TECH CONTROLLERS EU-L-5s Wired Controller Thermostatic Actuators User Manual

May 15, 2024
TECH CONTROLLERS

TECH CONTROLLERS EU-L-5s Wired Controller Thermostatic Actuators

TECH-CONTROLLERS-EU-L-5s-Wired-Controller-Thermostatic-Actuators-
product

SAFETY

Before using the device for the first time the user should read the following regulations carefully. Not obeying the rules included in this manual may lead to personal injuries or controller damage. The user’s manual should be stored in a safe place for further reference. To avoid accidents and errors it should be ensured that every person using the device has familiarized themselves with the principle of operation as well as security functions of the controller. If the device is to be sold or put in a different place, make sure that the user’s manual is there with the device so that any potential user has access to essential information about the device. The manufacturer does not accept responsibility for any injuries or damage resulting from negligence; therefore, users are obliged to take the necessary safety measures listed in this manual to protect their lives and property.

WARNING

  • High voltage! Make sure the controller is disconnected from the mains before performing any activities involving the power supply (plugging cables, installing the device etc.)
  • The device should be installed by a qualified electrician.
  • Before starting the controller, the user should measure the earthing resistance of the electric motors as well as the insulation resistance of the cables.
  • The controller should not be operated by children.

WARNING

  • The device may be damaged if struck by lightning. Make sure the plug is disconnected from the power supply during a storm.
  • Any use other than specified by the manufacturer is forbidden.
  • Before and during the heating season, the controller should be checked for the condition of its cables. The user should also check if the controller is properly mounted and clean it if dusty or dirty.
  • Changes in the merchandise described in the manual may have been introduced safterits completion on 25.11.2020.
  • The manufacturer retains the right to introduce changes to the structure. The illustrations may include additional equipment.
  • Print technology may result in differences in colours shown.
  • We are committed to protecting the environment. Manufacturing electronic devices imposes an obligation to provide for environmentally safe disposal of used electronic components and devices. Hence, we have been entered into a register kept by the Inspection For Environmental Protection.
  • The crossed-out bin symbol on a product means that the product may not be disposed of in household waste containers. Recycling of waste helps to protect the environment.
  • The user is obliged to transfer their used equipment to a collection point where all electric and electronic components will be recycled.

DEVICE DESCRIPTION

EU-L-5s controller is intended for controlling thermoelectric actuators obased onthe signal sent by the room temperature regulators. The controller can manage actuators via 8 two-state room temperature regulators. The controller has a WT 6,3A tube fuse link protecting the power supply.

TECH-CONTROLLERS-EU-L-5s-Wired-Controller-Thermostatic-Actuators-fig-
\(1\)

WARNING
HA higher amperage fuse should not be used as it may damage the controller.

  1. Icons of zones 1-8
  2. An icon indicating pump operation
  3. An icon indicating voltage-free contact operation
  4. An icon indicating that the controller is connected to the power supply

HOW TO INSTALL THE CONTROLLER

WARNING

  • Risk of fatal electric shock from touching live connections. Before working on the controller switch off the power supply and prevent it from being accidentally switched on.
  • Incorrect connection of cables may lead to controller damage.

WARNING
If the pump manufacturer requires an external main switch, power supply fuse or additional residual current device selective for distorted currents it is recommended not to connect pumps directly to pump control outputs. To avoid damage to the device, an additional safety circuit must be used between the regulator and the pump. The manufacturer recommends the ZP-01 pump adapter, which must be purchased separately. The device should be installed by a qualified electrician. The diagrams below illustrate the correct connection:

Connection of a regulator – 230V

TECH-CONTROLLERS-EU-L-5s-Wired-Controller-Thermostatic-Actuators-fig-
\(2\)

Connection of actuators and room regulators – batteries

TECH-CONTROLLERS-EU-L-5s-Wired-Controller-Thermostatic-Actuators-fig-
\(3\)TECH-CONTROLLERS-EU-L
-5s-Wired-Controller-Thermostatic-Actuators-fig- \(4\)

SIGNALS FROM ROOM REGULATORS
POSSIBILITY OF POWERING FROM THE MAIN CONTROLLER

TECH-CONTROLLERS-EU-L-5s-Wired-Controller-Thermostatic-Actuators-fig-
\(5\)

MAINTENANCE, TECHNICAL DATA
Before and during the heating season, the EU-L-5s controller should be checked for the condition of its cables. You should also check if the controller is properly mounted and clean it if dusty or dirty.

Technical data

Power supply 230V +/- 10% / 50Hz
Maximum power consumption 4W
Maximum power consumption of a room regulator 100mA
Ambient temperature 5÷50°C
Potential contacts 1-8 max. output load 0,3 A
Pump max. output load 0,5 A
Potential-free cont. nom. out. load 230V AC / 0,5A (AC1) *

24V DC / 0,5A (DC1) **

Fuse| 6,3 A

  • AC1 load category: single-phase, resistive or slightly inductive AC load.
  • DC1 load category: direct current, resistive or slightly inductive load.

EU Declaration of Conformity

Hereby, we declare under our sole responsibility that EU-L-5s manufactured by TECH STEROWNIKI II Sp. z o.o., head-quartered in Wieprz Biała Droga 31, 34-122 Wieprz, is compliant with Directive 2014/35/EU of the European Parliament and of the Council of 26 February 2014 on the harmonisation of the laws of Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits (EU OJ L 96, of 29.03.2014, p. 357), Directive 2014/30/EU of the European Parliament and of the Council of 26 February 2014 on the harmonisation of the laws of Member States relating to electromagnetic compatibility (EU OJ L 96 of 29.03.2014, p.79)

Directive 2009/125/EC establishes a framework for the setting of ecodesign requirements for energy-related products as well as the regulation by the MINISTRY OF ENTREPRENEURSHIP AND TECHNOLOGY of 24 June 2019 amending the regulation concerning the essential requirements as regards the restriction of the use of certain hazardous substances in electrical and electronic equipment, implementing provisions of Directive (EU) 2017/2102 of the European Parliament and of the Council of 15 November 2017 amending Directive 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment (OJ L 305, 21.11.2017, p. 8).

For compliance assessment, harmonized standards were used:
PN-EN IEC 60730-2-9:2019-06, PN-EN 60730-1:2016-10, EN IEC 63000:2018 RoHS.
Wieprz, 25.11.2020

Central headquarters
ul. Biata Droga 31, 34-122 Wieprz
Service: ul. Skotnica 120, 32-652 Bulowice
phone: +48 33 875 93 80
e-mail: serwis@techsterowniki.pl

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

TECH CONTROLLERS User Manuals

Related Manuals