific to your Aparian product.
INTRODUCTION
This quick start guide provides an basic overview of the installation, operation, and diagnostics of the Aparian DeviceNet Router Series B module. The DeviceNet Router/B provides intelligent data routing between either EtherNet/IP or Modbus TCP/RTU and a DeviceNet network. This allows the user to integrate DeviceNet devices into a Rockwell Logix platform (e.g., ControlLogix or CompactLogix) or any Modbus Client or Server device with minimal effort. The module can be configured to be either a DeviceNet Scanner or a DeviceNet Device allowing the user to not only integrate DeviceNet devices into a Logix or Modbus system, but to also allow the user to use EtherNet/IP or Modbus devices in an existing DeviceNet network (by using the DeviceNet Router/B in device mode).
REQUIRED SOFTWARE
The DeviceNet Router/B requires Aparian Slate software to setup and configure. The software installation can be found at www.aparian.com/software/slate.
MODULE INSTALLATION
The module has two Ethernet ports located at the lower front of the module.
There are also two ports at the bottom of the module for RS232/RS485 serial
and power. The power port uses a three-way connector which is used for the DC
power supply positive and negative (or ground) voltage as well as the earth
connection. The at the front of the module there is a 5-way connector which is
used for the DeviceNet network and can also be used for power. Both bottom and
front power connectors can be plugged in at the same time.
The nine-way connector is used to connect the RS232 and RS485 conductors for
serial communication. The shield terminal can be used for shielded cable in
high noise environments.
LED | Description |
---|---|
Ok | The module LED will provide information regarding the system-level |
operation of the module.
A / B| The Ethernet LED will light up when an Ethernet link has been detected
(by plugging in a connected Ethernet cable). The LED will flash every time
traffic was detected.
This module has two Ethernet ports A and B. Each LEDs represents each specific
port.
Act| The Act LED indicates if the module is operating as a DeviceNet target or
DeviceNet Scanner.
Solid Green – The local DeviceNet Router/B is operating as a DeviceNet
Scanner.
Off – The local DeviceNet Router/B is operating as a DeviceNet Target.
DN| The DeviceNet LED indicates the activity on the DeviceNet network.
Flashing Red – A corrupted or incorrect DeviceNet packet was received.
Flashing Green – A valid DeviceNet packet was received.
Off – No DeviceNet packets are being received.
Aux| The Aux LED will flash each time there was activity on any of the primary
interfaces.
Flashing Red – A corrupted or incorrect packet was received on one of the
Primary Interfaces (EtherNet/IP, Modbus TCP/RTU232/RTU485).
Flashing Green – A valid packet was received on one of the Primary Interfaces
(EtherNet/IP, Modbus TCP/RTU232/RTU485).
Off – No activity.
DEVICENET TERMINATION
All DeviceNet networks need to be terminated at the extremities (start and end point) of the communication conductor. The termination for the DeviceNet network can be enabled/disabled via the module configuration. Enabling the termination will connect an internal 120 Ohm resistor across the positive (+) and negative (-) conductors of the DeviceNet network.
ELECTRICAL AND ENVIRONMENTAL
Specification | Rating |
---|---|
Power requirements | Input: 10 – 32V DC, |
Power consumption | 2.2 W (Max.) |
Current: 180 mA @ 10 V
Current: 85 mA @ 24 V
Temperature| -20 – 70 °C
STUDIO 5000 CONFIGURATION
The module must be added to the Logix IO tree using a EDS AOP (Logix v21+).
NORTH AMERICAN HAZARDOUS LOCATION APPROVAL
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C AND D HAZARDOUS
LOCATIONS, OR NONHAZARDOUS LOCATIONS ONLY.
WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT WHILE THE
CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOW TO BE FREE OF IGNITABLE
CONCENTRATIONS.
WARNING – EXPLOSION HAZARD – SUBSTITUTION OF ANY COMPONENT MAY IMPAIR
SUITABILITY FOR CLASS I, DIVISION 2.
For professional users in the European Union
If you wish to discard electrical and electronic equipment (EEE), please
contact your dealer or supplier for further information.
WARNING – Cancer and reproductive harm –
www.p65warnings.ca.gov
ADDITIONAL INFORMATION
The following resources contain additional information that can assist the user with the module installation and operation.
Resource | Link |
---|---|
Slate Installation |
www.aparian.com/software/slate
DeviceNet Router/B User Manual
DeviceNet Router/B Datasheet| https://www.aparian.com/dnrb
Ethernet wiring standard|
www.cisco.com/c/en/us/td/docs/video/cds/cde/cde205_220_420/installation/guide/cde205_220_420_hig/Connectors.html
DeviceNet| http://www.odva.org
Slate Installation|
www.aparian.com/software/slate
SUPPORT
Technical support will be provided via the Web (in the form of user manuals,
FAQ, datasheets etc.) to assist with installation, operation, and diagnostics.
For additional support the user can use either of the following:
Contact Us web link| https://www.prosoft-technology.com/ServicesSupport
/Customer-Support
---|---
Support email| support@prosoft-technology.com
Document No. D154-011
Revision 1.1
01/2023
References
- technology.com
- Home
- ODVA | Industrial Automation | Technologies and Standards
- ODVA | Industrial Automation | Technologies and Standards
- p65warnings.ca.gov
- Regional Technical Support / Services & Support / Homepage - ProSoft Technology, Inc.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>