TECH CONTROLLERS EU-i-3 Central Heating Systems User Manual
- June 3, 2024
- TECH CONTROLLERS
Table of Contents
EU-i-3 Central Heating Systems
EU-i-3
1
TABLE OF CONTENTS
I. Safety…………………………………………………………………………………………………………………………………………………….. 5 II.
Device description …………………………………………………………………………………………………………………………………… 6 III.
How to install …………………………………………………………………………………………………………………………………………. 8 IV.
Main screen description…………………………………………………………………………………………………………………………. 11
1. Installation screen ……………………………………………………………………………………………………………………………….. 11
2. Parameter and panel screen …………………………………………………………………………………………………………………. 11
V. Quick setup of the controller …………………………………………………………………………………………………………………..
12
Part I. How to configure built-in valves, additional valves and room
regulators
I. How to configure built-in valve
……………………………………………………………………………………………………………….. 13 II. Weather-based control
………………………………………………………………………………………………………………………….. 17 III. Mixing valve settings
…………………………………………………………………………………………………………………………….. 18 IV. Quick setup of the
mixing valve ………………………………………………………………………………………………………………. 21 V. Additional
valves …………………………………………………………………………………………………………………………………… 22
Part II. Controller operation modes
I. Water tank priority………………………………………………………………………………………………………………………………… 23 II.
Parallel pumps………………………………………………………………………………………………………………………………………. 23 III.
House heating ………………………………………………………………………………………………………………………………………. 23 IV.
Summer mode………………………………………………………………………………………………………………………………………. 23 V.
Automatic summer mode ………………………………………………………………………………………………………………………. 24
Part III. DHW pump and Anti-legionella
I. How to configure DHW pump operation …………………………………………………………………………………………………..
24 II. Anti-legionella ………………………………………………………………………………………………………………………………………. 25
III. Pump ANTI-STOP …………………………………………………………………………………………………………………………………… 26
Part IV. Manual mode
I. Manual mode ……………………………………………………………………………………………………………………………………….. 27 Part
V. Additional contacts
I. Voltage contacts and voltage-free
contacts………………………………………………………………………………………………. 28 II. How to configure a
contact …………………………………………………………………………………………………………………….. 29 III. Voltage and
voltage-free contact algorithms…………………………………………………………………………………………….. 30
1. Circulating pump …………………………………………………………………………………………………………………………………. 30 2.
Buffer pump ……………………………………………………………………………………………………………………………………….. 30 3. CH
pump …………………………………………………………………………………………………………………………………………….. 31 4. Additional
heat source …………………………………………………………………………………………………………………………. 32 5.
Buffer…………………………………………………………………………………………………………………………………………………. 33 6. DHW
buffer ………………………………………………………………………………………………………………………………………… 33
2
7. Heating need ………………………………………………………………………………………………………………………………………. 34 8.
Operation control ………………………………………………………………………………………………………………………………… 35 9. DHW
………………………………………………………………………………………………………………………………………………….. 36 10. Controlling
the room regulator………………………………………………………………………………………………………….. 36 11. Relays
…………………………………………………………………………………………………………………………………………….. 37 12. Weekly control
………………………………………………………………………………………………………………………………… 37 13. Manual
mode………………………………………………………………………………………………………………………………….. 39 14. OFF
………………………………………………………………………………………………………………………………………………… 39
Part VI. Cascade I. Cascade
……………………………………………………………………………………………………………………………………………….. 39
1. Select operation algorithm……………………………………………………………………………………………………………………. 39
2. Operation mode ………………………………………………………………………………………………………………………………….. 40 3.
Additional contacts………………………………………………………………………………………………………………………………. 40 4.
Select sensor ………………………………………………………………………………………………………………………………………. 40 5. Main
boiler …………………………………………………………………………………………………………………………………………. 40 6. Reset
motohours …………………………………………………………………………………………………………………………………. 40 7. Factory
settings …………………………………………………………………………………………………………………………………… 40
Part VII. Ethernet module I. Ethernet module
…………………………………………………………………………………………………………………………………… 41
Part VIII. Solar collector I. Solar
collector……………………………………………………………………………………………………………………………………….. 42
1. Solar collector……………………………………………………………………………………………………………………………………… 42 2.
Accumulation tank ………………………………………………………………………………………………………………………………. 43 3. Pump
settings ……………………………………………………………………………………………………………………………………… 44 4. Additional
contact ……………………………………………………………………………………………………………………………….. 44 5. additional
contact 2……………………………………………………………………………………………………………………………… 44
Part IX. Cooling 1.
Cooling……………………………………………………………………………………………………………………………………………….. 45 2.
Condition of activation …………………………………………………………………………………………………………………………. 46 3.
Additional contact ……………………………………………………………………………………………………………………………….. 46 4.
Heating circuit …………………………………………………………………………………………………………………………………….. 46
Part X. Sensor settings I. Sensor settings
……………………………………………………………………………………………………………………………………… 47
Part XI. Factory settings I. Factory settings
…………………………………………………………………………………………………………………………………….. 47
3
Part XII. Settings I.
Settings………………………………………………………………………………………………………………………………………………… 48
1. Language selection ………………………………………………………………………………………………………………………………. 48 2.
Time settings ………………………………………………………………………………………………………………………………………. 48 3.
Screen settings ……………………………………………………………………………………………………………………………………. 48 4.
Alarm sounds………………………………………………………………………………………………………………………………………. 48 5.
Notifications ……………………………………………………………………………………………………………………………………….. 48 6. Lock
…………………………………………………………………………………………………………………………………………………… 48 7. Software
version …………………………………………………………………………………………………………………………………. 49
Part XIII. Weekly control I. Weekly control
……………………………………………………………………………………………………………………………………… 49 Technical
data…………………………………………………………………………………………………………………………………………………. 51 Protections
and alarms…………………………………………………………………………………………………………………………………….. 52 Software
update ……………………………………………………………………………………………………………………………………………… 53 Used
sensors…………………………………………………………………………………………………………………………………………………… 53
4
I. SAFETY
Before using the device for the first time the user should read the following
regulations carefully. Not obeying the rules included in this manual may lead
to personal injuries or controller damage. The user’s manual should be stored
in a safe place for further reference. In order to avoid accidents and errors
it should be ensured that every person using the device has familiarized
themselves with the principle of operation as well as security functions of
the controller. If the device is to be sold or put in a different place, make
sure that the user’s manual is there with the device so that any potential
user has access to essential information about the device. The manufacturer
does not accept responsibility for any injuries or damage resulting from
negligence; therefore, users are obliged to take the necessary safety measures
listed in this manual to protect their lives and property.
WARNING · High voltage! Make sure the regulator is disconnected from the mains
before performing any activities involving the power supply (plugging cables,
installing the device etc.). · The device should be installed by a qualified
electrician. · Before starting the controller, the user should measure
earthing resistance of the electric motors as well as the insulation
resistance of the cables. · The regulator should not be operated by children.
· The device may be damaged if struck by a lightning. Make sure the plug is
disconnected from the power supply during storm. · Any use other than
specified by the manufacturer is forbidden. · Before and during the heating
season, the controller should be checked for condition of its cables. The user
should also check if the controller is properly mounted and clean it if dusty
or dirty.
Changes in the merchandise described in the manual may have been introduced
subsequent to its completion on July 18th, 2022. The manufacturer retains the
right to introduce changes to the structure. The illustrations may include
additional equipment. Print technology may result in differences in colours
shown.
