hes 1500 Series Electric Strikes Instruction Manual

May 15, 2024
HES

1500 Series and 1600 Series Electric Strikes
Installation Instructions

IMPORTANT NOTE :
For the Schlage L9000 or Yale 8700 Series, please see Page 3 of instructions for installation with offset.

NOTE: Installation wiring for the product and wiring methods shall be in accordance with the National Electrical Code, ANSI/NFPA 70.

Product Components

  1. 1500 Series or 1600 Series Electric Strike
  2. Trim Enhancer
  3. Pigtails (12 VDC and 24 VDC)
  4. 5/64” Hex Wrench
  5. 6-32 x 3/16” Phillips Head Screws to Mount Trim Enhancer

Specifications

| Solenoids are rated at +/- 10% indicated value.
---|---
ELECTRICAL RATINGS FOR| Applies to AC Only: 10% max duty cycle
1500/1600 (Solenoid)| (2 min. max on time)
VOLTAGE| 12 VDC| 24 VDC| 12-16 VAC| 24 VAC
CONTINUOUS DUTY| 0.24A| 0.12A| –| –
INTERMITTENT DUTY
| –| –| 0.24-0.32A| 0.12A
ELECTRICAL RATINGS FOR 1500E/1600E (EcoStrikel| Input voltage: 10-30 VDC, Autosensing
---|---
Minimum Activation Duration: 1 second
VOLTAGE| 10 VDC| 12 VDC| 24 VDC| 30 VDC
IN RUSH CURRENT| 0.475A| 0.460A| 0.220A| 0.215A
CONTINUOUS DUTY| 0.010A| 0.009A| 0.005A| 0.004A
MINIMUM WIRE GAUGE REQUIREMENTS| VOLTAGE
---|---
12VDC| 24VDC
200 feet or less| 18 gauge| 20 gauge
200 – 300 feet| 16 gauge| 18 gauge
300 – 400 feet| 14 gauge| 16 gauge

NOTE: The above table applies to Models 1500, 1500E, 1600, and 1600E.

Models 1500E and 1600E: For Indoor Use Only
Models 1500 and 1600: For Outdoor Use

Ratings

Static Strength: 1,500 lbs
Dynamic Impact: 70 ft-lbs
Endurance: 250,000 cycles

ASSA ABLOY, the global leader in door opening solutions

UL294 Performance Levels

Destructive Attack: Level 1 (No attack test)
Line Security: Level I (No Line Security)
Endurance: Level IV (100,000 cycles)
Standby Power: Level I (No secondary power source)

Converting the Operation Mode

IMPORTANT NOTE: Converting the electric strike to FAIL SAFE mode negates the unit’s fire rating.
NOTE 1: The 1500 and 1600 Series Electric Strikes ship configured for FAIL SECURE OPERATION. The steps below are provided to convert to FAIL SAFE OPERATION, if desired. The operation mode of the 1500E and 1600E (EcoStrike ™ ) is set at the factory and cannot be changed.
NOTE 2: The suitability of the locks in the FAIL SECURE OPERATION mode is up to the local Authority Having Jurisdiction (AHJ) and emergency exit hardware may be required in such installations.

Connecting the Power

IMPORTANT NOTE : Before electrically connecting the device, the input voltage must be verified using a multimeter.
Many power supplies and low voltage transformers operate at higher levels than listed. Any input voltage exceeding 10% of the electrical specification (see Page 1) may cause severe damage to the unit and will void the warranty.

1500 or 1600:
For 12 VAC, 12 VDC, or 16 VAC, USE the pigtail marked “12 VDC.”
For 24 VAC or 24 VDC, USE the pigtail marked “24 VDC.”
1500E or 1600E: For 10–30 VDC, ALWAYS USE the pigtail marked “12 VDC.”
NOTE: No AC input voltage.

Preparing the Frame

MORTISE LOCKSETS
Please note the horizontal centerline of the electric strike in relation to the centerline of the mortise lockset.

  • Can be Mortise lock and option specific. See figures below if using a Schlage L9000 or Yale 8700 series.

CYLINDRICAL LOCKSETS
Please note the horizontal centerline of the electric strike in relation to the centerline of the cylindrical lockset.

METAL JAMB DIMENSIONS FOR FACEPLATES
Please see Notes 2 & 3 for dimensions when using Lip Extensions

Normally Used With Mortise Locks Without Deadbolt
*NOTE1: Cannot be used with Schlage L9000 or Yale 8700 series.
NOTE2: Add 1/4” [6 mm] to this dimension when using a lip extension.
NOTE3:** Add 3/8” [9.5 mm] to this dimension when using a lip extension.
Cutout dimenstions for option faceplates (metal jamb): 1J, 1KM, 1NM

Normally Used With Mortise Locks With Deadbolt
NOTE1: Can be used with Schlage L9000 or Yale 8700 series.

  • NOTE2: Add 1/4” [6 mm] to this dimension when using a lip extension.
    ** NOTE3: Add 3/8” [9.5 mm] to this dimension when using a lip extension.

Cutout dimenstions for option faceplates (metal jamb): 1KD, 1ND, 1NTD

Selecting the Appropriate Faceplate Option

OPTION DESCRIPTION 1500 1600
1J For Use With:
Compatible With: Cylindrical locksets with up to %” throw and all locksets
with center-lined bolts. All brands of cylindrical latchbolts X X
1K For Use With:
Compatible With: Mortise locksets with up to 3/4″ throw latchbolt. Baldwin,
Marks, PDQ X X
1KM For Use With:
Compatible With: Mortise locksets with up to 3/4″ throw latchbolt.

Accurate, Arrow, Best, Corbin Russwin, Falcon, Sargent (7800, 8200, and 9200), Yale (8800)| X| X
1KD| For Use With:
Compatible With:| Mortise locksets with up to 3/4″ throw latchbolt.
Dorma (9500), Jackson, Sargent (7700 and 8100), Schlage, Yale (8700)| X| X
1N| For Use With:
Compatible With:| Mortise locksets with deadbolt for night latch function only. Accurate, Baldwin, Marks, Omnia, PDQ, Schlage| | X
1NM| For Use With:
Compatible With:| Mortise locksets with deadbolt for night latch function only.
Accurate, Arrow, Baldwin, Best, Corbin Russwin, Falcon (45H, 47H, 34H, and 37H), Marks, PDQ, Sargent (7800, 8200, and 9200), Yale (8800)| | X
1ND| For Use With:
Compatible With:| Mortise locksets with deadbolt for night latch function only. Sargent (7700 and 8100), Schlage, Yale (8700)| | X
1NTD| For Use With:
Compatible With:| Mortise locksets with a normally extended 1″ deadbolt and center-lined deadlatch. Accurate, Arrow, Baldwin, Marks, Omnia, PDQ, Schlage| | X

Adjusting the Shim

NOTE: To adjust the shim height, it is necessary to power the electric strike to open keeper.

STEP 1
LOOSEN the locking screw with the 5/64” Hex Wrench.

STEP 2
ADJUST the shim height to the desired level by turning the upper and lower set screws (clockwise to raise and counterclockwise to lower).

STEP 3
TIGHTEN the locking screw to lock position.

HES, Inc.
Phoenix, AZ
800-626-7590
www.hesinnovations.com