Care for the natural environment is our priority. Being aware of the fact that
we manufacture electronic devices obligates us to dispose of used elements and
electronic equipment in a manner which is safe for nature. As a result, the
company has received a registry number assigned by the Main Inspector of
Environmental Protection. The symbol of a crossed out rubbish bin on a product
means that the product must not be thrown out to ordinary waste bins. By
segregating waste intended for recycling, we help protect the natural
environment. It is the user’s responsibility to transfer waste electrical and
electronic equipment to the selected collection point for recycling of waste
generated from electronic and electrical equipment.
5
II. DEVICE DESCRIPTION
EU-i-3 controller is a multi-function device intended for controlling central
heating systems. The principle of operation involves mixing the hot supply
water with the water returning from the heating circuit in order to reach the
desired temperature and maintain it on the same level all the time. The pump
connected to every valve circuit helps to distribute water through the heating
system. The pump should be installed downstream of the mixing valve and the
temperature sensor should be installed downstream of both the pump and the
valve to ensure precise water control at the valve output.
Thanks to advanced software, the controller offers a wide range of functions:
· Smooth control of three mixing valves · Control of DHW pump · Protection
against too high temperature of CH boiler water as well as too low temperature
of water returning to
CH boiler · Weather-based control · Weekly control · Two configurable no-
voltage outputs · Two configurable voltage outputs · Supporting three room
regulators with traditional communication (two-state) · Possibility of
connecting 3 dedicated room regulators with RS communication · Supporting a
room regulator with RS communication · Possibility of connecting ST-505
Ethernet module, ST-525 or WiFi RS which enable the user to control certain
functions and view some of the parameters via the Internet · Possibility of
connecting two additional modules controlling the valves (e.g. i-1, i-1m) it
enables the user to
control two additional valves · Possibility of controlling solar panels ·
Possibility of controlling CH boiler cascade
6
1
2
3
10
9
8
7
6
5
4
1. WiFi RS 2. ST-505 Internet module 3. ST-525 Internet module 4. ST-294v1 Room regulator 5. ST-280 Room regulator 6. ST-292 Room regulator 7. Dedicated room regulator RI-1 8. Dedicated room regulator RI-2 9. i-1m valve module 10. i-1 valve module
7
III. HOW TO INSTALL
EU-i-3 controller should be installed by a qualified person. It may be
installed as a free-standing device or as a panel mountable on a wall.
WARNING
Risk of fatal electric shock from touching live connections. Before working on
the controller switch off the power supply
and prevent it from being accidentally switched on. Remove the controller
cover to connect the wires.
Bolts fastening the controller cover
8
Left terminal strip
USB
Additional connector
RS Input
Earth bar
Right terminal strip
9
Connectors, symbols and example use 10
IV. MAIN SCREEN DESCRIPTION
The device is controlled using the touch screen. 1. INSTALLATION SCREEN
3
4
5
6
2 1
19 18 17 16
15
7
8 9 10
11
14 13
12
1. Pre-set room temperature 2. Current room temperature 3. Day of the week and time 4. Wi-Fi signal strength 5. Notification icon 6. Enter controller menu 7. External temperature 8. Current operation mode 9. Solar collector temperature 10. Pre-set and current DHW temperature 11. Accumulation tank temperature
12. Level of valve opening [%] 13. Scroll arrow 14. Return temperature 15.
Active additional contact (N1, N2 – voltage
contacts; B1, B2 – voltage-free contacts) 16. Temperature reading from CH
sensor 17. Pre-set and current temperature of the
heating circuit 18. Circuit switched off 19. Active cooling mode in each
circuit
2. PARAMETER AND PANEL SCREEN
· Parameter screen a record including the status of all active inputs and
outputs · Panel screen parameters of particular active circuits and
algorithms. Tap on a panel to start editing
its parameters.
11
V. QUICK SETUP OF THE CONTROLLER
12
Menu Fitter’s menu
Number of valves Valve 1
Additional contacts TECH RS regulator
Cascade Ethernet module
Solar collector Cooling
Sensor settings Factory settings
PART I
How to configure built-in valves, additional valves and room regulators I. HOW
TO CONFIGURE BUILT-IN VALVE
Only pump* Type of valve Opening time
CH sensor Pump activation Room regulator Weather-based control Mixing valve
settings Floor circuit settings** Factory settings
13
Valve menu
- select in case of circuit operation without a mixing valve ** this option appears when the floor valve type has been selected
1. Enter the fitter’s menu 2. Select the number of valves needed 3. Configure
one of then selecting `Valve 1′ option 4. Select the type of valve: CH valve,
Floor valve, Return protection, Swimming pool, Ventilation. The
principle of operation in the case of Swimming pool and Ventilation valves is
the same as in the case of CH valve. What changes is the graphics on the
installation screen.
· CO select if you want to control the temperature of the CH circuit with
the use of a valve sensor. The valve sensor should be installed downstream of
the mixing valve in the supply pipe.
· FLOOR select if you want to control the temperature of the underfloor
heating circuit. It protects the underfloor heating system against dangerous
temperature. If the user selects CH as the valve type and connects it to the
underfloor heating system, the fragile floor installation may be damaged.
· RETURN PROTECTION select if you want to control the return temperature of
the heating system with the use of a return sensor. With this type of valve,
only the return sensor and the CH boiler sensor are active; the valve sensor
is not connected to the controller. In this configuration, the valve protects
the CH boiler return against low temperature, and if the CH boiler protection
function is selected, it also protects the CH boiler against overheating. If
the valve is closed (0% opening), the water flows only through the short
circuit, while full valve opening (100%) means that the short circuit is
closed and water flows through the entire heating system.
WARNING
If CH boiler protection is disabled, the CH temperature does not influence the
valve opening. In extreme cases, CH boiler overheating is possible; therefore,
it is recommended to configure CH boiler protection settings.
Floor type
Floor circuit settings
Floor heating – summer
Decide if the valve should work in summer mode.
Max, floor temperature
The temperature above which the valve will close and the circulating pump will
be disabled.
WARNING If the selected valve type is different from the valve used in the
system, it may lead to the whole heating system damage.
NOTE The controller may support 3 built-in valves and two additional valves.
14
5. Set the opening time Opening time is the parameter defining the time
needed for the valve actuator to open the valve from 0% to 100%. CH opening
time should be the same as the value given on the rating plate of the valve
actuator.
Actuator opening time
6. Select CH sensor The selected sensor will serve as CH sensor. The reading
from the selected sensor determines the valve pump activation when the
function of pump activation above threshold is active.
EU-i-3
NOTE
If the CH sensor has not been connected and `Boiler protection’ function is
enabled, the controller will inform the user about the lack of sensor through
an alarm.
7. Enable the pump
Connecting CH sensor
Operation modes:
· Always OFF – the pump is disabled permanently and the device controls only
the valve. · Always ON – the pump operates all the time regardless of the
temperature of the heat source and the
valve. · ON above threshold – the pump is enabled above the pre-set activation
temperature. The setting range:
10°C – 55 °C. · Closing below temperature threshold – the valve will close
when the temperature drops below the
value defined in the parameter ON above threshold. As a result, the circuit
valve will be disabled.
8. Select one of the regulators in `Room regulator’ (optional). Once the option has been selected, define the type of regulator : standard regulator, TECH RS regulator).
15
Room regulator
OFF
Standard regulator
Tech RS regulator
Room controller
function
Standard regulator 1-3
Tech regulator Algorithm
Standard regulator
Select dedicated regulator
Room temperature difference
Room temperature difference
ST-280 regulator
Dedicated regulator 1-3
· Standard regulator a two-state regulator operating on an open/closed
basis. It offers the following functions: closing, room regulator temperature
lower, pump deactivation.
· Tech regulator Algorithm ( Tech RS regulator ) – controlling the pre-set
valve temperature on the basis of two parameters: Room temperature difference’ and
Change of pre-set valve temperature’. The pre-set valve
temperature is raised or lowered depending on the room temperature.
Additionally, it is possible to activate the room regulator functions: Pump
deactivation and Closing.
Example:
Room temperature difference 1°C Change of pre-set valve temperature 2°C When
the room temperature increases by 1°C, the valve pre-set temperature changes
by 2°C.
· Standard regulator (Tech RS regulator) a type of RS regulator operating on
the basis of the parameters defined in the room regulator functions: closing,
room regulator temperature lower and pump deactivation.
· Select dedicated regulator (Tech RS regulator) – Pre-set valve temperature
control is performed via room regulators dedicated to the EU-i-3 controller.
The user may register up to 4 dedicated regulators: the ST-280 regulator or
Dedicated regulators 1-3.
· How to register dedicated regulators: In order to register a dedicated
regulator, go to the MenuFitter’s menuValve (1,2 or 3)Room reg.Tech RS
reg.Select dedicated reg. Dedicated reg. (1,2 or 3). Tap on Dedicated regulator’ (1,2 or 3) to start the registration process of the dedicated regulator. Confirm registration by selecting OK. Next, start the registration process in the regulator. After successful registration, go back to
Tech RS
regulator’ in order to select the
16
regulator function: Standard regulator’ or
Tech regulator Algorithm’ (this
step is necessary to ensure proper operation of the regulator). Follow the
same steps while registering another regulator.
NOTE
It is possible to register up to 3 dedicated regulators to the controller. A
dedicated regulator does not cooperate with additional modules I-1 ( it only
supports built-in valves).
· Room regulator functions:
1. Closing – when the room regulator reports that the room temperature is too
low, the valve starts closing (to reach the minimum valve opening). 2 Room
regulator temperature lower – when the regulator reports that the pre-set room
temperature has been reached, the pre-set valve temperature will change by the
value of `Room reg. temp. lower’ parameter (pre-set temperature – pre-set
reduction temperature). 3. Pump deactivation – when the room regulator reports
that the pre-set room temperature has been reached, the circuit pump will be
disabled.
EU-i-3
II. WEATHER-BASED CONTROL
Example connection of a two-state regulator
For the function of weather control to be active, the external sensor mustn’t
be exposed to sunlight or influenced by the weather conditions. After it has
been installed in an appropriate place,
For the valve to operate correctly, the user defines the pre-set temperature
(downstream of the valve) for 4 intermediate external temperatures: -20ºC,
-10ºC, 0ºC and 10ºC.
In order to configure the pre-set temperature value, touch and drag
appropriate points up or down (the pre-set valve temperature will be displayed
on the left), or use arrows to select the temperature value. Subsequently, the
display will show the heating curve.
17
NOTE
This function requires the use of external sensor.
NOTE
Once this option has been activated, it is possible to change the preset valve
temperature only by selecting the range on the heating curve.
EU-i-3
Connecting the external sensor
NOTE When return protection valve type has been selected, the weather-based
control function does not work. The cooling mode has its own heating curve for
the weather-based control function: Cooling Heating circuit Circuit 1-3
Heating curve.
NOTE Further settings of the external sensor are available in Sensor settings.
III. MIXING VALVE SETTINGS
· Temperature control – This parameter determines the frequency of water
temperature measurement (control) behind the CH valve. If the sensor indicates
a change in temperature (deviation from the pre-set value), then the valve
actuator will open or close by the set stroke, in order to return to the pre-
set temperature.
· Opening direction – If, after connecting the valve to the controller, it
turns out that it is connected the other way round, then the power supply
cables do not have to be switched. Instead, it is enough to change the opening
direction in this parameter: LEFT or RIGHT. This function is available only
for built-in valves.
· Minimum opening – The parameter determines the smallest valve opening.
Thanks to this parameter, the valve may be opened minimally, to maintain the
smallest flow. If you set it at 0°, the valve pump will be disabled.
18
· Hysteresis the hysteresis between the pre-set temperature and current
valve temperature.
· Single stroke – This is a maximum single stroke (opening or closing) that
the valve may make during one temperature sampling. If the temperature is near
the pre-set value, the stroke is calculated on the basis of <proportionality
coefficient> parameter value. The smaller the single stroke, the more
precisely the set temperature can be achieved. However, it takes longer for
the set temperature to be reached.
· Proportionality coefficient – Proportionality coefficient is used for
defining valve stroke. The closer to the preset temperature, the smaller the
stroke. If the coefficient value is high, the valve takes less time to open
but at the same time the opening degree is less accurate. The following
formula is used to calculate the percent of a single opening:
(PRE-SET_TEMP – SENSOR_TEMP) * (PROP_COEFF /10)
· Sensor calibration – this function enables the user to calibrate the built-
in valve at any time. During this process the valve is restored to its safe
position in the case of CH valve it is fully opened whereas in the case of
floor valve it is closed.
· Opening in CH calibration this function enables the user to change the
direction of valve opening/closing during calibration.
· Weekly control – this function is described in section XIII.
· Valve deactivation – once this has been selected, valve operation depends on
weekly control settings and external temperature.
Weekly control – once this function has been selected, the user may
activate/deactivate weekly operation schedule and define the time when the
valve will be closed.
External temperature – the user may set nighttime and daytime temperature at
which the valve will be deactivated. It is also possible to program hours when
the controller will operate in day or night mode. The user sets the hysteresis
of valve deactivation temperature.
NOTE
The function of Valve deactivation based on outside temperature does not work
in cooling mode. The Return protection type does not offer Valve deactivation
function.
· Protections
Return protection – this function is used to set CH boiler protection against
too cool water returning from the main circuit, which could cause low-
temperature boiler corrosion. The return protection involves closing the valve
when the temperature is too low, until the short circulation of the boiler
reaches appropriate temperature. The user may set the temperature threshold
below which the return protection will be activated.
NOTE
To ensure the effectiveness of this protection, it is necessary to activate
the valve in the heating circuit menu and connect the return sensor.
19
CH boiler protection – this function serves to prevent hazardous growth of CH
boiler temperature. The user sets the maximum acceptable CH boiler
temperature. In case of hazardous growth in the temperature, the valve begins
to open in order to cool the CH boiler down. This function is disabled by
default.
NOTE This option is unavailable for floor valves.
20
IV. QUICK SETUP OF THE MIXING VALVE
NUMBER OF VALVES Select the number of valves
needed.
VALVE 1 Select a valve and move on
to configure it.
VALVE TYPE Select appropriate type of
valve.
OPENING TIME Copy the time from the actuator rating plate.
SELECT CH SENSOR Select appropriate sensor.
PUMP ACTIVATION Define the time of pump
operation.
ROOM REGULATOR If you have a two-state
regulator.
HEATING CIRCUIT Enable the circuit assigned
to the valve.
If you have more valves, follow the same steps.
21
V. ADDITIONAL VALVES
Registration: 1. Connect additional valve to the main controller using RS
cable 2. Fitter’s menu -> select the number of additional valves 3. Find the
additional valve, go to registration and enter the code from the additional
module.
OT OT
EU-i-3
Example connection between additional valve and EU-i-3 main controller
NOTE
An exclamation mark next to the circuit icon means that the circuit is
disabled or the additional valve has not been registered.
NOTE
Registration code consists of 5 digits and can be found on the rating plate on
the back of i-1m. In the case of i-1 valve controller, the code can be found
in software version submenu.
22
PART II Controller operation modes
Menu
Heating circuit Operation mode
I. WATER TANK PRIORITY
In this mode, water tank pump (DHW) is activated first in order to heat
domestic water. Mixing valves are activated once the pre-set DHW temperature
has been reached. The valves operate continuously until the water tank
temperature drops below the pre-set value by the pre-defined hysteresis.
NOTE The valves close to 0% opening.
NOTE
When the CH boiler protection is activated, the valves will open even if the
water tank temperature is too low.
NOTE
Return protection opens the valve to 5% if the water tank temperature is too
low.
II. PARALLEL PUMPS
In this mode, all pumps and valves operate simultaneously. The valves maintain
the pre-set temperature and the water tank is heated to the pre-set
temperature.
III. HOUSE HEATING
In this mode, only the house circuit is heated and the main task of the
controller is to maintain the pre-set valve temperature.
NOTE
DHW pump scheme will be displayed although the house heating mode is active.
To delete the pump image from the scheme, it is necessary to deactivate it in
`Operation modes’ of DHW pump.
NOTE
To avoid an alarm being activated when the DHW sensor is not connected,
disable the DHW pump in `Operation modes’ of DHW pump.
IV. SUMMER MODE
In this mode, the CH valves are closed to prevent unnecessary house heating.
If the CH boiler temperature is too high, the valve will be opened as an
emergency procedure ( it requires activating `CH boiler protection’ function).
23
V. AUTOMATIC SUMMER MODE
This option involves automatic switching between modes. When the external temperature exceeds the activation threshold of Summer automatic mode, the valves will close. When the external sensor detects that a given threshold has been exceeded, the controller switches to summer mode. Average temperature is calculated on an ongoing basis. When it is lower than the pre-set value, the operation mode will switch to the previous one.
· Summer mode temperature threshold this option enables the user to set the
outside temperature value above which summer mode will be enabled.
· Averaging time the user defines the period of time which will be used to
calculate the average outside temperature.
NOTE
U NOTE
NOTE
This function requires the external sensor to be active.
When the temperature drops below the threshold, the controller will switch to the previous mode.
When the connection is configured for the first time and the controller fails to switch the mode, it is necessary to reset it. It results from averaging time (Fitter’s menu > sensor settings).
PART III DHW pump and Anti-legionella
Menu
Heating mode DHW pump
I. HOW TO CONFIGURE DHW PUMP OPERATION
· Operation mode Operation mode
Automatic mode
DHW pump work according to the settings: pre-set temperature, hysteresis,
activation delta, activation temperature, maximum CH temperature and weekly
control.
OFF
When DHW is disabled, DHW image disappears from the main screen.
Heating
The pump operates until DHW reaches the pre-set temperature. In this mode the
source temperature and maximum CH temperature are not taken into account.
24
EU-i-3
Connecting DHW sensor · Pre-set DHW temperature – This option is used to
define the pre-set temperature of domestic hot water. Once
the temperature is reached, the pump is disabled.
· DHW hysteresis – the temperature difference between device activation and
its deactivation (e.g. when the preset temperature is set at 60ºC and the
hysteresis value is 3ºC, the device will be disabled when the temperature
reaches 60ºC and it will be activated again when the temperature drops to
57ºC).
· Activation delta this function is displayed only in automatic operation
mode. It is the minimum difference between DHW temperature and CH temperature
which is necessary for the pump is enabled. For example, if activation delta
is 2°C, CH pump will be enabled when the source temperature will exceed
current DHW tank temperature by 2°C provided that the activation threshold has
been reached.
· DHW pump activation temperature – this parameter defines the CH temperature
which must be reached to enable the pump.
· Maximum CH temperature – this parameter defines the temperature above which
the pump will be enabled to transfer the excess of hot water to water tank.
· Weekly control – this function is described in section XIII. · Source sensor
– this function enables the user to choose the source sensor which will
provide temperature data.
II. ANTI-LEGIONELLA
Thermal disinfection involves increasing the temperature to the required
disinfection temperature in the tank – reading from the upper sensor of the
tank. Its aim is to eliminate Legionella pneumophila, which reduces the
cellular immunity of the body. The bacteria often multiply in hot water
reservoirs. After activating this function, the water tank is heated up to a
certain temperature (Heating circuit> DHW pump> Anti-legionella> Pre-set
temperature) and the temperature is maintained for a specified disinfection
time (Heating circuit> DHW pump> Anti-legionella> Operation time). Next,
standard operation mode is restored.
25
From the moment the disinfection is activated, the disinfection temperature
must be reached within the time set by the user (Heating circuit> DHW pump>
Anti-legionella> Max. time of disinfection heating). Otherwise, this function
will be deactivated automatically.
Using
· Operation manual activation of the disinfection procedure, which is based
on Operation time’ and
Max. time of disinfection heating’.
· Automatic operation activation of the disinfection procedure based on
weekly schedule.
· Pre-set temperature the temperature maintained throughout disinfection
process.
· Operation time this function is used to set the duration time of
disinfection (in minutes) throughout which the temperature will be maintained
at a pre-set level.
· Max. time of disinfection heating it is the maximum time of thermal
disinfection process (LEGIONELLA function) from the moment of its activation
(regardless of the temperature at that time). If the water tank fails to reach
or maintain the pre-set disinfection temperature throughout the whole
disinfection period, the controller returns to basic operation mode after the
time defined in this parameter.
III. PUMP ANTI-STOP
Menu
Heating mode Pump anti-stop
When this function is active, the valve pump is enabled every 10 days for 5 minutes. It forces pump operation and prevents scale deposit outside the heating season when the pump inactivity periods are long.
26
PART IV
Manual mode
I. MANUAL MODE
This function enables the user to check if every device works properly by
switching on each device separately: DHW pump, additional contacts and valves.
In the case of valves, it is possible to initiate opening and closing as well
as check if the pump of a given valve works properly.
Manual mode
Valve 1
Valve 2 Valve 3 DHW pump Voltage contact 1,2 Voltage-free contact 1,2
Additional valve 1-2
Valve pump Valve opening Valve closing
Stop The same submenu as for Valve 1 The same submenu as for Valve 1
The same submenu as for Valve 1
NOTE Additional valves appear in manual mode only after they have been
registered.
Draw your heating system scheme including all active valves and devices
connected to additional contacts. It will help you to configure your heating
system.
27
Blank space for your scheme:
PART V Additional contacts
I. VOLTAGE CONTACTS AND VOLTAGE-FREE CONTACTS
An example connection scheme involves contact 1. In reality it may be any
other contact.
NOTE
Voltage contacts 1, 2 are intended for connecting devices powered by 230V.
NOTE
Voltage-free contacts 1,2 operate on `open/close’ basis.
28
II. HOW TO CONFIGURE A CONTACT
In each algorithm the user may configure the following parameters: · Activity
operation in summer mode, in the remaining modes or in both cases. · Status
during alarm this function enables the user to decide if the device
connected to this additional contact should be switched on (operating
according to the selected algorithm) or switched off during an alarm. NOTE
This section includes pictorial diagrams of system connections. They cannot
replace CH installation project. Their main aim is to present how the
controller system may be expanded.
29
III. VOLTAGE AND VOLTAGE-FREE CONTACT ALGORITHMS
1. CIRCULATING PUMP This algorithm is intended for controlling the operation
of e.g. a circulating pump. The user may select the operation mode and adjust
the pre-set temperature as well as the operation time and pause time of the
contact. Once the algorithm has been selected, the installation screen shows a
graphic representation of the circuit.
An example connection and control of the circulating pump Operation modes:
1. Weekly control select the days and time periods when the circulating
pump connected to the contact will be active. During these periods the contact
will operate according to the following parameters: operation time, pause time
and pre-set temperature.
2. Automatic operation the contact operation is based on operation time and
operation pause parameters. 2. BUFFER PUMP This algorithm is intended for
controlling the operation of e.g. buffer pump according to temperature
readings from two sensors: the source sensor and the buffer sensor. Condition
for activation: The device connected to the contact will be enabled when the
temperature read by the source sensor is higher than the temperature read by
the buffer sensor by the value of activation delta. The device will be
disabled if the activation condition has been met and the buffer sensor
temperature increases by the hysteresis value.
· Activation delta the user may define the difference between the source
temperature and the buffer temperature.
· Activation threshold the user may define the threshold temperature for the
device activation (read by the source sensor).
· Hysteresis – the user may define the value at which the contact will be
disabled (if the activation condition has been met).
· Buffer sensor the user may select the sensor. · Source sensor the user
may select the sensor.
30
Example:
Activation delta: 10°C
Hysteresis: 2°C
Source temperature: 70°C
The device connected to the contact will be enabled when the buffer temperature drops below 60°C (source temp. delta). It will be disabled when the temperature increases to 62°C (Source temp. – delta) + hysteresis.
3. CH PUMP
This algorithm is intended for controlling the operation of e.g. CH pump
according to the readings from one temperature sensor. The device connected to
the contact will be enabled when the activation threshold temperature has been
reached. It will be disabled when the temperature drops (including
hysteresis).
· Range (additional settings) select this option to create a temperature
range within which the CH pump will operate.
· Activation threshold select this option to set the temperature value above
which the contact will be enabled. · Deactivation threshold (additional
settings) this option appears after the RANGE function has been selected.
The user may set the temperature value above which the contact will be
disabled, taking into account stable overheating value (deactivation threshold
- stable overheating value 3°). · Hysteresis the user may set the
temperature value below which the contact will be disabled (Activation
Threshold-Hysteresis). · Heating need (additional settings) it is a pre-set
value which will be taken into account when you select the contact with the CH
pump operating in Heating need algorithm. This function appears after the
RANGE function has been selected. · External temperature (additional settings)
the contact operates according to external temperature value (if an external
temperature sensor is used). The user may set a threshold external temperature
at which the contact will be disabled. It will be enabled when the external
temperature drops below the threshold and when the activation threshold has
been reached. · Sensor the user may select the heat source sensor. · Room
regulator the user may configure the influence of the room regulators on the
contact operation. If this option has been selected, the device connected to
the contact will be enabled if the activation threshold has been reached and
if any of the selected regulators reports too low temperature (heating need).
The device will be disabled when all selected regulators report that the room
temperature has been reached.
31
4. ADDITIONAL HEAT SOURCE The algorithm is based on the readings from one
temperature sensor. The device connected to the contact will be enabled when
the temperature measured by the sensor drops. It will be disabled when the
temperature increases by the pre-set overheating value.
· Activation threshold the user may set the temperature value below which
the contact will be enabled. · Overheating (additional settings) – the user
may set the temperature value above which the contact will be
disabled, taking into account activation threshold (Activation threshold +
Overheating threshold). · Sensor the user may select the heat source sensor
which will provide data for contact activation/deactivation. · Room regulator
the user may configure the influence of the room regulators and DHW on the
contact
operation. If this option has been selected, the device connected to the
contact will be enabled if the activation threshold has been reached and if
any of the selected options reports too low temperature (heating need). The
device will be disabled when all selected options report that the set
temperature has been reached or when the condition (Activation
threshold+Hysteresis) has been met. Example: Part of the CH system is heated
by a fireplace and a boiler. The boiler is connected to the voltage-free
contact and the fireplace temperature is read by the T4 sensor (CH). The
additional heat source will be activated when the sensor temperature drops
below the activation threshold. It will operate until the temperature exceeds
the threshold value by the overheating value. The device will be disabled when
the room regulator informs that the set temperature has been reached or when
the temperature read by the T-4 sensor exceeds the activation threshold by the
overheating value.
32
5. BUFFER
The algorithm is based on the readings from two temperature sensors. The
device connected to the contact will be enabled when the temperature of both
sensors drops below the pre-set value. It will operate until the pre-set
temperature of the buffer bottom sensor is reached.
·
Pre-set buffer top the user may define the pre-set temperature.
·
Pre-set buffer bottom the user may define the pre-set temperature.
·
Top sensor – the user may select the sensor.
·
Bottom sensor – the user may select the sensor.
6. DHW BUFFER The algorithm is based on the readings from two temperature
sensors. The device connected to the contact will be enabled if the
temperature on any of the sensors drops below the set value by the value of
hysteresis. After the pre-set temperature of buffer top has been reached, the
device will continue to work for the delay time defined by the user. It will
be disabled after the pre-set temperature of both sensors has been reached. It
is also possible to set the operation of this device based on a weekly program
(described in detail in part XIII), which controls the set temperature of the
upper sensor. The user can select which sensor will function as the upper and
lower sensor.
33
· Pre-set buffer top – this function enables the user to define the pre-set
temperature for the upper part of the buffer (top sensor). Once this value is
reached and the delay time is over, the pump is disabled (provided that the
pre-set buffer temperature bottom has also been reached).
· Pre-set buffer bottom – this function enables the user to define the pre-set
temperature for the lower part of the buffer (bottom sensor).
· Top hysteresis the user may set the temperature value at which the contact
will be enabled, taking into account pre-set top temperature (Pre-set
temperature-Hysteresis).
· Bottom hysteresis the user may set the temperature value at which the
contact will be enabled, taking into account pre-set bottom temperature (Pre-
set temperature-Hysteresis).
· Delay this function enables the user to define how long the device should
remain active after the pre-set buffer temp. top has been reached.
· Weekly control – this function is described in detail in section XIII · Top
sensor the user may select the sensor which will function as the top sensor.
· Bottom sensor – the user may select the sensor which will function as the
bottom sensor.
7. HEATING NEED
The algorithm is based on the readings from one temperature sensor. The device
connected to the contact will be enabled if the temperature on the selected
sensor drops below the highest set value minus the hysteresis of the selected
circuits with a valve. It is also possible to select the DHW circuit; the
device will be enabled when the pre-set temperature decreases by the DHW
hysteresis. It will be disabled after the highest pre-set temperature of the
selected circuits with valves increases by the overheating value, and in the
case of DHW – by the the value of DHW overheating, or when the pre-set
temperatures in all the selected circuits are reached.
The heating need function may also be based on the operation of the following
contacts ( after setting the algorithm: CH pump, additional heat source,
buffer, DHW buffer).
· Sensor – the user may select the sensor to provide readings for the contact
operation. · Hysteresis – the user may set the temperature value below which
the contact will be enabled, taking into account
the pre-set valve temperature (Pre-set temperature-Hysteresis). · DHW
HYSTERESIS – the user may set the temperature value below which the contact
will be enabled, taking into
account the pre-set DHW temperature (Pre-set DHW temperature-Hysteresis). ·
Overheating the user may set the value of the pre-set temperature increase
for the selected sensor (Pre-set
temperature+Overheating). · DHW overheating – the user may set the value of
the pre-set temperature increase for the DHW circuit (Pre-set
DHW temperature+Overheating).
Example:
The controller controls a system heated with CH boiler connected with a
buffer, with an additional heating device with three valves. Boiler is
connected to a voltage-free contact and operates in Heating need mode. When
the temperature of any selected heating circuit is too low and the T4 sensor
temperature is too low to heat such a circuit, the additional heat device will
be enabled. It will remain active until it reaches the maximum necessary
temperature + the pre-set overheating value. The contact will be disabled when
this value has been reached or when all selected devices reach their pre-set
temperatures. It will be enabled again when the heat source temperature drops
below the pre-set value by the hysteresis value or when the selected circuits
report too low temperature.
34
8. OPERATION CONTROL
The algorithm is based on the readings from one temperature sensor. The device
connected to the additional contact will be used to control the operation of a
different contact, DHW pump or room regulators. The device connected to the
contact will be enabled when the controlled contact is switched on and the
selected sensor fails to reach the pre-set temperature when the delay time is
over. It will be disabled when the controlled contact switches off or when the
selected sensor reaches the pre-set temperature. When the pre-set temperature
is reached and the temperature drops again below the hysteresis, the device
will be enabled after the time defined as delay after error is over.
· Pre-set the user may define the pre-set temperature value for the selected
sensor. · Hysteresis – the user may set the temperature value below which the
contact will be enabled, taking into account
the pre-set temperature (Pre-set temperature-Hysteresis). · Delay the user
may set the delay time after which the contact will be enabled. · Delay after
error – the user may set the delay time after which the contact will be
enabled if the temperature
drops again. · Sensor – the user may select the sensor which will be used to
control the contact operation. · Additional contact – the user may select the
device to be controlled – additional contact, DHW pump or room
regulator. · Weekly control – the user may define the time and days when the
operation control function will be active.
Example: Part of the heating system is handled by 2 CH boilers and a buffer.
The task of the boilers is to heat the water in the buffer. Boiler is
connected to voltage-free contact 2 with operation control function. The other
boiler is connected to voltagefree contact 3 with buffer function. Buffer
temperature is read by sensor T4 (CH). Additional contact supporting the
boiler will be used to control the operation of the other boiler. If the
controlled device does not get activated and the selected sensor fails to
reach the pre-set temperature within the delay time, the controller will
activate the device connected to the controlling contact.
35
9. DHW
This algorithm is intended for controlling the operation of e.g. DHW pump. It
is based on the readings from two sensors. The device connected to the
additional contact will be enabled if the temperature measured by the source
sensor is 2°C higher than the activation threshold and when the temperature
drops below the pre-set value by the value of hysteresis. It will be disabled
when the pre-set temperature of DHW sensor has been reached and if the source
sensor hasn’t reached the activation threshold.
· Activation threshold the user may set the temperature value above which
the contact will be enabled. · Hysteresis the user may set the temperature
value below which the contact will be enabled, taking into account
the pre-set temperature (Pre-set temperature+Hysteresis). · Pre-set DHW
temperature the user may define the pre-set temperature. · Maximum
temperature the user may define the maximum temperature for the source
sensor. When this value
is reached, the contact is enabled and it will remain active until the source
temperature drops by 2 °C below the maximum temperature or the DHW sensor
temperature exceeds the source temperature. This function protects the system
against overheating. · Source sensor the user may select the sensor which
will provide temperature readings for controlling the contact. · DHW sensor –
the user may select the sensor which will provide temperature readings for
controlling the contact (pre-set temperature).
10. CONTROLLING THE ROOM REGULATOR
This algorithm is based on the signal from the room regulator. The device
connected to the contact will be enabled when the regulator fails to reach the
pre-set temperature (the regulator contact is closed). It will be disabled
when the regulator reaches the pre-set temperature value (the regulator
contact is open). The device operation may also depend on the signal from more
than one room regulator – it will be disabled only after all room regulators
report that the pre-set room temperature has been reached. If DHW option is
selected, the device connected to the additional contact will be enabled and
disabled depending on the pre-set DHW temperature – when the pre-set
temperature value has been reached, the device will be disabled.
36
11. RELAYS
This algorithm is intended for controlling the device which will be activated
together with the selected system devices. Enter Operation modes and configure
the mode of contact activation:
· All – the contact will be enabled when all selected relays are active. · Any
– the contact will be enabled when any of the selected relays is active. ·
None – the contact will be enabled if none of the selected relays is active. ·
Activation delay the pre-set time after which the contact will be enabled. ·
Deactivation delay – the pre-set time after which the contact will be
disabled.
12. WEEKLY CONTROL
Weekly control algorithm enables the user to configure a schedule of contact
activation. The user defines the days and time periods during which the device
connected to the contact will be operating.
6
1
2
3
4
5
37
1. OFF 2. Copy the previous step 3. ON 4. Change the time period backwards 5. Change the time period forwards 6. Time period bar (24 hours)
Example:
In order to program valve closing for 09:00 – 13:00, follow these steps:
1. Select
2. Use the icon
to set the time period: 09:00 – 09:30
3. Select
4. Use the icon
to copy the setting (the colour will change to red)
5. Use the icon
to set the time period: 12:30 – 13:00
6. Confirm by pressing
It is possible to copy the settings for selected days of the week: Select
Select the day to copy the settings from
Select day(s) to which the settings will be copied
38
Voltag e Contact 1
Voltag e Contact 2 Volt.-free Contact 1 Volt.-free Contact 2
13. MANUAL MODE This option enables the user to enable/disable a given
contact permanently. 14. OFF This function enables the user to deactivate the
additional contact altogether.
Part VI Cascade
I. CASCADE
This algorithm is used to control the devices e.g. CH boilers using additional
contacts. Depending on the mode selected, the boilers will be switched on one
by one.
1. SELECT OPERATION ALGORITHM · Schedule – In schedule mode, the contacts are
enabled according to the pre-set order, which a qualified fitter may define in
Schedule modification function. All contacts are activated after the pre-set
pause time, when the need for activating a contact is reported. If the need to
disable the contact is reported, the contact is deactivated after the pre-set
operation time. If a change (enable/disable) is introduced during one of the
two timers’ operation, the countdown starts anew from the moment of
introducing the change.
There are separate settings for DAY and NIGHT. They work in the same way.
Operation time and pause time is separate for each contact. It is also
different for day and night in the case of every contact. It is possible to
reset the motohours. · Motohours – The order in which particular contacts are
activated is determined by their operation time so far (motohours). The
contacts with the smallest number of motohours will be activated first
(current number of motohours is displayed in panel view). The contacts will be
deactivated one by one, starting from the one with the largest number of
motohours. The operation time and pause time are the same for all contacts.
When the need for activating the first contact is reported, the contact is
enabled at once (Pre-set temp. – Hysteresis). The next contacts are activated
after the pre-set pause time. When it is necessary to deactivate a contact, it
happens after the pre-set operation time. The only exception is when main
boiler option is selected on the selected contact. Such a boiler will always
be enabled as the first one and disabled as the last one. If the main boiler
is active, the next boiler which will be activated after the need to activate
the contact is reported, will be switched on after the pause time is over.
39
2. OPERATION MODE
· Pre-set temperature the cascade will operate on the basis of the readings
from the selected source sensor and the pre-set temperature. Go to Additional
contacts and select the additional contacts working in a cascade. Next,
configure the pre-set temperature and hysteresis and select the source sensor.
When the temperature measured by the source sensor drops (Pre-set temp. –
Hysteresis), the first contact will be enabled (according to the selected
operation algorithm). The contact will operate for the pre-set pause time.
When the pause time is over, another contact will be enabled (according to the
selected operation algorithm). Operation time works similarly to pause time.
When the heat source temperature has been reached when the operation time is
over, the contacts will be disabled one by one.
· Heating need The algorithm is based on the readings from one temperature
sensor. The first contact selected in Additional contacts will be enabled when
the temperature measured by the selected sensor drops below the highest pre-
set temperature by the hysteresis of the selected circuits with a valve. It is
also possible to select DHW circuit – the device will be enabled when the
temperature drops by the value of DHW hysteresis. Within the range of pre-set
temperature reduced by hysteresis (Pre-set temp. – Hysteresis) and the pre-set
temperature next contacts will not be enabled – the contacts’ operation will
be maintained without activating next contacts. When the temperature drops
below the pre-set value by hysteresis, the contacts are activated one by one,
according to pause time parameter. When the source sensor exceeds the pre-set
temperature by the value of overheating, the contacts will be disabled one by
one, according to operation time parameter. If all selected circuits report no
heating need, all contacts will be disabled at once, regardless of the
operation time.
· Weather-based control – This operation mode depends on the outside
temperature. The user defines temperature ranges and a corresponding number of
boilers which will be enabled (Fitter’s menu > Cascade > Weather-based control
CH boiler activation temperature 1-4).
3. ADDITIONAL CONTACTS
All contacts may operate in a cascade. This option enables the user to select particular contacts for a cascade.
4. SELECT SENSOR
The user may select the sensor which will provide temperature readings for the cascade.
5. MAIN BOILER If Main boiler option is selected in a given contact (optional), in every operation mode this contact will be enabled as the first one and disabled as the last one. Only in Heating need mode, when all selected circuits report no heating need, all contacts will be disabled at the same time.
6. RESET MOTOHOURS It is possible to reset the motohours for all contacts: Fitter’s menu > Cascade > Reset motohours. 7. FACTORY SETTINGS This function enables the user to restore factory settings of the cascade algorithm.
40
PART VII
Ethernet module
I. ETHERNET MODULE
Internet module is a device enabling the user remote control of the heating
system. The user controls the status of all heating system devices on a
computer screen, a tablet or a mobile phone. Apart from the possibility to
view the temperature of every sensor, the user can change the pre-set
temperature of the pumps as well as the mixing valves. This module may also
support additional contacts or a solar collector. If a dedicated module ST-525
is connected, it is necessary to choose an appropriate WiFi network (and enter
the password if necessary). After switching the module on and selecting DHCP
option, the controller automatically downloads such parameters as IP address,
IP mask, Gateway address and DNS address from the local network. If any
problems arise when downloading the network parameters, they may be set
manually. The procedure of obtaining these parameters is described in detail
in the instruction manual of the Internet module.
NOTE This type of control is available only after purchasing and connecting an
additional controlling module ST-505, ST-525 or WiFi RS, which is not included
in the standard controller set.
41
PART VIII
Solar collector
I. SOLAR COLLECTOR
This option is used to configure the settings of solar collector and
accumulation tank.
ON Automatic control mode ON. OFF Automatic control mode OFF.
NOTE ON/OFF option appears only after the contact has been selected.
1. SOLAR COLLECTOR
NOTE
The contacts which have been selected in other algorithms will not be
displayed in Additional contact function.
· Collector overheat temperature – it is the acceptable alarm temperature of
the solar collector at which the pump is forced to activate in order to cool
down the solar panels. The discharge of warm water will take place regardless
of the tank pre-set temperature. The pump will operate until the tank
temperature drops below the alarm temperature by alarm hysteresis value
(Fitter’s menu > Solar collector > Solar collector > Alarm hysteresis).
· Maximum collector temperature – using this setting the user declares the
maximum value of the collector alarm temperature at which the pump may be
damaged. This temperature should be adjusted according to the collector
technical specification.
· Minimum heating temperature – if the collector temperature is higher and
starts to drop, the controller disables the pump when the minimum heating
temperature is reached. When the collector temperature is below this
42
threshold and starts to increase, the pump is activated when the minimum
heating temperature plus hysteresis ( 3°C ) is reached. The threshold heating
temperature is not active in the emergency mode, manual mode or collector
defrosting.
· Alarm hysteresis – using this function the user sets the value of the
collector alarm hysteresis. If the collector reaches the alarm temperature
(Overheat temperature) and the pump is activated, it will be deactivated again
when the collector temperature drops below the overheat temperature by the
value of this hysteresis.
· Anti-freeze temperature – this parameter determines the minimum safe
temperature at which glycol liquid does not freeze. In case of a significant
drop in the collector temperature (to the value of Anti-freeze temperature),
the pump is activated and operates continuously until the collector reaches
safe temperature.
· Defrosting time – using this function the user determines for how long the
pump will be activated once Collector defrosting function is selected.
· Collector defrosting – this function enables the user to activate the
collector pump manually in order to cause the snow deposited on the solar
panels to melt. Once this function is activated, the mode is active for a
userdefined period of time. After this time automatic operation is resumed.
NOTE Before activating the solar collector, make sure that PT-1000 sensor is
connected to C4 sensor.
2. ACCUMULATION TANK
· Pre-set temperature This option is used to define the pre-set tank
temperature at which the collector pump will be disabled.
· Maximum temperature This function is used to set the maximum safe
temperature which the tank may reach in case of collector overheat.
· Minimum temperature This function is used to set the minimum temperature
which the tank may reach. Below this temperature the pump will not be enabled
in collector defrosting mode.
· Hysteresis If the tank reaches the pre-set temperature and the pump
switches off, it will be enabled again after the tank temperature drops below
the pre-set temperature by the hysteresis value.
· Cooling to set temperature When the collector temperature is lower than
the tank temperature, the pump is activated to cool the tank down.
· Sensor selection This option is used to select the sensor which will send
temperature data to the main controller. Return sensor is the default sensor.
· Pre-set temp. of tank 2 this function is used to define the pre-set
temperature of tank 2. When this value has been reached, the valve switches to
heat the tank with heating need to its pre-set temperature.
· Maximum temp. of tank 2 this parameter is used to define the maximum safe
temperature value which tank 2 may reach in case of collector overheating.
43
· Hysteresis of tank 2 if tank 2 reaches the pre-set temperature and the
pump is disabled, it will be enabled again when the temperature of tank 2
drops below the pre-set value by this hysteresis.
· Sensor of tank 2 this option enables the user to select the sensor which
will provide the main controller with temperature readings. Additional sensor
2 is the default setting.
· Valve hysteresis this setting concerns the control of a switching valve
while cooling down the collector in summer mode or alarm mode or during
defrosting. The valve hysteresis is the difference between the tanks’
temperatures at which the valve switches to the other tank.
3. PUMP SETTINGS · Solar pump deactivation delta This function determines
the difference between the collector temperature and the tank temperature at
which the pump is deactivated in order not to cool down the tank. · Solar pump
activation delta This function determines the difference between the
collector temperature and the tank temperature at which the pump is activated.
4. ADDITIONAL CONTACT This option is used to select the additional contact
which will handle the solar collector pump. The user may only choose these
contacts which have not been assigned other algorithm. 5. ADDITIONAL CONTACT 2
This option is used to select the additional contact for the valve switching
between the two accumulation tanks. The collector circuit graphic on the
installation screen will change to illustrate 2 accumulation tanks and a
switching valve.
44
Part IX Cooling
Fitter’s menu Cooling
Condition of activation
Additional contact
Heating circuit Factory settings
Operation mode Summer mode Constant mode Regulator input
1,2,3 Pre-set temperature Voltage contact
1,2 Voltage-free contact 1,2
Circuit 1-3
Additional circuit 1,2
OFF
All
Any
Activity
Select sensor Pre-set
temperature Hysteresis
Activity Pre-set temperature Heating curve Pump activation threshold Activity
Pump activation threshold
1. COOLING
Select this function to control the temperature of the cooling system (the
valve opens when the pre-set temperature is lower than the temperature
measured by the valve sensor).
NOTE With this valve type, the following options do not work: CH boiler protection, return protection.
45
2. CONDITION OF ACTIVATION In this submenu, the user selects the operation
mode and defines the necessary condition which must be met to activate cooling
in a particular circuit. Example: The selected condition is Regulator 1 and 2
inputs and the selected operation mode is All. The condition which must be met
to activate cooling is a signal from both regulator inputs. If the user
selects Any as the operation mode, cooling is enabled when any of the inputs
sends a signal. 3. ADDITIONAL CONTACT During cooling, the selected additional
contact is enabled. 4. HEATING CIRCUIT This submenu enables the user to select
the circuit which will operate in cooling mode. To ensure proper operation,
configure activity and define the pre-set temperature for the circuit
operation in the cooling mode. If the selected circuit operates according to
Weather-based control function, the user may edit the heating curve for active
cooling. Additionally, it is possible to set the temperature of pump
activation. Example: If the pump activation temperature is set at 30°C, the
circuit pump will operate below the pre-set temperature. When the temperature
measured by the CH sensor is higher than 30°C, the pump will be disabled.
NOTE If the CH sensor has been disabled, the pump operates all the time. The
parameter selected in the valve menu (Pump activation Always OFF) becomes
deactivated and the circuit pump in cooling mode operates according to the
parameter configured in Cooling Heating circuit Circuit Pump activation
threshold.
46
Menu
PART X Sensor settings
Fitter’s menu Sensor settings
I. SENSOR SETTINGS
· External sensor calibration it is performed while mounting or after the
regulator has been used for a long time, if the external temperature displayed
differs from the actual temperature. Calibration range is from -10C to +10C.
· CH sensor this option enables the user to set the threshold of CH sensor
operation. If you select Activity, the sensor temperature which exceeds this
threshold will activate an alarm. It is possible to configure the top and
bottom temperature threshold. If the system does not include CH sensor,
Activity should be deselected.
· Additional sensors 1,2,3,4 this option enables the user e.g. to set the
sensor operation threshold. If Activity’ has been selected, the sensor will activate an alarm when the temperature threshold has been exceeded. It is possible to set the top and bottom threshold of the sensor temperature.
Sensor selection’ option enables the user to select the type of sensor: KTY
or PT1000.
NOTE
If the device controls a solar heating system, `Additional sensor 4′ will
automatically be set as PT1000.
Menu
PART XI Factory settings
Fitter’s menu
Factory settings
I. FACTORY SETTINGS
This function enables the user to return to the controller settings saved by
the manufacturer.
NOTE Restoring factory settings of the valves does not result in resetting all
controller parameters.
47
Menu
PART XII Settings
Settings
I. SETTINGS
Language selection Time settings
Clock settings Date settings
Settings
Screen settings Alarm sound Notifications
Lock Software version
Screen brightness
Blank screen brightness
Valve temperature too low
Water tank temperature too low
1. LANGUAGE SELECTION This option is used to select the language version of the software.
2. TIME SETTINGS
This option is used to set the date and time displayed in the main screen.
To set these parameters, use the icons
and confirm by pressing OK.
3. SCREEN SETTINGS
Screen brightness may be adjusted to individual user’s needs. New settings are
saved once the user exits the screen settings menu.
4. ALARM SOUNDS This option is used to activate/deactivate an alarm sound informing about failure.
5. NOTIFICATIONS This option enables the user to configure notifications informing that the valve or water tank temperature is too low.
6. LOCK This function enables the user to lock access to the main menu. Follow these steps:
48
1. Select Access code option 2. Set your PIN code which will enable you to
access the menu 3. Click OK to confirm.
NOTE The default PIN code is 0000. If the PIN code has been changed by the
user, 0000 will not work. If you forget the new PIN code, enter the following
code: 3950.
7. SOFTWARE VERSION When this option is selected, the display will show the
manufacturer’s logo and the software version.
NOTE The software version number is necessary while contacting the service
staff.
PART XIII Weekly control
I. WEEKLY CONTROL
Weekly control function enables the user to program daily temperature changes.
The pre-set temperature deviation range is +/- 20°C.
6
1
2
3
1. Decrease temperature deviation 2. Copy previous step 3. Increase temperature deviation 4. Change time period backwards 5. Change time period forwards 6. Time period bar (24 hours)
4
5
49
Example: 1. Set current time and date (Menu > Settings > Time settings > Clock
settings/Date settings).
2. Select day of the week (Schedule modification) to program temperature
deviation for certain hours. In order to program +5C deviation for 06:00AM –
07:00AM and -5C for 07:00AM- 3:00PM, follow these steps:
· Select
and set time period: 06:00AM – 07:00AM
· Select
and set temperature deviation: +5C
· Select
and set time period: 07:00AM – 08:00AM
· Select
and set time deviation: -5C
· Select · Select
to copy the setting (the colour will change to red) to set time period: 02:00PM 03:00PM
· Press
3. It is possible to copy the settings for selected days of the week:
Select
Select the day to copy the settings from
50
Select day(s) to which the settings will be copied
TECHNICAL DATA
Power supply Max. power consumption Ambient temperature Valve max. output load
Pump max. output load Voltage contact max. output load Potential-free cont.
nom. out. load Sensor thermal resistance Fuse
230V ± 10% / 50Hz 10W
5oC ÷ 50oC 0,5A 0,5A 0,5A
230V AC / 0,5A (AC1) * 24V DC / 0,5A (DC1) **
-30oC ÷ 99oC 6,3A
- AC1 load category: single-phase, resistive or slightly inductive AC load. ** DC1 load category: direct current, resistive or slightly inductive load.
51
PROTECTIONS AND ALARMS
In case of an alarm, a sound signal is activated, and the display shows an appropriate message.
Alarm
How to fix it
CH sensor damaged
DHW sensor damaged Valve 1,2,3 sensor damaged Additional valve 1, 2 sensor damaged Return sensor damaged External temperature sensor damaged Return sensor of additional valve 1,2 damaged External sensor of additional valve 1,2 damaged
– Check if the sensor has been installed properly.
-If the cable has been extended, check the quality of the connection (soldered joints are recommended).
– Check if the cable has not been damaged (especially the feeder sensor – it
often gets melted.
– Exchange the sensors (e.g. DHW sensor with the feeder sensor). In this way
you can check if the sensors work properly.
– Check the sensor resistance
– Call the service
Additional sensor 1, 2, 3, 4 damaged
52
SOFTWARE UPDATE
In order to install new software, the controller must be unplugged from the
power supply. Next, insert the flash drive with the new software into the USB
port. Connect the controller to the power supply. A single sound means that
the software update process has been initiated.
NOTE
Software update shall be conducted only by a qualified fitter. After the
software has been updated, it is not possible to restore previous settings.
NOTE
After conducting the software update restart the controller.
USED SENSORS
KTY-81-210 -> 25°C 2000 PT-1000 -> 0°C 1000
The pictures and diagrams are for illustration purposes only. The manufacturer reserves the right to introduce some hanges.
53
EU DECLARATION OF CONFORMITY
Hereby, we declare under our sole responsibility that EU-i-3 controller
manufactured by TECH, head-quartered in Wieprz Biala Droga 31, 34-122 Wieprz,
is compliant with Directive 2014/35/EU of the European Parliament and of the
Council of 26 February 2014 on the harmonisation of the laws of Member States
relating to the making available on the market of electrical equipment
designed for use within certain voltage limits (EU OJ L 96, of 29.03.2014, p.
357), Directive 2014/30/EU of the European Parliament and of the Council of 26
February 2014 on the harmonisation of the laws of Member States relating to
electromagnetic compatibility (EU OJ L 96 of 29.03.2014, p.79), Directive
2009/125/EC establishing a framework for the setting of ecodesign requirements
for energy-related products as well as the regulation by the Ministry of
Entrepreneurship and Technology of 24 June 2019 amending the regulation
concerning the essential requirements as regards the restriction of the use of
certain hazardous substances in electrical and electronic equipment,
implementing provisions of Directive (EU) 2017/2102 of the European Parliament
and of the Council of 15 November 2017 amending Directive 2011/65/EU on the
restriction of the use of certain hazardous substances in electrical and
electronic equipment (OJ L 305, 21.11.2017, p. 8). For compliance assessment,
harmonized standards were used: PN-EN IEC 60730-2-9:2019-06, PN-EN
60730-1:2016-10.
Wieprz, 18.07.2022
54
55
56
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>